R311451 VA Amarillo - ADDENDUM A (RFI) 032923.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25723B0032
About this file
This document package includes electrical drawings and specifications for providing a primary electrical feeder to Building 1 at the Thomas E. Creek VA Medical Center in Amarillo, Texas. The project involves upgrading transformers and switchgear, installing new underground duct banks and conduits, and replacing electrical panels and equipment in Buildings 1 and 4. New pad-mounted transformers and an exterior switchboard will supply 480V power to the buildings. Drawings show demolition plans, new equipment details, panel schedules, riser diagrams and one-line diagrams. The Department of Veterans Affairs is the contracting agency for the project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25723B0032 0003_1.docx | DOCX document | |
| 36C25723B0032 0003 VA Amarillo RFI Responses 040823.pdf | ||
| 36C25723B0032 0002_1.docx | DOCX document | |
| 36C25723B0032 0001 Amendment.pdf | ||
| 36C25723B0032 0001_1.docx | DOCX document | |
| 36C25723B0032 Solicitation.pdf | ||
| VA AMR Elec Bid Set Drawings.pdf | ||
| VA AMR Elec Bid Set Specifications.pdf | ||
| 36C25723B0032_2.docx | DOCX document | |
| VA AMR Elec Bid Set Narrative.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL CONNECTION (NON-MOTOR); SQUARE
DENOTES CONNECTION TO WALL MOUNTED
DEVICE, CIRCLE DENOTES CONNECTION TO
CEILING OR FLOOR MOUNTED DEVICE.
JUNCTION BOX; SQUARE DENOTES WALL MOUNTED,
CIRCLE DENOTES CEILING OR FLOOR MOUNTED
BRANCH PANELBOARD WITH WORKING CLEARANCE,
208/120V
DISTRIBUTION PANELBOARD WITH WORKING
CLEARANCE, 480/277V
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER
EMERGENCY POWER OFF MUSHROOM HEAD BUTTON
WITH CLEAR COVER
3/4" Ø x 10'L COPPER CLAD STEEL GROUNDING ROD
DUPLEX RECEPTACLE, 125V, 20A, 2P, 3W
NEMA 5-20R
SINGLE RECEPTACLE, 125V, 20A, 2P, 3W
NEMA 5-20R
CLOCK HANGER SINGLE RECEPTACLE, 125V, 20A, 2P, 3W
NEMA 5-20R
QUADRAPLEX RECEPTACLE, 125V, 20A, 2P, 3W
NEMA 5-20R
DUPLEX RECEPTACLE, MOUNTED 6" (0.15m) ABOVE
COUNTER OR BACKSPLASH,125V, 20A, 2P, 3W, NEMA 5-20R
5-30R
SPECIAL PURPOSE RECEPTACLE, 125V, 30A, 2P, 3W
NEMA 5-30R
E
ELECTRICAL SYMBOLSRECEPTACLE SYMBOLS
GFI
DUPLEX RECEPTACLE, 125V, 20A, 2P, 3W, NEMA 5-20R,
(GROUND FAULT CIRCUIT INTERRUPTER)
SINGLE OR THREE PHASE MOTOR ELECTRICAL
CONNECTION
WIRE/CONDUIT EXPOSED
UNDERGROUND DUCT BANK - ELECTRIC
GROUND BUS
J
LP-5:7
TYPICAL RECEPTACLE CIRCUIT DESIGNATION
TRANSFORMER, REFER TO TRANSFORMER SCHEDULE
ON E-504 FOR ADDITIONAL INFORMATION
WIRE/CONDUIT CONCEALED
J
VARIABLE FREQUENCY DRIVE WITH HORSEPOWER
DESIGNATION, REFER TO VFD SCHEDULE ON 2E-603
FOR ADDITIONAL INFORMATION
(LP-5) INDICATES PANEL DESIGNATION, (7) INDICATES
CIRCUIT BREAKER NUMBER. PROVIDE 20A/1P AND 2#12
FOR EACH CIRCUIT NUMBER & 1#12G, IN 3/4 " CONDUIT,
UNLESS OTHERWISE NOTED OR SCHEDULED.
WIRE/CONDUIT CONCRETE ENCASED OR DIRECT
BURIED
HOME RUN INDICATION WITH PANEL DESIGNATION
(LP-5) AND CIRCUIT No.(7). PROVIDE 20A/1P BREAKER
AND 2 #12 & 1 #12G IN 3/4" CONDUIT, UNLESS
OTHERWISE INDICATED.
T
VFD-#
LP-5:7
M
SINGLE POLE SWITCH, 20A, 120-277VACS
RECESSED FLOOR BOX
SINGLE RECEPTACLE, 125V, 20A, 2P, 3W
NEMA 5-15RL
SPECIAL PURPOSE RECEPTACLE, COORDINATE NEMA
CONFIGURATION WITH EQUIPMENT
BRANCH PANELBOARD WITH WORKING CLEARANCE,
480/277V
EPO
AUTOMATIC TRANSFER SWITCH WITH AMPERE
DESIGNATION
ATS-#
SWITCHBOARD WITH WORKING CLEARANCE, 480/277V
INDOOR 15KV METAL CLAD SWITCHGEAR WITH
WORKING CLEARANCE
INDOOR UNIT SUBSTATION WITH WORKING
CLEARANCE 480V
HANDHOLEHH
DEMOLITION SYMBOLS
EXISTING PANELBOARD
EXISTING SECURITY CONTROL BOX
EXISTING RECEPTACLE
E E
ELECTRICAL ABBREVIATIONS
A, AMP AMPERES
AC ALTERNATING CURRENT
AF AMPERE FRAME (CIRCUIT BREAKER)
AFF ABOVE FINISHED FLOOR
AFU AMPERE FUSE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AT AMPERE TRIP (CIRCUIT BREAKER)
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
C CONDUIT
CAT CATERGORY
CC CONTROL COIL
CCTV CLOSED CIRCUIT TELEVISION
CIB CCTV INTERFACE BOX
CT CURRENT TRANSFORMER
DC DIRECT CURRENT
DEMO DEMOLITION
DIA DIAMETER
DPM DIGITAL POWER METER
AV AUDIO VISUAL
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEV ELEVATOR
EMT ELECTRICAL METALLIC TUBING
DP DISTRIBUTION PANELBOARD
EO ELECTRICALLY OPERATED
EOL END OF LINE
EPO EMERGENCY POWER OFF
EQ EQUAL
EWC ELECTRIC WATER COOLER
EX EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FDS FUSED DISCONNECT SWITCH
FLA FULL LOAD AMPERE
FLR, FL FLOOR
FPB FAN POWERED BOX
FUT FUTURE
G GROUND (CONDUCTOR)
GCC GENERATOR CONNECTION CABINET
GEN GENERATOR
GF GROUND FAULT
GFI GROUND FAULT INTERRUPTER
GND, GRD GROUND
GPS GENERATOR PARALLELING SWITCHGEAR
GRS GALVANISED RIGID STEEL
H, HT HEIGHT
HDP 480V DISTRIBUTION PANELBOARD
HH HANDHOLE
HOA HAND-OFF AUTOMATIC CONTROLS
HP HORSE POWER
HV HIGH VOLTAGE
HWP HOT WATER PUMP
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
J JUNCTION BOX
KCM THOUSAND CIRCULAR MILS
KI KEY INTERLOCK
KV THOUSAND VOLTAGE, KILO-VOLTS
KVA THOUSAND VOLTAGE-AMPERE, KILO-VOLT-AMPERE
KW THOUSAND WATTAGE, KILO-WATTS
L LENGTH
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
LP 208V BRANCH PANELBOARD
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND FAULT
LTG LIGHTING
IDF INTERMEDIATE DISTRIBUTION FRAME
ELECTRICAL ABBREVIATIONS
NO NORMALLY-OPEN
NTS NOT TO SCALE
OL OVERLOAD(S)
OS OCCUPANCY SENSOR
P POLE
PA PUBLIC ADDRESS
PB PUSH BUTTON, PULLBOX
PC PHOTOCELL
PDU POWER DISTRIBUTION UNIT
PF POWER FACTOR
PH, Φ PHASE
PNL PANEL
PWR POWER
QTY QUANTITY
RE REFER
RECEPT RECEPTACLE
REQ REQUIRED
RF RETURN FAN
RM ROOM
RR RESTROOM
RTU ROOFTOP UNIT
SCCR SHORT CIRCUIT CURRENT RATING
PFC POWER FACTOR CORRECTION
SD SMOKE DETECTOR
SEC SECONDARY
SF SUPPLY FAN
SG SWITCHGEAR
SB SWITCHBOARD
SIB SECURITY INTERFACE BOX
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SS STAINLESS STEEL
STP SHIELDED TWISTED PAIR
SYM SYMETRICAL
T TRANSFORMER
TELECOM TELECOMMUNICATIONS
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UC UNDER-COUNTER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UP UNINTERRUPTIBLE POWER SUPPLY BRANCH
PANELBOARD
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
V VOLTAGE(S)
VA VOLT-AMPERE
VAV VARIABLE AIR VOLUME BOX
VFD VARIABLE FREQUENCY DRIVE
W WATTAGE, WIDTH
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION-PROOF
∆Y DELTA-WYE
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
GENERAL PROJECT NOTES
A. BECOME FAMILIAR WITH THE SCOPE OF WORK REQUIRED BY THE DRAWING AND
SPECIFICATION DOCUMENTS. INCLUDE ALL DEMOLITION WORK IMPLIED OR REQUIRED
IN THE SCOPE OF THIS CONTRACT.
B. PERFORM ALL ELECTRICAL WORK IN ACCORDANCE WITH NFPA 70, VA BARRIER FREE
DESIGN STANDARD (ABAAS) WITH AMMENDMENTS, LIFE SAFETY, FIRE PROTECTION,
AND ANY APPLICABLE LOCAL STANDARDS WITH AMENDMENTS. IN THE EVENT OF A
CONFLICT BETWEEN STANDARDS, THE MORE STRINGENT STANDARD WILL GOVERN.
C. MANUFACTURER'S NAME AND MODEL NUMBERS INDICATED ON THE DRAWINGS ARE
BASIS OF DESIGN. SUBSTITUTIONS ARE PERMITTED PROVIDED THAT THE PROPOSED
SUBSTITUTIONS FULLY COMPLY WITH CONTRACT DOCUMENTS. CONFIRM THE
CORRECTNESS OF ALL MODEL NUMBERS SO AS TO MEET THE SPECIFIED PROJECT
REQUIREMENTS AND MINIMUM INDICATED PERFORMANCE.
D. PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, AND SERVICES NECESSARY FOR A
COMPLETE AND OPERABLE INSTALLATION AS SPECIFIED AND SHOWN ON THE
DRAWINGS, FULLY TESTED, ADJUSTED AND READY FOR USE.
E. THE DRAWING SHOW THE EXTENT OF THE WORK AND THE GENERAL ARRANGEMENT.
ALL CIRCUITS ARE SHOWN SCHEMATICALLY. FINAL ROUTING DECISIONS ARE BY THE
CONTRACTOR.
F. COORDINATE THE EXACT LOCATION OF THIS WORK WITH THE WORK OF THE OTHER
TRADES AND/OR EXISTING CONDITIONS PRIOR TO FABRICATION OR INSTALLATION OF
THE SAME. VERIFY ALL DIMENSIONS AND ELEVATIONS. PROVIDE ADDITIONAL OFFSETS
AND SECTIONS OF MATERIALS AS REQUIRED TO MEET THE APPLICABLE JOB
CONDITION REQUIREMENTS.
G. COORDINATE WITH THE SUPPLIERS AS TO WHICH DEVICES ARE SUPPLIED WITH THE
EQUIPMENT, REQUIRED WIRING, VOLTAGES, AND OTHER COORDINATION ITEMS AS
RELATED TO A PROPER AND OPERABLE INSTALLATION.
H. PROVIDE ALL CIRCUITS IN CONDUIT. PROVIDE A DEDICATED EQUIPMENT GROUNDING
CONDUCTOR, SIZED PER THE NEC, WITH EACH BRANCH CIRCUIT. SHARED NEUTRALS
ARE NOT ALLOWED; PROVIDE ALL 120 AND 277 VOLT CIRCUITS WITH A DEDICATED
NEUTRAL.
I. DIMENSIONAL LOCATIONS INCLUDING ELEVATIONS INDICATED ON THE DRAWINGS ARE
APPROXIMATE AND FOR REFERENCE ONLY. THE CONTRACTOR SHALL COORDINATE TO
AVOID INTERFERENCES IN ROUTING OF CONDUITS.
J. LEAVE PULL STRING IN EMPTY CONDUITS. PLUG OR CAP BOTH ENDS OF EMPTY
CONDUITS AND LABEL AS TO THEIR INTENDED USE.
K. UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE SIZED FOR COPPER TYPE THWN,
THHN, AND RATED FOR 75 DEGREE C (MINIMUM).
L. UNLESS OTHERWISE NOTED, CIRCUITS ARE SIZED ASSUMING NO MORE THAN THREE
CURRENT CARRYING CONDUCTORS ARE INSTALLED IN A SINGLE CONDUIT.
M. VERIFY ALL REQUIREMENTS AND SIZES FOR OVERCURRENT PROTECTIVE DEVICE,
DISCONNECT SWITCH, CIRCUIT WIRE, AND CONDUIT SIZE WITH THE FINAL APPROVED
MECHANICAL EQUIPMENT TO BE INSTALLED. PROVIDE ALL ELECTRICAL COMPONENTS
AS REQUIRED.
N. FLUSH MOUNT ALL SWITCHES AND RECEPTACLES IN FINISHED AREAS. SWITCHES AND
RECEPTACLES MAY BE SURFACE MOUNTED IN EXPOSED SPACES. UNLESS OTHERWISE
NOTED, CONCEAL ALL CONDUIT IN WALLS, ABOVE ACCESSIBLE CEILING, OR IN FLOOR
SLAB. CONDUIT IN ROOMS WITH NO CEILING AND/OR ARE EXPOSED MAY BE MOUNTED
TO THE BUILDING STRUCTURE. DO NOT INSTALL CONDUITS IN CONCRETE FLOORS
WITH TOPPINGS LESS THAN 3" THICK.
O. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REINSTALLING ANY EXISTING
CEILING TILES AS REQUIRED FOR THE WORK THAT IS REQUIRED IN THE EXISTING
FACILITY. SCHEDULE ALL INTERIOR WORK THAT MIGHT INTERFERE WITH DAILY
OPERATIONS WITH CONTRACTING OFFICER AT LEAST (2) WEEKS IN ADVANCE. ANY
DAMAGE TO EXISTING FACILITIES BY THE CONTRACTOR SHALL BE CORRECTED, AND
DAMAGED EQUIPMENT (CEILING TILES, ETC.) REPLACED WITH NEW.
P. SEAL ALL CONDUIT PENETRATIONS, USING A LISTED SEALANT FOR THE APPROPRIATE
APPLICATION, OF WALLS, PARTITIONS, FLOORS, ROOF, ETC.
Q. "PROVIDE", "FURNISH", AND "INSTALL", WHERE USED, ARE DEFINED HEREIN AS
CONTRACTOR-PROVIDED, AND CONTRACTOR-INSTALLED. WHERE EQUIPMENT IS TO BE
"PROVIDED," IT IS ALSO TO BE INSTALLED IN ITS ENTIRETY BY THE CONTRACTOR, AND
WHERE EQUIPMENT IS TO BE "INSTALLED," IT IS ALSO TO BE PROVIDED, OR
FURNISHED, IN ITS ENTIRETY BY THE CONTRACTOR. ALL EQUIPMENT INSTALLATIONS
SHALL BE COMPLETE AND OPERATIONAL.
R. WORKING SPACES ABOUT ELECTRICAL EQUIPMENT SHALL BE PER NEC 110.26, WITH
THE EXCEPTION THAT THE ELECTRICAL HEIGHT OF WORKING SPACE SHALL EXTEND
FROM THE FLOOR TO THE STRUCTURAL CEILING. NO PIPING, DUCTS, OR OTHER
EQUIPMENT FOREIGN TO ELECTRICAL SYSTEMS SHALL BE PERMITTED IN THE
WORKING SPACE ABOUT ELECTRICAL EQUIPMENT.
S. PROVIDE ALL SUPPLEMENTAL SUPPORTING DEVICES REQUIRED FOR ELECTRICAL
EQUIPMENT WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR DIRECT
MOUNTING.
T. FLEXIBLE CONDUIT MAY ONLY BE USED FOR FINAL EQUIPMENT CONNECTIONS, AND
SHALL BE LIMITED TO 6'-0" IN LENGTH. VERIFY ALL MODULAR FURNITURE AND
EQUIPMENT.
U. PROVIDE ASPHAULT AND CONCRETE TESTING FOR PAVEMENT REPLACEMENT AND
EQUIPMENT PADS AS SPECIFIED IN SECTION 01 42 49.
M METER (POWER), MANUAL PULL BOX (FIRE ALARM)
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT BREAKER
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MV MEDIUM VOLTAGE
N NEUTRAL, NORMAL
NC NORMALLY-CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
APPLICABLE CODES
A. NFPA 70, NATIONAL ELECTRICAL CODE (NEC)
B. INTERNATIONAL BUILDING CODE (IBC)
C. NFPA 101, LIFE SAFETY CODE
D. INTERNATIONAL ENERGY CONCERVATION CODE (IECC)
EXISTING CONDUIT
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ELECTRICAL ABBREVIATIONS,
LEGEND, AND SYMBOLS
E-001
-2
-1
E
-0
J U
L Y
.p d f
A ADDENDUM A 03/29/2023
A jroberts jroberts Stamp
4A
PN
L
BL
PN
L 7B
2A
PN
L 7B
PN
L 7− B 1E
Q
SP
LIC
E B
O X
G R O U
ND
B
AR
PN
L 7
−B 3E
C
OI&T
LOT E
AREA 1
LO
T I
LOT D
SWITCH
SERVICES
LO
D G
E
H O
S P
IT
A L
(O R
IG
X
FM
R -2
8-
X
FM
R -2
8-
X
FM
R -2
8-
X
FM
R -4
-2 X
FM
R -4
-1
T
MH
E
NEW 1600A, 480V, 3Φ
4W SWITCHBOARD
EXISTING MANHOLE.
E
EXTEND NEW PRIMARY
CIRCUITS FROM EXISTING
TRANSFORMERS THROUGH
EXISTING MANHOLE TO NEW
TRANSFORMERS
NEW 13.2KV-480V XFMR
ALTERNATE #1
PROPOSED 2"
CONDUIT ROUTING
FOR EMERGENCY
POWER TO BUILDING 7
EXISTING PRIMARY CIRCUITS
IN EXISTING DUCTBANK NO
WORK
T
T
T
NEW ELECTRICAL
DUCTBANK
E-100
A
A
SHEET LEGEND
GRAY/HALF-TONE LINES AND TEXT INDICATE
EXISTING TO REMAIN
DIAGIONAL-UP HATCH INDICATE EXISTING TO BE
REMOVED. REFER TO SHEET ED-401 AND E-401 FOR
ADDITIONAL INFORMATION
SHEET KEY NOTES
1. EXISTING UNDERGROUND 13.2 KV FEEDER TO FROM MAIN SWITCHGEAR
IN BUILDING 39 TO EXISTING PAD MOUNTED TRANSFORMER AT BUILDING
7. REMOVE EXISTING SINGLE PHASE CABLE AND INSTALL NEW THREE
PHASE 15KV CABLE. REFER TO MV RISER DIAGRAM ON SHEET E-402 FOR
ADDITIONAL INFORMATION.
2. PROTECT EXISTING PRIMARY FEEDER DUCT BANK DURING
INSTALLATION OF NEW GENERATOR FEEDER DUCTBANK TO BUILDING 7.
3. NEW GENERATOR SERVICE FEEDER DUCT BANK FROM BUILDING 20 TO
BUILDING 7 ROUTED THROUGH UNPAVED AREA BETWEEN SIDEWALK
AND PARKING LOT PAVING. COORDINATE FINAL ROUTING WITH OWNER.
REFER TO RISER DIAGRAM ON SHEET E-401 FOR ADDITIONAL
INFORMATION.
4. SAW CUT EXISTING PARKING LOT PAVING AND CURB AND TRENCH TO
INSTALL NEW GENERATOR SERVICE FEEDER DUCT BANK UNDER
ROADWAY. REPLACE AND REPAIR PAVING AND CURB TO MATCH
EXISTING.
5. SAW CUT EXISTING SIDEWALK AND TRENCH TO INSTALL NEW
GENERATOR SERVICE FEEDER DUCT BANK UNDER SIDEWALK. REPLACE
AND REPAIR PAVING AND CURB TO MATCH EXISTING.
6. PROVIDE 30”X30”X24”D REINFORCED CONCRETE JUNCTION BOX WITH
CAST IRON, TRAFFIC RATED LID MARKED “ELECTRIC” AT RIGHT ANGLE OF
NEW GENERATOR SERVICE FEEDER DUCT BANK.
7. EXTEND BUILDING 7 GENERATOR SERVICE DUCT BANK TO CORNER OF
BUILDING 20 AND TURN UP ON OUTSIDE WALL AND PROVIDE TYPE LB
FITTINGS INTO BUILDING.
8. EXISTING 480/3 FEEDER TO BUILDING 8 TRANSFORMER. REMOVE
EXISTING CONDUCTORS FROM BUILDING 1 TO BUILDING 8 AND REMOVE
EXPOSED RACEWAY. ABANDON UNDERGROUND RACEWAY IN PLACE.
9. REMOVE EXISTING 150 KVA, 480-208/120V, 3-PHASE DRY TYPE
TRANSFORMER AT BUILDING 8 AND REPLACE WITH NEW 150 KVA,
13.2KV-208/120V 3- PHASE LIQUID FILLED PAD MOUNT LOOP FEED
TRANSFORMER. REFER TO RISER DIAGRAM ON SHEET E-401 FOR
ADDITIONAL INFORMATION.
10. REPLACE EXISTING 50 KVA, 13.2KV-240/120V, 1-PHASE PAD MOUNTED
TRANSFORMER WITH NEW 150 KVA, 13.2KV-208/120V, 3-PHASE PAD
MOUNTED LOOP FEED TRANSFORMER. PROVIDE NEW CONCRETE PAD,
REFER TO DETAIL 4-E-301. REFER TO RISER DIAGRAM ON SHEET E-402
FOR ADDITIONAL INFORMATION.
11. COORDINATE BUILDING 7 GENERATOR SERVICE ENTRY INTO BUILDING 7
LOWER LEVEL. REFER TO DETAIL 2/E-202 FOR LOCATION OF BUILDING
ENTRY AND AUTOMATIC TRANSFER SWITCH.
12. NEW 208/120V, 3-PHASE, 500 AMP BUILDING ELECTRIC SERVICE ENTRY.
REFER TO DETAIL 2/E-202 FOR ADDITIONAL INFORMATION.
13. DISCONNECT BUILDING 8 FEEDER FROM CIRCUIT BREAKER IN
SWITCHBOARD 1 IN BUILDING 4. LABEL BREAKER AS "SPARE".
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ENLARGED SITE PLAN
E-011
-2
-1
E
-0
J U
L Y
.p d f
1" = 20'-0"
ENLARGED ELECTRICAL SITE PLAN
10' 20' 40'0'
1" = 20'SCALE
N
A ADDENDUM A 03/29/2023
IT10
XFMR
1BC9EL
PNL
1BC10
PNL
1BC11EL
PNL
TELECOMM
PNL DC
PNL 1BB6
PNL DCEC
PNL L
1155A
1155B
1155C 1161
1165 1164
1131B
1158A
1118A
1154 1134A 1132A
1108A
1140 1138 1136 1134 1132 1130 1126 1124 1122 1120
1118 1111 1110 1110A 1104
1131B 1131A 1131
1127 1125 1123
1123A
1117A 1112 1105 1103 1101
E E
UNDERGROUND
CONCRETE
CONDUIT
DUCTBANK
STUB-UP CONDUITS
ALONG EXTERIOR
WALL AND EXTEND
ABOVE INTERIOR
FINISHED CEILING.
ROUTE CONDUITS
ABOVE FINISHED
CEILING
WIREWAY
ABOVE CEILING
PENETRATE THROUGH
EXTERIOR WALL TO ROUTE
CONDUITS ABOVE INTERIOR
FINISHED CEILING
E
EXISTING
ELECTRICAL
MANHOLE
RE: SHEET 1/E-301
PROVIDE 15KV LOAD BREAK FEED
THROUGH BUSHING INSERTS AND
EXTEND EXISTING PRIMARY CIRCUIT
TO NEW TRANSFORMERS
4-WAY CONCRETE
ENCASED DUCTBANK
RE:3/E-301
4'-0"
TYP
U P
S
UPS
PNL "IDF"
PNL "3LCB"EXISTING UPS
1 1 1
PNL 1BA4 PNL 1BA5
PNL 1BA6
PNL 1BA7
PNL 11C4EL
PNL 11C3EL
PNL 11C2
PNL 11C1EC
EXTEND ABOVE TO:
PANEL "1-4B1"
PANEL "1-5C8"
E-201
E-201
REMOVEABLE
BOLLARDS, TYPICAL
OF 11. RE: 5/E-301.
T T
NEW SWITCHBOARD,
RE:7/E-301 FOR PAD
4 NEW
XFMR 1-1
NEW
XFMR 1-2
E
E
E
PNL 1BA2
PNL 1BA3EC
PNL 1BAEC14
2-WAY CONCRETE
ENCASED DUCTBANK
RE:6/E-301
E-202
A
SHEET LEGEND
GRAY/HALF-TONE LINES AND TEXT INDICATE
EXISTING TO REMAIN
DIAGIONAL-UP HATCH INDICATE EXISTING TO BE
REMOVED. REFER TO SHEET ED-401 AND E-401 FOR
ADDITIONAL INFORMATION
SHEET KEY NOTES#
1. REMOVE THE THREE EXISTING WINDOWS IN THE WAITING ROOM
AND PATCH THE THREE OPENINGS. ON THE EXTERIOR OF THE
BUILDING, REMOVE EXISTING CUT BLOCKS AND INFILL OPENING TO
MATCH EXISTING RUNNING BOND PATTERN. MATCH COLOR OF
EXISTING MASONRY VENEER. INSTALL NEW FRAMING FOR THE
OPENINGS IN THE WALL TO MATCH EXISTING FRAMING. ON THE
NEW FRAMING INSTALL NEW SHEATHING AND EXTERIOR
WATERPROOFING AS REQUIRED. ON THE INTERIOR INSTALL NEW
GYPSUM BOARD AS REQUIRED TO MATCH THE FINISH SURFACE OF
THE EXISTING WALL SURFACE. FLOAT, TEXTURE AND SAND TO
MATCH EXISTING WALL FINISH ABOVE THE EXISTING CHAIR
RAIL. REPAINT “BEIGE” PORTION OF THE WALL ABOVE THE CHAIR
RAIL. CARE SHOULD BE TAKEN NOT TO DAMAGE EXISTING
CONSTRUCTION TO REMAIN AND NOT ALLOW PAINT TO TOUCH
EXISTING CHAIR RAIL, CEILING GRID, WAINSCOT, BASE OR
FLOORING.
2. COORDINATE WITH LOCAL VA ELECTRICAL STAFF AND REMOVE
UNUSED CONDUITS ABOVE CEILING FROM BUILDING 4
SWITCHBOARDS IN ROOM 1023 TO ELECTRICAL EQUIPMENT IN
BUILDING 1.
3. SAW CUT EXISTING DRIVEWAY AND CURB AND TRENCH TO INSTALL
NEW BUILDING 1 SERVICE MEDIUM VOLTAGE FEEDER DUCT BANK
UNDER ROADWAY. REPLACE AND REPAIR PAVING AND CURB TO
MATCH EXISTING. COORDINATE ROADWAY OUTAGE WITH VA COR.
REFER TO E-402 FOR ADDITIONAL INFORMATION. ROUTE DUCT
BANK FROM EXISTING MANHOLE, RE: DETAIL 1/E-301, TO PRIMARY
COMPARTMENTS OF NEW TRANSFORMERS 1-1 AND 1-2.
4. SAW CUT EXISTING PARKING LOT PAVING AND CURB AND TRENCH
TO INSTALL NEW BUILDING 480V SERVICE FEEDS DUCT BANK
UNDER PAVEMENT. REPLACE AND REPAIR PAVING AND CURB TO
MATCH EXISTING. REFER TO E-401 FOR ADDITIONAL INFORMATION.
5. SAW CUT EXISTING PARKING LOT PAVIING AND CURB AND TRENCH
TO INSTALL NEW FEEDERS TO NEW PANELS IN ROOM 113A.
REPLACE AND REPAIR PAVING AND CURB TO MATCH EXISTING.
6. EXTEND CONDUITS FROM NEW EXTERIOR SWITCHBOARD
UNDERGROUND TO CORNER OF BUILDING 1 AND STUB UP 6” ABOVE
GRADE AND CAP FOR FUTURE AHU TOWER.
7. STUB UP CONDUITS OUTSIDE OF BUILDING 1 AND ROUTE UP
EXTERIOR WALL AND TURN INTO ROOM 113A FOR NEW SERVICE TO
PANELS 1BA4 AND 1BA6.
8. EXTEND FEEDERS TO PANELS 1BA4 AND 1BA6.
9. EXTEND NEW FEEDERS INTO EXISTING ELECTRICAL ROOM. REFER
TO ENLARGED PLAN FOR CONTINUATION.
10. REMOVE EXISTING UPS CIRCUIT TO BUILDING 7 FROM EXISTING
PANEL “3LCB”. EXISTING CONDUCTORS TO BUILDING 7 AND REMOVE
RACEWAY WHERE ACCESSIBLE. LABEL EXISTING CIRCUIT BREAKER
IN PANEL “3LCB” AS “SPARE”.
11. REMOVE AND REPLACE EXISTING PANELS “1BB6” AND “DC”. REFER
TO E-401 FOR ADDITIONAL INFORMATION.
12. REMOVE AND REPLACE EXISTING PANEL “11C2”. REFER TO E-401
FOR ADDITIONAL INFORMATION.
13. REMOVE AND REPLACE EXISTING PANEL “1-BC10”. REFER TO E-401
FOR ADDITIONAL INFORMATION.
14. REMOVE AND REPLACE EXISTING PANE "1BA2". REFER TO ED-401
AND E-401 FOR ADDITIONAL INFORMATION.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ELECTRICAL PLANS - BUILDINGS 1 & 4
E-100
-2
-1
E
-1
J U
L Y
.p d f
12" = 1'-0"
BUILDINGS 1 AND 4 - FLOOR PLANS
4' 8' 16'0'
1/8" =1'-0"SCALE
5' -0
5'-0"
N
1 & 4
1/8" = 1'-0"
A ADDENDUM A 03/29/2023
EXIST. WATER PIPE
EXIST. PANEL IBC7EC
EXIST. PANEL IBC6EC
EXIST. PANEL IBC5
EXIST. XFMR 1−T4
EXIST.
1−T4 DISCONNECT
EXIST. 8"X8"
WIREWAY
EXIST.
1−T6 DISCONNECT
EXIST.
RTU −1
EXIST.
ION
METER
EXIST.
PANEL 1BDE
EXIST.
XFER
SWITCH
ATS−1X5
EXIST. XFMR 1−T1
(TOP)
EXIST. XFMR 1−T9
(BOT)
EXIST. 1−T4
DISCONNECT
EXIST. 1−T1
DISCONNECT
EXIST. 1−T9
SPLICE BOX
EXIST.
42" W x 6" H
CONCRETE
CURB
EXIST.
XFMR 1−T7
EXIST. 1−T5
DISCONNECT
EXIST. 1−T7
DISCONNECT
EXIST.
XFMR 1−T5
EXIST.
XFMR 1−T6
EXIST. 1−T6
DISCONNECT
EXIST.
XFER SWITCH
ATS−1X1
EXIST.
PNL 1BC1
EXIST.
6 PNL 1BC3
EXIST.
12"x12"x6" 1BC3
NEUTRAL SPLICE
BOX
EXIST. PNL 1BC2
EXIST. XFMR 1−T4
EXIST.
GROUND BAR
EXIST. 7B−1 70A DISCONNECT
EXIST. GROUND BAR
EXIST. XFER SWITCH ATS−1X2
EXIST. PNL 1BC14EL
EXIST. XFMR 1−T12
EXIST.
PNL 1BC16E
EXIST. XFER
SWITCH
ATS−1X3 EXIST. XFMR 1−T13
EXIST. PNL 1BC12EC
EXIST.
PNL 1BC15E
EXIST. PNL
1BC18EC
EXIST. PNL 1BC13EC
EXIST. XFER SWITCH ATS−1X4
EXIST. XFMR 1−T11
ELECTRICAL
ROOM
ELECTRICAL
ROOM
ELECTRICAL
ROOM
BUILDING 1 - ENLARGED ELECTRICAL ROOMS
1127 AND 1129 POWER PLAN - DEMOLITION
SCALE: 1" = 1'-0"1
BUILDING 1 - ENLARGED ELECTRICAL
ROOM 1163 POWER PLAN - DEMOLITION
SCALE: 1/2" = 1'-0"2
SHEET LEGEND
DIAGIONAL-UP HATCH INDICATE EXISTING TO BE
REMOVED. REFER TO SHEET ED-401 AND E-401 FOR
ADDITIONAL INFORMATION
SHEET KEY NOTES#
1. EXISTING ELECTRICAL EQUIPMENT SHALL REMAIN.
2. REMOVE EXISTING ELECTRICAL EQUIPMENT. EXISTING FEEDER AND
BRANCH CIRCUIT SHALL REMAIN FOR RECONNECTION TO NEW
EQUIPMENT.
3. REMOVE EXISTING ELECTRICAL EQUIPMENT. REMOVE EXISTING
FEEDER BACK TO UPSTREAM TRANSFORMER. EXISTING BRANCH
CIRCUITS SHALL REMAIN FOR RECONNECTION TO NEW EQUIPMENT.
4. REMOVE EXISTING DISCONNECT SWITCH SERVING 480/3 EQUIPMENT
IN BUILDING 7. REMOVE EXISTING FEEDER AND RACEWAY BACK TO
SOURCE. REMOVE CONDUCTORS TO BUILDING 7. ABANDON
INACCESSIBLE RACEWAYS IN PLACE.
5. REMOVE EXISTING 480V-240/120V TRANSFORMER. REMOVE LINE AND
LOAD FEEDER CONDUCTORS AND RACEWAYS.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ENLARGED DEMOLITION PLAN -
BUILDING 1
ED-201
-2
-1
E
D -2
J U
L Y
.p d f
PLAN
A ADDENDUM A 03/29/2023
A
EXIST. WATER PIPE
EXIST. PANEL IBC7EC
EXIST. PANEL IBC6EC
EXIST. PANEL IBC5
EXIST. XFMR 1−T4
EXIST.
1−T4 DISCONNECT
EXIST. 8"X8"
WIREWAY
EXIST.
1−T6 DISCONNECT
EXIST.
RTU −1
EXIST.
ION
METER
EXIST.
PANEL 1BDE
EXIST.
XFER
SWITCH
ATS−1X5
EXIST. XFMR 1−T1
(TOP)
EXIST. XFMR 1−T9
(BOT)
EXIST. 1−T4
DISCONNECT
EXIST. 1−T1
DISCONNECT
EXIST. 1−T9
SPLICE BOX
EXIST.
42" W x 6" H
CONCRETE
CURB
EXIST.
XFMR 1−T7
EXIST. 1−T5
DISCONNECT
EXIST. 1−T7
DISCONNECT
EXIST.
XFMR 1−T5
EXIST.
XFMR 1−T6
EXIST. 1−T6
DISCONNECT
EXIST.
XFER SWITCH
ATS−1X1
EXIST.
PNL 1BC1
EXIST.
6 PNL 1BC3
EXIST.
12"x12"x6" 1BC3
NEUTRAL SPLICE
BOX
EXIST. PNL 1BC2
EXIST. XFMR 1−T4
EXIST.
GROUND BAR
EXIST. GROUND BAR
EXIST. XFER SWITCH ATS−1X2
EXIST. PNL 1BC14EL
EXIST. XFMR 1−T12
EXIST.
PNL 1BC16E
EXIST. XFER
SWITCH
ATS−1X3 EXIST. XFMR 1−T13
EXIST. PNL 1BC12EC
EXIST.
PNL 1BC15E
EXIST. PNL
1BC18EC
EXIST. PNL 1BC13EC
EXIST. XFER SWITCH ATS−1X4
EXIST. XFMR 1−T11
ELECTRICAL
ROOM
ELECTRICAL
ROOM
ELECTRICAL
ROOM
BUILDING 1 - ELECTRICAL ROOMS
1127 AND 1129 ENLARGED POWER PLAN
SCALE: 1" = 1'-0"1
BUILDING 1 - ELECTRICAL ROOM
1163 ENLARGED POWER PLAN
SCALE: 1/2" = 1'-0"2
REPLACE EXISTING
PANEL 1BC1 WITH A
120/208V, 600A, 3
PHASE, 4 WIRE
PANEL.
REPLACE
EXISTING XFMR
WITH A
112.5KVA,
480-120/208V, 3
PHASE, 4 WIRE.
REPLACE EXISTING PANEL WITH A
120/208V, 400A, 3 PHASE, 4 WIRE PANEL
REPLACE EXISTING
PANEL"1BC3" WITH
A 120/208V, 400A, 3 PHASE, 4 WIRE
PANEL
REPLACE
N
N
NEW PANEL IBC5
NEW
NEW
NEW
1 NEW
NEW PANEL
1BC18EC
NEW
PANEL 1BC15E
NEW PANEL 1BC13EC
NEW XFER SWITCH ATS-1X4
NEW XFMR 1-T11
NEW PANEL 1BC22
3NEW XFMR 1-T13
NEW PANEL 1BC12EC
REPLACE
EXISTING XFMR
WITH A 112.5KVA,
480-120/208V, 3
PHASE, 4 WIRE.
REPLACE EXISTING DISCONNECT SWITCH
WITH A 200AA, 3 POLE BREAKER
A
SHEET LEGEND
SHEET KEY NOTES#
1. PROVIDE NEW ELECTRICAL EQUIPMENT. CONNECT TO EXISTING
FEEDER AND BRANCH CIRCUITS. EXTEND CONDUCTORS AS NEEDED
TO MAKE CONNECTIONS.
2. PROVIDE NEW ELECTRICAL EQUIPMENT. CONNECT EXISTING
BRANCH CIRCUITS TO NEW DEVICES. EXTEND CONDUCTORS AS
NEEDED TO MAKE CONNECTIONS. PROVIDE NEW FEEDER CIRCUIT
TO UPSTREAM DEVICE. REFEER TO RISER DIAGRAM, E-401.
3. PROVIDE NEW 480V-208/120V, 3 PHASE TRANSFORMER. PROVIDE
NEW LINE FEEDER FROM EXISTING SOURCE AND NEW LOAD
FEEDERS TO DOWNSTREAM PANEL. REFER TO TRANSFORMER
SCHEDULE FOR ADDITIONAL INFORMATION. REFER TO RISER
DIAGRAM, E-401.
GRAY/HALF-TONE LINES INDICATE EXISTING TO
REMAIN
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
AuthorChecker
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ENLARGED ELECTRICAL PLAN -
BUILDING 1
E-201
-2
-1
E
-2
J U
L Y
.p d f
A ADDENDUM A 03/29/2023
MANHOLE
FLOOR
MANHOLE EAST WALLMANHOLE WEST WALL
MANHOLE SOUTH WALL
MANHOLE NORTH WALL
4' CONDUITS, TYPICAL
TO XFMR T4-2TO XFMR T4-1
NEW 13.2KV, 3P,
CABLE TO NEW
BLDG 1 XFMRS.
RE: E-402
TO BLDG 39 SECTION 7
SWITCH "WEST"
TO BLDG 39 SECTION 1
SWITCH "EAST"
NEW 4-CELL DUCT BANK TO NEW
BLDG 1 PAD MOUNTED
TRANSFORMERS. RE: 3/E-301
TO XFMR T1-2TO XFMR T1-1
NOTES:
PRIMARY CIRCUIT ROUTING SHOWN HERE IS
ESTIMATED FROM OBSERVATIONS. FIELD VERIFY
ACTUAL ROUTING WITH CONDITIONS IN FIELD.
TAP CHANGER
LOW VOLTAGE COMPARTMENT
PRESSURE GAUGE
TEMPERATURE
LOW VOLTAGE BUSHINGS
BARE #3/0 TINNED COPPER
BAYONET FUSES
GROUND CONDUCTOR SHIELDS
FINISH GRADE
6" COMPACTED GRAVEL SUBBASE
CONCRETE ENCASED
PRIMARY DUCTBANK
HIGH VOLTAGE COMPARTMENT
METAL ENCLOSED TRANSFORMER
LIQUID LEVEL GAUGE
HIGH VOLTAGE TERMINATIONS
3/4" CHAMFER
3/4" DIA. x 10'-0" GROUND ROD 3/4 " DIA. x 10'-0" GROUND ROD
(TYP. OF FOUR. THIS DETAIL)
ONE AT EACH CORNER
CURRENT TRANSFORMERS RATED
FOR OUTDOOR AND 600 VOLTS NOMINAL.
TRANSFORMER SHALL CONFORM TO
ANSI C12.11, BIL 10KV AND ACCURACY
CLASS 0.3 THRU B-0.5
THREE POSITION FEEDER
SELECT SWITCH (ON/OFF/ON)
UNDERGROUND SECONDARY
CONDUITS TO BUILDING MAIN
SERVICE ENTRANCE SEE E-401
RAISER DIAGRAM
PAD MOUNTED TRANSFORMER
DUAL FEED 13,200 VOLT TO 480/277 VOLT
3 PHASE DELTA TO WYE
NEW CONCRETE PAD. RE: 4/E301.
COORDINATE ACTUAL DIMENSIONS WITH
TRANSFORMER SHOP DRAWINGS
10"
MIN.
24" M
IN 4"
6"
11"
6"
4"
7"
3"
REINFORCEMENT SCHEDULE PAD
WITH BEAM
NOTES:
A
SECTION "A-A"
NUMBERS OF #3
BARS LENGTH
82"
56"
8"
13"
92" 25.9
1.6
1.5
10.5
15.4
WIEGHT (LBS)
(1.97 CU. YARDS CONCRETE TOTAL WEIGHT OF PAD 7,710 LBS)
A
B
REFER TO UTILITY PROVIDER
SPECIFICATIONS FOR ELECTRICAL
UNDERGROUND DISTRIBUTION SYSTEMS
FROM PADMOUNTED TRANSFORMATION,
SECONDARY SERVICE ACCOUNTS.
B
11" 8"11" 25"
17"
96"
6"3"
12"
6"
SECTION "B-B"
86"
3"
14"
6"
12"
6"3" 3"
CONCRETE ENCASEMENT
FINISHED GRADE
4" PVC SCHEDULE 40
CONDUIT (TYPICAL)
CONDUIT SPACER
(TYPICAL)
3" 3" CONCRETE ENCASEMENT 3" MINIMUM
ALL FOUR SIDES OF DUCT
2"
MARKING TAPE
#3/0 BARE COPPER GROUND
D E
P T
H
M
II
N
IM
U M
1'- 6"
DOMED WELDED CAP
4", RED REFLECTIVE TAPE
WRAPPED AROUND BOLLARD
4" SCHD 40 STEEL PIPE
GALVANIZED BOLLARD
PAINTED SEMI-GLOSS
TRAFFIC YELLOW
EXISTING PAVEMENT
560-C-3250 CONCRETE
2 - 1" DIA. WEEPHOLES IN
BOLLARD SLEEVE
4", RED REFLECTIVE TAPE
WRAPPED AROUND BOLLARD
5" SCHD 40 PIPE
GALVANIZED SLEEVE SET IN
PAVING
3/4" GRAVEL
5"
NOTES:
1. SEE PLAN FOR LOCATION OF ALL BOLLARDS.
2. ALL BOLLARDS ARE 4'-0" O.C. (TYPICAL).
3. EASE ALL CORNERS, GRIND ALL WELDS SMOOTH.
CONCRETE ENCASEMENT
FINISHED GRADE
4" PVC SCHEDULE 40
CONDUIT (TYPICAL)
CONDUIT SPACER
(TYPICAL)
CONCRETE ENCASEMENT 3" MINIMUM
ALL FOUR SIDES OF DUCT
MARKING TAPE
#3/0 BARE COPPER GROUND
D E
P T
H
M
II
N
IM
U M
3" 3"2"
6"
MIN
6"
MIN
M
IN
M
IN
8"
MIN
8" MIN
OUTLINE OF
EQUIPMENT
REFER TO
MANUFACTURERS'
REQUIREMENTS FOR
ANCHORAGE,
TYPICAL, UNLESS
NOTED OTHERWISE
3-#5 CONTINUOUS
#4@12" ON CENTER,
EACH WAY CENTERED
IN SLAB
NOTE: ANCHORAGE TO BE DESIGNED
BY EQUIPMENT MANUFACTURER PER
GOVERNING CODE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ELECTRICAL DETAILS
E-301
-2
-1
E -3
J
U L Y
.p d f
NTS
ELECTRICAL MANHOLE CABLE ROUTING
NTS
TYPICAL PAD-MOUNTED TRANSFORMER DETAIL
NTS
TRANSFORMER PAD DETAIL (CONCEPT)
NTS
4-CELL CONTRETE ENCASED DUCT BANK
NTS
REMOVABLE BOLLARD DETAIL
NTS
2-CELL CONTRETE ENCASED DUCT BANK
A ADDENDUM A 03/29/2023
NTS
EXTERIOR EQUIPMENT PAD
7A
U P
S "3
L C
B
T O
B L D
G
A
C B
T O
B L D
G
P A
N E
L C
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
EMERGENCY GENERATORS IN BUILDING 20
C B
S S
C B
A T
S
S
SWBD 1
SWBD 1
SS
SS
M T
R
SWBD 2
SWBD 2
SWBD 2
DTS BLDG 4
4-B13EC
4-B11EL
7-B2
SWBD 2
FIFTH FLOOR
(O R
IG
IN
A L
P A
N E
L
C
E
C
CB
CB
EMERGENCY
SWITCHBOARD
20-EMSB
GENERATOR
CONTROL
SWITCHBOARD
180KW/225KVA
DIESEL EMERGENCY
GENERATOR
(STANDBY TO 750KW)
750KW/938KVA
DIESEL EMERGENCY
GENERATOR
C
E
C
MAIN
TS-3 TS-1
MAIN
MAIN
1BC6E
THIS C OULD BE DELETED AT A LATER DATE BY R ERO UTING THRU JBOX.
THIS C OULD BE DELETED AT A LATER DATE BY R ERO UTING THRU JBOX.
OLD N UMBER 1 OF 2 1-X2 NUMBERS
OLD NU MBER 1X-4 THERE WERE 2 1X-4'S
MAIN
1BC7E
SWBD 2
SWBD 1
4B10E
4-11
SWBD 1
O
LD
N U
M B
E R
W A
S
-X 6.
O
LD
N U
M B
E R
W A
S
-X 8.
O
LD
N U
M B
E R
W A
S
-X 9.
ELEVATOR P-1
OLD NU MBER 1X-10.
P A
N E
L
-4 C
E
C
P A
N E
L
-5 C
E
L
P A
N E
L
-5 C
E
C
P A
N E
L
-5 C
E
P A
N E
L
-5 C
P A
N E
L
-5 C
P A
N E
L
-5 C
E
L
P A
N E
L
-4 B
P A
N E
L
-5 C
E
C
TRANS
1-T17EC
P A
N E
L
-3 A
P
A N
E L
-2
A
P A
N E
L
-3 A
E
P A
N E
L
-2 A
E
P A
N E
L
-1 A
P A
N E
L
-1 A
E
C
P A
N E
L
-1 C
E
C
P A
N E
L
-1 C
E
L
P A
N E
L
-1 C
P A
N E
L
P A
N E
L
-1 B
P A
N E
L
-1 B
E
P A
N E
L
-1 B
P A
N E
L
-2 B
E
C
P A
N E
L
-2 B
P A
N E
L
-3 B
E
C
P A
N E
L
-3 B
P A
N E
L
-2 C
E
C
P A
N E
L
-2 C
T R
A N
S
-T D
P A
N E
L
-2 C
E
L
P A
N E
L
-3 C
P A
N E
L
-3 C
E
L
P A
N E
L
-3 C
E
C
TRANS
X F
E R
-X
X F
E R
T S
-3
X F
E R
T S
-1 T
R A
N S
-T
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
P A
N E
L
-B C
E
T R
A N
S
-T
T R
A N
S
-T
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
E
C
P A
N E
L
-B A
P A
N E
L
-B A
E
C
P A
N E
L
-B A
X F
E R
-X
T R
A N
S
-T
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
P A
N E
L
-B C
E
L
P A
N E
L
-B C
E L
P A
N E
L
-B C
E
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
E C
P A
N E
L
-B C
E C
T R
A N
S
-T
X F
E R
-X
X F
E R
-X
P A
N E
L
-B C
E
T R
A N
S
-T
P A
N E
L
-B C
T R
A N
S
-T
T R
A N
S
-T
T R
A N
S
-T
X F
E R
-X
P
A N
E L
-B
C
E
P A
N E
L
-B C
P A
N E
L
-B C
F P
P A
N E
L
-1 C
E
L (A
P A
N E
L D
C
P A
N E
L
"I D
F
P A
N E
L
5 5 5 5 5
A
C
B
5 5
P A
N E
L
-3 C
E
L A
P A
N E
L
-5 C
S E
C
P A
N E
L
-4 C
S E
C
FIRST FLOOR
P A
N E
L
-D P
A
A
A
SHEET LEGEND
GRAY/HALF-TONE LINES AND TEXT INDICATE
EXISTING TO REMAIN
DIAGIONAL-UP HATCH INDICATE EXISTING TO BE
REMOVED. REFER TO SHEET ED-401 AND E-401 FOR
ADDITIONAL INFORMATION
SHEET KEY NOTES#
1. REMOVE EXISTING FEEDER FROM BUILDING 4 SWITCHBOARD.
DISCONNECT FROM EXISTING SWITCHBOARD CIRCUIT BREAKER.
LABEL CIRCUIT BREAKER AS “SPARE”. REMOVE EXISTING CONDUIT
AND WIRE FROM BUILDING 4 SWITCHBOARD TO PANEL IN BUILDING 1.
2. REMOVE EXISTING FEEDER SERVING EQUIPMENT IN BUILDING 7.
REMOVE CONDUCTORS IN THEIR ENTIRETY. REMOVE ACCESSIBLE
RACEWAYS IN BUILDINGS 1 AND 7. INACCESSIBLE AND
UNDERGROUND CONDUITS SHALL BE ABANDONED IN PLACE.
3. REMOVE EXISTING AUTOMATIC TRANSFER SWITCH. EXISTING
FEEDER AND LOAD CIRCUITS SHALL REMAIN. EXISTING CONTROL
CONDUCTORS SHALL REMAIN.
4. REMOVE EXISTING TRANSFORMER. EXISTING INCOMING FEEDER AND
LOAD CIRCUITS SHALL REMAIN. EXISTING HOUSEKEEPING PAD SHALL
REMAIN.
5. REMOVE EXISTING PANEL. EXISTING FEEDER AND LOAD CIRCUITS
SHALL REMAIN.
6. REMOVE EXISTING PANEL. EXISTING BRANCH CIRCUITS SHALL
REMAIN. REMOVE EXISTING INCOMING FEEDER CONDUCTORS BACK
TO SOURCE.
7. REMOVE EXISTING FEEDER. REMOVE ALL CONDUCTORS FROM
CONDUIT. RACEWAYS MAY REMAIN IF SERVICEABLE FOR NEW
FEEDER CIRCUIT.
8. REMOVE DISCONNECT SWITCH. EXISTING FEEDER AND LOAD
CIRCUIT SHALL REMAIN.
9. REMOVE UPS FEEDER TO BUILDING 7. REMOVE CONDUCTORS IN
THEIR ENTIRETY. REMOVE ACCESSIBLE RACEWAYS IN BUILDINGS 1
AND 7. INACCESSIBLE AND UNDERGROUND CONDUITS SHALL BE
ABANDONED IN PLACE.
10. REMOVE GENERATOR CIRCUIT TO BUILDING 7 ELEV & A/C. REMOVE
CONDUCTORS IN THEIR ENTIRETY. REMOVE ACCESSIBLE RACEWAYS
IN BUILDINGS 1 AND 7. INACCESSIBLE AND UNDERGROUND
CONDUITS SHALL BE ABANDONED IN PLACE.
11. EXISTING PANEL AND BRANCH CIRCUITS SHALL REMAIN.
DISCONNECT AND REMOVE EXISTING FEEDER.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ELECTRICAL DEMOLITION - RISER
DIAGRAM
ED-401
-2
-1
E
D -4
J U
L Y
.p d f
NTS
ELECTRICAL DEMOLITION RISER DIAGRAM BUILDING NO. 1
A ADDENDUM A 03/29/2023
MAIN MAINTIE
NEW BUILDING 1
PRIMARY
ELECTRICAL
SERVICE
RE: 1/E-402
NEW EXTERIOR
SWITCHBOARD
1600A, 480V,3PH, 4W
600A, 480V, 3Φ, 4W PNL
"1-BC1"
225A, 480V, 3Φ, 4W PNL
"1-4B1"
400A, 208V, 3Φ, 4W PNL
"1-BC3"
75KVA
480-208V
XFMR
30KVA
480-208V
XFMR
75KVA
480-208V
XFMR
225A, 480V, 3Φ, 4W
PANEL
"1-C13EC"
175A 208V 3Φ, 4W
PANEL
"1-BC12EC"
400A 208V 3Φ, 4W
PANEL
"1-BC16E"
100A 208V 3Φ, 4W
PANEL
"1-BC18E"
225A 208V 3Φ, 4W
PANEL
"1-BC14EL"
225A, 208V, 1Φ, 4W
PANEL
"1-BC10"
225A, 208V, 1Φ 4W
PNL
"1-1C2"
2 SETS: (4) #350KCMIL,
(1) #1GND, IN 3"
CONDUIT
112.5KVA
480-208V
XFMR
225A, 208V, 1Φ, 4W PNL
"1-1B2"
100A, 208V, 1Φ, 4W PNL
"1-2B1EC"
100A, 208V, 1Φ, 4W PNL
"1-3B1EC"
100A, 208V, 3Φ, 4W PNL
"1-3C3EC"
225A, 208V, 3Φ, 4W PNL
"1-3C2"
100A, 208V, 3Φ, 4W PNL
"1-3A1E"
225A, 208V, 3Φ, 4W
PANEL
"1-5C2"
100A, 208V, 3Φ, 4W PNL
"1-2A1E"
400A, 208V, 1Φ, 4W
PANEL
"1-BC5"
(4) #2, (1) #6GND, IN
1-1/4" CONDUIT
(4) #4/0, (1) #4GND, IN
2-1/2" CONDUIT
(4) #4/0, (1) #4GND, IN
2" CONDUIT
(4)#2, (1)#6GND, IN
1-1/4 INCH CONDUIT
(4)#1/0, (1)#6GND, IN
EXISTING CONDUIT
(3)#1/0, (1)#6GND, IN
EXISTING CONDUIT
(4)#2, (1)#6GND, IN
2" CONDUIT
(4)#2, (1)#6GND, IN
2" CONDUIT
U P
S
225A, 240V, 3Φ, 4W PNL
"3LCB"
100A, 208V, 1Φ, 4W PNL
"11C2"
600A, 208V, 3Φ, 4W
PANEL
"1-BC2"
U P
S "3
L C
B
P A
N E
L C
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
EMERGENCY GENERATORS IN BUILDING 20
C B
S S
C B
A T
S
SSS
SS
M T
R
DTS BLDG 4
4-B13EC
4-B11EL
FIFTH FLOOR
(O R
IG
IN
A L
P A
N E
L
C
E
C
CB
CB
EMERGENCY
SWITCHBOARD
20-EMSB
GENERATOR
CONTROL
SWITCHBOARD
180KW/225KVA
DIESEL EMERGENCY
GENERATOR
(STANDBY TO 750KW)
750KW/938KVA
DIESEL EMERGENCY
GENERATOR
C
E
C
MAIN
TS-3 TS-1
MAIN
MAIN
1BC6E
THIS C OULD BE DELETED AT A LATER DATE BY R ERO UTING THRU JBOX.
THIS C OULD BE DELETED AT A LATER DATE BY R ERO UTING THRU JBOX.
OLD N UMBER 1 OF 2 1-X2 NUMBERS
OLD NU MBER 1X-4 THERE WERE 2 1X-4'S
MAIN
1BC7E
4B10E
4-11
O
LD
N U
M B
E R
W A
S
-X 6.
O
LD
N U
M B
E R
W A
S
-X 8.
O
LD
N U
M B
E R
W A
S
-X 9.
ELEVATOR P-1
OLD NU MBER 1X-10.
P A
N E
L
-4 C
E
C
P A
N E
L
-5 C
E
L
P A
N E
L
-5 C
E
C
P A
N E
L
-5 C
E
P A
N E
L
-5 C
P A
N E
L
-5 C
P A
N E
L
-5 C
E
L
P A
N E
L
-4 B
P A
N E
L
-5 C
E
C
TRANS
1-T17EC
P A
N E
L
-3 A
P
A N
E L
-2
A
P A
N E
L
-3 A
E
P A
N E
L
-2 A
E
P A
N E
L
-1 A
P A
N E
L
-1 A
E
C
P A
N E
L
-1 C
E
C
P A
N E
L
-1 C
E
L
P A
N E
L
-1 C
P A
N E
L
P A
N E
L
-1 B
P A
N E
L
-1 B
E
P A
N E
L
-1 B
P A
N E
L
-2 B
E
C
P A
N E
L
-2 B
P A
N E
L
-3 B
E
C
P A
N E
L
-3 B
P A
N E
L
-2 C
E
C
P A
N E
L
-2 C
T R
A N
S
-T D
P A
N E
L
-2 C
E
L
P A
N E
L
-3 C
P A
N E
L
-3 C
E
L
P A
N E
L
-3 C
E
C
TRANS
X F
E R
-X
X F
E R
T S
-3
X F
E R
T S
-1 T
R A
N S
-T
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
P A
N E
L
-B C
E
T R
A N
S
-T
T R
A N
S
-T
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
P A
N E
L
-B A
E
C
P A
N E
L
-B A
P A
N E
L
-B A
E
C
P A
N E
L
-B A
X F
E R
-X
T R
A N
S
-T
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
P A
N E
L
-B C
E
L
P A
N E
L
-B C
E L
P A
N E
L
-B C
E
T R
A N
S
-T
P A
N E
L
-B C
E
P A
N E
L
-B C
E C
P A
N E
L
-B C
E C
T R
A N
S
-T
X F
E R
-X
X F
E R
-X
P A
N E
L
-B C
E
T R
A N
S
-T
P A
N E
L
-B C
T R
A N
S
-T
T R
A N
S
-T
T R
A N
S
-T
X F
E R
-X
P
A N
E L
-B
C
E
P A
N E
L
-B C
P A
N E
L
-B C
F P
P A
N E
L
-1 C
E
L A
P A
N E
L D
C
P A
N E
L
"I D
F
P A
N E
L
P A
N E
L
-3 C
E
L (A
P A
N E
L
-5 C
S E
C
P A
N E
L
-4 C
S E
C
FIRST FLOOR
(4) #4/0, (1) #4GND, IN
2-1/2" CONDUIT
(3) #2, (1) #6GND, IN
1-1/4" CONDUIT
(3) #2/0, (1) #6 GND, IN
2" CONDUIT
(4) 500KCMIL,
(1) #1/0 GND,
IN 4" CONDUIT
(4) 500KCMIL,
(1) #1/0 GND,
IN 4" CONDUIT
(4) #4/0, (1) #4 GND, IN
2-1/2" CONDUIT
P A
N E
L
-D P
A
(4) #4/0, (1) #4 GND, IN
2-1/2" CONDUIT
4 3
2 SETS:
(4) #350KCMIL
(1) #1GND,
IN 3" CONDUIT
3 3 3 3 3
(4) #4/0,
(1) #4GND,
IN 2-1/2"
CONDUIT
(4) #2, (1) #8 GND, IN
1-1/4" CONDUIT
(4)#2, (1)#6GND, IN
2" CONDUIT
(4) #4/0, (1) #4 GND, IN
4" CONDUIT TO
BUILDING 7
112.5KVA
480-208V
XFMR
A
50A/3P/CB
NEMA 1 8 A
A
(4) #4/0, (1) #4GND,
IN 2-1/2" CONDUIT
A
A
(4) #4/0, (1) #4 GND, IN
2-1/2" CONDUIT
100A, 208V, 3Φ, 4W PNL
"1-1A1EC"
A
(4) #1, (1) #8 GND, IN
1-1/2" CONDUIT
SHEET LEGEND
GRAY/HALF-TONE LINES AND TEXT INDICATE
EXISTING TO REMAIN
BLACK LINES INDICATES NEW
SHEET KEY NOTES#
1. PROVIDE NEW AUTOMATIC TRANSFER SWITCH. CONNECT TO
EXISTING FEEDER AND LOAD CIRCUITS. CONNECT EXISTING
CONTROL CONDUCTORS.
2. PROVIDE NEW TRANSFORMER. REFER TO TRANSFORMER
SCHEDULE. CONNECT TO EXISTING INCOMING FEEDER AND LOAD
CIRCUITS. MODIFY EXISTING HOUSEKEEPING PAD AS NEEDED TO
ACCOMMODATE NEW TRANSFORMER.
3. PROVIDE NEW PANEL. REFER TO PANEL SCHEDULE FOR ADDITIONAL
INFORMATION. CONNECT EXISTING FEEDER AND LOAD CIRCUITS.
4. PROVIDE NEW PANEL REFER TO PANEL SCHEDULE FOR ADDITIONAL
INFORMATION. CONNECT EXISTING BRANCH CIRCUITS SHALL
REMAIN. PROVIDE NEW FEEDER AS INDICATED. EXISTING RACEWAYS
MAY BE REUSED IF SERVICEABLE FOR NEW FEEDER CIRCUIT.
5. PROVIDE NEW DISCONNECT SWITCH. CONNECT EXISTING FEEDER
AND LOAD CIRCUIT.
6. PROVIDE NEW 225A, 3 POLE CIRCUIT BREAKER IN EMERGENCY
SWITCHBOARD IN BUILDING 20 AND EXTEND FEEDER TO NEW
AUTOMATIC TRANSFER SWITCH IN BUILDING 7. REFER TO SITE PLAN,
E-011 FOR ROUTING OF FEEDER. REFER TO E-202 FOR ADDITIONAL
INFORMATION AT BUILDING 7.
7. CONNECT NEW FEEDER TO EXISTING PANEL.
8. PROVIDE NEW ENCLOSED CIRCUIT BREAKER COORDINATE AIC
RATING WITH EXISTING DEVICES.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
ELECTRICAL RISER DIAGRAM
E-401
-2
-1
E -4
J
U L Y
.p d f
NTS
ELECTRICAL RISER DIAGRAM BUILDING NO. 1
A ADDENDUM A 03/29/2023
A
TRANSFORMER SCHEDULE
NAME EXISTING NEW TYPE
T1-1 N/A 13.2KV-480/277V, 3Φ, 750KVA PAD MOUNT
T1-2 N/A 13.2KV-480/277V, 3Φ, 750KVA
T-7 13.2KV-240/120V,1Φ, 50KVA 13.2KV-480/277V, 3Φ
8-1 480V-208/120V, 3Φ, 150KVA 13.2KV-208/120V, 3Φ, 150KVA
1-T5 480V-240/120V, 3Φ, 75KVA 480V-208/120V, 3Φ, 112.5KVA DRY TYPE
1-T7 480V-240/120V, 3Φ, 100KVA 480V-208/120V, 3Φ, 112.5KVA
1-T9 480V-240V, 3Φ, 3W 150KVA 480V-208/120V, 3Φ, 150KVA
1-T11 480V-208/120V, 3Φ, 75KVA 480V-208/120V, 3Φ, 75KVA
1-T12 480V-208/120V, 3Φ, 112.5KVA 480V-208/120V, 3Φ, 112.5KVA
1-T13 480V-208/120V, 3Φ, 50KVA 480V-208/120V, 3Φ, 75KVA
PAD MOUNT
PAD MOUNT
PAD MOUNT
DRY TYPE
DRY TYPE
DRY TYPE
DRY TYPE
DRY TYPE
A
AUTOMATIC TRANSFER SWITCH SCHEDULE
NAME SIZE POLES FEEDS
1X-1 225A 3P XFRMS 1-T1 (75KVA) AND 1-T9 (75KVA)
1X-2 150A 3P
1X-4 150A 3P
XFMR 1-T12 (112.5KVA) & 7B-1
1BC-13EC
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
MEP ENGINEER:
HUITT-ZOLLARS, INC.
500 W. 7th St. Ste. 300 Fort Worth, Texas 76102 817-335-3000 POC: Joel Colwell jcolwell@Huitt-Zollars.com
ARCHITECT:
CB DESIGN GROUP
421 KING STREET
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
POC: PAUL W. BRIDGES
PROFESSIONAL SEAL:
6010 Amarillo Blvd.
Amarillo, TX 79106
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
THOMAS E. CREEK VA MEDICAL CENTER
22 DECEMBER 2021
504-21-120
JTJR
PROVIDE PRIMARY FEED
TO BUILDING - 1
100% BID SET SUBMISSION
BUILDING 1 - PANEL SCHEDULES
E-504
-2
-1
E -5
J
U L Y
.p d f
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
59 SPACE -- 1 -- -- 1 -- SPACE 60
57 SPACE -- 1 -- -- 1 -- SPACE 58
55 SPACE -- 1 -- -- 1 -- SPACE 56
53 SPACE -- 1 -- -- 1 -- SPACE 54
51 SPACE -- 1 -- -- 1 -- SPACE 52
49 EX. RANGE - RM 4121 20 A 1 0 0 1 20 A EX. EWC C3-30 50
47 EX. RANGE - RM 4121 20 A 1 0 0 48
45 EX. HEAT TAPE - ATTIC 20 A 1 0 0 46
43 EX. RECEPTACLE - RM 4127, 4129 20 A 1 0 0
3 20 A EX. P1P 1-1/2 HP
41 EX. SPARE 20 A 1 0 0 42
39 EX. RECEPTACLE - RM 4128 20 A 1 0 0 40
37 EX. SPARE 20 A 1 0 0
3 30 A EX. P1P 1-1/2 HP
35 EX. FCU #16 - RM 4136 20 A 1 0 0 36
33 EX. SPARE 20 A 1 0 0 34
31 EX. PBPU RM 4125, 4127, 4127A 20 A 1 0 0
3 50 A EX. P1P 1-1/2 HP
29 EX. EXISTING 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4128 30
27 EX. RECEPTACLE - RM 4125, 4127, 4127A 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4128 28
25 EX. PBPU RM 4119A, 4121, 4123 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4128 26
23 EX. PBPU RM 4119A, 4121, 4123 20 A 1 0 0 1 20 A EX. PBPU - RM 4124, 4126 24
21 EX. PBPU RM 4119A, 4121, 4123 20 A 1 0 0 1 20 A EX. PBPU - RM 4124, 4126 22
19 EX. MOD. FURN. - RM 4129 20 A 1 0 0 1 20 A EX. PBPU - RM 4124, 4126 20
17 EX. SPARE - RM 4125, 4129 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4119, 4121 18
15 EX. MOD. FURN. - RM 4129 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4159, 4163 16
13 EX. LIGHTING - RM 4125, 4127, 4127A, 4129 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4149, 4160, 4163, C3-30 14
11 EX. EXISTING 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4160, 4162, 4164 12
9 EX. LTG - RM 4126,4128,4130,4130A,4134,4136 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4134, C3-28 10
7 EX. LIGHTING - RM 4124, 4126 20 A 1 0 0 1 20 A EX. WATER METER - FLOW SENSOR 8
5 EX. LIGHTING - RM 4163, 4164 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4130, 4134, 4136 6
3 EX. PBPU RM 4159, 4160, 4161, C3-30 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4119 4
1 EX. PBPU RM 4119A, 4121, 4123 20 A 1 0 0 1 20 A EX. RECEPTACLE - RM 4124, 4126 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type:
Location: Volts: 208/120V 3Φ A.I.C. Rating:
New Branch Panel: 1-3C2
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
23 EXISTING 20 A 1 0 -- 1 -- SPACE 24
21 EXISTING 20 A 1 0 0 22
19 EXISTING 20 A 1 0 0 20
17 EXISTING 20 A 1 0 0
3 20 A EXISTING
15 EXISTING 20 A 1 0 0 1 20 A EXISTING 16
13 EXISTING 20 A 1 0 0 1 20 A EXISTING 14
11 EXISTING 20 A 1 0 0 1 20 A EXISTING 12
9 PBPU NIGHT LIGHTS - 4127A,4130,4134,4136 20 A 1 0 0 1 20 A EXISTING 10
7 PBPU NIGHT LIGHTS - 4119,4123-4125,4127 20 A 1 0 0 1 20 A EXISTING 8
5 SPACE -- 1 -- 0 6
3 SPACE -- 1 -- 0 4
1 SPACE -- 1 -- 0
3 100 A MAIN
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type:
Location: Volts: 208/120V 3Φ A.I.C. Rating:
Ex. Branch Panel: 1-3C3EC
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
29 SPACE -- 1 -- -- 1 -- SPACE 30
27 0 -- 1 -- SPACE 28
EX. AC BLOWER 20 A 2
0 -- 1 -- SPACE 26
23 0 -- 1 -- SPACE 24
21 0 -- 1 -- SPACE 22
EX. SPARE 20 A 3
0 -- 1 -- SPACE 20
17 0 0 18
15 0 0 16
EX. SPARE 20 A 3
0 0
3 20 A EX. HEATER
11 0 0 12
9 0 0 10
EX. SPARE 20 A 3
0 0
3 20 A EXISTING
5 0 0 6
3 0 0 4
EX. AC CONDENSOR 20 A 3
0 0
3 20 A EXISTING
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type:
Location: Volts: 208/120V 3Φ A.I.C. Rating:
New Branch Panel: 1-5C2
NEW PANEL EXISTING PANEL
NEW PANEL
A ADDENDUM A 03/29/2023
A
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 SPARE 20 A 1 0 0 1 20 A SPARE 42
39 AIR COMPRESSOR - RM 1158 20 A 1 0 0 1 20 A RECEPTACLE & LIGHTS - RM 1155 40
37 AIR COMPRESSOR - RM 1158 20 A 1 0 0 1 20 A RECEPTACLE & LIGHTS - RM 1155 38
35 EF-2 - RM 1158 20 A 1 0 0 1 20 A FLOOR RECEPTACLE - RM 2133 36
33 EF-1 - RM 1158 20 A 1 0 0 1 20 A LIGHTS - RM 1147 34
31 DUST COLLECTOR 20 A 1 0 0 1 20 A EF-2 - RM 1144 32
29 HELIODENT - RM 1154 20 A 1 0 0 1 20 A RECEPTACLE - RM 1150 30
27 RECEPTACLE - RM 1147 20 A 1 0 0 1 20 A RECEPTACLE - RM 1150 28
25 RECEPTACLE - RM 1130 20 A 1 0 0 1 20 A RECEPTACLE - RM 1158 26
23 NEVIN CASEWORK - RM 1158 20 A 1 0 0 1 20 A NEVIN CASEWORK - RM 1158 24
21 NEVIN CASEWORK - RM 1158 20 A 1 0 0 1 20 A RECEPTACLE - RM 1158 22
19 RECEPTACLE - HALL 20 A 1 0 0 1 20 A RECEPTACLE - RM 1132 20
17 RECEPTACLE - RM 1138, 1136 20 A 1 0 0 1 20 A RECEPTACLE - RM 1156 18
15 RECEPTACLE - RM 1119 20 A 1 0 0 1 20 A RECEPTACLE - RM 1137 16
13 RECEPTACLE - RM 1147, 1145 20 A 1 0 0 1 20 A RECEPTACLE - RM 1139 14
11 RECEPTACLE - RM 1143, 1141 20 A 1 0 0 1 20 A HELIODENT - RM 1145 12
9 NEVIN CASEWORK - RM 1158 20 A 1 0 0 1 20 A HELIODENT - RM 1142 10
7 NEVIN CASEWORK - RM 1158 20 A 1 0 0 1 20 A NEVIN CASEWORK - RM 1158 8
5 RECEPTACLE & LIGHTS - RM 1148 20 A 1 0 0 1 20 A NEVIN CASEWORK - RM 1158 6
3 RECEPTACLE - RM 1142 20 A 1 0 0 1 20 A RECEPTACLE - RM 1140 4
1 RECEPTACLE - RM 1144, 1146 20 A 1 0 0 1 20 A RECEPTACLE - RM 1140 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: Do Not Use
Location: Volts: 208/120V 3Φ A.I.C. Rating: 10KACI
NEW Branch Panel: DC
A
Notes:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A
Total Load: 0 VA 0 VA 0 VA
41 EX SPARE 20 A 1 0 0 1 20 A EX LIGHTING 42
39 EX SPARE 20 A 1 0 0 1 20 A EX LIGHTING 40
37 EX RECEP RM NE WALL 20 A 1 0 0 1 20 A EX LIGHTING 38
35 EX RECEP RM S WALL SINK 20 A 1 0 0 1 20 A EX LIBRARY LIGHTS E END 36
33 EX CONSTRUCTION AREA 20 A 1 0 0 1 20 A EX LIGHT THROUGH LIBRARY 34
31 EX SPARE 20 A 1 0 0 1 20 A EX SPARE 32
29 EX CARDIAC REHAB, RECEP S 30 A 1 0 0 1 20 A EX RECEP W CARD REHAB 30
27 EX CONSTRUCTION AREA 20 A 1 0 0 1 20 A EX RECEP RM 2112B 28
25 EX LTS LIBRARY W END 20 A 1 0 0 1 20 A EX SPARE 26
23 EX RECEP S CARD WALL 20 A 1 0 0 1 20 A EX LIGHTING LIBRARY 24
21 EX RECEP WEST WALL 20 A 1 0 0 1 20 A EX SPARE 22
19 EX RECEP RM 7 WEST 20 A 1 0 0 1 20 A EX LIBRARY OVERHEAD DOOR 20
17 EX RECEP ECARD REHAB 20 A 1 0 0 1 20 A EX LIBRARY DOWNLIGHTS 18
15 EX BATHROOM SHOWER 20 A 1 0 0 1 20 A EX CONSTRUCTION AREA 16
13 EX CONSTRUCTION AREA 30 A 1 0 0 1 20 A EX LIGHTS RM 14
11 EX CONSTRUCTION AREA 20 A 1 0 0 1 20 A EX LTG LIBRARY OFFICE 12
9 EX CONSTRUCTION AREA 20 A 1 0 0 1 20 A EX RECEP LIBRARY 10
7 EX RECEP LIBRARY 20 A 1 0 0 1 20 A EX RECEP LIBRARY 8
5 EX RECEP LIBRARY 20 A 1 0 0 1 20 A EX RECEP RM 2107 6
3 EX SMOKE DAMPER 20 A 1 0 0 1 30 A EX RECEP EM NE WALL 4
1 EX X-RAY CORRIDOR WALL 20 A 1 0 0 1 20 A EX 2114 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: COORDINATE WITH EXISTING Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: Do Not Use
Location: Volts: 208/120V 3Φ A.I.C. Rating: 10KAIC
NEW Branch Panel: 1-1A2 A
NEW PANEL
NEW PANEL
| Sheets |
| E-001 - ELECTRICAL ABBREVIATIONS, LEGEND, AND SYMBOLS |
| E-010 - ELECTRICAL SITE PLAN |
| E-011 - ENLARGED SITE PLAN |
| E-100 - ELECTRICAL PLANS - BUILDINGS 1 & 4 |
| ED-201 - ENLARGED DEMOLITION PLAN - BUILDING 1 |
| E-201 - ENLARGED ELECTRICAL PLAN - BUILDING 1 |
| E-202 - ENLARGED PLANS - BUILDINGS 4 & 7 |
| E-301 - ELECTRICAL DETAILS |
| ED-401 - ELECTRICAL DEMOLITION - RISER DIAGRAM |
| E-401 - ELECTRICAL RISER DIAGRAM |
| E-402 - ELECTRICAL ONE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .