36C25623R0096 Drawings.pdf
PDF 7 MB Posted
- Attached to
- Replace Chiller # 3 - Pineville, LA - VA (Project No. 502-21-110) Federal contract opportunity
- Solicitation number
- 36C25623R0096
About this file
This document is a solicitation for a replacement chiller project at a VA medical center in Pineville, Louisiana. The solicitation number is 36C25623R0096 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16.
The project involves replacing Chiller #3. Drawings and specifications are provided for demolishing the existing chiller and related mechanical and electrical systems and installing a new water-cooled chiller, chilled water pump, variable frequency drives, and all associated mechanical piping and electrical work. The required products and services include a new 650-ton water-cooled chiller, chilled water pump, variable frequency drives, conduit, wiring, and all other components necessary for a fully functioning and code-compliant system. The contractor will also be responsible for demolition and disposal of the existing equipment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25623R0096 0004.docx | DOCX document | |
| 36C25623R0096 0003.docx | DOCX document | |
| 36C25623R0096 0002.docx | DOCX document | |
| Attachment 1A00002 - 2023-08-18 Addendum No. 1.pdf | ||
| Attachment 2A00002 236400 3-20 Packaged Water Chillers - Addendum 1.pdf | ||
| 36C25623R0096 0001.docx | DOCX document | |
| 36C25623R0096 - Site Visit Sign in Sheet 502-21-110 Aug 15 23.jpg | JPG image | |
| 36C25623R0096.docx | DOCX document | |
| 36C25623R0096 EXHIBIT F.docx | DOCX document | |
| Final SOW - Formatted.docx | DOCX document | |
| 36C25623R0096 EXHIBIT C.docx | DOCX document | |
| 36C25623R0096 EXHIBIT E.docx | DOCX document | |
| PRA 502-21-110 Chiller 3 Replacement - Copy.pdf | ||
| DBA WD LA20220041 Mod 5 (6-16-23).pdf | ||
| 36C25623R0096 EXHIBIT A.docx | DOCX document | |
| 36C25623R0096 EXHIBIT B.docx | DOCX document | |
| 36C25623R0096 EXHIBIT D.docx | DOCX document | |
| 36C25623R0096 Design Analysis.pdf | ||
| 36C25623R0096 Specifications.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHILLER #3 REPLACEMENT
PROJECT NUMBER: 502-21-110
2495 SHREVEPORT HIGHWAY, PINEVILLE, LA 71360
ALEXANDRIA VA HEALTH CARE SYSTEM
DRAWING TITLEDWG
NO.
INDEX OF DRAWINGS
DRAWING TITLEDWG
NO.
BID DOCUMENTS
PROJECT
LOCATIONPROJECT
LOCATION
COVER SHEET
G001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHILLER #3 REPLACEMENT
PINEVILLE, LOUISIANA
502-21-110
Project Director
11-09-2022 JH SJRevisions: Date:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AREA MAP
AutoCAD SHX Text
NTS
AutoCAD SHX Text
LOCATION MAP
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
AD101
AutoCAD SHX Text
FIRST FLOOR DEMO PLAN
AutoCAD SHX Text G001
AutoCAD SHX Text
COVER SHEET
AutoCAD SHX Text G002
AutoCAD SHX Text
LEGENDS, ABBREVIATIONS AND NOTES
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text A101
AutoCAD SHX Text
FIRST FLOOR PLAN
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M001
AutoCAD SHX Text
MECHANICAL LEGEND, ABBREVIATIONS, AND NOTES
AutoCAD SHX Text
MD101
AutoCAD SHX Text
CHILLER PLANT MECHANICAL DEMOLITION PLAN
AutoCAD SHX Text
MP101
AutoCAD SHX Text
CHILLER PLANT MECHANICAL PIPING PLAN
AutoCAD SHX Text M401
AutoCAD SHX Text
ENLARGED MECHANICAL PIPING PLAN
AutoCAD SHX Text M501
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text M601
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text M801
AutoCAD SHX Text
WATER COOLED CHILLER CONTROL SEQUENCE AND SCHEMATIC
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text E001
AutoCAD SHX Text
ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
AutoCAD SHX Text E002
AutoCAD SHX Text
ELECTRICAL LEGEND
AutoCAD SHX Text
ED101
AutoCAD SHX Text
ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text E101
AutoCAD SHX Text
MECHANICAL POWER PLAN
AutoCAD SHX Text
STRUCTURAL
AutoCAD SHX Text S001
AutoCAD SHX Text
STRUCTURAL NOTES
AutoCAD SHX Text S101
AutoCAD SHX Text
ROOF FRAMING PLAN
AutoCAD SHX Text
590 MEANS STREET NW STE. 200 ATLANTA, GA 30318
GENERAL ARCHITECTURAL NOTESGENERAL PROJECT NOTES ARCHITECTURAL ABBREVIATIONSARCHITECTURAL LEGEND
LEGENDS, ABBREVIATIONS AND
NOTES
G002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHILLER #3 REPLACEMENT
PINEVILLE, LOUISIANA
502-21-110
Project Director
11-09-2022 JH SJRevisions: Date:
AutoCAD SHX Text A. DIMENSIONS, UNLESS OTHERWISE INDICATED, ARE TO: DIMENSIONS, UNLESS OTHERWISE INDICATED, ARE TO: FACE OF EXISTING WALL SURFACE FACE OF NEW MASONRY FACE OF NEW WALL STUDS TOP OF SLAB TOP OF MASONRY ALIGN NEW WALLS WITH EXISTING WHERE NOT OTHERWISE INDICATED. B. COORDINATE WITH ALL DISCIPLINE DRAWINGS FOR COORDINATE WITH ALL DISCIPLINE DRAWINGS FOR ADDITIONAL REQUIREMENTS. COORDINATE OPENINGS IN SLABS, ROOF, AND WALLS. WHERE NEW HOLES IN EXISTING WALLS AND SLABS ARE CREATED FOR CONDUIT, DUCT, OR PIPE PENETRATIONS, COORDINATE SIZE AND LOCATION. PATCH HOLES CAUSED BY THE REMOVAL OF EQUIPMENT, PIPING, CONDUIT, DUCT, GRILLES, ETC. WITH MATERIALS MATCHING EXISTING SLAB OR WALL IN STRUCTURE, MATERIAL, THICKNESS, ALIGNMENT, GRADES, AND QUALITY. C. COORDINATE AND PROVIDE SOLID FIRE RETARDANT TREATED COORDINATE AND PROVIDE SOLID FIRE RETARDANT TREATED WOOD BLOCKING FOR WALL-MOUNTED ITEMS BETWEEN STUDS. COORDINATE LOCATIONS WITH COR FOR GOVERNMENT FURNISHED EQUIPMENT. D. `PROVIDE' IS DEFINED AS PROVIDING MATERIALS, DELIVERY, `PROVIDE' IS DEFINED AS PROVIDING MATERIALS, DELIVERY, STORAGE, HANDLING, INSTALLATION, ADJUSTMENT, AND CLEANING FOR THE ITEM INDICATED. E. SEAL PIPE PENETRATIONS THROUGH SLABS, MASONRY, SEAL PIPE PENETRATIONS THROUGH SLABS, MASONRY, SMOKE RATED PARTITIONS AND FIRE-RATED PARTITIONS WITH THE APPROPRIATE FIRESTOP TO MAINTAIN THE RATING OF THE WALL OR SLAB. SUBMIT CUT SHEETS AND SPECIFICATIONS TO THE COR FOR APPROVAL PRIOR TO INSTALLATION. PROVIDE UL LISTED ASSEMBLIES. F. SKIM COAT ALL DAMAGED EXISTING WALL SURFACES THAT SKIM COAT ALL DAMAGED EXISTING WALL SURFACES THAT REQUIRE PAINTING. G. REMOVED MATERIALS WHICH ARE INDICATED TO BE TURNED REMOVED MATERIALS WHICH ARE INDICATED TO BE TURNED OVER TO THE COR SHALL BE DELIVERED BY THE CONTRACTOR TO A PLACE INDICATED BY THE COR IF APPLICABLE. H. REMOVE COMPLETELY ALL MATERIALS AS INDICATED ON THE REMOVE COMPLETELY ALL MATERIALS AS INDICATED ON THE DRAWINGS AND AS REQUIRED FOR NEW CONSTRUCTION. EDGES AND FACES OF DEMOLISHED AREAS SHALL BE REPAIRED TO ACCEPT NEAT INSTALLATION OF NEW CONSTRUCTION OR FINISHES. WHERE EXISTING MATERIALS ARE TO BE REPLACED (WALLS, INSULATION, FLOORING, ETC.) EXISTING MATERIALS, ADHESIVES, ETC. SHALL BE REMOVED AND EXPOSED SURFACES SHALL BE PREPARED AS INDICATED OR SPECIFIED PRIOR TO INSTALLATION OF NEW MATERIALS. I. PREVENT DAMAGE TO MATERIALS AND FINISHES TO REMAIN. PREVENT DAMAGE TO MATERIALS AND FINISHES TO REMAIN. REPAIR DAMAGES FROM CONSTRUCTION ACTIVITIES TO EXISTING ITEMS TO REMAIN, AT NO ADDITIONAL COST. WHERE SUCH EXPOSED MATERIALS OR FINISHES TO REMAIN ARE DAMAGED.
AutoCAD SHX Text A. THE CONTRACTOR SHALL NOT ORDER OR INSTALL ANY THE CONTRACTOR SHALL NOT ORDER OR INSTALL ANY MATERIALS OR EQUIPMENT UNTIL SUBMITTALS FOR SUCH HAVE BEEN APPROVED. B. THE CONTRACTOR WILL BE RESPONSIBLE FOR ACQUIRING THE CONTRACTOR WILL BE RESPONSIBLE FOR ACQUIRING I.D. BADGES FOR EACH MEMBER OF HIS WORK FORCE. VALID FORMS OF I.D. ARE REQUIRED TO RECEIVE BADGES. COORDINATE WITH COR. C. ANY SMOKE DETECTORS HAVING ANY POTENTIAL FOR ANY SMOKE DETECTORS HAVING ANY POTENTIAL FOR EXPOSURE TO CONSTRUCTION SMOKE, DUST, AND DEBRIS SHALL BE SUITABLY PROTECTED TO PREVENT ACCIDENTAL ALARM. ALL SUCH ACTION MUST BE FIRST COORDINATED AND CLEARED WITH COR. ALL FIRE ALARM DEVICES SHALL BE ACTIVE WHENEVER CONTRACTOR'S FORCES ARE NOT PRESENT IN WORK AREA. D. CONTRACTOR SHALL COORDINATE ONLY WITH THE COR AND CONTRACTOR SHALL COORDINATE ONLY WITH THE COR AND CONTRACTING OFFICER. E. CONTRACTOR SHALL FIELD VERIFY DIMENSIONS & ALL CONTRACTOR SHALL FIELD VERIFY DIMENSIONS & ALL EXISTING CONDITIONS PRIOR TO PROCEEDING WITH THE WORK. EXISTING CONDITIONS ARE BASED ON GOVERNMENT FURNISHED EXISTING DRAWINGS AND LIMITED FIELD INVESTIGATION. NOTIFY COR OF ANY DISCREPANCIES PRIOR TO PROCEEDING. F. ALL FINISH COLORS TO BE SELECTED BY COR WHERE NOT ALL FINISH COLORS TO BE SELECTED BY COR WHERE NOT OTHERWISE INDICATED.
AutoCAD SHX Text
AIR CONDITIONING
AutoCAD SHX Text
ACOUSTICAL CEILING TILE
AutoCAD SHX Text
ABOVE FINISH FLOOR
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text
BOTTOM OF
AutoCAD SHX Text
CEMENTITIOUS BACKER BOARD
AutoCAD SHX Text
CEMENTITIOUS CRYSTALLINE WATERPROOFING
AutoCAD SHX Text
COLD-FORMED METAL FRAMING
AutoCAD SHX Text
CORNER GUARD
AutoCAD SHX Text
CENTERLINE
AutoCAD SHX Text
CERAMIC MOSAIC TILE
AutoCAD SHX Text
CONCRETE MASONRY UNIT
AutoCAD SHX Text
CASED OPENING
AutoCAD SHX Text
COMMUNICATION
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
CONTINUOUS
AutoCAD SHX Text
CONTRACTING OFFICER'S REPRESENTATIVE
AutoCAD SHX Text
CERAMIC TILE
AutoCAD SHX Text
CERAMIC TILE BASE
AutoCAD SHX Text
CARPET TILE
AutoCAD SHX Text
DIAMETER
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
EQUAL
AutoCAD SHX Text
EXPOSED STRUCTURE
AutoCAD SHX Text
ET CETERA
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXPOSED
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
FIRE EXTINGUISHER CABINET
AutoCAD SHX Text
FIRE HOSE CABINET
AutoCAD SHX Text
FINISHED FLOOR
AutoCAD SHX Text
FINISH
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FACE OF
AutoCAD SHX Text
FIELD VERIFY (PRIOR TO ORDERING OR CUTTING)
AutoCAD SHX Text
FABRIC WALLCOVERING
AutoCAD SHX Text
GAGE
AutoCAD SHX Text
GYPSUM WALL BOARD
AutoCAD SHX Text
HANDICAPPED
AutoCAD SHX Text
HOLLOW METAL
AutoCAD SHX Text
HIGH-PRESSURE DECORATIVE LAMINATE
AutoCAD SHX Text
HEATING VENTILATION AND AIR-CONDITIONING
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
MASONRY OPENING
AutoCAD SHX Text
METAL
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
ON CENTER
AutoCAD SHX Text
OPPOSITE HAND
AutoCAD SHX Text
PORCELAIN BASE
AutoCAD SHX Text
PLASTIC LAMINATE
AutoCAD SHX Text
PRESSURE TREATED
AutoCAD SHX Text
PAIR
AutoCAD SHX Text
PAINT
AutoCAD SHX Text
QUARRY TILE
AutoCAD SHX Text
RESILIENT BASE
AutoCAD SHX Text
REFRIGERATOR
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
RESINOUS FLOORING
AutoCAD SHX Text
RESINOUS EPOXY WALL - CEILING
AutoCAD SHX Text
ROUGH OPENING
AutoCAD SHX Text
RUBBER FLOORING
AutoCAD SHX Text
SEALED HIGH BUILD GLAZED COATING
AutoCAD SHX Text
SOLID CORE WOOD
AutoCAD SHX Text
SIMILAR
AutoCAD SHX Text
SPECIAL FACED
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
SUBSTRATE
AutoCAD SHX Text
SHEET VINYL
AutoCAD SHX Text
SOLID VINYL TILE
AutoCAD SHX Text
TO BE DETERMINED
AutoCAD SHX Text
TELEPHONE
AutoCAD SHX Text
TOP OF
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
UNLESS NOTED OTHERWISE
AutoCAD SHX Text
VINYL COMPOSITION TILE
AutoCAD SHX Text
VINYL WALL COVERING
AutoCAD SHX Text
WALL COVERING
AutoCAD SHX Text
WOOD
AutoCAD SHX Text
WELDED SEAM SHEET FLOORING
AutoCAD SHX Text
AC
AutoCAD SHX Text
ACT
AutoCAD SHX Text
AFF
AutoCAD SHX Text
ALUM
AutoCAD SHX Text
BATT
AutoCAD SHX Text
BO
AutoCAD SHX Text
CBB
AutoCAD SHX Text
CCW
AutoCAD SHX Text
CFMF
AutoCAD SHX Text
CG
AutoCAD SHX Text C
AutoCAD SHX Text
CMT
AutoCAD SHX Text
CMU
AutoCAD SHX Text
CO
AutoCAD SHX Text
COMM
AutoCAD SHX Text
CONC
AutoCAD SHX Text
CONT
AutoCAD SHX Text
COR
AutoCAD SHX Text
CT
AutoCAD SHX Text
CTB
AutoCAD SHX Text
CT
AutoCAD SHX Text
DIA
AutoCAD SHX Text
EWC
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
EQ
AutoCAD SHX Text
ES
AutoCAD SHX Text
ETC
AutoCAD SHX Text
EXIST
AutoCAD SHX Text
EXP
AutoCAD SHX Text
FD
AutoCAD SHX Text
FEC
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FF
AutoCAD SHX Text
FIN
AutoCAD SHX Text
FLR
AutoCAD SHX Text
FO
AutoCAD SHX Text
FV
AutoCAD SHX Text
FWC
AutoCAD SHX Text
GA
AutoCAD SHX Text
GWB
AutoCAD SHX Text
HC
AutoCAD SHX Text
HM
AutoCAD SHX Text
HPDL
AutoCAD SHX Text
HVAC
AutoCAD SHX Text
MATL
AutoCAD SHX Text
MAX
AutoCAD SHX Text
MECH
AutoCAD SHX Text
MFR
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MO
AutoCAD SHX Text
MTL
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NTS
AutoCAD SHX Text
OC
AutoCAD SHX Text
OH
AutoCAD SHX Text
PB
AutoCAD SHX Text
PLAM
AutoCAD SHX Text
PT
AutoCAD SHX Text
PR
AutoCAD SHX Text P
AutoCAD SHX Text
QT
AutoCAD SHX Text
RB
AutoCAD SHX Text
REF
AutoCAD SHX Text
REQ'D
AutoCAD SHX Text
RES
AutoCAD SHX Text
RES-W
AutoCAD SHX Text
RO
AutoCAD SHX Text
RF
AutoCAD SHX Text
SC
AutoCAD SHX Text
SCW
AutoCAD SHX Text
SIM
AutoCAD SHX Text
SP
AutoCAD SHX Text
SS
AutoCAD SHX Text
STL
AutoCAD SHX Text
SUBS
AutoCAD SHX Text
SV
AutoCAD SHX Text
SVT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TELE
AutoCAD SHX Text
TO
AutoCAD SHX Text
TYP
AutoCAD SHX Text
UNO
AutoCAD SHX Text
VCT
AutoCAD SHX Text
VWC
AutoCAD SHX Text
WC
AutoCAD SHX Text
WD
AutoCAD SHX Text
WSF
AutoCAD SHX Text L
AutoCAD SHX Text
SEALED CONCRETE
AutoCAD SHX Text
SCONC
AutoCAD SHX Text
PORCELAIN TILE
AutoCAD SHX Text
POR
AutoCAD SHX Text
CONTROL JOINT
AutoCAD SHX Text
CJ
AutoCAD SHX Text
GALVANIZED METAL STUD(S)
AutoCAD SHX Text
GMS
AutoCAD SHX Text
REFLECTED CEILING PLAN
AutoCAD SHX Text
RCP
AutoCAD SHX Text
LUXURY VINYL TILE
AutoCAD SHX Text
LVT
AutoCAD SHX Text
COMPOUNDING ASEPTIC CONTAINMENT ISOLATOR
AutoCAD SHX Text
CACI
AutoCAD SHX Text F.E.C.
AutoCAD SHX Text
FIRE EXTINGUISHER CABINET
AutoCAD SHX Text
ROOM NAME AND NUMBER
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
NAME
AutoCAD SHX Text
AutoCAD SHX Text
SOLID SURFACE MATERIAL
AutoCAD SHX Text
SSM
AutoCAD SHX Text
WALL PROTECTION
AutoCAD SHX Text
WP
590 MEANS STREET NW STE. 200 ATLANTA, GA 30318
147-P-4147-P-2147-P-3
147-P-1
CHILLER
CHILLER
CHILLER
147-P-9
(E)AIR
SEPARATOR
147-P-6
CHILLER
147-P-8
147-P-7
WTR TMT
MUW
EL
EC
TR
IC
AL
EL
EC
TR
IC
AL
ELECTRICAL ELECTRICAL
CONCRETE
PAD (TYP)
TANK
FFM
FIRST FLOOR DEMO PLAN
AD101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHILLER #3 REPLACEMENT
PINEVILLE, LOUISIANA
502-21-110
Project Director
11-09-2022 JH SJRevisions: Date:
DEMO KEY NOTES
DEMO PLAN LEGEND
DEMO GENERAL NOTES
AutoCAD SHX Text
EXISTING WINDOW UNIT
AutoCAD SHX Text
SIEMENS CTRL PANEL
AutoCAD SHX Text
EXISTING UNIT HEATER
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
CHWP-1 VFD
AutoCAD SHX Text
CDWP-3 VFD
AutoCAD SHX Text
CHWP-2
AutoCAD SHX Text
CDWP-4
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
COOLING TWR #3
AutoCAD SHX Text
COOLING TWR #6
AutoCAD SHX Text
COOLING TWR #5
AutoCAD SHX Text
EXISTING EF
AutoCAD SHX Text
EXISTING EXHAUST DUCT
AutoCAD SHX Text
CEILING MOUNTED EXHAUST FAN TO ROOF
AutoCAD SHX Text
REFRIGERATED AIR DRYER
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
45 KVA TRANSFORMER
AutoCAD SHX Text
PANEL HA
AutoCAD SHX Text
EXISTING FRIDGE
AutoCAD SHX Text
147-CT-2
AutoCAD SHX Text
147-CT-1
AutoCAD SHX Text
FD
AutoCAD SHX Text
COOLING TWR #1
AutoCAD SHX Text
COOLING TWR #2
AutoCAD SHX Text
COOLING TWR #4
AutoCAD SHX Text
147-CT-6
AutoCAD SHX Text
BRANCH#4 UNDERGROUND CS/R LINES TO BLDG 7
AutoCAD SHX Text
BRANCH#3 UNDERGROUND CS/R LINES TO BLDGS 4, 5, 6, 49, & 9
AutoCAD SHX Text
BRANCH#1 UNDERGROUND CS/R LINES TO BLDGS 7, 45, & 46
AutoCAD SHX Text
BRANCH#2 UNDERGROUND CS/R LINES TO BLDG 1, 2, 3, 7 & 8
AutoCAD SHX Text
AD101
AutoCAD SHX Text
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
FIRST FLOOR DEMO PLAN
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DEMOLITION ELEVATION
AutoCAD SHX Text SAW CUT CMU AND BRICK VENEER FOR WIDENED OPENING AND INSTALL OF NEW LINTEL BEAM (SEE STRUCTURAL)
AutoCAD SHX Text
EXIST CMU W/ CELLS SAW CUT FOR JAMB REINFORCING BOTH SIDES (SEE STRUCTURAL)
AutoCAD SHX Text
EXIST HM FRAME AND HM DOOR REMOVED. STORE AND PREP FOR REINSTALL.
AutoCAD SHX Text EXIST SCREEN PANEL FRAME, TRANSOM AND SCREEN DOOR REMOVED. STORE AND PREP FOR REINSTALL
AutoCAD SHX Text
590 MEANS STREET NW STE. 200 ATLANTA, GA 30318
AutoCAD SHX Text
1. DEMOLISH EXISTING MASONRY CONSTRUCTION AS SHOWN TO INSTALL NEW DEMOLISH EXISTING MASONRY CONSTRUCTION AS SHOWN TO INSTALL NEW WORK. MAKE ALL CUTS CLEAN AND SHARP. PATCH MASONRY WHERE CHIPPED OR DAMAGED. 2. REMOVE EXISTING HM DOOR AND FRAME. STORE AND PREPARE FOR REMOVE EXISTING HM DOOR AND FRAME. STORE AND PREPARE FOR REINSTALLATION AFTER COMPLETION OF MECHANICAL WORK. RETAIN DOOR HARDWARE FOR REUSE. 3. REMOVE EXISTING METAL SCREEN WIRE DOOR AND FRAME. STORE AND REMOVE EXISTING METAL SCREEN WIRE DOOR AND FRAME. STORE AND PREPARE FOR REINSTALLATION AFTER INSTALLATION OF HM FRAME. RETAIN DOOR HARDWARE FOR REUSE. 4. EXISTING ELECTRICAL PANELS TO BE REMOVED AND RELOCATED. SEE EXISTING ELECTRICAL PANELS TO BE REMOVED AND RELOCATED. SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION. 5. EXISTING MECHANICAL EQUIPMENT TO BE REMOVED. SEE MECHANICAL EXISTING MECHANICAL EQUIPMENT TO BE REMOVED. SEE MECHANICAL DRAWINGS FOR MORE INFORMATION.
AutoCAD SHX Text A. DEMOLISH EXISTING WALL AND BASE FINISHES AS REQUIRED TO INSTALL NEW WORK. DEMOLISH EXISTING WALL AND BASE FINISHES AS REQUIRED TO INSTALL NEW WORK. B. WHERE WALL IS BEING REMOVED TO INSTALL NEW WORK, PROTECT EXISTING WALL WHERE WALL IS BEING REMOVED TO INSTALL NEW WORK, PROTECT EXISTING WALL MOUNTED OR SUSPENDED DEVICES AND COMPONENTS. EXISTING DEVICES MAY BE TEMPORARILY SUPPORTED AND PROTECTED IN PLACE WHERE POSSIBLE. IF REQUIRED FOR NEW WORK INSTALLATION, REMOVE EXISTING DEVICES AND COMPONENTS, STORE AND REINSTALL COORDINATED WITH OTHER WORK. REPLACE DAMAGED DEVICES AND COMPONENTS TO MATCH EXISTING. THIS NOTE APPLIES TO ALL DEVICES AND COMPONENTS HUNG FROM STRUCTURE ABOVE REQUIRED TO BE REMOVED TO INSTALL NEW WORK. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
147-P-4147-P-2147-P-3
147-P-1
CHILLER
CHILLER
CHILLER
147-P-9
(E)AIR
SEPARATOR
147-P-6
CHILLER
147-P-8
147-P-7
MUW
EL
EC
TR
IC
AL
EL
EC
TR
IC
AL
ELECTRICAL ELECTRICAL
CONCRETE
PAD (TYP)
TANK
FFM
FIRST FLOOR PLAN
A101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHILLER #3 REPLACEMENT
PINEVILLE, LOUISIANA
502-21-110
Project Director
11-09-2022 JH SJRevisions: Date:
PLAN KEY NOTES
PLAN LEGEND
GENERAL NOTES
AutoCAD SHX Text
EXISTING WINDOW UNIT
AutoCAD SHX Text
SIEMENS CTRL PANEL
AutoCAD SHX Text
EXISTING UNIT HEATER
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
CHWP-1 VFD
AutoCAD SHX Text
CDWP-3 VFD
AutoCAD SHX Text
CHWP-2
AutoCAD SHX Text
CDWP-4
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
COOLING TWR #3
AutoCAD SHX Text
COOLING TWR #6
AutoCAD SHX Text
COOLING TWR #5
AutoCAD SHX Text
EXISTING EF
AutoCAD SHX Text
EXISTING EXHAUST DUCT
AutoCAD SHX Text
CEILING MOUNTED EXHAUST FAN TO ROOF
AutoCAD SHX Text
REFRIGERATED AIR DRYER
AutoCAD SHX Text
EXISTING ELEC. EQUIP
AutoCAD SHX Text
45 KVA TRANSFORMER
AutoCAD SHX Text
PANEL HA
AutoCAD SHX Text
EXISTING FRIDGE
AutoCAD SHX Text
147-CT-2
AutoCAD SHX Text
147-CT-1
AutoCAD SHX Text
FD
AutoCAD SHX Text
COOLING TWR #1
AutoCAD SHX Text
COOLING TWR #2
AutoCAD SHX Text
COOLING TWR #4
AutoCAD SHX Text
147-CT-6
AutoCAD SHX Text
BRANCH#4 UNDERGROUND CS/R LINES TO BLDG 7
AutoCAD SHX Text
BRANCH#3 UNDERGROUND CS/R LINES TO BLDGS 4, 5, 6, 49, & 9
AutoCAD SHX Text
BRANCH#1 UNDERGROUND CS/R LINES TO BLDGS 7, 45, & 46
AutoCAD SHX Text
BRANCH#2 UNDERGROUND CS/R LINES TO BLDG 1, 2, 3, 7 & 8
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
FIRST FLOOR PLAN
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DOOR TYPES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FRAME TYPES
AutoCAD SHX Text
STEEL LINTEL (SEE STRUCTURAL)
AutoCAD SHX Text
EXIST CMU W/ CELLS GROUTED SOLID BOTH SIDES (SEE STRUCTURAL)
AutoCAD SHX Text
ALUM LOUVER W/ BUG SCREEN
AutoCAD SHX Text
EXIST HM FRAME REINSTALLED
AutoCAD SHX Text
EXIST STEEL FRAME FOR SCREEN DOOR REINSTALLED
AutoCAD SHX Text
EXIST SCREEN PANEL REINSTALLED
AutoCAD SHX Text
EXISTING HM DOORS TO BE REINSTALLED W/ EXISTING HARDWARE
AutoCAD SHX Text
EXISTING SCREEN DOORS TO BE REINSTALLED W/ EXISTING HARDWARE
AutoCAD SHX Text
1. PATCH AND REPAIR FLOOR AND WALL FINISHES TO MATCH EXISTING INTERIOR PATCH AND REPAIR FLOOR AND WALL FINISHES TO MATCH EXISTING INTERIOR AND EXTERIOR FINISHES. PAINT TO EXTENT DETERMINED BY COR. 2. REINSTALL EXISTING HM DOOR AND FRAME. RESTORE TO FULL FUNCTIONALITY. REINSTALL EXISTING HM DOOR AND FRAME. RESTORE TO FULL FUNCTIONALITY. 3. REINSTALL EXISTING WIRE SCREEN DOOR, TRANSOM AND FRAME. RESTORE TO REINSTALL EXISTING WIRE SCREEN DOOR, TRANSOM AND FRAME. RESTORE TO FULL FUNCTIONALITY 4. INSTALL NEW 2'-0" WIDE ALUM LOUVER WITH BIRD/INSECT SCREEN. INSTALL NEW 2'-0" WIDE ALUM LOUVER WITH BIRD/INSECT SCREEN. 5. CLEAN EXISTING CONTROL JOINT OF REMNANTS OF OLD CAULK. RESEAL JOINT CLEAN EXISTING CONTROL JOINT OF REMNANTS OF OLD CAULK. RESEAL JOINT WITH NEW CAULK TO MATCH EXISTING ADJACENT FINISHES AS APPROVED BY COR.
AutoCAD SHX Text A. REPAIR EXISTING FLOOR AND WALL FINISHES AS REQUIRED TO INSTALL NEW REPAIR EXISTING FLOOR AND WALL FINISHES AS REQUIRED TO INSTALL NEW WORK. B. PATCH, REPAIR AND PAINT WALLS OR STRUCTURE ABOVE WHERE IMPACTED BY PATCH, REPAIR AND PAINT WALLS OR STRUCTURE ABOVE WHERE IMPACTED BY REPAIR AND PAINT WALLS OR STRUCTURE ABOVE WHERE IMPACTED BY NEW WORK TO EXTENT AS DETERMINED BY COR. MATCH EXISTING FINISHES UNLESS NOTED OTHERWISE. . C. WHERE DEVICES OR EQUIPMENT WERE REMOVED TO INSTALL NEW WORK, WHERE DEVICES OR EQUIPMENT WERE REMOVED TO INSTALL NEW WORK, REINSTALL EXISTING DEVICES AND COMPONENTS. THIS NOTE APPLIES TO ALL DEVICES AND COMPONENTS WHERE REMOVED TO INSTALL NEW WORK. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
EXISTING CONSTRUCTION TO REMAIN
NEW CONSTRUCTION
3380 T rickum Road
W oodstock, G A. 30188 770-517-5507 voice 770-517-5508 fax
B ldg. 500, Ste. 100 ww w.ie iusa.com
IN C O R PO R A TED
INNO VATIVE
EN G IN EER IN G
Veterans Affairs
VA FO R M 08-6231
1 2 3 4 5 6 7 8 9
D ate:
D raw ing T itle :
A pproved: Pro ject D irector
P ro ject T itle :
1 2 3 4 5 6 7 8 9
590 M EA N S ST N W
P hase P roject N um ber
B uild ing N um ber
D raw ing N um berLocation
Issue D ate C heckedFU LLY SPR IN KLER ED
S TA M P
S TE . 200
A TLA N TA , G A 30318
AR C H ITEC T/EN G IN EE R O F R EC O R DC O N SU LTAN T
F ile
P a th
A
B
C
D
E
F
U .S. D epartm ent of V eterans A ffairs
O ffice o f C onstruction and Facilities M anagem ent
D raw n
R evisions:
A
B
C
D
E
F
STR U C TU R AL N O TES C H ILLER #3 R EPLAC EM EN T
PIN EVILLE, LO U IS IANA
S001
502-21-110
11-09-2022
BID D O C U M EN TS
D C AS LW
S101
R E
F
/4
REF.
91' - 5 1/4"
NEW LINTEL,
SE E ELE VATIO N
EXIST. LO AD BE ARING 8"
CM U W ALL, E NTIRE
PE RIM ETER O F BUILD ING
EXIST. PRECA ST
DO UBLE TEE RO O F
PA NELS
A B
SEE NO TE 4
PLAN
NO RTH
TRUE
NO RTH
1. F IELD V ERIFY EXISTING CO NDIT IO NS P RIO R TO SUB M ISS IO N O F
SHO P DRA W IING S FO R REVIEW
2. REF . DENO TES FO R REFE RENCE O NLY. CO NTRACTO R S HALL
FIELD V ERIFY
3. ALL EXTERIO R EXPO SED STEEL SHA LL BE HO T D IPPE D
G ALVANIZED
4. SHO RE E XIST ING RO O F AND W ALL AS RE Q UIRE D TO INSTALL
NEW LINTEL. DESIG N AND CO NSTRUCTIO N O F ALL SHO RING
SHA LL BE BY THE CO NTRACTO R. SUBM IT ALL S HO RING DES IG N
CALCULATIO NS AND DRAW ING S FO R REVIEW . DES IG N
CALCULATIO NS SHA LL BE S IG NED AND SE ALED BY A
PRO FESSIO NAL E NG INE ER LICENSED IN THE STA TE O F THE
PRO JECT.
IND ICATES EXISTING PRECA ST RO O F DO UBLE TEES
INDICATES NEW LINTEL
INDICATES EXISTING CM U
10'-0" MAX.
EXIST 8"
CM U W ALL
FILL CELLS W ITH 3,000
P S I G RO UT TYP.
A
A
TYP.
8" MIN.
HSS12x8X1/4 LSH
EXISTING SLA B
NO TE S:
1. REB AR SHO W N O NLY REQ UIRED IF NO T FO UND IN E XIST ING CO NDITIO N
2. CO O RDINATE DO O R / O P ENING RE M O V AL W ITH ARCH. DRAW ING S
3. HSS S HALL BE HO T D IPPE D G A LVANIZE D
4. CO O RDINATE LO CA TIO N / RELO CA TIO N O F E XIST ING W ALL M O UNTED
UTILIT IES W ITH A LL D ISC IPLINE DRAW ING S
DRILL HO LE INTO EXISTING CO NCRETE 10
BA R D IAM S DEE P BY O NE BAR D IAM + 1/4"
M AX IN D IAM ETE R A ND E PO XY DO W EL INTO
FO O TING AND BO ND BE AM A BO VE IN
ACCO RDA NCE W ITH M ANUFACTURERS
RECO M M ENDATIO NS
(1) #5
EXIST. PRECA ST DO UBLE TEE
E X
IS
T
IN
G
F
IE
LD
V
E R
IF
Y
EXIST. 8"
CM UHS S 12x8x1/4 LSH
SEC TIO N A-A
EXIST. BR ICK
O PE NING
HO LLO W BLO CK
O NE PER CELL AS REQ UIRED
ALIG N SAW CUT W ITH W EBS
FILL CHASE W ITH G RO UT
3380 T rickum Road
W oodstock, G A. 30188 770-517-5507 voice 770-517-5508 fax
B ldg. 500, Ste. 100 ww w.ie iusa.com
IN C O R PO R A TED
INNO VATIVE
EN G IN EER IN G
Veterans Affairs
VA FO R M 08-6231
1 2 3 4 5 6 7 8 9
D ate:
D raw ing T itle :
A pproved: Pro ject D irector
P ro ject T itle :
1 2 3 4 5 6 7 8 9
590 M EA N S ST N W
P hase P roject N um ber
B uild ing N um ber
D raw ing N um berLocation
Issue D ate C heckedFU LLY SPR IN KLER ED
S TA M P
S TE . 200
A TLA N TA , G A 30318
AR C H ITEC T/EN G IN EE R O F R EC O R DC O N SU LTAN T
F ile
P a th
A
B
C
D
E
F
U .S. D epartm ent of V eterans A ffairs
O ffice o f C onstruction and Facilities M anagem ent
D raw n
R evisions:
A
B
C
D
E
F
R O O F FR AM IN G PLAN C H ILLER #3 R EPLAC EM EN T
PIN EVILLE, LO U IS IANA
S101
502-21-110
11-09-2022
BID D O C U M EN TS
D C AS LW
3/16" = 1 '-0"S101
1 R O O F FR A M IN G PLAN R O O F FR AM IN G N O TE SR O O F FR AM IN G LEG EN D
3/8" = 1 '-0"S101
2 ELEVATIO N AT N EW O P EN IN G
1 1/2" = 1 '-0"S101
3 SE C TIO N
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
2"
4"
4"
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER
METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL
VALVE
3 WAY MOTORIZED
CONTROL VALVE
PRESSURE REDUCING
VALVE
REFRIGERANT SOLENOID
VALVE
BUTTERFLY VALVE
2"
BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY
CNTRL
2" PRV
3/8"
SOLENOID
2"
BUTTERFLY
CAP
PLUG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL
OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN
ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
F
S
M
B
D
C
48"x2 1/2"
SLB3
LINEAR BAR
GRILLE
RTU-XX
VAV-XX
EQUIPMENT
TAG
EQUIPMENT TAG
VAV TERMINAL
AIR HANDLING UNIT
MANUAL BALANCING
DAMPER
BACKDRAFT DAMPER
COMBINATION
FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
CWS
CD
MPS
CR
CS
HWR
HWS
LPS
CWR
CHILLED WATER
RETURN
CHILLED WATER
SUPPLY
CONDENSATE
DRAINAGE
MEDIUM PRESSURE
STEAM
CONDENSER WATER
RETURN
CONDENSER WATER
SUPPLY
HEATING WATER
RETURN
HEATING WATER
SUPPLY
LOW PRESSURE
STEAM
LPSR
LOW PRESSURE
STEAM RETURN
MPSR
PCD
CDR
MEDIUM PRESSURE
STEAM RETURN
PUMP CONDENSATE
DISCHARGE
CONDENSATE
RETURN
GENERAL MECHANICAL NOTES
A. CONTRACTOR SHALL PHASE ALL WORK AS REQUIRED TO MAINTAIN
CONTINUOUS OPERATION OF THE HOSPITAL.
B. HOSPITAL OPERATIONS SHALL NOT BE INTERRUPTED DUE TO THE
WORK OF THIS PROJECT EXCEPT FOR SCHEDULED SHUTDOWNS OF
NO LONGER THAN ONE HOUR. CONTRACTOR SHALL GIVE
REASONABLE NOTICE TO COR BEFORE ANY SUCH SHUTDOWN OR
INTERRUPTION.
C. WHERE LONGER SHUTDOWNS ARE REQUIRED TO COMPLETE THE
WORK DESCRIBED IN THIS DOCUMENT, THE CONTRACTOR SHALL
SCHEDULE THE EVENT A MINIMUM OF 3 WEEKS PRIOR TO
COMMENCING WORK. ALL SUCH SHUTDOWNS AND INTERRUPTIONS
SHALL BE MINIMIZED AND SHALL UTILIZE WEEKENDS, FEDERAL
HOLIDAYS, NIGHTS, AND OTHER TIMES WHEN HOSPITAL OPERATIONS
ARE MINIMIZED AND OTHER SUCH TIMES AGREEABLE TO THE COR.
D. WHERE NECESSARY TO INTERRUPT CONTINUOUS OPERATION OF THE
HOSPITAL, THE CONTRACTOR SHALL DIVIDE WORK INTO PHASED
CONSTRUCTION THAT IS NOT NECESSARILY SHOWN ON THESE
DOCUMENTS. AS PART OF SCHEDULING AN INTERRUPTION OR
SHUTDOWN, THE CONTRACTOR SHALL PROVIDE THE COR WITH A
DETAILED SHUTDOWN PLAN INDICATING THE SYSTEMS AFFECTED,
INCLUDING BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL,
MECHANICAL, PLUMBING, FIRE PROTECTION, AND OTHER SYSTEMS
INVOLVED. THE PLAN SHALL INCLUDE THE WORK TO BE PERFORMED,
THE LENGTH OF INTERRUPTION, AND A DETAILED PHASING AND
MANNING DESCRIPTION. THE PLAN SHALL INCLUDE AND ADDRESS
CONTINGENCY FOR MITIGATING ANY DELAYS THAT MAY OCCUR IN THE
PLANNED WORK. PROVIDE THIS PLAN TO THE COR 5 WEEKS BEFORE
THE EVENT FOR APPROVAL.
A. THE TEST AND BALANCE CONTRACTOR SHALL BE A SUBCONTRACTOR
TO THE PRIME CONTRACTOR AND NOT A SUBCONTRACTOR TO THE
MECHANICAL OR ANY OTHER SUBCONTRACTOR.
PHASING MECHANICAL NOTES
TEST AND BALANCE MECHANICAL NOTES
PIPING SYMBOLSHVAC SYMBOLS
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
LIMIT OF DEMOLITION
(E)
2"
1/8" / 12" SLOPE
PIPE SIZE TAG (DIAMETER)
BELOW GROUND PIPING
EXISTING PIPE TAG
PIPING BEING DEMOLISHED
INVERT: -105' - 1" PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
NEW WORK NOTES
DEMOLISHED WORK NOTES
CONNECT NEW DUCT TO EXISTING DUCT
ACCESS DOOR ON TOP OF DUCT
ACCESS DOOR ON SIDE OF DUCT
ACCESS DOOR ON BOTTOM OF DUCT
Room
AREA NOT IN CONTRACT
SHEET NOMENCLATURE
M P # # #
SHEET
SERIES
MECHANICAL
(H) HVAC
(P) PIPING
(D) DEMO
SERIES
0 - SYMBOLS AND NOTES
1 - PLAN VIEWS
3 - ELEVATIONS AND SECTIONS
4 - LARGE SCALE - PLANS AND SECTIONS
5 - SCHEMATICS AND DETAILS
6 - SCHEDULES
8 - CONTROLS
16"x8"
16"/8"
16"Ø
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
ROUND DUCT SIZE TAG (DIAMETER)
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
(E)16"Ø
3-CONE
DIFFUSER
CFM
NECK SIZE
TYPE (SEE SCHEDULE)
EGGCRATE
RETURN GRILLE
10"x10"
RG1
CFM
NECK SIZE
TYPE (SEE SCHEDULE)
10"Ø
SD1
VAV-XX
RTU-XX
EQUIPMENT ID
SYMBOL
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY
SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
TYPE (SEE SCHEDULE)
CFM
ACTIVE SLOT LENGTH
(PLENUM LENGTH)
GRILLES, REGISTERS & DIFFUSERS TAG
MECHANICAL EQUIPMENT TAGS
DATA DEVICE TAGS
DAMPER TAGS
ABBREVIATIONS
KG KILOGRAM
KG/HR KILOGRAM PER HOUR
kPa KILOPASCAL
KW KILOWATT
KWH KILOWATT HOUR
L LITER
L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUEFIED PETROLEUM GAS
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN
(CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/S METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1,000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN
(STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
Nm NEWTON METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC &
ATMOSPHERIC ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD
AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD
REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTDOOR AIR DAMPER
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
P PUMP
Pa PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER
(SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE)
STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD RETURN AIR DAMPER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RELAD RELIEF AIR DAMPER
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND
DISTRIBUTION
SPRV STEAM PRESSURE REDUCING
VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT
EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING
VALVE
SVS STEAM VENT SILENCER
SW SOFTWATER
SWHX STEAM TO WATER HEAT
EXCHANGER
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
V VENT
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL
OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH
ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT
EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFIER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN
(STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J INTENTIONALLY LEFT BLANK
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,
TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
AQST AQUASTAT
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING
REFRIGERATION AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BE BOTTOM ELEVATION
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS
(SUBMISSION1)
CD-2 CONSTRUCTION DOCUMENTS
(SUBMISSION2)
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO
COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM
COOLING TOWER)
D DAMPER - AUTOMATIC
Db DRY-BULB TEMPERATURE
DB DECIBELS
DCW DOMESTIC COLD WATER
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
A. EQUIPMENT INDICATED TO BE REMOVED SHALL BE REMOVED FROM
THE PROJECT SITE IN ITS ENTIRETY INCLUDING ALL HANGERS,
ELECTRICAL CONDUIT, WIRING, JUNCTION BOXES, PIPING, CONTROLS,
ACCESSORIES AND ALL APPURTENANCES THAT ARE RENDERED
USELESS OR ABANDONED BY THE REMOVAL OF THE INDICATED
EQUIPMENT.
B. WHERE THESE DOCUMENTS REQUIRE REMOVAL OF PIPING,
EQUIPMENT OR ASSOCIATED APPURTENANCES, CONTRACTOR SHALL
PROTECT ALL EXISTING-TO-REMAIN COMPONENTS FROM DAMAGE.
CONTRACTOR SHALL COVER ALL OPENINGS IN DUCT, PIPING,
EQUIPMENT, AND ANY OTHER DEVICE FROM CONSTRUCTION DUST
AND DEBRIS.
C. WHERE EQUIPMENT OR PIPING IS TO BE REMOVED THAT IS IN-
SERVICE, CONTRACTOR SHALL GIVE NOTICE TO THE COR OF ANY
INTERRUPTIONS ANTICIPATED. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE ALL SHUTDOWNS OR INTERRUPTIONS
TO THE SATISFACTION OF THE COR AND HOSPITAL STAFF.
DEMOLITION MECHANICAL NOTES
AI
GROE
G
KNO
W
L E S
J E R
E M Y
NO. 034176
PROFESSIONAL
TIS RE
DEER
G
E
NG I NEE
R
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Revisions:
PINEVILLE, LOUISIANA
M001
502-21-110
JMK JSP11/09/2022
MECHANICAL LEGEND, ABBREVIATIONS,
AND NOTES
CHILLER #3
REPLACEMENT
BID DOCUMENTS
A. THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS,
BOTH EXISTING AND THOSE ILLUSTRATED BY THESE DOCUMENTS, AS
WELL AS THOSE WHICH CAN BE REASONABLY ANTICIPATED
INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL,
PLUMBING, FIRE PROTECTION, AND OTHER SYSTEMS INVOLVED ON
THIS PROJECT.
B. FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM
AND SHALL CONFORM TO ALL CURRENT REQUIREMENTS FOUND IN
THE UNITED STATES DEPARTMENT OF VETERANS AFFAIRS TECHNICAL
INFORMATION LIBRARY, INCLUDING BUT NOT LIMITED TO THE
PHYSICAL SECURITY MANUAL, HVAC DESIGN MANUAL, AND STEAM,
HEATING HOT WATER, AND OUTSIDE DISTRIBUTION SYSTEM DESIGN
MANUAL. ALL WORK SHALL ALSO CONFORM TO ALL FEDERAL, STATE,
AND LOCAL CODES, INCLUDING BUT NOT LIMITED TO THE
INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL
CODE.
C. INSTALL ALL EQUIPMENT AND DEVICES IN ACCORDANCE WITH THEIR
RESPECTIVE MANUFACTURER’S INSTALLATION INSTRUCTIONS AT A
LEVEL OF QUALITY AND WORKMANSHIP CONSISTENT WITH THESE
DOCUMENTS. ANY DEVIATIONS BETWEEN THE INSTALLATION
INSTRUCTIONS AND THESE DOCUMENTS WILL BE BROUGHT TO THE
ATTENTION TO THE COR BEFORE ANY COURSE OF ACTION BY THE
CONTRACTOR IS INITIATED, INCLUDING PURCHASE OF EQUIPMENT.
D. CONTRACTOR SHALL COORDINATE ALL WORK DESCRIBED AND
ILLUSTRATED IN THESE DRAWINGS. LOCATIONS OF PIPING AND
EQUIPMENT AS INDICATED ON THESE DRAWINGS ARE APPROXIMATE
AND SUBJECT TO ADJUSTMENTS IN THE FIELD. OFFSET PIPING, AND
SHIFT EQUIPMENT AS REQUIRED TO AVOID INTERFERENCE AND
CONFLICTS IN THE FIELD. COORDINATE DUCT AND PIPE ROUTING AND
EQUIPMENT LOCATIONS WITH PLUMBING AND ELECTRICAL
INSTALLATIONS AND WITH BUILDING STRUCTURAL MEMBERS.
E. THESE MECHANICAL DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE
NOT TO BE SCALED. BEFORE BEGINNING WORK, THE CONTRACTOR
SHALL VISIT THE SITE AND COMPLETE MEASURED SURVEY AND
CREATE LAYOUT DRAWINGS AS REQUIRED BY THE
SPECIFICATIONS. WORK SHALL NOT BEGIN UNTIL ALL LAYOUT
DRAWINGS ARE APPROVED BY THE COR.
F. PIPE SUPPORTS ARE NOT SHOWN ON DRAWINGS.
G. SUPPORT ALL PIPING, AND EQUIPMENT FROM PRIMARY BUILDING
STRUCTURAL MEMBERS. PROVIDE ADDITIONAL STRUCTURAL
MEMBERS WHERE NECESSARY TO ACCOMPLISH THIS REQUIREMENT.
H. NEW AND EXISTING SUPPORT, RODS, AND ASSOCIATED
APPURTENANCES SHALL NOT RESTRICT EQUIPMENT SERVICE AND
MAINTENANCE ACCESS. EXISTING SUPPORTS SHALL BE MODIFIED TO
PROVIDE FOR EQUIPMENT SERVICE AND MAINTENANCE ACCESS.
I. CONTRACTOR SHALL PROVIDE A LIST OF ALL MECHANICAL
EQUIPMENT, DEVICES, AND ALL APPURTENANCES REQUIRING POWER
TO THE COR FOR REVIEW AND APPROVAL AS PART OF COORDINATION
FOR THIS PROJECT. LIST ALL ELECTRICAL REQUIREMENT
CHARACTERISTICS, INCLUDING BUT NOT LIMITED TO VOLTAGE,
AMPERAGE, PHASE, DISCONNECTING MEANS, OVER CURRENT
PROTECTION AND ALL CHARACTERISTICS FOR A FULLY FUNCTIONAL
AND COORDINATED SYSTEM. REFER TO ELECTRICAL DRAWINGS FOR
VOLTAGE REQUIREMENTS OF ALL EQUIPMENT.
J. DO NOT USE SCHEDULED EQUIPMENT IDENTIFICATION NUMBERS
SHOWN ON DRAWINGS FOR FINAL EQUIPMENT SIGNS AND FOR
CONTROL SYSTEM SCHEMATICS. CONTACT COR AND OBTAIN FROM
REFRIGERATION AND HVAC MAINTENANCE SUPERVISOR THE
CORRECT NOMENCLATURE AND EQUIPMENT NUMBERS FOR
INCLUSION IN SIGNAGE, CONTROL SCHEMATICS, AND AS-BUILT
DRAWINGS.
SIEMENS CTRL
PANEL
EXISTING
UNIT
HEATER
EXISTING
ELEC. EQUIP
EXISTING
ELEC. EQUIP
FD
FD
FD
COOLING TWR #3COOLING TWR #6COOLING TWR #5
EXISTING
EF
EXISTING
EXHAUST
DUCT
CEILING
MOUNTED
EXHAUST
FAN TO
ROOF
REFRIGERATE
AIR DRYER
EXISTING ELEC. EQUIP
45 KVA
TRANSFORMER
PANEL
HA
EXISTING
FRIDGE
147-CT-2147-CT-1
FD
COOLING TWR #1 COOLING TWR #2
COOLING TWR #4
147-CT-6
CONCRETE
PAD (TYP)
EXISTING
ELEC. EQUIP
EXISTING
ELEC. EQUIP
(E)147-P-4 (E)147-P-2(E)147-P-3
(E)147-P-1
(E)CHILLER 1
(E)CHILLER 4
(E)CHILLER 2
(E)147-P-9
(E)AIR SEPARATOR
(E) 147-P-6
(E)CHILLER 3
(E)147-P-8
(E) 8" CWR
(E
8" C
R
(E
8" C
R
(E
8" C
W R
(E) 10" CWS
(E) 10" CWR
(E) 8" CWS
(E) 10" CR
(E) 8" CWR
(E) 6" CWR
(E) 6" CWS
(E) 10" CWS
(E
C W
R
(E
C W
S
(E
C S
(E) 8" CWR
(E)147-P-7
(E)MUW
(E) 10" CWR
E
LE
C T
R
IC
A L
E
LE
C T
R
IC
A L
ELECTRICAL ELECTRICAL
CONCRETE
PAD (TYP)
(E)TANK
(E
C W
S
(E)FFM
(E)FFM
(E
8" C
W R
(E)VFD - P-3 (E)VFD - P-2 (E)VFD - P-4
(E)VFD - P-5
(E)VFD - P-1
(E)WATER
TREATMENT
(E)VFD - P-6
(E)VFD - P-7
(E)TANK
(E)CHEMICAL
TREATMENT
AI
GROE
G
KNO
W
L E S
J E R
E M Y
NO. 034176
PROFESSIONAL
TIS RE
DEER
G
E
NG I NEE
R
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PLAN
NORTH
TRUE
NORTH
PINEVILLE, LOUISIANA
MD101
502-21-110
JMK RCP/JSP11/09/2022
CHILLER #3
REPLACEMENT
CHILLER PLANT MECHANICAL
DEMOLITION PLAN
BID DOCUMENTS
MD101 DEMOLITION NOTES
NOTE
NUMBER NOTE TEXT
1 (E)147-P-7, CONDENSER WATER PUMP TO BE REUSED IN PROJECT.
CONTRACTOR SHALL EXERCISE THE ISOLATION VALVES TO VERIFY
FUNCTIONALITY BEFORE BEGINNING WORK. THE INTENT IS TO REUSE
EXSTING VALVES, STRAINERS, AND CHECK VALVES FOR THIS
ASSEMBLY. THE CONTRACTOR SHALL PREPARE TO REPLACE ALL
THERMOMETERS AND GAUGES.
2 (E)147-P-6, CONTRACTOR SHALL REMOVE CHILLED WATER PUMP
COMPLETELY. CONTRACTOR SHALL EXERCISE THE ISOLATION VALVES
TO VERIFY FUNCTIONALITY BEFORE BEGINNING WORK. THE INTENT IS
TO REPLACE ALL HYDRONIC SPECIALTY COMPONENTS. REMOVE
EXISTING INERTIA BASE. PATCH AND REPAIR FLOOR AND PREPARE FOR
NEW WORK.
3 (E)CHILLER 3, CONTRACTOR SHALL REMOVE WATER COOLED CHILLER
COMPLETELY. REMOVE ALL CONTROL WIRING, ELECTRICAL WIRING,
AND ALL APPURTENANCES. IT IS THE INTENT TO REUSE THE EXISTING
HOUSEKEEPING PAD.
4 CONTRACTOR SHALL REMOVE EXISTING VFD FOR PUMP (E)147-P-6 AND
ALL ITS APPURTENANCES.
5 CONTRACTOR SHALL REMOVE EXISTING VFD FOR PUMP (E)147-P-7 AND
ALL ITS APPURTENANCES.
1/4" = 1'-0"MD101
1 CHILLER PLANT MECHANICAL PIPING DEMOLITION PLAN
0 4' 8'2'
EXISTING
UNIT
HEATER
EXISTING
ELEC. EQUIP
EXISTING
ELEC. EQUIP
FD
FD
FD
COOLING TWR #3COOLING TWR #6COOLING TWR #5
EXISTING EF
EXISTING
EXHAUST
DUCT
CEILING
MOUNTED
EXHAUST
FAN TO
ROOF
REFRIGERATED AIR DRYER
EXISTING ELEC. EQUIP
45 KVA
TRANSFORMER
PANEL
HA
EXISTING
FRIDGE
147-CT-2147-CT-1
FD
COOLING TWR #1 COOLING TWR #2
COOLING TWR #4
147-CT-6
CONCRETE
PAD (TYP)
EXISTING
ELEC. EQUIP
EXISTING
ELEC. EQUIP
M401
(E)CHILLER 2(E)CHILLER 1
(E)CHILLER 4
(E)147-P-4(E)147-P-2(E)147-P-3
(E)147-P-1
(E)147-P-9
(E)AIR SEPARATOR
(E)147-P-8
147-P-6
(E) 8" CWR
(E) 8" CWR
(E) 8" CWR (E
8" C
R
(E
8" C
R
(E) 6" CWR
(E) 6" CWS
(E) 10" CWS
(E
C W
R
(E
C W
S
(E) 8" CWR
(E) 8" CWS
(E
8" C
R
(E
8" C
R
(E
8" C
W R
(E) 10" CWS
(E) 10" CWR
(E
8" C
W R
(E) 10" CWR
(E)147-P-7
(E) 10" CWS
(E) 10" CWR
(E)TANK
(E)MUW
E
LE
C T
R
IC
A L
E
LE
C T
R
IC
A L
ELECTRICAL ELECTRICAL
CONCRETE
PAD (TYP)
8" CWS
(E)VFD - P-3
(E)VFD - P-2 (E)VFD - P-4
(E)VFD - P-5
(E)VFD - P-1
(E
8" C
W S
(E) 8" CWR
(E) 8" CWS
(E) 6" CWS
(E) 6" CWR
(E
8" C
W R
(E
C W
S
(E
C W
R
(E)WATER
TREATMENT
FFM-2
M-CONTRL-2
FFM-1
M-CONTRL-1
147-CH-3
(E)FFM
(E) 10" CR
10" CS8" CWS
8" CWR
VFD - P-6
VFD - P-7
(E)TANK
(E)CHEMICAL
TREATMENT
RECONNECT EXISTING
CHEMICAL TREATMENT.
AI
GROE
G
KNO
W
L E S
J E R
E M Y
NO. 034176
PROFESSIONAL
TIS RE
DEER
G
E
NG I NEE
R
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PLAN
NORTH
TRUE
NORTH
PINEVILLE, LOUISIANA
MP101
502-21-110
JMK JSP11/09/2022
CHILLER #3
REPLACEMENT
CHILLER PLANT MECHANICAL PIPING
PLAN
BID DOCUMENTS
1/4" = 1'-0"MP101
1 CHILLER PLANT MECHANICAL PIPING PLAN
MP101 NEW WORK NOTES
NOTE
NUMBER NOTE TEXT
1 CONTRACTOR SHALL INSTALL NEW CHILLER IN APPROXIMATE
LOCATION AS EXISTING. REUSE EXISTING HOUSEKEEPING PAD AND
ENLARGE TO FIT NEW EQUIPMENT.
2 CONTRACTOR SHALL INSTALL NEW CHILLED WATER PUMP IN
APPROXIMATE LOCATION AS EXISTING. PROVIDE NEW INERTIA
BASE TO SUPPORT PUMP. GROUT PUMP BASE AFTER FINAL
BALANCING.
3 CONTRACTOR SHALL REMOVE AND REPLACE INSULATION ON
CHILLED WATER SUPPLY AND CHILLED WATER RETURN PIPING TO
THE LIMITS INDICATED. (DEDUCTIVE ALTERNATE)
4 CONTRACTOR SHALL WIDEN EXISTING OPENING TO FIT NEW
EQUIPMENT. SEE ARCHITECTURAL. CLEAR DOOR OPEN SIZE
APPROXIMATELY 88½”X 116½”.
5 CONTRACTOR SHALL INSTALL NEW VFD FOR PUMP 147-P-6 AND ALL
ITS APPURTENANCES. SEE ELECTRICAL PLAN.
6 CONTRACTOR SHALL INSTALL NEW VFD FOR PUMP 147-P-7 AND ALL
ITS APPURTENANCES. SEE ELECTRICAL PLAN.
7 RECONNECT EXISTING CHEMICAL TREATMENT.
0 4' 8'2'
SIEMENS CTRL
FD
FD
M401
(E
C R
147-P-6
(E) 10" CWS
(E) 10" CWR
(E
8" C
W R
(E)CHILLER 4
(E) 8" CWS
(E) 8" CWR
(E) 8" CWR
M401
M401
(E) 6" CWR
(E) 6" CWS
(E) 8" CWR
(E) 8" CR
(E) 8" CR
(E
8" C
W S
(E
C S
8" C
W S
(E
8" C
W R
(E
8" C
W R
(E)147-P-7
(E
8" C
R
(E
8" C
R
(E) 8" CR
(E) 10" CWR
(E) 10" CWS
(E) 8" CWR
(E) 8" CWS
(E) 6" CWR
(E) 6" CWS
EXISTING CONCRETE PAD
147-CH-3
M-CONTRL-2
10" CS
(E) 10" CS
(E)WATER
TREATMENT
8" CWR
8" C
W S
FFM-1
M-CONTRL-1
(E)FFM
10" CR
(E) 8" CWR
(E)CHEMICAL
TREATMENT
Level 1 0' - 0"
Roof 14' - 0"
(E)147-P-7
(E
8" C
W R
EXISTING CONCRETE PADEXISTING CONCRETE PAD
8" CWS
(E) 10" CWR
(E) 8" CWR
(E) 8" CWS
(E) 10" CWS
10" CR
8" CWR
8" CWR
8" CWS
(E
C
S
10" CS
(E) 10" CR
(E) 8" CWR
147-CH-3
(E)WATER
TREATMENT
FFM-2
M-CONTRL-2
FFM-1
M-CONTRL-1
TO PIPING ON ROOF
Level 1 0' - 0"
Roof 14' - 0"
147-P-6
8" C
W R
NEW CONCRETE PAD
(E) 8" CWR
(E) 10" CR
8" C
W R
10" M-CNTRL
NEW INTERTIA BAS
Level 1 0' - 0"
Roof 14' - 0"
EXISTING CONCRETE PAD
(E) 10" CWR
147-CH-3
8" C
W S
8" C
W R
10" CS
AI
GROE
G
KNO
W
L E S
J E R
E M Y
NO. 034176
PROFESSIONAL
TIS RE
DEER
G
E
NG I NEE
R
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PLAN
NORTH
TRUE
NORTH
PINEVILLE, LOUISIANA
M401
502-21-110
JMK RCP/JSP11/09/2022
CHILLER #3
REPLACEMENT
ENLARGED MECHANICAL PIPING PLAN BID DOCUMENTS
1/2" = 1'-0"M401
1 ENLARGED NEW MECHANICAL ROOM MECHANICAL PIPING PLAN
1/2" = 1'-0"M401
2 SECTION MECHANCIAL PIPING NEW WORK
0 2' 4'1'
0 2' 4'1' 1/2" = 1'-0"M401
4 SECTION MECHANICAL PIPING NEW WORK
0 2' 4'1'1/2" = 1'-0"M401
3 SECTION MECHANICAL PIPING NEW WORK
0 2' 4'1'
M401 NEW WORK NOTES
NOTE
NUMBER NOTE TEXT
1 CONNECT NEW CHILLED WATER RETURN PIPING TO EXISTING PIPE
AT THIS APPROXIMATE LOCATION.
2 CONNECT NEW CONDENSER SUPPLY PIPING TO EXISTING PIPE AT
THIS APPROXIMATE LOCATION.
3 CONNECT NEW CHILLED WATER SUPPLY PIPING TO EXISTING PIPE
AT THIS APPROXIMATE LOCATION.
4 NEW 147-CH-3 ON EXISTING CONCRETE PAD. EXTEND PAD AS
NECESSARY TO INSTALL NEW CHILLER.
5 CONNECT NEW CHILLED WATER RETURN PIPING TO EXISTING PIPE
AT THIS APPROXIMATE LOCATION.
6 CONNECT NEW CHILLED WATER RETURN PIPING TO EXISTING PIPE
AT THIS APPROXIMATE LOCATION.
7 CONTRACTOR SHALL REMOVE AND REPLACE INSULATION ON
CHILLED WATER PIPING TO THE LIMITS INDICATED. (DEDUCTIVE
ALTERNATE)
8 CONTRACTOR SHALL INSTALL NEW CHILLED WATER PUMP IN
APPROXIMATE LOCATION AS EXISTING. PROVIDE NEW INERTIA
BASE TO SUPPORT PUMP. GROUT PUMP BASE AFTER FINAL
BALANCING.
9 CONNECT NEW CONDENSER RETURN PIPING TO EXISTING PIPE AT
THIS APPROXIMATE LOCATION.
10 RECONNECT EXISTING CHEMICAL TREATMENT.
(E) TANK
TO PIPING ON ROOF
VAPOR BARRIER AND
MOISTURE MIGRATION
SEAL
PIPE
INSULATION
APPLY INSULATION AND
VAPOR JACKET SEAL
AROUND ROD ON COLD
SERVICE INSTALLATION
TYPE 3 DOUBLE
BOLT PIPE
CLAMP
ADHESIVE (TYPICAL)
TAPE APPLIED AT
EACH BUTT JOINT
TYPE 17
WELDLESS
EYENUT
IN…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .