36C25722Q0220_2.docx

DOCX document 17 KB Posted

Attached to
J041--HVAC Service & Monitoring
Solicitation number
36C25722Q0220
Issued by

About this file

This document is an amendment to a previous combined solicitation from the Department of Veterans Affairs seeking offers for HVAC service and monitoring at the El Paso VA Health Care System. The solicitation is set aside for Service Disabled Veteran Owned Small Businesses and seeks a firm-fixed price contract for the base year running from April 18, 2022 to April 17, 2023. Offerors must be verified in the Vendor Information Pages database and registered in SAM.gov. The response due date is extended to April 8, 2022. The amendment provides answers to technical questions from offerors to clarify requirements such as integrating an existing solar system into the building management system, definitions of repair cost thresholds, certification requirements for servicing equipment, and diagnostic services to be included in pricing.

View the file

Other files

File Type Posted
Attachment 1 Wage Determination No 2015-5229 Rev 17.pdf PDF
36C25722Q0220_3.docx DOCX document
36C25722Q0220_Small Business.pdf PDF
36C25722Q0220 0001.pdf PDF
Q_A RFQ 36C25722Q0220.pdf PDF
HVAC Drawings.pdf PDF
Attachment 1 Wage Determination No. 2015-5229 - Rev 16.pdf PDF
36C25722Q0220_1.docx DOCX document
S02 - RFQ - 36C25722Q0220.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
HVAC Service & Monitoring Q&A and Extend RFQ Closing Date to 04-08-2022

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
78240
SOLICITATION NUMBER*
36C25722Q0220
RESPONSE DATE/TIME/ZONE
04-08-2022 15:00 CENTRAL TIME, CHICAGO, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
J041
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department Of Veterans Affairs

Network Contracting Office 17

5441 Babcock Road Ste. 302 San Antonio TX 78240

POINT OF CONTACT*

Contract Specialist Jose Campa Jose.Campa@va.gov

(210) 694-6311

PLACE OF PERFORMANCE

ADDRESS
El Paso VA Health Care System

5001 North Piedras Street

El Paso TX

POSTAL CODE
79930
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS
Jose.Campa@va.gov

EMAIL DESCRIPTION

DESCRIPTION

Solicitation 36C25722Q0220 Closing Date is hereby extended to close on Friday, April 8, 2022, at 3:00 PM/CDT per this Amendment to Previous Combined Solicitation

Q & As 36C25722Q0220 - HVAC Service & Monitoring

1. What do you mean by integration of the solar system into BMS? What do you want done?

The existing solar system is currently a stand alone system. There is an existing contract with a 3rd party company that monitors our Solar production. The intent of this item is for the Controls Contractor to provide integration of the PV system into the KMC EMS in order to keep track of Solar Production (and trends) and other metrics provided by the PV System. This will allow the VA to rescind from the 3rd party contracts to keep track of these metrics.

2. On the pricing schedule of values, what doe “Not to Exceed Threshold for Repairs,” mean?

That’s for repairs to the equipment which are not responsible for under the terms of the contract. Not to Exceed Threshold for Repairs. **The Quantity for Repairs is only an estimate, Contractor will only be paid for work ordered and completed". This will minimize the need for a contract Mod for additional repairs if required during the life of the contract.

3. Do you want the EVAPCO’s level sensors that are not working repaired? Yes, please include this repair.

4. Will there be an initial site inspection to verify the condition of each piece of equipment after award? Yes, the Government will allow 30 Days to provide a report on existing conditions as well as proposal for repairs for those items not covered under contract terms.

5. Task #5: “Daily Runtime Reports”. Does this mean that the VA would like a tech there every day to log the chillers? This Task is under “Monthly”; however, the task mentions “Daily”. Task will be done on a monthly basis only.

6. A KKT chiller is on this list. KKT does not allow anyone to service their machines unless that company is OEM certified. Do you expect the tech to be OEM certified? Yes, an OEM certified technician shall be provided as required by manufacturer.

7. Task#3 “Daily Runtime Reports”. Does this mean that the VA would like a tech there every day to log the chillers? This task is under “Monthly” however the task mentions “Daily”? Task will be done on a monthly basis only.

8. EMS Controls: if an air flow monitoring station is currently not on the network. Do you want us to price for diagnosis or replacement? No. Once the contract is awarded, then a proposal for repair would be requested. However, please note all diagnostic services should be included into the contract cost.

9. If a VAV controller is offline. Do you want pricing to diagnose or replace? No. Once the contract is awarded, then a proposal for repair would be requested. However, please note all diagnostic services should be included into the contract cost.

10. If Chiller #2 is currently offline. Do you want us to price for diagnosis or repair? No, Chiller#2 is currently offline due to an active project to upgrade the Facility’s Critical Power Distribution System and will be brought on-line once finished.

11. If an Operating Room Phoenix valve is offline, do you want pricing to diagnose or repair? No. Once the contract is awarded, then a proposal for repair would be requested. However, please note all diagnostic services should be included into the contract cost.

12. Chiller #1 has a refrigerant leak around the motor terminals. This would require an open and inspect in order to provide a firm price. What do you want us to do to this chiller? Include all diagnostic services into the cost of the contract. Once the contract is awarded, a proposal for repair should be provided to the VA to make the repairs.

13. Do you want “EVERYTHING:” Chilled water plant, AHU’s and Operating Room AHU’s to appear to be operating in non-Manual mode-that is do you want us to verify operation of all of this equipment? Yes, Chilled Water Plant shall operate in Auto Mode. Provide Diagnostics Services into the Cost of the Contract. If any repairs, are needed which require replacing controllers or control devices, then a proposal to perform this work should be provided to the VA after contract award.

See attached document: Q_A RFQ 36C25722Q0220.

See attached document: HVAC Drawings.

*= Required Field
Amendment to a Previous Combined Solicitation

Page 1 of

Amendment to a Previous Combined Solicitation

File details come from the government source that posted it. Updated .