36C25625R0108 Combined Drawings.pdf
PDF 21 MB Posted
- Solicitation number
- 36C25625R0108
About this file
The provided file contains detailed construction drawings for the Fisher House Site Preparation project at the Overton Brooks VA Medical Center in Shreveport, Louisiana. The comprehensive set of 24 engineering and electrical drawings, dated May 8, 2025, covers site grading, utility installation, electrical infrastructure, and site logistics for VA Project #667-23-113.
Key drawing sets include site plans showing demolition and erosion control, construction traffic control, site utility plans, storm drain profiles, electrical site plans, and detailed specifications for infrastructure elements like telecommunications manholes, ground rod installations, and electrical distribution. The drawings specify site preparation involving tree and pavement removal, utility relocation, new electrical service installation including a transformer pad, underground conduit systems, and provisions for future Viking Drive roadway development. Drawings are prepared by Apogee Consulting Group for the U.S. Department of Veterans Affairs, with civil engineering signed off by Louisiana Professional Engineer J. Bryan Butler.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25625R0108 0002.docx | DOCX document | |
| 36C25625R0108 RFI Registrar 667-23-113 081425.pdf | ||
| 36C25625R0108 0001.docx | DOCX document | |
| 36C25625R0108 Sign in Sheet 667-23-113.pdf | ||
| 36C25625R0108 ICRA - Fisher House.pdf | ||
| 36C25625R0108 EXHIBIT F.docx | DOCX document | |
| 36C25625R0108 EXHIBIT B.docx | DOCX document | |
| 36C25625R0108 EXHIBIT A.docx | DOCX document | |
| 36C25625R0108.docx | DOCX document | |
| 36C25625R0108 WD LA20250031 022825.pdf | ||
| 36C25625R0108 SPECIFICATIONS FISHER HOUSE OVERTON BROOKS VAMC 6-26-2025.pdf | ||
| 36C25625R0108 EXHIBIT E.docx | DOCX document | |
| 36C25625R0108 EXHIBIT D.docx | DOCX document | |
| 36C25625R0108 EXHIBIT C.docx | DOCX document | |
| 36C25625R0108 SOW - Fisher House 062325.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SITE MAP PROJECT LOCATION MAP
SHEET INDEX
FISHER HOUSE SITE PREP
OVERTON BROOKS VA MEDICAL CENTER
510 E. STONER AVE.
SHREVEPORT LA. 71101
VA PROJECT #: 667-23-113
G-001
COVER SHEET
OVERTON BROOKS VA MEDICAL CENTER
510 E. STONER AVE.
SHREVEPORT LA. 71101
PROJECT LOCATION
COVER SHEET
DEMOLITION & EROSION CONTROL PLAN
CONSTRUCTION TRAFFIC CONTROL PLAN
SITE GRADING PLAN
STORM DRAIN PROFILE
SITE UTILITY PLAN
SEWER LINE PROFILE
SITE UTILITY PLAN
CATCH BASINS & DRAINAGE DETAILS
HEADWALL SECTIONS AND DETAILS
TELECOMMUNICATION MANHOLE, DUCT BANK, AND DETAILS
WATER UTILITY DETAILS
THRUST BLOCKING DETAILS
SEWER AND GAS UTILITY DETAILS
WOOD FENCE DETAILS
EROSION CONTROL DETAILS
ELECTRICAL GENERAL NOTES,
SYMBOL LEGEND AND ABBREVIATIONS
ELECTRICAL SUB BASEMENT FLOOR PLAN
ELECTRICAL BASEMENT FLOOR PLAN
ELECTRICAL FIRST FLOOR PLAN
ELECTRICAL SITE PLAN
ELECTRICAL SITE PLAN
ELECTRICAL DETAILS
ELECTRICAL AND TELECOMMUNICATIONS RISERS
G-001
C-100
C-101
C-200
C-201
C-300
C-301
C-302
C-400
C-401
C-402
C-403
C-404
C-405
C-406
C-407
E-001
E-101
E-102
E-103
ES101
ES102
E-501
E-601
100% CONSTRUCTION DOCUMENTS
MAY 8, 2025
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
N/A
U.S. Department of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
100% CONSTRUCTION DOCUMENTS
May 8, 2025
S
TA
TE
OF LOUISIANA
PROFESSIONAL ENGINEER
IN
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
05-08-2025
N O
R T
H
40FT 10 00
C-100
SCALE: 1" = 20’
E. STONER AVE.
V E
T E
R A
N S
W
A Y
THE LOCATION OF EXISTING UNDERGROUND
REMOVE EXISTING
TREES & STUMP
REMOVE EXISTING
TREES & STUMP
REMOVE STONE
WALKING PATH
LIMITS OF SITE
PREP FOR GRADING
AND FILL MATERIAL
REMOVE CONC.
WALKING PATH
SILT FENCING
SILT FENCING
DEMOLITION &
EROSION CONTROL PLAN
BLDG. 57
DEMOLITION &
EROSION CONTROL PLAN
CONTRACTOR
LAYDOWN
AREA
REMOVE 80’ OF 12"
STORM DRAIN PIPE
EXISTING FENCE
TO REMAIN
REMOVE EXISTING
TREES & STUMP
SAWCUT, REMOVE &
REPLACE PAVEMENT
FOR EHRM LINE
INSTALLATION
EXISTING PAVED DITCH
TO BE REMOVE
SILT FENCING
BALED HAY (TYP.)
PAVEMENT REMOVAL
ITEMS TO BE DEMOLISHED
OR REMOVED
TREES AND STUMPS
TO BE REMOVED
WORK ZONE
ENTRANCE
LIMITS OF SITE
CONSTRUCTION
CUT & FILL LIMITS
CONSTRUCTION
ENTRANCE
CAUTION:
ALL CONSTRUCTION TRUCK TRAFFIC SHALL BE BETWEEN
PRESENT DURING OPERATIONS.
9 AM AND 4 PM, OR ON WEEKENDS WITH TWO FLAGMEN
ROCK FILTER DAM
UTILITY STATEMENT:
GROUND UTILITIES.
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
CONTRACTOR’S FAILURE TO EXACTLY LOCATE AND
DEMOLTION NOTES:
CONTRACTOR SHALL VERIFY THAT ALL SERVICE CONNECTIONS HAVE
BEEN DISCONNECT FROM MAINS PRIOR TO STARTING DEMOLITION.
(GAS, WATER, SEWER, POWER, TELEPHONE AND ANY MISC. SERVICES).
ONCE THE DEMOLITION OF THE SITE IS COMPLETE, THE CONTRACTOR
SHALL GRADE THE SITE TO CREATE POSITIVE DRAINAGE ACROSS
THE PROPERTY, NO PONDING OR HOLDING OF WATER.
THERE WILL BE NO BURNING ALLOWED ON SITE, ALL DEMOLITION ITEMS
SHALL BE DISPOSED OF IN A LEGAL MANNER.
ANY AND ALL CONSTRUCTION SIGNAGE SHALL REMAIN IN PLACE AND SIGNAGE
CONFLICTING WITH NEW CONSTRUCTION SHALL BE RELOCATED AS NEEDED.
ANY SIGN DAMANGED DURING CONSTRUCTION SHALL BE REPLACED WITH
NEW SIGNS AND MUST MEET THE VA SPECIFICATIONS AT NO COST TO THE OWNER.
ALL DEMOLITION WORK SHALL BE COORDINATED BY THE GENERAL
CONTRACTOR.
ALL WORK PERFORMED SHALL BE DONE IN ACCORDANCE WITH V.A.
STANDARD PRACTICE AND SPECIFICATIONS.
THE CONTRACTOR SHALL COORDINATE ALL NEW WORK WITH OTHER WORK
BEING PERFORMED ON SITE.
1.
2.
3.
4.
5.
6.
7.
REMOVE CONC.
WING WALLS
BACK HEADWALL
(TO REMAIN)
REMOVE CONC.
SIDEWALK FOR
GAS LINE
INSTALLATION
SILT FENCING
REMOVE EXIST.
S.S. M.H. & PLUG
ALL PIPES
FUTURE VIKING
DRIVE ENTRANCE
REMOVE EXISTING
OVERHEAD ELEC.
SERVICE LINE
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
U.S. Department of Veterans Affairs05-08-2025
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
CONTRACTOR SHALL COORDINATE ALL
WORK WITH THE VA HOSPITAL ENGINEERING
OFFICE.
ALL ASPHALT ROADWAYS AND PARKING AREAS
SHALL BE OPEN CUT UNLESS OTHERWISE
NOTED. COORDINATE WITH THE VA
ENGINEERING OFFICE.
ALL CONCRETE SIDEWALKS, ROADWAYS, OR
PARKING LOTS SURFACES THAT ARE OPEN CUT
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
100% CONSTRUCTION DOCUMENTS
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
May 8, 2025
B O
C
.5
B O
C
.2
B O
C
.2
COCO
S
S
S
S
S
S
S S S
S
SS
S
UGFO
UGFO UGFO UGFO
UGFO UGFO UGFO
XXX X
XX X
X X X
XX X X X
X
X
X
X
X
X
X
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
O H
E
O H
E
OHE OHE
OHEOHE OHE UGFO
UGFO
UGFO
S
S
S
OHE
OHE
OHE
O H
E
O H
E
OHE OHE OHE OHE OHE OHE
S
S
S
S
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
S
SS
S S S
S S S
S S
FW
FW
FW
FW FW
FW
FW
W
W
W
W
W
W
W
W W
W W W W W W W W W W W W W W W W W W W
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
S
S
S
S
S
S
S
S
S
S
U G
E
U G
E
U G
E
U G
E
U G
E
CO
FW
FW
FW
FW
FW
FW
G
G
G
G
G
G
G
G
OHE
OHE
OHE
R T
H
60FT 00
C-101
SCALE: 1" = 30’
E. STONER AVE.
V E
T E
R A
N S
W
5:
1 3:
3:1
:1
BLDG. 57
NEW MINOR CONTOUR LINE
NEW MAJOR CONTOUR LINE
NEW CATCH BASIN
NEW STORM DRAIN PIPE
NEW STONE RIPRAP
DIRECTION OF SLOPE
LINE
EXIST. MINOR CONTOUR
LINE
EXIST. MAJOR CONTOUR
LIMITS OF CONSTRUCTION
CONSTRUCTION
ENTRANCE
WORK ZONE
ENTRANCE
T O
S T
O P
BE
PR
EPA
R
ED
TR
U
C K
S E N
TER
IN
G
A N
D E
X
IT
IN
G
TH
E R
O A
D
TO STOP
BE
PREPARED
TRUCKS ENTERING
AND EXITING
THE ROAD
T O
S T
O P
BE
PR
EPA
R
ED
TR
U
C K
S E N
TER
IN
G
A N
D E
X
IT
IN
G
TH
E R
O A
D
CONSTRUCTION TRAFFIC
CONTROL PLAN
T O
S T
O P
B E
P R
E P
A R
E D
T R
U C
K S
E N
T E
R
IN
G
A N
D E
X
IT
IN
G
T H
E R
O A
D
300’ 300’
E A
S
T R
E E
T
V
IK
G
D
R
IV
E
T O
S T
O P
B E
P R
E P
A R
E D
T R
U C
K S
E N
T E
R
IN
G
A N
D E
X
IT
IN
G
T H
E R
O A
D
CONSTRUCTION TRAFFIC
CONTROL PLAN
NOTES:
ALL TRUCKS (OTHER THAN POVS) ENTERING AND EXITING PROJECT
SITE MUST DO SO BETWEEN 9 AM AND 4 PM.
FLAGMEN MUST BE PRESENT TO CONTROL TRAFFIC WHEN TRUCKS ARE
ENTERING AND EXITING PROJECT SITE.
ALL SIGNS SHALL BE BAGGED OR SIGNS REMOVED AFTER HOURS AND DURING
PERIODS OF NO WORK.
FUTURE VIKING
DRIVE ENTRANCE
X X
X
X X
X X
X
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs05-08-2025
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
100% CONSTRUCTION DOCUMENTS
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
May 8, 2025
BOC
2.
BOC
3.
BOC
4.
CO
S
S
S
S
S
S
S S S
S
SS
S
UGFO
UGFO UGFO UGFO
UGFO UGFO UGFO
XXX X
XX X
X X X
XX X X X
X
X
X
X
X
X
X
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
O H
E
O H
E
OHE OHE
OHEOHE OHE UGFO
UGFO
UGFO
S
S
S
X
XX XX
XXX X X X X X X
OHE
OHE
OHE
O H
E
O H
E
OHE
OHE
OHE
OHE
OHE
OHE
OHE OHE
OHE
OHE
OHE
OHE OHE OHE OHE OHE OHE
S
S
S
S
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
S
SS
S S S
S S S
S S
S
FW
FW
FW
FW FW
FW
FW
W W W
W W
W
W W W W W W W W W W W W W W W W W W W W
W
W W
W
W
W
W
W
W
W
W W
W W W W W W W W W W W W W W W W W W W W
UGFO UGFO
UGFO
UGFO UGFO UGFO UGFO
UGFO
UGFO
UGFO
UGFO UGFO
UGFO
UGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGT
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
S
S
S
S
S
S
S
S
S
S
U G
E
U G
E
U G
E
U G
E
U G
E
G G G G G G G G G G G G G G G G G G G G
U G
E
CO
W
U G
E
CO
FW
FW
FW
FW
FW
FW
G
G
G
G
G
G
G
G
G
G
W
R T
H
40FT 10 00
C-200
SCALE: 1" = 20’
E. STONER AVE.
V E
T E
R A
N S
W
A Y
SITE GRADING PLAN
NEW STONE
RIPRAP
24’ STORM DRAIN PIPE
F.L. =174.50
HIGH POINT
ELEV. = 193.00
NEW HEADWALL 5:
1 3:
3:1
:1
BLDG. 57
SITE GRADING PLAN
NEW C.B.
TOP= 191.75
F.L.= 186.75
12" 12"
O
F
S .D
P
IP
E
12" S.D. PIPE
F.L. =182.00
EXIST. C.B.
TOP= 194.78
F.L.= 189.52
THE CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL EXISTING
UTILITIES PRIOR TO PLACEMENT OF ANY UTILITIES OR DRAIN PIPE, TAKE CARE
TO PROTECT UTILITIES THAT ARE TO REMAIN. CONTRACTOR SHALL REPAIR DAMAGE
ACCORDING TO CURRENT LOCAL STANDARDS AND AT THE CONTRACTOR’S EXPENSE.
THE CONTRACTOR SHALL COMPLY WITH ALL LOCAL CODES, OBTAIN ALL
PERMITS, AND PAY ALL FEES PRIOR TO BEGINNING WORK.
PAVEMENT. FIELD ADJUSTMENT OF FINAL GRADES MAY BE NECESSARY.
INSTALL ALL UTILITIES PRIOR TO INSTALLATION OF PAVEMENT.
FACE OF BUILDING, UNLESS OTHERWISE NOTED.
NOTED TO REMAIN, SHALL BE REPLACED WITH LIKE MATERIALS
THE EXPOSED SUBGRADE SHALL BE PROOFROLLED BY THE CONTRACTOR TO
LOCATE AREAS OF SOFT OR WEAK SOILS AND IDENTIFY UNSATISFACTORY
SOIL AT THE SUBGRADE. SUBSTITUTE METHODS FOR DETERMINING SOFT
OR WEAK SOILS SHALL BE SUBMITTED BY CONTRACTOR FOR APPROVAL BY
ENGINEER.
AT CONTRACTOR’S EXPENSE AND TO THE SATISFACTION OF THE OWNER
OF THE ROADWAY.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY
AND ACCEPTABILITY OF THE SUBGRADE AND EMBANKMENTS EVEN AFTER
CONDITIONAL ACCEPTANCE BY THE ENGINEER. CONSTRUCTION ACTIVITIES
WHICH MAY CAUSE SUBSEQUENT SUBGRADE OR EMBANKMENT DAMAGE OR
DEGRADATION SHALL BE AVOIDED. CONTRACTOR SHALL CORRECT DEGRADED
AREAS TO THE ORIGINAL COMPACTION REQUIREMENTS AT NO ADDITIONAL COST
TO THE OWNER. PRIOR TO INSTALLING THE SUBSEQUENT EMBANKMENT LIFTS
OR PAVEMENT WORK. OWNER RESERVES THE RIGHT TO PERFORM ADDITIONAL
TESTING OF IN-PLACE WORK TO ENSURE COMPLIANCE WITH THE SPECIFICATION.
MAINTENANCE: THE CONTRACTOR SHALL PROTECT THE COMPLETED SUBBASE
COURSE FROM DAMAGE FROM THE CONTRACTOR’S OPERATIONS TO PREVENT
CONTAMINATION, SEGREGATION, SOFT SPOTS, WET SPOTS, LAMINATIONS AND
OTHER DEFICIENCIES, AND SHALL SATISFACTORILY MAINTAIN THE COMPLETED
COURSE TO THE LINES AND GRADES SHOWN ON THE PLANS. ANY DAMAGED
COURSE SHALL BE REPAIRED BY THE CONTRACTOR AT NO COST TO
OWNER. IF PATCHING OF THE COURSE IS REQUIRED, IN ADDITION TO REMOVING
DAMAGED OR UNSOUND COURSE, THE CONTRACTOR SHALL REMOVE A SUFFICIENT
WIDTH AND DEPTH OF COURSE TO ENSURE SATISFACTORY PLACEMENT OF
PATCHING MATERIAL.
EXISTING DATA SHOWN IS FROM "RECORD DRAWINGS" OR FIELD SURVEYS.
CONTRACTOR SHALL LOCATE AND VERIFY LOCATION & DEPTH ALL OF BURIED
UTILITIES PRIOR TO EXCAVATION.
ANY SITE WORK PERFORMED PRIOR TO BEGINNING CONSTRUCTION SHALL BE
PROOF ROLLED AND CHECKED FOR PROPER COMPACTION AND SITE PREPARATION
TO MEET THE GEOTECH REPORT.
COORDINATE ALL CONSTRUCTION WITH THE APPROPRIATE UTILITY COMPANY
CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION LAYOUT BASED ON
CONTROL SHOWN ON THE DRAWING. CONTRACTOR IS RESPONSIBLE FOR
PROTECTING EXISTING & ESTABLISHING ADDITIONAL CONTROL AS REQUIRED
AS CONSTRUCTION PROGRESSES.
CONTRACTOR SHALL MAINTAIN ALL EROSION CONTROL DEVICES FOR THE
DURATION OF THE PROJECT. AFTER EACH 0.5" RAINFALL EVENT, THE
CONTRACTOR SHALL INSPECT EXISTING EROSION CONTROL DEVICES FOR
EFFECTIVENESS AND REPLACE AS NECESSARY IMMEDIATELY. THE
CONTRACTOR’S REPORT SHALL BE SUBMITTED TO THE ENGINEER WITHIN
2 DAYS OF EACH RAINFALL EVENT.
THE CONTRACTOR SHALL CLEAR & GRUB ALL AREAS WITHIN THE LIMITS OF
CONSTRUCTION AND WITHIN PROPERTY LIMITS. THE CONTRACTOR
SHALL STRIP, LOAD, REMOVE, HAUL, AND STOCKPILE EXISTING TOPSOIL MATERIAL
FROM THE CLEARED AREAS AT LOCATIONS SHOWN OR AS DIRECTED, ON-SITE.
PROVIDE A SMOOTH TRANSITION BETWEEN EXISTING PAVEMENT AND NEW
DIMENSIONS ARE TO THE BACK OF CURB, EDGE OF CONCRETE, OR TO THE
EXCESS MATERIAL SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND
ALL CONSTRUCTION DAMAGE TO EXISTING PAVEMENT OR OTHER FACILITY
GENERAL NOTES:
VA OR MUNICIPALITY.
ADDITIONAL COST IN A LEGAL MANNER.
SHALL BE DISPOSED OF AWAY FROM THE OWNER’S PROPERTY AT NO
JOB SITE FOR DISTRIBUTION TO THE ARCHITECT UPON COMPLETION.
CONTRACTOR SHALL MAINTAIN ONE SET OF AS-BUILT DRAWINGS ON THE
NEW MINOR CONTOUR LINE
NEW MAJOR CONTOUR LINE
NEW CATCH BASIN
NEW STORM DRAIN PIPE
NEW STONE RIPRAP
DIRECTION OF SLOPE
LINE
EXIST. MINOR CONTOUR
LINE
EXIST. MAJOR CONTOUR
CAUTION:
ALL CONSTRUCTION TRUCK TRAFFIC SHALL BE BETWEEN
PRESENT DURING OPERATIONS.
9 AM AND 4 PM, OR ON WEEKENDS WITH TWO FLAGMEN
C-400
C-400
C-400
C-401
TRANSFORMER
PAD
C-402
LIMITS OF CONSTRUCTION
LIMITS OF CONSTRUCTION
C-400
NEW C.B.
TOP= 181.30|
F.L.= 173.50|
UTILITY STATEMENT:
GROUND UTILITIES.
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
THE LOCATION OF EXISTING UNDERGROUND
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
CONTRACTOR’S FAILURE TO EXACTLY LOCATE AND
8.
9.
10.
11.
12.
13.
14.
15.
16. PRIOR TO AND AT THE END OF CONSTRUCTION THE CONTRACTOR SHALL
HYDRO SEED ALL THE AREA DISTURBED BY AND WITHIN THE LIMITS OF
THE PROJECT, INCLUDING THE CONTRACTOR LAYDOWN YARD.
24’ STORM DRAIN PIPE
F.L. =178.60|
(FIELD VERIFY)
NEW C.B.
TOP= 191.00
F.L.= 178.47
C-400
NEW C.B.
TOP= 191.00
F.L.= 175.61
193.0
193.0
193.5
193.0
193.0
193.0
191.0
191.0
191.0
’ O
F
S
.D . P
IP
E
.7
’ O
F
" S
.D . P
IP
E
1.7%
C-406
16’ OF 24" S.D. PIPE
@ 0.8%
20.0’
.0
7’ HIGH WOOD
PRIVACY FENCE
W/ GATE
BLOCK RETAINING
WALLC-406
NEW ELECTRIC
MANHOLE
X X
X
X X
X X
X
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs05-08-2025
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
100% CONSTRUCTION DOCUMENTS
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
May 8, 2025
B O
C
.5
B O
C
.2
B O
C
.2
CO
S
S
S
S
S
S
S S S
S
SS
S
UGFO
UGFO UGFO UGFO
UGFO UGFO UGFO
XXX X
XX X
X X X
XX X X X
X
X
X
X
X
X
X
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
O H
E
O H
E
OHE OHE
OHEOHE OHE UGFO
UGFO
UGFO
X
XX XX
XXX X X X X X X
OHE
OHE
OHE
O H
E
O H
E
OHE
OHE
OHE
OHE
OHE
OHE
OHE OHE
OHE
OHE
OHE
OHE OHE OHE OHE OHE OHE
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
S
SS
S S S
S
FW
FW
FW
FW FW
FW
FW
W W
W
W W W W W W W W W W W W W W W W W W W
W
W
W W
W W W W W W W W W W W W W W
UGFO UGFO
UGFO
UGFO UGFO UGFO UGFO
UGFO
UGFO
UGFO
UGFO UGFO
UGFO
UGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGT
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
S
S
S
S
S
U G
E
U G
E
U G
E
U G
E
U G
E
G G G G G G G G G G G G G G G G G G G G
U G
E
CO
U G
E
CO
FW
FW
FW
FW
FW
FW
G
G
G
C-201
6005004003001000
EXISTING CONC.
ARCH PIPE W/
PAVED CHANNEL
‘ EXISTING DITCH
EXISTING CONC.
HEADWALL W/
WINGWALLS
NEW MINOR CONTOUR LINE
NEW MAJOR CONTOUR LINE
NEW CATCH BASIN
NEW STORM DRAIN PIPE
NEW STONE RIPRAP
DIRECTION OF SLOPE
N E
W C
.B
T O
P
.0
F .L
.6
HIGH POINT
ELEV. = 193.00
EXISTING 24" RCP
F.L. IN = 174.03
NEW STONE
RIPRAP
V E
T E
R A
N S
W A
Y
NEW C.B.
TOP= 191.00
F.L.= 175.61
STORM DRAIN PROFILE
168168
NEW 24" RCP
F.L. IN = 174.50
EXISTING 24" RCP
24’ STORM DRAIN PIPE
F.L. =178.50
3:1
LINE
EXIST. MINOR CONTOUR
LINE
EXIST. MAJOR CONTOUR
NEW HEADWALL
37’ OF 12"
S.D. PIPE
NEW C.B.
TOP= 191.75
F.L.= 186.75
37’ OF 12"
S.D. PIPE
12" S.D. PIPE
F.L. =182.00|
C-400
C-400
NEW STONE
RIPRAP
C-400
24’ STORM DRAIN PIPE
F.L. =174.50
C-401
C-400
C-400
EXISTING CONC.
ARCH PIPE W/
PAVED CHANNEL
EXISTING CONC.
HEADWALL W/
WINGWALLS
N E
W C
.B
T O
P
.7
F
.L
.7
37’ OF 12"
S.D. PIPE
C-400
NEW HEADWALL
3:1 3:1
NEW C.B.
TOP= 181.30|
F.L.= 173.50|
C-400
NEW C.B.
TOP= 181.30|
F.L.= 173.50|
C-400
40FT 10 00 2020
2 00 44
VERT. SCALE: 1" = 4’
8FT
HORIZ. SCALE: 1" = 20’
STORM DRAIN PROFILE
THE LOCATION OF EXISTING UNDERGROUND
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
C-401
24’ STORM DRAIN PIPE
F.L. =178.60|
(FIELD VERIFY)
NEW C.B.
TOP= 191.00
F.L.= 178.47
N E
W C
.B
T O
P
.0
F
.L
.4
C-400
5:1
N E
W C
.B
T O
P
.5
F
.L
.4
5:1
C-400
C-401
NEW HEADWALL
168’ OF 24" S.D. PIPE
@ 1.7%
65’ OF 24" S.D. PIPE
@ 1.7%
16’ OF 24" S.D. PIPE
@ 0.8%
168’ OF 24" S.D. PIPE @1.7%
65’ OF 24" S.D. PIPE@ 1.7%
16’ OF 24" S.D. PIPE
@ 0.8%
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
100% CONSTRUCTION DOCUMENTS
May 8, 2025
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
05-08-2025
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
B O
C
.2
B O
C
.2
S
S
S
S
S
S
S
S
S
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X X
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
U G
FO
U G
FO
U G
FO
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
O H
E
UGFO
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
S
S
S
FW
FW
W
W
W
W
W
W
W
W
W
W
W
W
U G
F O
U G
F O
U G
F O
UGE
FW
R T
H
40FT 10 00
C-300
SCALE: 1" = 20’
E. STONER AVE.
V E
T E
R A
N S
W
NEW TRANSFORMER
NEW UNDERGROUND
ELECTRIC SERVICE
LINE
SITE UTILITY PLAN
BLDG. 57
SITE UTILITY PLAN
TIE INTO
EXISTING EHRM
MANHOLE
(3) 4" CONDUITS
IN A CONC. DUCT BANK
6" TAPPING SLEEVE,
VALVE & BOX
NEW 6" CLEANOUT
W/ TEMPORARY CAPS
DEPTHS OF EXISTING GAS & WATER LINES ARE UNKNOWN. CONTRACTOR SHALL
UNCOVER AND VERIFY DEPTH OF ALL EXISTING UTILITIES AND OTHER POTENTIAL
UNDERGROUND CONFLICTS PRIOR TO PLACING ANY UTILITIES. IF A CONFLICT
EXIST, THE ENGINEER SHALL BE NOTIFIED TO DETERMINE AN ALTERNATIVE SOLUTION
PRIOR TO ANY WORK BEING DONE.
CONTRACTOR SHALL FIELD ADJUST ANY NEW UTILITY LINE WORK AS REQ’D. IN
THE FIELD WITH APPROVALS BY ENGINEER.
INSTALLING SERVICE LINES AND METER SETUPS PRIOR TO CONSTRUCTION.
UTILITY NOTES:
TOPS OF ALL UTILITY BOXES SHALL ADJUST AS REQ’D. AND BE FINISHED FLUSH
WITH FINAL GRADES OR CONCRETE SURFACE ELEVATIONS.
WATER METER ASSEMBLIES - CONTRACTOR SHALL CONTACT THE VA
OR LOCAL UTILITY COMPANY PRIOR TO CONSTRUCTION FOR PROCEDURES OF
CO
W
G
TDB
NEW 8" SEWER SERV.
TIE INTO EXIST.
SEWER MANHOLE
INV.=180.94
EXIST. S.S. M.H.
TOP =192.46
INV.=180.94
BOTTOM OF
DUCT BANK
ELEV.=192.5
BOTTOM OF
DUCT BANK
ELEV.=210.00 (MIN.)
100’ OF 6" SEWER
SERVICE LINE @
1.0 % MIN.
NEW S.S. M.H.
TOP =188.25|
INV.=182.50
400’ OF 8" SEWER LINE @ 0.4%
CONCRETE ENCASE
400 L.F. OF 8" PVC
SEWER LINE
CONNECT TO EXIST.
GAS LINE (HOT TAP)
CONNECT TO EXIST.
WATER LINE W/
2" SERVICE SADDLE
& 2" CORP STOP
(HOT TAP)
CAUTION:
ALL CONSTRUCTION TRUCK TRAFFIC SHALL BE BETWEEN
PRESENT DURING OPERATIONS.
9 AM AND 4 PM, OR ON WEEKENDS WITH TWO FLAGMEN
FUTURE VIKING
DRIVE ENTRANCE
C-402
C-405
C-405
NEW 6" CLEANOUT
W/ TEMPORARY CAPSC-405
C-405
C-405
C-403
C-403
C-402
C-402
FUTURE RETAINING WALLS
VIKING ROAD PROJECT
FUTURE CENTERLINE
VIKING ROAD PROJECT
C-405
C-405
C-405
C-405
C-403
C-403
62" VALVE, BOX
& PAD (WATER)
6" VALVE, BOX
& PAD (FIRE
WATER)
2" VALVE, BOX
& PAD (GAS)
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
THE LOCATION OF EXISTING UNDERGROUND
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
SEWER LINE INSTALLATION NOTES:
THE CONTRACTOR SHALL COORDINATE THE TIE-IN TO THE EXISTING SYSTEM
WITH THE VA.
THE CONTRACTOR SHALL MAKE THE TIE-IN TO THE EXISTING SEWER
MANHOLE AT THE TIME OF LOW FLOW, WHICH IS USUALLY AT NIGHT
PRIOR TO NORMAL OPERATIONS RESUMING AT 7 AM.
CONTRACTOR SHALL BRAKE INTO THE EXISTING MANHOLE INSERT A JOINT
OF NEW SEWER PIPE, GROUT, AND PLUG THE NEW LINE. THE PLUG WILL
REMIAN IN PLACE AND WILL BE REMOVED FOLLOWING THE TESTING AND
ACCEPTANCE OF THE NEW SEWER LINE.
IN THE EVENT THAT THE EXISTING SEWER FLOW IS GREATER THAN CAN
EXPECTED. THE CONTRACTOR PLUG THE UPSTREAM MANHOLE AND
BYPASS PUMP SEWER TO EXISTING SEWER MANHOLE JUST SOUTH OF
MANHOLE THAT THE TIE-IN IS MADE TO. IF THIS IS REQ’D THEN COORDINATE
WITH THE CITY OF SHREVEPORT.
NEW C.B.
TOP= 181.30|
F.L.= 173.50|
C-400
C-403
C-403
C-405
FIRE HYDRANT
ASSEMBLYC-403
UGFO
FIRE WATER LINE
DOMESTIC WATER LINE
SEWER SERVICE LINE
SEWER CLEANOUT
SEWER MANHOLE
GAS LINE
TELECOM. DUCT BANK
UNDERGROUND FIBER
OPTIC LINE
LP
LP
CONTRACTOR SHALL LOCATE AND AVOID
UNDERGROUND ELECTRIC LINES TO LIGHT
POLES, AS WELL AS WATER, & GAS LINES
C-406
NEW COMM.
MANHOLE
TEMPORARY CAP
NEW UTILITY LINES
(TYP.)
NEW 6" C900 FIRE
WATER LINE
NEW 2" PE GAS
SERVICE LINE
NEW 2" PE WATER
SERVICE LINE
NOTE:
CONTRACTOR MAY USE FUSIBLE
C905 PIPE IN LIEU OF STANDARD
C900 AND FITTINGS
6" M.J. 45^ FITTINGS
W/ R.J. ADAPTERS
& THRUST BLOCKING
C-403
20.0’
.0
’ 7’ HIGH WOOD
PRIVACY FENCE
W/ GATE
BLOCK RETAINING
WALL
C-406
NEW ELEC.
SERVICE POLE
CONNECT TO
EXISTING UG ELEC.
SERVICE LINE
NEW ELECTRIC
MANHOLE
NEW UNDERGROUND
ELECTRIC SERVICE
LINE
NEW UNDERGROUND
ELECTRIC SERVICE
LINE
FW
FW
W
W
G
G
T D
B
T D
B
T D
B
T D
B
TDB
G
G
G
CO
S
S S S S S S S S S S S S S S S S S S
T D
B
CO
TDB
F W
FW
FW
FW
FW
W
W
W
W
W
G
G
G
G
G
X X
X
X X
X X
X
U G
E
U G
E
U G
E
U G
E
UGE
UGE
UGE
UGE
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs05-08-2025
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
100% CONSTRUCTION DOCUMENTS
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
May 8, 2025
B O
C
.5
B O
C
.2
B O
C
.2
CO
S
S
S
S
S
S
S S S
S
SS
S
UGFO
UGFO UGFO UGFO
UGFO UGFO UGFO
XXX X
XX X
X X X
XX X X X
X
X
X
X
X
X
X
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
O H
E
O H
E
OHE OHE
OHEOHE OHE UGFO
UGFO
UGFO
S
S
S
OHE
OHE
O H
E
O H
E
OHE
OHE
OHE
OHE
OHE
OHE OHE
OHE OHE OHE OHE OHE OHE
S
S
S
S
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
U G
FO
U G
FO
U G
FO
S
SS
S S S
S S S
S S
FW
FW
FW
FW FW
FW
FW
W W W W W W W W W W W W W W W W W W
W
W
W
W
W
W W
W W W W W W W W W W W W W W W W W W W W
UGFO
UGFO
UGFO UGFO UGFO UGFO
UGFO
UGFO
UGFO
UGFO UGFO
U G
F O
U G
F O
U G
F O
U G
F O
U G
FO
U G
FO
S
S
S
S
S
S
S
S
S
S
U G
E
U G
E
U G
E
U G
E
U G
E
G G G G G G G G G
U G
E
CO
W
U G
E
CO
FW
FW
FW
FW
FW
FW
G
G
G
G
G
G
R T
H
C-301
E. STONER AVE.
V E
T E
R A
NEW TRANSFORMER
NEW UNDERGROUND
ELECTRIC SERVICE
LINE
SEWER LINE PROFILE
SEWER LINE PROFILE
NEW 55 LB.
STONE RIPRAP
NEW 6" CLEANOUT
W/ TEMPORARY CAPS
‘ PROPOSED VIKING DRIVE
EXIST. S.S. M.H.
TOP =192.46
INV.=180.94
E X
I S
T S
.S M
.H
T O
P
.4
IN
V
.9
N.G. ALONG TOP OF SEWER LINE
N.G. ALONG TOP OF SEWER LINE
EXIST. 24" RCP
FILL AREA FOR
PROPOSED SITE PAD
NEW 8" SEWER SERV.
TIE INTO EXIST.
SEWER MANHOLE
INV.=180.94
NEW 8" SEWER SERV.
TIE INTO EXIST.
SEWER MANHOLE
INV.=180.94
NEW S.S. M.H.
TOP =187.00|
INV.=182.50
100’ OF 6" SEWER
SERVICE LINE
100’ OF 6" SEWER
SERVICE LINE @
1.0 % MIN.
N E
W S
.S
M .H
T O
P
.0
IN
V
.5
400’ OF 8" SEWER LINE @ 0.4%
400’ OF 8" SEWER LINE @ 0.4%
M
IN
C O
V E
R
6005004003001000
CONCRETE ENCASE
140 L.F. OF 8" PVC
SEWER LINE
CONCRETE ENCASE
140 L.F. OF 8" PVC
SEWER LINE
FUTURE VIKING
DRIVE ENTRANCE
40FT 10 00 2020
2 00 44
VERT. SCALE: 1" = 4’
8FT
HORIZ. SCALE: 1" = 20’
LIMITS OF CONSTRUCTION
CUT HILL TO
INSTALL SEWER LINE
FUTURE VIKING
DRIVE ENTRANCE
CONSTRUCTION
C-405 C-405
NEW 6" CLEANOUT
W/ TEMPORARY CAPS
C-405
C-405
C-402
C-400
C-405
.6
6 4
C-405
C-405
INSTALL 3’| OF DIRT
COVER OVER SEWER LINE
C-405
C-405
THE LOCATION OF EXISTING UNDERGROUND
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
CONTRACTOR’S FAILURE TO EXACTLY LOCATE AND
UTILITY STATEMENT:
GROUND UTILITIES.
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
NEW C.B.
TOP= 181.30|
F.L.= 173.50|
C-400
C-405
NEW 6" CLEANOUT
W/ TEMPORARY CAPSC-405
FW
S
CO
W
G
TDB
C-406
20.0’
.0
7’ HIGH WOOD
PRIVACY FENCE
W/ GATE
BLOCK RETAINING
WALL
C-406
CONNECT TO
EXISTING UG ELEC.
SERVICE LINE
NEW UNDERGROUND
ELECTRIC SERVICE
LINE
NEW ELEC.
SERVICE POLE
NEW ELECTRIC
MANHOLE
CO
S
S S S S S S S S S S S S S S S S S S
CO
X X
X
X X
X X
X
U G
E
U G
E
U G
E
U G
E
UGE
UGE
UGE
UGE
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
100% CONSTRUCTION DOCUMENTS
May 8, 2025
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
05-08-2025
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
B O
C
.5
B O
C
.2
S S S
S
SS
S
UGFO
UGFO UGFO UGFO
UGFO UGFO UGFO
XXX X
XX X
X X X
XX X X X
X
X
X
X
X
X
U G
E
U G
E
U G
E
O H
E
O H
E
OHE OHE
OHEOHE OHE UGFO
UGFO
UGFO
X
XX X
XXX X X X X X X
OHE
OHE
O H
E
O H
E
OHE
OHE
OHE
OHE
OHE
OHE OHE
OHE
OHE
OHE
OHE OHE OHE OHE OHE OHE
S
S
S
S
U G
F O
U G
F O
U G
F O
S
SS
S S S
S S S
S S
S
W W W W W W W W W W W W W W W W W W
W
W
W
W
W
W
W W
W W W W W W W W W W W W W W W W W W W
UGFO
UGFO
UGFO UGFO UGFO UGFO
UGFO
UGFO
UGFO
UGFO UGFO
UGFO
UGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGTUGT
U G
F O
U G
F O
U G
F
G G G G G G G G G G G G G G G G G G
R T
H
520FT 5 00
C-302
SCALE: 1" = 10’
V E T E R
A N
S W
SITE UTILITY PLAN
BLDG. 57
SITE UTILITY PLAN
TIE INTO
EXISTING EHRM
MANHOLE
(3) 4" CONDUITS
IN A CONC. DUCT BANK
6" TAPPING SLEEVE,
VALVE & BOX
DEPTHS OF EXISTING GAS & WATER LINES ARE UNKNOWN. CONTRACTOR SHALL
UNCOVER AND VERIFY DEPTH OF ALL EXISTING UTILITIES AND OTHER POTENTIAL
UNDERGROUND CONFLICTS PRIOR TO PLACING ANY UTILITIES. IF A CONFLICT
EXIST, THE ENGINEER SHALL BE NOTIFIED TO DETERMINE AN ALTERNATIVE SOLUTION
PRIOR TO ANY WORK BEING DONE.
CONTRACTOR SHALL FIELD ADJUST ANY NEW UTILITY LINE WORK AS REQ’D. IN
THE FIELD WITH APPROVALS BY ENGINEER.
INSTALLING SERVICE LINES AND METER SETUPS PRIOR TO CONSTRUCTION.
UTILITY NOTES:
TOPS OF ALL UTILITY BOXES SHALL ADJUST AS REQ’D. AND BE FINISHED FLUSH
WITH FINAL GRADES OR CONCRETE SURFACE ELEVATIONS.
WATER METER ASSEMBLIES - CONTRACTOR SHALL CONTACT THE VA
OR LOCAL UTILITY COMPANY PRIOR TO CONSTRUCTION FOR PROCEDURES OF
CO
W
G
TDB
CONNECT TO EXIST.
GAS LINE (HOT TAP)
CONNECT TO EXIST.
WATER LINE W/
2" SERVICE SADDLE
& 2" CORP STOP
(HOT TAP)
CAUTION:
ALL CONSTRUCTION TRUCK TRAFFIC SHALL BE BETWEEN
PRESENT DURING OPERATIONS.
9 AM AND 4 PM, OR ON WEEKENDS WITH TWO FLAGMEN
C-403
C-403
C-402
C-405
THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE UNDER-
GROUND UTILITIES SHOWN ARE IN EXACT LOCATION INDICATED
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDER-
IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
GROUND UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES
THE SURVEYOR MAKES NO GUARANTEE THAT THE UNDER-
FROM FIELD SURVEY INFORMATION AND EXISTING DRAWINGS.
THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED
AS ACCURATELY AS POSSIBLE FROM INFORMATION AVAILABLE.
ALTHOUGH THE SURVEYOR DOES CERTIFY THAT THEY ARE LOCATED
THE LOCATION OF EXISTING UNDERGROUND
PROTECT ANY AND ALL UNDERGROUND UTILITIES.
UTILITIES ARE SHOWN AS APPROXIMATE ONLY.
THE CONTRACTOR SHALL DETERMINE THE EXACT
LOCATION OF ALL EXISTING UTILITIES BEFORE
COMMENCING WORK. THE CONTRACTOR AGREES
TO BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES WHICH MAY OCCUR DUE TO THE
CONTRACTOR’S FAILURE TO EXACTLY LOCATE AND
C-403
C-403
C-405
LP
CONTRACTOR SHALL LOCATE AND AVOID
UNDERGROUND ELECTRIC LINES TO LIGHT
POLES, AS WELL AS WATER, & GAS LINES
6" M.J. 45^ FITTINGS
W/ R.J. ADAPTERS
& THRUST BLOCKING
NOTE:
CONTRACTOR MAY USE FUSIBLE
C905 PIPE IN LIEU OF STANDARD
C900 AND FITTINGS
NEW 2" PE WATER
SERVICE LINE
NEW 2" PE GAS
SERVICE LINE
NEW 6" C900 FIRE
WATER LINE
FW
FW
W
W
G
G
T D
B
T D
B
T D
B
T D
B
TDB
G
G
G
TDB
F W
FW
W
W
G
G
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
N/A
LEGEND:
of Veterans Affairs05-08-2025
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
J. BRYAN BUTLER
FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES.
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN ARE APPROX.
THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXIST.
UNDERGROUND UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR WILL BE FULLY
Know what’s before you dig below Call
CALL LOUISIANA ONE CALL - JUST DIAL 811
LOUISIANA STATE LAW, SECTION R.S.40:1749.15, REQUIRES EXCAVATORS
AND DEMOLISHERS TO CALL 1-800-272-3020 OR 504-275-3700, A REGIONAL
NOTIFICATION CENTER BY TELEPHONE 48 HOURS UP TO 120 HOURS IN
ADVANCE OF ANY EXCAVATION OR DEMOLITION ACTIVITY. THE OWNERS/
OPERATORS OF ANY UNDERGROUND FACILITY MUST THEN MARK THE AREA
OR PROVIDE INFORMATION THAT WILL ENABLE AN EXCAVATOR OR
DEMOLISHER TO DETERMINE THE LOCATION OF UNDERGROUND FACILITIES.
CONTRACTOR SHALL COORDINATE ALL
SHALL BE RESTORED TO ORIGINAL CONDITIONS.
100% CONSTRUCTION DOCUMENTS
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT "OCCUR" DUE TO HIS
May 8, 2025
CO
S
S
S
S
S
S
U G
E
U G
FO
U G
FO
U G
FO
U G
FO
FW
FW
FW
FW FW
FW
FW
S
S
S
S
U G
E
U G
E
U G
E
U G
E
U G
E U
G E
CO
W
U G
E
CO
FW
FW
FW
FW
FW
FW
G
G
G
G
G
G
G
G
G
G
C-400
#4 REBAR @ 12" O.C.
EACH WAY
CONCRETE
SEE SPECS.
S.D. PIPE
CONC. WALL
N.T.S.
CONC. WALL
S.D. PIPES.D. PIPE
N.T.S.
MIN. MIN.
#6 BARS @
6" o.c. e.w.
#6 BARS @
6" o.c. e.w.
#4 BARS @
8" o.c. e.w.
OD
1/2 OD
N.T.S.
6" MIN.
SLOPE VARIES W/SOIL
CONDITIONS. REFER TO
OSHA REQUIREMENTS
FOR SLOPE.
FINAL BACKFILL
O.D. +12"
DEPTH
VARIES
HAUNCHING
4"-6" LIFTS
(BEDDING MATERIAL)
(STONE)
2" BEDDING MATERIAL
(STONE)
PIPE TIE DOWN
STRAP, 2 PER
JOINT(MIN.)
SCREW TYPE
ANCHOR
INITIAL BACKFILL
(BEDDING MATERIAL)
(SELECT MATERIAL)
PIPE O.D. +2’-0" MIN.
P I P
E O
.D
M
I N
PIPE O.D. +2’-0" MIN.
FINISH GRADE
(V-5724-1)
(V-5724-1)
BOX WIDTH
VARIES 2’-1 7/8 " VARIES
PIPE O.D.6" 6"
6" THICK
D E
P T
H V
A R
IE
S
N
T R
A F
F
IC
CAST IRON GRATE
& FRAME
OR APPROV. EQUAL
NOTE:
1. TO PREVENT FLOTATION OR DISLOCATION DURING INITIAL BACKFILLING,
CONTRACTOR SHALL SECURE PIPE FROM VERTICAL & HORIZONTAL
MOVEMENT AT 8’ INTERNALS OR TO THE SATISFICATION OF THE
ENGINEER DURING HAUNCHING INITIAL BACKFILL OPERATIONS.
(MIN. 2 STRAPS PER JOINT)
2. SOFT FOUNDATIONS MAY REQUIRE ADDITIONAL BEDDING.
S.D.
PIPE
S.D.
PIPE
S.D.
PIPE
S.D.
PIPE
BOX WIDTH
2’-1 7/8 " VARIESVARIES
6"
V A
R
IE
S
/8
V A
R
IE
S
B O
X W
ID
T
H
CAST IRON GRATE
& FRAME
OR APPROV. EQUAL
NOTE:
1. ALL PIPES IN CATCH BASINS SHALL BE GROUTED
INSIDE AND OUTSIDE WITH NON-SHRINK GROUT.
PATTERN NO.
V-5724-1
A
B
1 7/8
C
10 1/2
D
E
1 1/2
F
25 7/8
G
22 1/4
H
2 5/8
E
D
OR APPROVED EQUAL
B
H
A/SQ.
C
F/SQ
G/SQ
O .D
R .C
.P
INITIAL BACKFILL
PLACE PER
SPECIFICATIONS
NOTE:
OVEREXCAVATION SHALL BE BACKFILLED
WITH CRUSHED STONE
FINAL
BACKFILL
SLOPE VARIES W/ SOIL
CONDITIONS REFER TO
O.S.H.A. REQUIREMENTS
FOR SLOPE
N.T.S.
(M
IN
FILTER FABRIC - MIRAFI 500X
OR APPROVED EQUAL
4" OF #4 FILTER
STONE MIN.
N.T.S.
RIPRAP
(MATCH
EXIST.)
CATCH BASINS &
DRAINAGE DETAILS
18"
18"
SECTION
PLAN VIEW
TRENCH DETAILS FOR R.C.P.
TYPICAL SINGLE PIPE BEDDING AND
CATCH BASIN (CB-01)
TRENCH DETAIL FOR STORM DRAIN PIPE
STORM PIPE (ADS) OR A2000
RIPRAP SECTION
VULCAN V-5700 SERIES
C-400
C-400
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
N/A
U.S. Department of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
100% CONSTRUCTION DOCUMENTS
May 8, 2025
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
C-401
BARS A & A
1 BAR A
BARS B
/2
D
FRONT ELEVATION
HEADWALL SECTIONS
AND DETAILS
1.00’
1.00’
EXISTING CONC.
HEADWALL
NEW 24" STORM
DRAIN PIPE
0.84’
N.T.S.
12"
16’-6"
D
SEE DETAIL ’A’
1.00’
2.84’
5"
2.84’
.0
1.00’
EXISTING CONC.
HEADWALL
24" S.D. PIPE
.0
PIPE BEDDING MATERIAL
SEE SPECS.
.0
1.00’
3’-9"
1.00’
.0
.0
M
IN
INV. OF PIPE TO
MATCH INVERT OF
PAVED DITCH
(FIELD VERIFY)
DRILL & INSTALL 1/2 " DIA.
1.00’.84’
CONC. RETAINING
WALL
CONSTRUCTION
JOINT
#4 BARS @ 12"
O.C.E.W.
OUTSIDE FACE
OF EXISTING
RETAINING WALL
N.T.S.
NEW CONCRETE HEADWALL
TOP VIEW
N.T.S.
X 12" LONG HILTI EPOXY
HEADWALL @ 12" O.C.
FILTER FABRIC
SIDE ELEVATION VIEW
F
IE
L D
V E
R
IF
Y
‘ PIPE
#4 BARS @ 12"
#4 BARS @ 12"
#4 BARS @ 12"
(BAR "C")
#4 BARS @ 12"
(BAR "A")
CONSTRUCTION
JOINT
.0
16’-6"
5’-11"|
FIELD VERIFY
N.T.S.
N.T.S.
#4 BARS @ 12"
(BAR "A")
#4 BARS @ 12"
(BAR "A")
.0
.0
.0
#4 BARS @ 12"
(BAR "B")
#4 BARS @ 12"
(BAR "B")
#4 BAR CONT.
#4 BARS @ 12"
(BAR "C")
5’-11"|
FIELD VERIFY
.0
.8
SEE DETAIL ’A’
X 12" LONG HILTI EPOXY
HEADWALL @ 12" O.C.
ANCHOR (C100) IN EXIST.
DRILL & INSTALL 1/2 " DIA.
6"
/2
R =1"
N.T.S.
#4 BAR "A"
N.T.S.
#4 BAR "C"
2’-0"
R =1"
R =1"
DRILL & INSTALL 1/2 " DIA.
X 12" LONG HILTI EPOXY
HEADWALL @ 12" O.C.
ANCHOR (HY-100) IN EXIST.
ANCHOR (HY-100) IN EXIST.
‘ PIPE
N.T.S.
DETAIL ’A’
10" 12"
EXIST. NEW
5"
MIN.
ANCHOR (HY-100) IN EXIST.
SEE DETAIL ’A’
DRILL & INSTALL 1/2 " DIA.
X 12" LONG HILTI EPOXY
HEADWALL @ 12" O.C.
ANCHOR (HY-100) IN EXIST.
PLAN VIEW
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
N/A
U.S. Department of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
100% CONSTRUCTION DOCUMENTS
May 8, 2025
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
C-402
BB
EMBED CHANNEL
OR CABLE RACK
(TYP)
EQUIPMENT
GROUND
CONDUCTOR
EXOTHERMIC
CONNECTION (TYP)
WELD
CABLE CLIP
(TYP)
DRILL AND
TAP GROUND
CONNECTION
DRAIN WIRES
BRAIDED SHIELD
(TYP)
SUMP FRAME
PER SECTION 26 05
GROUND ROD
WELD
CONNECTION
EXOTHERMIC
BARE CU COMPLETE
#3/0 STRANDED
RING.
PULLING IRONS
CABLE
BANK
DUCT
(TYP)
BARE CU CABLE
#6 STRANDED
SPLICES
CABLE
CONNECTION
FRAME GROUND
MANHOLE COVER
MANHOLE GROUNDING DETAIL
NO SCALE
1930mm
(6’-4")
(3’-2") 965mm
(3’-2") 965mm m m m m m m
(3
COMMUNICATION
AA
TOP VIEW
GRADE RINGS AS REQ’D
TO MATCH CIVIL
ELEVATION.
FINISHED GRADE
CABLE
STANCHION
m m
(8 m m
(1
M
IN
(6 m mFINISHED
GRADE
m m
(7
PULLING
IRON
(5’-0")
1524mm
FRAME &
SUMP
COVER
SUMP 305mm (12")
CONC.
ENVELOPE
GROUND ROD
PER SECTION
26 05 26.
GRAVEL SUMP
YARD) 19mm (3/4")
0.764 CUBIC METERS
(1 CUBIC
m m
(8
V A
R
IE
S
SECTION "A-A"
m m
915mm
(3’-0")
NO SCALE
COMMUNICATION MANHOLE DETAILS
GENERAL NOTES:
(6’-4")
1930mm
(5’-0")
1524mm
(8 m m
SLOPE
SUMP
305x305mm (12"x12")
(8")
203mm m m m m
S L
O P
E
S L O
P E m m
CABLE
STANCHION
PER SECTION
26 05 41.
m m
(3")
76mm
GROUND
ROD SLEEVE
PULLING IRON
A A
(4) BOLT SLOTS 1" WIDE
ON A 42 1/2 " DIA. B.C.
3/4 " FLAT FACE
GOTHIC
M-PIC MULTI-TOOL
PICKBAR
1 9/16 "
T-GASKET (WITH BEAD)
1 9/16 "
6"
36"\
46"\
NO SCALE
38 1/4 "\
38"\
STAINLESS STEEL
CAM LOCK W/
CAM LOCK WRENCH
FRAME SECTION A-A
COVER SECTION A-A
ERGO XL Assembly
FRAME & COVER DETAIL
NO SCALE
DUCT BANK STANDARD DETAIL
DETECTABLE UNDERGROUND
WARNING TAPE.
M A
X
A S
R E
Q U
IR
E
D
(1
M
IN
IM
U M
NOTE:
WORDS "WARNING - TELECOMMUNICATIONS CABLE
A. WARNING TAPE SHALL BE IMPRINTED WITH THE
BELOW" AT NO MORE THAN 48" INTERVALS. TAPE
SHALL HAVE MINIMUM THICKNESS OF 0.004" AND SHALL
HAVE MINIMUM STRENGTH OF 1750 PSI. TAPE SHALL
HAVE INTEGRAL MEANS OF DETECTION BY A METAL
DETECTOR WHEN THE TAPE IS BURIED 3 FEET DEEP
DEGRADATION CAUSED BY SOIL CONDITIONS.
AND SHALL BE MADE OF MATERIALS RESISTANT TO
B. REFER TO TECHNOLOGY SITE PLAN FOR ADDITIONAL
INFORMATION INCLUDING INNER DUCT REQUIREMENTS.
C. STANDARD DUCT BANK CONSISTS (4) 4" CONDUITS.
CONCRETE ENVELOPE
STANDARD DUCT BAND CONSISTS OF (3) 4"
CONDUITS. SEE SHEETS GS013 - GS016 FOR
FINAL NUMBER OF CONDUITS IN EACH ROUTE.
EXISTING GRADE
42" MIN.
UNLESS
OTHERWISE NOTED
‘ MANWAY OPENING
FINISHED
GRADE
CONCRETE
ADJUSTMENT RING
G
R O
U T
(N O
N -S
H R
IN
K
REINFORCED
MANHOLE TOP
NON-TRAFFIC TRAFFIC AREA
RAISED COVER AND FRAME,
EJ 1845Z/1845A OR APPROVED
EQUAL (FLUSH W/ FIN. GRADE)
LOCKABLE COVER
NO SCALE
NO SCALE
SECTION "B-B"
NO SCALE
DUCT BANK CONFLICT DETAIL
A S
R E
Q U
IR
E
D
(2
M
IN
IM
U M
EXISTING GRADE
6’ (MIN.)
10’
HORIZ. VERTICAL
6’ (MIN.)
10’
6’ (MIN.)
5’ (MIN.)
3’ (MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
24"
UTILITY TYPE
WATER
SEWER
SEWER FORCE MAIN
CHILLED WATER
STORM SEWER / DRAIN
DUCT BANK / PIPED UTILITY
6’ (MIN.)
10’
18"(MIN.)
UTILITY CONFLICT
NEW DUCT BANK
20’ (MIN.) 20’ (MIN.)
CLEARANCE CHART (MIN.)
SEE CHART
BELOW
NOTE:
DEFLECT DISTANCE MAY VERY IN DISTANCE
PENDING DEPTH AND/OR SIZE OF
UTILITY CONFLICT
PIPE DEFLECTION DISTANCE PIPE DEFLECTION DISTANCE
D E
P T
H V
A R
IE
S
(F
IE
L D
V E
R
IF
Y
D E
P T
H V
A R
IE
S
F O
R C
O N
F L
IC
T
S
L E
S S
T H
A N
D
E E
P
3-WAY DUCT LINE
NO SCALE
DUCT BANK DETAILS
CONCRETE SHALL BE 4000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2.
1.
3.
4.
5.
GENERAL NOTES:
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41.
MAXCELL INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
PROVIDE MINIMUM 76mm (3") SPACE BETWEEN TELECOMMUNICATION
DUCTS. INCREASE SIZE AS REQUIRED.
MASONRY LEVELING
BLOCKS AT BASE OF
CONDUITS AS NEEDED
(3")
76mm
(3")
76mm
76mm
(3") m m
(3 m
DETECTABLE UNDERGROUND
WARNING TAPE.
TIE WIRE
9"
" 1111 1111 11 11 11
#3 BARS CONT.
9"
#3 BARS CONT.
8" THICK CONC. SLAB
W/ 6X6 #6/6 WWF
NO SCALE
C L
R
8’-2"
9" SQ. BLOCKOUT FOR
ELEC. RISER CONDUITS (TYP.)
(COORD. WITH POWER COMP.)
8’-2" x 5’-5"
PLAN VIEW
SECTION VIEW
TRANSFORMER PAD
TELECOMMUNICATION MANHOLE,
DUCT BANK, & DETAILS
C-402
C-402
LOCKABLE COVER
C-402
#6 BARS @
6" o.c. e.w.
#4 BARS @
8" o.c. e.w.
#4 REBAR @ 12" O.C.
EACH WAY
#6 BARS @
6" o.c. e.w.
#4 BARS @
8" o.c. e.w.
INCLUDE FIBERGLASS LADDER
(NOT SHOWN FOR CLARITY)
NO SUMP PUMP INCLUDED IN
PROJECT (PUMP BY OTHERS)
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
N/A
U.S. Department of Veterans Affairs
244200
OVERTON BROOKS VA MEDICAL CENTER
510 E STONER AVE.
SHREVEPORT, LA. 71101
FISHER HOUSE SITE PREP 667-23-113
U.S. Small Business
Administration
S
100% CONSTRUCTION DOCUMENTS
May 8, 2025
S
TA
REGISTERED
REG. NO. 27013
C
IV
IL ENGINEER
IN
G
C-403
FINISH GRADE
V A
R
IE
S
INSTALL BRIGHT COLORED
PLASTIC CAP TO TOP
OF IRON ROD
1/2 " IRON ROD
W/ WIRE CLAMP
N.T.S.
UTILITY PIPE
W/ LOCATOR WIRE
CAP DETAIL FOR UTILITY LINE
CAP
M.J. TAPPING VALVE
6"(MIN.)-12"(MAX.)
POLYETHYLENE ENCASEMENT
AT ALL FITTINGS PER
AWWA C105
3/4 " CORP. STOP
FOR DISINFECTION
TRACE WIRE
TOP ‘ PIPE (TYP.)
EXISTING WATER LINE
NEW C900 WATER MAIN
NATIVE SOIL
MIN. 12" EACH
SIDE OF PIPE
COMPACTED 95% OF STANDARD
PROCTOR DENSITY IN LIFTS OF
FIRM SUPPORT ENTIRE
BARRELL LENGTH
BELL HOLES
BASE AS REQUIRED
PAVEMENT SURFACE
NO GREATER THAN 8" COMPACTED
THICKNESS.
SIDE ELEVATION
TYPE 6 BEDDING
BY TYPICAL…
This is the start of the file's text. The full file is on GovTribe.