Project 586-18-101 - Drawings.pdf

PDF 27 MB Posted

Attached to
Y1DA--Project 586-18-101 Renovate Inpatient Ward 2A
Solicitation number
36C25621R0120
Issued by

About this file

This notice describes a federal contract opportunity for renovation services. The Michael E. DeBakey VA Medical Center in Houston, Texas is seeking proposals for site preparation and construction work related to Project 586-18-101 to renovate approximately 26,000 square feet of space currently used as an inpatient ward into physical therapy and occupational therapy facilities. The solicitation will be set aside exclusively for service-disabled veteran-owned small businesses. Interested parties should monitor the website for release of the Request for Proposals and amendments on or around August 4, 2021. Proposals will be accepted for 90 days, and performance and payment bonds will be required from the contractor receiving the award. The work must be completed within 365 calendar days of notice to proceed. The contract value is estimated between $1,000,000 to $5,000,000.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES APPLICABLE TO ALL DRAWINGS FOR

THIS PROJECT

1. ALL NOTES ON ALL DRAWINGS PERTAIN TO THE CONTRACTOR.

2. NO SMOKING IN AREAS OTHER THAN OFFICIALLY MARKED AS SMOKING AREA WILL BE PERMITTED ON VA

PREMISES.

3. THE CONTRACTOR SHALL BE PREPARED TO STOP ANY WORK AND CLEAR UP THE WORK AREA IF SO ASKED

IN MEDICAL SITUATIONS REQUIRING SUCH ACTION.

4. ALL TOOLS AND MATERIAL USED IN THE PROJECT SHALL BE PROPERLY SECURED AT ALL TIMES BY THE CONTRACTOR TO REDUCE THE POSSIBILITY OF ANY OF THESE TOOLS BEING A HAZARD TO PATIENTS, VISITORS OR STAFF.

5. ALL VA PROPERTY THAT IS NOT PERMANENTLY REMOVED FROM VA PREMISES UNDER THIS PROJECT WHICH IS DAMAGED BY CONSTRUCTION OF THIS PROJECT, SHALL BE REPLACED OR REPAIRED TO MATCH OR

EXCEED THE QUALITY THAT EXISTED BEFORE THE DAMAGE.

6. THE CONTRACTOR, AT HIS EXPENSE WILL BE RESPONSIBLE FOR TRAINING EACH MEMBER OF HIS WORK FORCE ON VA POLICIES FOR ON-SITE WORK BEFORE ANY MEMBER WILL BE ALLOWED TO PERFORM WORK ON VA PREMISES. BACKGROUND CHECKS WILL BE REQUIRED ON ALL EMPLOYEES AND ALL EMPLOYEES

MUST BE BADGED IN ACCORDANCE WITH VA POLICE DEPARTMENT AND THE VA.

7. ABSOLUTELY NO VA TOOLS, MATERIALS OR EQUIPMENT WILL BE LOANED OR GIVEN BY THE VA TO ANY

MEMBER OF THE CONTRACTOR’S WORK FORCE AT ANY TIME.

8. ANY SMOKE DETECTORS HAVING ANY POTENTIAL FOR EXPOSURE TO CONSTRUCTION SMOKE, DUST AND DEBRIS SHALL BE SUITABLY ATTENDED TO IN ORDER TO PREVENT ACCIDENTAL ALARM. ALL SUCH ACTION MUST BE FIRST COORDINATED AND CLEARED WITH THE COR AND THE VA SAFETY OFFICER. ALL FIRE ALARM DEVICES SHALL BE ACTIVE WHEN CONTRACTOR’S FORCES ARE VACANT FROM ANY AREA AT ANY

TIME.

9. CONTRACTOR SHALL COORDINATE WITH THE COR AND CONTRACTING OFFICER.

10. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS.

11. GENERAL HOURS OF WORK SHALL BE RESTRICTED FROM 0730 TO 1600 MONDAY THRU FRIDAY EXCEPT FEDERAL HOLIDAYS. CONTRACTOR MAY SUBMIT A REQUEST FOR OFF-HOUR WORK A MINIMUM 72 HOURS IN ADVANCE. APPROVAL IS AT SOLE DISCRETION OF THE VA. WHEN SOME NIGHT/WEEKEND WORK IS

REQUIRED, COORDINATE WITH PHASING PLAN SHEET A101.

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

VA APPROVAL

DEPARTMENT SIGNATURES

MEDICAL CENTER DIRECTOR

MEDICAL CENTER ASSOCIATE DIRECTOR

CHIEF OF STAFF

ASSOCIATE DIRECTOR OF PATIENT CARE

DEPUTY CHIEF OF STAFF /

PHYSICAL MEDICINE & REHAB

SERVICE REPRESENTATIVE

SAFETY OFFICE

PROJECT MANAGER

INFECTION PREVENTION

ENGINEERING CHIEF

DEPARTMENT OF VETERANS AFFAIRS

G.V. (SONNY) MONTGOMERY VAMC

JACKSON, MS

AD101 SECOND FLOOR DEMOLITION

AD102 SECOND FLOOR REFLECTED CEILING DEMOLITION

A101 EXISTING / PHASING PLAN

A102 FIRST FLOOR PLAN

A103 SECOND FLOOR PLAN

A104 LARGE SCALE PLAN

A105 LARGE SCALE PLAN

A106 LARGE SCALE PLAN

A107 1ST FLOOR REFLECTED CEILING PLAN

A108 2ND FLOOR REFLECTED CEILING PLAN

A201 INTERIOR ELEVATIONS

A202 INTERIOR ELEVATIONS

A203 INTERIOR ELEVATIONS

A204 INTERIOR ELEVATIONS

A301 SECTIONS

A401 ENLARGED PLANS

A501 DETAILS

A601 SCHEDULES & DIAGRAMS

G001 COVER SHEET

G002 PROJECT DATA

LS101 LIFE SAFETY PLAN

Project Location

INDEX OF DRAWINGS

ELECTRICAL

ARCHITECTURAL

MECHANICAL

PROJECT NO. 586-18-101

RENOVATE WARD 2A

VICINITY MAP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

9/

/2

4:

:4

PM

G001

COVER SHEET

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

P001 PLUMBING SYMBOLS AND ABBREVIATIONS

PD101 PLUMBING - FIRST FLOOR DEMOLITION

PD102 PLUMBING - SECOND FLOOR DEMOLITION PLAN

P101A PLUMBING - FIRST FLOOR PLAN - AREA A

P101B PLUMBING - FIRST FLOOR PLAN - AREA B

P101C PLUMBING - FIRST FLOOR PLAN - AREA C

P101D PLUMBING - FIRST FLOOR PLAN - AREA D

P102A PLUMBING - SECOND FLOOR PLAN - AREA A

P102B PLUMBING - SECOND FLOOR PLAN - AREA B

P102C PLUMBING - SECOND FLOOR PLAN - AREA C

P102D PLUMBING - SECOND FLOOR PLAN - AREA D

P401 PLUMBING - WASTE & VENT ISOMETRIC

P402 PLUMBING - WATER ISOMETRIC

P601 PLUMBING - DETAILS & SCHEDULES

M001 MECHANICAL SYMBOLS AND ABBREVIATIONS

MD102 MECHANICAL - SECOND FLOOR DEMOLITION PLAN

M102A MECHANICAL - SECOND FLOOR PLAN - AREA A

M102B MECHANICAL - SECOND FLOOR PLAN - AREA B

M102C MECHANICAL - SECOND FLOOR PLAN - AREA C

M102D MECHANICAL - SECOND FLOOR PLAN - AREA D

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

M900 MECHANICAL CONTROLS - SYMBOLS AND

SEQUENCES

M901 MECHANICAL CONTROLS - POINTS LIST

M902 MECHANICAL CONTROLS - ROOM TYPICAL

CAMPUS MAP

Project Location

T001 TECHNOLOGY SYMBOLS & ABBREVIATIONS

TD102 TECHNOLOGY - SECOND FLOOR DEMOLITION PLAN

TD202 TECHNOLOGY DEMOLITION DETAILS

T102 TECHNOLOGY - SECOND FLOOR PLAN

T202 TECHNOLOGY ROOM DETAIL SHEET

T501 TECHNOLOGY DETAILS

T801 RTLS SYMBOLS AND ABBREVATIONS

T802 RTLS - SECOND FLOOR PLAN

TECHNOLOGY

FIRE PROTECTION

F001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

FD101 FIRE PROTECTION - SECOND FLOOR DEMOLITION

PLAN

F102 FIRE PROTECTION - SECOND FLOOR PLAN

F501 FIRE PROTECTION DETAILS

PLUMBING

E001 ELECTRICAL SYMBOLS AND ABBREVIATIONS

ED102 ELECTRICAL - SECOND FLOOR DEMOLITION PLAN

E501 ELECTRICAL DIAGRAMS

E601 ELECTRICAL DETAILS

E602 FIRE ALARM RISER AND MATRIX

E701 ELECTRICAL SCHEDULES

E702 ELECTRICAL SCHEDULES

E710 LIGHTING SCHEDULES

EL102 LIGHTING - SECOND FLOOR PLAN

EP102A POWER - SECOND FLOOR PLAN - AREA A

EP102B POWER - SECOND FLOOR PLAN - AREA B

EP102C POWER - SECOND FLOOR PLAN - AREA C

EP102D POWER - SECOND FLOOR PLAN - AREA D

ES102 SYSTEMS - SECOND FLOOR PLAN

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

ANA

Reg. No. 3470

WOOD

WOOD FINISH

ALUMINUM

STEEL

EARTH

GYPSUM - PLASTER

MASONRY -

CONCRETE BLOCK

RIGID INSULATION

BATT INSULATION

PLYWOOD

CONCRETE

NORTH ARROW

Room name

101ROOM TAG

EQUIPMENT TAG

COLUMN GRID TAG

LEVEL ANNOTATION

BUILDING SECTION

VIEW / DETAIL TITLE

PARTITION TAG

DOOR TAG

CENTERLINE

REVISION CLOUD

BREAK LINE

SPOT ELEVATION

ENLARGED PLAN / DETAIL REFERENCE

x'-x"

BUILDING ELEVATION

WALL SECTION

REVISION

INTERIOR ELEVATION

GLAZING TYPE TAG

SECTION / DETAIL

FLOOR LINES IN EXTERIOR ELEVATION; CENTER

PROPERTY LINE, BOUNDARY LINES

MATCH LINE

FX

BX

WX

WX

WX WXROOM FINISH TAG

FLOORWALL FINISH

BASE

FINISH MATERIAL TAG XX-##

PARTITION WITH CORNER GUARD

PARTITION WITH WALL GUARD

PARTITION WITH END CAP

PARTITION WITH ADDITIONAL BRACING

A203

A1

DRAWING BLOCK TITLE

SCALE: 1"=1'-0"

Name Elevation

A-100

A001

A

A-101

A-101

A-101

A-101

2010: ADA STANDARDS FOR ACCESSIBLE DESIGN.

OCCUPATIONAL SAFETY AND HEALTH STANDARDS, U.S. DEPARTMENT OF LABOR

(OSHA): 29 CFR, PART 1926, AS AMENDED, INCLUDING FINAL RULE.

2019: NFPA 241, CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS.

2018: INTERNATIONAL BUILDING CODE, NO LOCAL AMENDMENTS.

2017: NFPA 70, NATIONAL ELECTRICAL CODE.

2017: VA BARRIER FREE DESIGN STANDARD REV. 11/1/18

2018: IPC INTERNATIONAL PLUMBING CODE, NO LOCAL AMENDMENTS.

2018: IMC INTERNATIONAL MECHANICAL CODE, NO LOCAL AMENDMENTS.

ICC / ANSI 117.1 - 2009 AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND

USEABLE BUILDINGS AND FACILITIES.

2018: NFPA 101, LIFE SAFETY CODE FOR LOCAL JURISDICTION COMPLIANCE.

2018: NFPA 101, LIFE SAFETY CODE FOR FEDERAL CERTIFICATION. *(COMPLY WITH THE

MOST RESTRICTIVE REQUIREMENTS IF THESE TWO NFPA 101 STANDARDS

CONFLICT).

2018: NFPA 99, HEALTH CARE FACILITIES.

2018: GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES,

FACILITIES GUIDELINES INSTITUTE.

JOINT COMMISSION FOR ACCREDITATION OF HEALTHCARE ORGANIZATIONS

(JCAHO), STANDARD EC5.50, INTERIM LIFE SAFETY MEASURES (ILSM), AS

PUBLISHED IN THE COMPREHENSIVE ACCREDITATION MANUAL FOR HOSPITALS:

THE OFFICIAL HANDBOOK (CAMH), 2004 EDITION.

2019: NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.

2019: NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE.

FIRE PROTECTION OFFICE OF SAFETY, HEALTH AND ENVIRONMENTAL

COMPLIANCE (10NA8), 7th EDITION, Dec. 2015.

THE RENOVATE WARD 2A PROJECT INCLUDES RENOVATION OF APPROXIMATELY

19,967 SQUARE FEET OF AREA WITHIN THE EXISTING VA MEDICAL CENTER.

THE WORK GENERALLY INCLUDES BUT IS NOT LIMITED TO:

1. INSTALLATION OF TEMPORARY PARTITIONS, DOOR AND OTHER PROTECTIVE

MEASURES TO ISOLATE THE CONSTRUCTION AREA. PROVIDE NEGATIVE

PRESSURE FOR DUST CONTROL AND ACOUSTICAL SEPARATION SO AS NOT TO

DISRUPT THE ONGOING ACTIVITIES IN THE HOSPITAL.

2. TEMPORARY MODIFICATIONS OR RELOCATION OF EXISTING SYSTEMS TO

PRESERVE EXISTING LIFE SAFETY FEATURES SUCH AS EXITS, SPRINKLER

SYSTEMS, ALARM SYSTEMS AND OTHER SPECIAL SYSTEMS.

3. DEMOLITION OF THE EXISTING CONSTRUCTION IN THE FOOTPRINT OF THE

PROJECT SITE AND SAFE REMOVAL AND DISPOSAL OF DEBRIS.

4. INSTALLATION OF NEW PARTITION SYSTEM, CEILING SYSTEM AND ALL

PLUMBING, MECHANICAL AND ELECTRICAL SYSTEMS AS DEFINED IN THE

DOCUMENTS TO INTERFACE WITH EXISTING SYSTEMS.

5. PHASING OF THE WORK SUCH THAT THE ABOVE CEILING WORK OUTSIDE OF

THE PROJECT SITE AND SIMILAR WORK OUTSIDE OF THE PROJECT AREA BE

SCHEDULED TO MINIMIZE DISRUPTION AND DOWN-TIME TO AREAS OUTSIDE OF

THE PROJECT SITE.

6. INSTALLATION OF ALL ARCHITECTURAL FINISHES AND BUILT-IN EQUIPMENT.

7. FINAL CLEANING AND REMOVAL OF ALL TEMPORARY PARTITION SYSTEMS AND

PROTECTIVE MEASURES. REPAIR OR RESTORATION OF ANY EXISTING

FINISHES OR CONSTRUCTION DAMAGED DURING THE CONSTRUCTION

PROCESS.

8. FINAL TESTING OF NEW SYSTEMS, TRAINING AND DEMONSTRATION OF NEW

SYSTEMS AND SUBMISSION OF CLOSE-OUT DOCUMENTS.

9. MODIFICATIONS TO EXISTING HVAC, PLUMBING, ELECTRICAL, FIRE

PROTECTION AND SPECIAL SYSTEMS.

GENERAL NOTES

A. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE

COMPLEMENTARY. SPECIFIC INFORMATION MAY BE FOUND IN

EITHER OR BOTH.

B. CONTRACTOR TO VISIT THE SITE PRIOR TO BIDDING AND

BECOME FAMILIAR WITH ALL ASPECTS OF THE WORK. FAILURE

TO INSPECT THE SITE OR FULLY ACQUAINT HIMSELF WITH THE

PLANS AND SPECIFICATIONS PRIOR TO BIDDING WILL NOT

RELIEVE THE CONTRACTOR OF PERFORMANCE OF ANY OF THE

WORK REQUIRED BY EXISTING CONDITIONS OR THE INTENT OF

THE CONTRACT DOCUMENTS. BID SUBMITTAL SHALL REFLECT

ANY EXTRANEOUS CONDITIONS THAT MAY OCCUR.

C. LAYOUT OF WORK

1. EXERCISE PROPER PRECAUTION TO VERIFY ALL EXISTING

CONDITIONS AND LAYOUT OF THE WORK. CONTRACTOR TO

NOTIFY THE CONTRACTING OFFICER OF ANY DISCREPANCIES

IMMEDIATELY.

.2 CONTRACTOR IS RESPONSIBLE FOR ANY ERROR

RESULTING FROM FAILURE TO EXERCISE SUCH PRECAUTION.

SUCH ERROR WILL NOT BE CONSIDERED SUBSEQUENTLY AS A

BASIS FOR EXTRA COMPENSATION.

3. GC TO LAYOUT WORK AND BE RESPONSIBLE FOR ALL

LINES, MEASUREMENTS OF THE BUILDING AND OTHER WORK

EXECUTED UNDER CONTRACT.

4. SHOULD A CONTRACTOR FIND DISCREPANCIES IN, OR

OMISSIONS FROM THE DRAWINGS OR SPECIFICATIONS OR

SHOULD HE BE IN DOUBT AS TO THEIR MEANING, HE SHOULD

NOTIFY THE CONTRACTING OFFICER AT ONCE.

D. EXAMINATION

1. ANY DISCREPANCIES, ERRORS OR OMISSIONS

DISCOVERED IN THE CONTRACT DOCUMENTS BY THE

CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE

CONTRACTING OFFICER BEFORE PROCEEDING WITH RELATED

WORK, OTHERWISE THE CORRECTION OF SUCH ITEMS IS THE

RESPONSIBILITY OF THE CONTRACTOR.

E. CODES AND STANDARDS

1. ALL WORK, MATERIALS AND INSTALLATION SHALL BE IN

STRICT ACCORDANCE'S WITH ALL VA AND NATIONAL BUILDING

CODES, LATEST EDITION.

2. DESIGN LOADS AND CODE RESTRICTIONS FOR ALL DESIGN

CONSIDERATIONS SHALL CONFORM TO THE VA AND NATIONAL

GOVERNING CODES.

F. DEMOLITION

1. THIS SECTION IS INCLUDED FOR GENERAL REFERENCE OF

DEMO WORK BY THE GENERAL CONTRACTOR.

2. DEMOLITION INCLUDES OBJECTS IDENTIFIED BY THE

CONTRACT DOCUMENTS AND SPECIFICATIONS.

3. ARRANGE WITH THE OWNER A CONVENIENT TIME TO

PERFORM DEMOLITION WORK.

4. THE CONTRACTOR SHALL REPAIR, RESTORE AND

REPLACE PORTIONS OF CONSTRUCTION WHERE INDICATED ON

DRAWINGS OR AS REQUIRED TO INSTALL THE WORK. ANY

PORTIONS OF THE CONSTRUCTION WHICH ARE CRACKED,

SPALLED, BROKEN, MISSING OR OUT OF LINE OR ADJUSTMENT,

MECHANICALLY OR STRUCTURALLY UNSOUND OR UNSAFE,

SHALL BE REMOVED, REPLACED, RESTORED OR

SATISFACTORILY REPAIRED.

5. REMOVE, PROTECT AND REINSTALL ALL ITEMS AFFECTED BY

CONSTRUCTION THAT ARE NOT INDICATED TO BE REMOVED

INCLUDING, BUT NOT LIMITED TO SPEAKERS, WIFI AND OTHER

EXISTING MISCELLANEOUS DEVICES.

G. ALL WORK SHALL BE PERFORMED IN CONFORMANCE WITH

APPLICABLE STANDARD SPECIFICATIONS. WORKMANSHIP AND

MAINTAINING STANDARDS OF QUALITY SHALL BE THE

RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE

GENERAL CONTRACTOR SHALL PROVIDE ALL WORK SHOWN IN

THESE CONTRACT DOCUMENTS AND IS REQUIRED TO PROVIDE

A COMPLETE, FINISHED, FULLY OPERABLE INSTALLATION,

UNLESS OTHERWISE NOTED. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR AND EACH OF THE SUBCONTRACTORS TO BE

ACQUAINTED WITH ALL PROJECT REQUIREMENTS AND BUILDING

STANDARDS REGARDLESS OF WHETHER THEY HAVE BEEN

SPECIFICALLY REFERENCED IN THE DOCUMENTS OR NOT.

I. CONTRACTOR SHALL COORDINATE WITH THE CONTRACTING

OFFICER THE SELECTION AND APPROVAL OF ALL SUBSTITUTED

ITEMS PRIOR TO SUBMISSIONS OF THE BID. IT IS EACH

CONTRACTOR'S RESPONSIBILITY TO ENSURE AND TO

DEMONSTRATE THAT ALL SUBSTITUTIONS USED IN THE WORK

COMPLY WITH THE CONTRACT DOCUMENTS. SHOULD A

SUBSTITUTED PRODUCT FAIL TO PERFORM FOR ANY REASON,

WHERE THE ORIGINALLY SPECIFIED PRODUCT WOULD HAVE

PERFORMED PROPERLY, THE CONTRACTOR SHALL PERFORM

ALL WORK NECESSARY TO INCORPORATE THE ORIGINALLY

SPECIFIED PRODUCT AT NO ADDITIONAL COST.

J. EACH SUBCONTRACTOR SHALL CHECK AND VERIFY PRIOR TO

BID, ALL PLANS, SPECIFICATIONS, EXISTING CONDITIONS AND

DIMENSIONS AT THE JOB SITE AND SHALL NOTIFY THE

CONTRACTING OFFICER OF ANY DISCREPANCIES IN OR

BETWEEN THE CONTRACT DOCUMENTS AND THE FIELD

CONDITIONS PRIOR TO COMMENCING THE WORK.

K. DO NOT TAKE SCALED MEASUREMENTS FROM THESE

DRAWINGS. CONSULT WITH THE COR FOR MISSING DIMENSIONS.

L. EACH CONTRACTOR SHALL ANALYZE THE CONTRACT

DOCUMENTS AND IMMEDIATELY REPORT ANY DISCREPANCIES

TO THE CONTRACTING OFFICER PRIOR TO BID. EACH

CONTRACTOR SHALL BE REQUIRED TO CORRECT ANY

DEFECTIVE WORK CAUSED BY WORK DONE AS A RESULT OF

INCONSISTENCIES OR DISCREPANCIES IN THE DRAWINGS WHEN

CLARIFICATION FROM THE CONTRACTING OFFICER HAS NOT

BEEN SOUGHT.

M. ARCHITECTURAL, PLUMBING, ELECTRICAL, MECHANICAL AND

ALL OTHER DOCUMENTS SHALL BE REVIEWED AND

COORDINATED BY THE CONTRACTOR. REPORT ANY

INCONSISTENCIES WITHIN THE DOCUMENTS TO THE

CONTRACTING OFFICER.

N. CONTRACTOR SHALL PROVIDE THE COR WITH A SET OF

REPRODUCIBLE AS-BUILT DOCUMENTS AND DVD AT THE

PROJECT CLOSE-OUT PER SPECIFICATIONS.

O. AS SCOPE AND PERFORMANCE DOCUMENTS, THE DRAWINGS

AND SPECIFICATIONS INDICATE THE MINIMUM WORK REQUIRED

FOR THE PERFORMANCE AND COMPLETION OF BUILDING

ASSEMBLIES. THE CONTRACTOR SHALL BE SOLELY

RESPONSIBLE FOR THE FABRICATION AND INSTALLATION OF ALL

MISCELLANEOUS METAL ITEMS INDICATED, DESCRIBED OR

IMPLIED ON ALL DRAWINGS. MISCELLANEOUS METAL ITEMS,

WITHIN OR REQUIRED TO SUPPORT AN ASSEMBLY, WHETHER

OR NOT ATTACHED TO THE STRUCTURE, ARE THE

RESPONSIBILITY OF THE GENERAL CONTRACTOR AND HIS

SUBCONTRACTORS WHETHER THEY ARE SHOWN OR NOT

SHOWN ON THE ARCHITECTURAL, STRUCTURAL, CIVIL,

MECHANICAL OR ELECTRICAL DRAWINGS. SUCH ASSEMBLIES

INCLUDE BUT ARE NOT LIMITED TO EXTERIOR AND INTERIOR

WALL, CEILING, PARTITION, ROOF, MECHANICAL AND

ELECTRICAL ASSEMBLIES AS WELL AS ALL SIMILAR

ASSEMBLIES. ANY MISCELLANEOUS METAL ITEMS INDICATED

ON THE ARCHITECTURAL DRAWINGS AND NOT SHOWN ON

STRUCTURAL DRAWINGS SHALL BE A MINIMUM OF L3x3x1/2", C7x9.8, 3/8" PLATE OR TS4x4x3/8" UNLESS OTHERWISE

APPROVED BY THE STRUCTURAL ENGINEER. STEEL BEAMS

SHOWN ON THE ARCHITECTURAL DRAWINGS BUT NOT ON THE

STRUCTURAL DRAWINGS SHALL BE ASSUMED TO BE A MEDIUM

WEIGHT BEAM CONNECTED FROM COLUMN TO COLUMN WITH A

SIZE CONSISTENT WITH THE SCALED HEIGHT OF THE BEAM.

P. ALL CONTRACTORS WORKING IN THE HOSPITAL WILL HAVE

TO GO THROUGH A BASIC BACKGROUND CHECK. THE PROCESS

WILL REQUIRE FINGERPRINTING AND APPROXIMATELY THREE

WEEKS OF PROCESSING TIME BEFORE WORKERS /

CONTRACTORS CAN ENTER THE PROJECT AREA.

AFF ABOVE FINISHED FLOOR

ACT ACOUSTICAL CEILING TILE

ALUM ALUMINUM

BD BOARD

BOT BOTTOM

BUR BUILT-UP ROOFING

CIP CAST-IN-PLACE

CEM CEMENT

CTR CENTER

CL CENTER LINE

CT CERAMIC TILE

CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

CO CLEANOUT, CASED OPENING

COL COLUMN

CONC CONCRETE

COR CONTRACTING OFFICER OF RECORD

CJ CONTROL JOINT

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DR DOOR

DS DOWNSPOUT

EWC ELECTRIC WATER COOLER

EQ EQUAL

EXP EXPANSION

EJ EXPANSION JOINT

FRP FIBER REINFORCED POLYESTER

FIN FLR FINISH FLOOR

FE FIRE EXTINGUISHER

FD FLOOR DRAIN

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GYP GYPSUM

HVAC HEATING, VENTILATING & AIR CONDITIONING

HEPA HIGH EFFICIENCY PARTICULATE AIR

HM HOLLOW METAL

INT INTERIOR

LAM LAMINATE

LAV LAVATORY

MO MASONRY OPENING

MECH MECHANICAL

MTL METAL

MOD BIT MODIFIED BITUMEN

MS MOP SINK

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTERS

OPP OPPOSITE

O/O OUT TO OUT

OA OVERALL

OH OVERHANG

PT PAINT

PNL PANEL

PTD PAPER TOWEL DISPENSER

PLAS PLASTER

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLYWD PLYWOOD

PL PROPERTY LINE

QT QUARRY TILE

RA RETURN AIR

REV REVISION

RTU ROOF TOP UNIT

RO ROUGH OPENING

SAB SOUND ATTENUATION BATTS

SND SANITARY NAPKIN DISPENSER

SJ SCORED JOINT

SS SERVICE SINK, STAINLESS STEEL

SIM SIMILAR

SD SOAP DISPENSER

SC SOLID CORE

TER TERRAZZO

TPD TOILET PAPER DISPENSER

TO_ TOP OF_

UNO UNLESS NOTED OTHERWISE

UR URINAL

VFCI VA FURNISHED, CONTRACTOR INSTALLED

VFVI VA FURNISHED, VA INSTALLED

VAV VARIABLE AIR VOLUME

VTR VENT THROUGH ROOF

VCT VINYL COMPOSITION TILE

WC WATER CLOSET

WR WEATHER RESISTANT

WD WOOD

GENERAL SCHEDULING NOTE TO CONTRACTOR

1. WORK FOR EACH AREA IS TO BE COORDINATED WITH THE COR OR PROJECT ENGINEER.

THE BUILDING SHALL REMAIN OCCUPIED THROUGHOUT CONSTRUCTION. WORK SHALL

BE ARRANGED TO ALLOW AS LITTLE INTERRUPTION AND INCONVENIENCE AS POSSIBLE.

2. THE CONTRACTOR IS TO SUBMIT A WRITTEN SCHEDULE OF WORK TO THE COR FOR

APPROVAL WHICH DETAILS CONSTRUCTION START AND CONSTRUCTION COMPLETION

FOR EACH AREA. SCHEDULE OF WORK SHALL BE SUBMITTED AND APPROVED BY THE

COR PRIOR TO STARTING ANY WORK ACTIVITIES

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

MATERIAL SYMBOLS

GRAPHIC SYMBOLS

CODES

PROJECT DESCRIPTION

CLIENT

PROJECT NAME

PROJECT ADDRESS

OCCUPANCY TYPE

PROJECT GROSS FLOOR

AREA

HEIGHT ABOVE GROUND

NUMBER OF STORIES

TYPE OF CONSTRUCTION

Veterans Administration

Renovate Ward 2A

1500 E. WOODROW WILSON AVE, JACKSON, MS

PROJECT DATAABBREVIATIONS

20,018 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

8/

/2

8:

:1

AM

G002

PROJECT DATA

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

ANA

Reg. No. 3470

HEALTH CARE (NFPA)

INSTITUTIONAL I2 (IBC)

28'

4 STORIES

TYPE 1A (IBC)

TYPE 1 (332)(NFPA)

SP

SP

SP SP

SP

SP

SP

SP

SP

SP

SP SPSP SP SP SP SP SP SP SP

SP SPSP SP SP SP SP SP SP SP SP SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

S S

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP SPSP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP

SP

SP

SP

SP

SP

SP SPSP

SP

SP

SP

SP

SP

SP

SP

SP

SP

S S

S S

S SS

S S

S S

S

SP

SP

SP

SP

SP

SP

SP

SP

SP SPSP SP SP SP SP SP SP SP SP SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP SPSP SP SP SPSP SP SP SP SP SP SP SP

SP SPSP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP SP

SP SPSP SP SP SP SP SP

SP

SP

S S

S S

S S

S S

S S

S S

S S

S S

S S

S

S S

S S

SP

SP

SP SP

S S

SS

S S

SP

SP

SP SPSP SP SP SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP SPSP SP SP SP SP SP

SP

SP

S S

S

S S

S S

S S

S S

S S

S S

S SS

SP SPSP

SP SP

SP SP

SP

SP

SP

SP

SP SPSP SP SP

SP SP

S S

SP

SP

SP ONE HOUR FIRE BARRIER WALL ASSEMBLY

TWO HOUR FIRE BARRIER WALL ASSEMBLY

30 MINUTE SMOKE BARRIER WALL ASSEMBLY

SMOKE PARTITION WALL ASSEMBLY

TRAVEL DISTANCE TO EXIT (TD)

EXIT LIGHT SIGN (SEE ELECT)

COORDINATE WALL VERSUS CEILING MOUNTED

RECESSED FIRE EXTINGUISHER & CABINET

RATED DOOR; INDICATES REQUIRED RATING

ACCUMULATION SPACE

HAZARDOUS AREA

LEGEND

FEC

S S

SP SP

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

TD = 176 FT to Exit

EXIT

Treatment

Treatment

Treatment

Student Room

Conference / Multipurpose

Patient Toilet 234 Treatment

Treatment 236 Splint Fabrication

Yoga/Tai Chi Room

CVT Room

OT Gymnasium

Staff Workroom

Staff Workroom

PT Gymnasium

Housekeeping

Vestibule

Storage

Rec Supervisor

Rec Gym

Elevator

Womens Restroom

Vestibular Rehab

UV Treatment

Treatment 275Mobility Storage

Mobility

Storage

Cube Stations

Office Supply

Chief

Stair

Reception

Waiting Area

Supervisor

Cardio/Pulmonary

Sub-Wait

Patient Toilet 214Treatment

Treatment

Break Room

Female Staff RR

EMG

Male Staff RR

Supervisor

EMG

Mechanical

Elect

Storage

Stair

Mens Restroom

Stair

Elec / Storage Room

Provider Workroom

Treatment

Treatment

Treatment

Scales

Nursing Workroom

Storage

Lymphedema/CVT

Clean Supply

Medication

Telecommunications

Chute

AO Office

Staff Toilet

ADL

Waiting

MAS

Gym Storage

Priv Treatment

Priv Treatment

Priv Treatment

Corridor 200B

Corridor 200C

Corridor 200D

Corridor 200A

Toilet

Janitor

TD = 181 FT

TD = 170 FT to Exit

EXIT

FEC

FEC

FEC

FEC

FEC

Storage

FEC

TD

FT

FEC

FEC

TD

= 7

4 F T

TO

FE

C

FEC

FEC

Janitor

EXIT

EXISTING STAIR TO REMAIN

EXISTING STAIR TO REMAIN

EXISTING STAIR TO REMAIN

EXISTING TO REMAIN

EXISTING 1 HOUR FIRE RATED WALL & DOOR TO REMAIN

Fire Alarm 269.1

45 45

EXISTING RATED FIRE

WALLS TO REMAIN

5"

ACCUMULATION SPACE :

6 SQ FT / AMBULATORY PERSON OR

30 SQ FT / NON-AMBULATORY PERSON

STAIR EGRESS CAPACITY :

STAIRS 48" ÷ .3 = 160 PERSONS

DOORS 34" ÷ .2 = 170 PERSONS

STAIR EGRESS CAPACITY :

STAIRS 48" ÷ .3 = 160 PERSONS

DOORS 34" ÷ .2 = 170 PERSONS

STAIR EGRESS CAPACITY :

STAIRS 48" ÷ .3 = 160 PERSONS

DOORS 34" ÷ .2 = 170 PERSONS

SMOKE COMPARTMENT 2A SMOKE COMPARTMENT 2B

SMOKE COMPARTMENT 2A SMOKE

COMPARTMENT

2B

SMOKE

COMPARTMENT

2C

SMOKE

COMPARTMENT

2A

SMOKE

COMPARTMENT

2C

SMOKE

COMPARTMENT

2C

SMOKE

COMPARTMENT

2A

SMOKE

COMPARTMENT

2C

SMOKE

COMPARTMENT

2A

TD = 123 FT to Smoke COMPARTMENT 2A

TD

FT

to Sm oke

CO

MP

AR

TM

EN

T 2 A

SUITE 2A SUITE 2A

COMPARTMENT 2A CMPT 2BCOMPARTMENT 2C TD = 95 FT to Smoke COMPARTMENT 2B

EXISTING WALL & DOOR TO REMAIN

EXISTING WALL &

DOOR TO REMAIN

1. ALL FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS & SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. THE ARE TO BE LOCATED IN ACCESSIBLE CONCEALED FLOOR, FLOOR- CEILING OR ATTIC SPACES; BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL AND AT INTERVALS NOT EXCEEDING 30' MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION; AND INCLUDE LETTERING NOT LESS THAN 3" IN HEIGHT WITH A MINIMUM 3/8" STROKE IN A CONTRASTING COLOR INCORPORATING THE SUGGESTED

WORDING. "FIRE AND/OR SMOKE BARRIER-PROTECT ALL OPENINGS" OR OTHER WORDING.

2. PROVIDE SURFACE MOUNTED LIGHT FIXTURES AT RATED CEILINGS, UNLESS NOTED/DETAILED OTHERWISE.

3. REFER TO ELECTRICAL DRAWINGS FOR STROBE, FIRE ALARM AND CARBON MONOXIDE DETECTORS, EMERGENCY LIGHTS, PULL STATIONS, FIRE PANEL LOCATIONS, OTHER

AUDIO AND VISUAL DEVICES, INCLUDING LOCATIONS AND MOUNTING HEIGHT.

4. PROVIDE CORRESPONDING RATED ACCESS PANEL AT RATED WALLS/CEILINGS. LATCHING AND FINISH TO BE AS SPECIFIED.

5. REFER TO CORRESPONDING ARCHITECTURAL DRAWINGS FOR WALL AND FLOOR DETAILS.

6. GC TO PROVIDE CORRESPONDING FIRE CAULK AT RATED WALLS.

7. SMOKE & DRAFT CONTROL - FIRE DOOR ASSEMBLIES SHALL ALSO MEET THE REQUIREMENTS FOR A SMOKE AND DRAFT CONTROL DOOR ASSEMBLY TESTED IN

ACCORDANCE WITH UL1784. DOOR LOUVERS ARE PROHIBITED. INSTALLATION OF SMOKE DOORS SHALL BE IN ACCORDANCE WITH NFPA 105.

8. PER NFPA 101-8.3.4 GLAZING IN DOOR ASSEMBLIES - IN A 20-MINUTE FIRE DOOR ASSEMBLY, THE GLAZING MATERIAL IN THE DOOR ITSELF SHALL HAVE A MINIMUM FIRE-

PROTECTION RATED GLAZING OF 20 MINUTES AND SHALL BE EXEMPT FROM THE HOSE STREAM TEST.

9. PROVIDE THROUGH-PENETRATION FIRESTOP SYSTEM AS REQUIRED PER THE FIRE RESISTANCE RATING OF THE WALL. REFER TO NFPA 101-8.3.5.

10. PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OF THE CEILING MEMBRANE OR A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH NFPA 101-8.3.5.

11. PROVIDE WALL MOUNTED EXIT SIGNS. LOCATE ABOVE ALL EXIT DOORS. REFER TO ELECTRICAL DRAWINGS FOR MOUNTING HEIGHTS AND MODELS.

12. WHERE AN AIR DUCT PENETRATES ONLY ONE FLOOR OR ONE FLOOR AND AN AIR-HANDLING EQUIPMENT PENTHOUSE FLOOR, AND THE AIR DUCT CONTAINS A FIRE DAMPER

LOCATED WHERE THE DUCT PENETRATES THE FLOOR, AN AIR DUCT ENCLOSURE SHALL NOT BE REQUIRED.

13. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION DAMPERS LOCATION TO BE COORDINATED AT ALL SMOKE AND/OR FIRE

RATED PARTITIONS. REFER TO CODE COMPLIANCE PLANS, ELECTRICAL DRAWINGS FOR WIRING DESIGN AND MECHANICAL DRAWINGS.

14. PORTABLE FIRE EXTINGUISHERS SHALL BE SELECTED, INSTALLED AND MAINTAINED IN ACCORDANCE NFPA 10. BASED ON THIS OCCUPANCY TYPE, CLASS A FOR

ORDINARY(MODERATE) HAZARD OCCUPANCY TYPE 2-A FIRE EXTINGUISHERS ARE REQUIRED NO MORE THAN 75' APART AND ON EACH STORY PER TABLE 6.2.1.1 IN NFPA 10.

15. PROVIDE RECESSED FIRE EXTINGUISHERS AS INDICATED. MOUNT FIRE EXTINGUISHER IN OR WITHOUT CABINET AT 48" AFF TO THE HANDLE. REFER TO SPECIFICATIONS.

16. CONTRACTOR TO PROVIDE PORTABLE FIRE EXTINGUISHERS EVERY 75’ ON THE JOB SITE DURING CONSTRUCTION.

17. BUILDING UNDER EMERGENCY GENERATOR POWER AS WELL AS UPS. REFER TO OWNER PROVIDED INFORMATION FOR EXISTING SYSTEM REQUIREMENTS.

18. WHERE CONDUIT, CABLES, AND OTHER ELECTRICAL PROVISIONS PENETRATE RATED WALL AND FLOOR PENETRATIONS PROVIDE ASSEMBLIES CLASSIFIED WITH A UL

DESIGNATION AND COMPLY WITH ALL APPLICABLE CODES AND CORRESPONDING TESTING. SUBMIT SUBMITTALS WITH INDICATED UL DESIGNATIONS FOR EACH CONDITION.

19. CONTRACTOR TO SEAL ALL VOIDS AT INTERSECTION OF PARTITIONS AND FLOOR OR SLAB CONDITIONS, BETWEEN PIPE SLEEVES, AND OTHER PENETRATIONS AT SMOKE

AND FIRE RATED WALL AND FLOOR PENETRATIONS.

20. NO PENETRATIONS UNRELATED FOR THE PURPOSE OF THE EXIST ACCESS STAIRWAY SHALL BE PERMITTED IN EXIT ACCESS STAIRWAY ENCLOSURES. CONTRACTOR TO

NOT INSTALL ELECTRICAL BOXES/OUTLETS, SWITCHES, ETC NOT FOR USE FOR THE EXIT ACCESS STAIRWAY AT ALL THE FIRE RATED PARTITIONS.

21. REFER TO ELECTRICAL DRAWINGS FOR EMERGENCY GENERATOR LOCATION AND REQUIREMENTS.

22. EMERGENCY LIGHTING SHALL BE DESIGNED IN ALL PATHS OF EGRESS, IN ROOMS WITH AN OCCUPANCY LOAD OF 50 OR MORE.

CODE COMPLIANCE GENERAL NOTES

OCCUPANCY TYPE ______________________

OCCUPANT LOAD ______________________

MAXIMUM TRAVEL DISTANCE ______________________

MAXIMUM COMMON PATH OF TRAVEL ______________________

MAXIMUM DEAD END ______________________

MAXIMUM EXIT CAPACITY ______________________

HEALTH CARE (NFPA 101)

194 PERSONS

200 FT.

100 FT.

30 FT.

480 OCCUPANTS

SMOKE COMPARTMENT SIZE SF ALLOWABLE SIZE SF ALLOWABLE TRAVEL DISTANCE FT ACTUAL TRAVEL DISTANCE TO ANOTHER ZONE

SMOKE COMPARTMENTS (nfpa 101 19.3.7)

SMOKE COMPARTMENT 2A 11,098 22,500 200 95

SMOKE COMPARTMENT 2B N/A 22,500 200 N/A

SMOKE COMPARTMENT 2C 8,920 22,500 200 181

SUITE SUITE ID NAME USE SIZE (SF) MAX SIZE (SF) VARIANCE

SUITE INFORMATION (nfpa 101 19.2.5.7.3)

2A OT GYMNASIUM &

PT GYMNASIUM 5,449 10,000 SF NO VARIANCE

AS TWO EXITS PROVIDED

ROOMS 241, 242, 250, 251,

252, 253, 254, 255, 256, 257, 258, 259

OCCUPATIONAL THERAPY, PHYSICAL THERAPY,

PATIENT CARE, NON-SLEEPING SUITE

TYPE AREA LOAD FACTOR OCCUPANTS

OCCUPANCY LOADS

(nfpa 101 7.3.1.2)

EXERCISE ROOMS WITH EQUIPMENT

WAITING

STORAGE

INPATIENT TREATMENT

DEPARTMENTS

(ALL AREAS OUTSIDE OF THOSE

LISTED ABOVE)

4,746

13,735

50 SF / PERS

15 SF / PERS

500 SF / PERS

240 SF / PERS

TOTAL

95 PERSONS

47 PERSONS

2 PERSONS

50 PERSONS

194 PERSONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

8/

/2

1:

:0

PM

LS101

LIFE SAFETY PLAN

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

1/8" = 1'-0"LS101

1 Second Floor Egress Plan

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

ANA

08/26/2020

F F

G G

H H

E E

D D

C C

B B

A A

20'

- 0

20'

- 0

25'

- 0

20'

- 0

25'

- 0

20'

- 0

20'

- 0

A-234

A-233

A-233a

A-234a

A-235

A-237 A-238

A-238a

A-239a

A-239

A-240

A-241a

A-240a A-241 A-244

A-242 A-244a

A-246a A-246

A-247b

A-247a

A-247 A-250

A-250a

A-251

A-250b

A-252

A-252a

A-236

A-229a

A-243a

A-229

A-243

A-227

A-245

A-225 A-224 A-223

A-221 A-220

Shaft

A-248 A-249

A-210a

A-232

A-232a

A-231a

A-231

A-230

A-228 A-226a

A-228a

A-226 A-222a

A-222b

A-219a

A-222 A-219

A-219b

A-218

A-213

A-212

A-257

A-256

A-255a

A-255

A-210

A-214

A-214a

A-211 A-208 A-206 A-203 A-201

A-208a

A-206a

A-201a

A-203a

A-209 A-207

A-259 A-261

A-205a

A-263a

A-263

A-205

A-204 A-202

A-258 A-260 A-262 A-264 A-265

A-264a

A-265a

A-262a

A-260a

A-217a

A-217

A-215a

A-215 Chase

Stair

JAN

Stair

Chase

JAN

A-253

A-253a

Electrical / Storage Room

Stair

20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 24' - 10" 15' - 2" 20' - 0" 20' - 0" 20' - 0" 19' - 11 1/2" 20' - 0" 22' - 0"

5 5

EXISTING DOORS & FRAME ARE TO

REMAIN - PROTECT FROM DAMAGE

INSTALL TEMPORARY 1 HOUR

FIRE RATED CONSTRUCTION

DOORS PRIOR TO DEMOLITION

LIMITS OF WORK

THIS PARTITION AND THIS SIDE

FINISHES ETC, TO REMAIN

INSTALL TEMPORARY 1 HOUR

FIRE RATED CONSTRUCTION

DOOR PRIOR TO DEMOLITION

LINE OF TEMPORARY ONE HOUR

FIRE RATED PARTITION - INSTALL

PRIOR TO DEMOLITION AND NEW

WORK

REMOVE EXISTING DOOR AND

FRAME AND INSTALL

TEMPORARY ONE HOUR FIRE

RATED CONSTRUCTION

EXISTING DOOR & FRAMES ARE TO

REMAIN - PROTECT FROM DAMAGE

5 5

GENERAL DEMOLITION NOTES

1. ALL EXISTING PLUMBING FIXTURES MAY NOT BE SHOWN IN THIS DRAWING BUT ARE TO

BE REMOVED WITH LINES CAPPED UNDER THIS SCOPE. GC IS TO REFER TO PREVIOUS

RENOVATION DRAWINGS DATED 1/14/97 FOR MORE DETAIL OF ITEMS TO BE REMOVED.

2. REMOVE EXISTING FLOORING THROUGHOUT THE LIMITS OF WORK.

3. REMOVE ALL EXTERIOR WALL FINISHES. EXTERIOR WALL CONSTRUCTION IS TO

REMAIN UNLESS NOTED OTHERWISE.

4. ITEMS SHOWN DASHED ARE TO BE REMOVED, INCLUDING ALL CABINET WORK.

5. REMOVE EXISTING PARTITIONS HANDRAILS, CRASHRAILS, CORNERGUARDS, AND

SHEET WALL PROTECTION PANELS THROUGHOUT THE LIMITS OF WORK.

6. REMOVE EXISTING CEILING AND ALL CEILING DEVICES THROUGHOUT THE LIMITS OF

WORK. SEE ELECTRICAL FOR ITEMS TO BE RELOCATED

7. REMOVE AND DELIVER TO COR ALL EQUIPMENT, FIXTURES, OR ACCESSORIES

IDENTIFIED BY THE COR TO BE SALVAGED. DELIVER SALVAGEABLE ITEMS TO THE COR

AS DIRECTED.

8. REMOVE ALL EXISTING PLUMBING FIXTURES THROUGHOUT THE LIMITS OF WORK.

CONTRACTOR TO COORDINATE REMOVAL OF PLUMBING FIXTURES AND CAPPING

PIPING TO MINIMIZE DISRUPTION TO PLUMBING ABOVE AND BELOW THIS SECOND

FLOOR. RE-ROUTING OF PLUMBING LINES THAT SERVE THE FIRST AND THIRD FLOORS

WILL NEED TO BE PHASED AND COORDINATED WITH THE COR TO MINIMIZE

DISRUPTIONS TO SYSTEMS ABOVE AND BELOW THE SECOND FLOOR.

9. COORDINATE SLAB DEMOLITION AND RESTORATION WITH NEW PLUMBING WORK.

10. COORDINATE DEMOLITION MATERIALS REMOVAL PROCEDURES WITH THE COR.

DEMOLITION KEY NOTES

EXISTING CEILING SYSTEMS TO REMAIN - PROTECT FROM DAMAGE.

TEMPORARILY REMOVE EXISTING CEILING SYSTEM TO INSTALL NEW ABOVE

CEILING WORK. RESTORE OR REPLACE EXISTING CEILING SYSTEM TO MATCH

AFTER INSTALLATION.

REMOVE ALL EXISTING PLUMBING FIXTURES

EXISTING FINISHES ARE TO REMAIN IN THIS AREA - PROTECT FROM DAMAGE

REMOVE ALL DRYWALL AND FURRING AT EXTERIOR WALL AND AROUND ALL

COLUMNS, TYPICAL

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

1/8" = 1'-0"AD101

1 Second Floor Demolition Plan

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

9/

/2

:0 4:

A

M

AD101

SECOND FLOOR DEMOLITION

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

F F

G G

H H

E E

D D

C C

B B

A A

A-234

A-233

A-233a

A-234a

A-235

A-237 A-238

A-238a

A-239a

A-239 A-240

A-241a

A-240a

A-241 A-244

A-242 A-244a

A-246a

A-246

A-247b

A-247a

A-247 A-250

A-250a

A-251

A-250b

A-252

A-252a

A-236

A-229a

A-243a

A-229

A-243

A-227

A-245

A-225 A-224 A-223

A-221 A-220

Shaft

A-248 A-249

A-210a

A-232 A-232a

A-231a

A-231

A-230

A-228 A-226a

A-228a

A-226 A-222a

A-222b

A-219a

A-222 A-219

A-219b

A-218

A-213

A-212

A-257

A-256

A-255a

A-255

A-210

A-214

A-214a

A-211 A-208 A-206 A-203 A-201

A-208a

A-206a

A-201a

A-203a

A-209 A-207

A-259 A-261

A-205a

A-263a

A-263

A-205

A-204 A-202

A-258 A-260 A-262 A-264 A-265

A-264a

A-265a

A-262a

A-260a

A-217a

A-217

A-215a

A-215 Chase

Stair A-216

Stair Chase

A-254 A-253

A-253a

Electrical / Storage Room

Stair

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

SUPPLY AIR GRILL

RETURN AIR GRILL

LIGHT FIXTURE, LAY-IN

LIGHTING FIXTURE, RECESSED

DOWNLIGHTING

REFLECTED CEILING DEMOLITION LEGEND

SUSPENDED ACOUSTICAL

CEILING TILE AND GRID

PLASTER CEILING, PAINTED-

PROVIDE ACCESS PANELS WHERE

REQ'D TO ACCESS MEP VALVES,

CONTROLS, J-BOXES, ETC.

TYPE A

TYPE B

EXIT LIGHTS

A B

GENERAL REFLECTED CEILING DEMOLITION NOTES

1. REMOVE ALL EXISTING CEILING SYSTEMS INCLUDING ALL CEILING MOUNTED DEVICES AND

SYSTEMS WITHIN THE PROJECT AREA. COORDINATE WITH THE COR AND ITEMS TO BE

SALVAGED OR RE-USED. NOT ALL CEILING MOUNTED DEVICES ARE SHOWN ON THIS DRAWING.

CONTRACTORS ARE TO VISIT THE SITE AND TAKE NOTE OF THE SCOPE OF ALL EXISTING

DEVICES TO BE REMOVED.

2. REMOVE ALL EXISTING WINDOW COVERINGS WITHIN THE PROJECT AREA.

3. COORDINATE ANY REMOVAL OF ANY SYSTEM(S) THAT MIGHT DISRUPT OR INTERRUPT THE

ONGOING OPERATIONS OF ANY AREA OUTSIDE OF THE PROJECT AREA.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

8/

/2

5:

:1

PM

AD102

SECOND FLOOR REFLECTED

CEILING DEMOLITION

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

1/8" = 1'-0"AD102

1 Second Floor Reflected Ceiling Plan Demo

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

F F

G G

H H

E E

D D

C C

B B

A A

J J

A-234

A-233

A-233a

A-234a

A-235

A-237 A-238

A-238a

A-239a

A-239

A-240

A-241a

A-240a A-241 A-244

A-242 A-244a

A-246a A-246

A-247b

A-247a

A-247 A-250

A-250a

A-251

A-250b

A-252

A-252a

A-236

A-229a

A-243a

A-229

A-243

A-227

A-245

A-225 A-224 A-223

A-221 A-220

Shaft

A-248 A-249

A-210a

A-232

A-232a

A-231a

A-231

A-230

A-228 A-226a

A-228a

A-226 A-222a

A-222b

A-219a

A-222 A-219

A-219b

A-218

A-213

A-212

A-257

A-256

A-255a

A-255

A-210

A-214

A-214a

A-211 A-208 A-206 A-203 A-201

A-208a

A-206a

A-201a

A-203a

A-209 A-207

A-259 A-261

A-205a

A-263a

A-263

A-205

A-204 A-202

A-258 A-260 A-262 A-264 A-265

A-264a

A-265a

A-262a

A-260a

A-217a

A-217

A-215a

A-215 Chase

Stair

HVAC

Stair

Chase

HVAC

A-253

A-253a

Electrical / Storage Room

Stair

B-228

B-230

B-227 B-225

B-232B-231

TEMPORARY PARTITION, DOOR & FRAME

COORDINATE THE ACCEPTABLE

USE OF THIS DOOR WITH COR

TEMPORARY PARTITION,

DOOR AND FRAME

COORDINATE ACCEPTABLE

CORRIDOR CLEARANCE WITH COR

269.1

GENERAL PHASING NOTES

CONTRACTOR TO COORDINATE WITH COR AND SUBMIT A DETAILED

PHASING PLAN FOR THE WORK BEFORE CONSTRUCTION BEGINS.

PHASING PLAN SHALL BE APPROVED BY THE COR.

THE DETAILED PHASING PLAN SHOULD INCLUDE PHASED DISRUPTION

DURATIONS OF SPACES ABOVE THE SECOND FLOOR AND SPACES

BELOW THE SECOND FLOOR THAT WILL BE NECESSARY TO INSTALL

THIS NEW WORK.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

8/

/2

5:

:4

PM

A101

EXISTING / PHASING PLAN

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

1/8" = 1'-0"A101 1 Second Floor Phasing Plan

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

UP

F F

G G

H H

E E

D D

C C

B B

A A

J J

Closet A-124

Pharmacy A-129

Prosthesis A-127

Elect A-119

HVAC

Patient E-148E Patient

E-148C

Patient Toilet A-120

Isolation A-121

Ex/Trt A-123

Ex/Trt A-125

Ex/Trt A-127 Ex/Trt

A-129

Storage A-109B

S.U.

A-109A

Corridor

Signal Closet A-104

Transformer A-118

Female Toilet A-117

Police Break D-101

E-152

Toilet A-118

On-Call A-118

E-150

Clean Supply E-149B

HVAC

E-140

Linen E-141

E-139

Outpatient Xray E-138C

Medication E-142B

Staff Tlt E-142A

Isol Patient A-148C

Ambulance Entrance E-149

Check-In A-119

Toilet A-132

Toilet E-144A

Procedure P-528

Soiled Uniforms

A-130

Elect A-131

Mens Toilet E-136

Womens Toilet E-136

General Xray E-143

E-138A

E-143A

Social Activities

A-115

Narcotics Vault A-122A

Staff Tlt A-123

Waiting A-109

Air Lock

Male Toilet A-117

Ex/Trt A-122

Ex/Trt A-124

Ex/Trt A-126 Ex/Trt

A-128 A-101A

Corridor A-129A

Patient E-148F

Patient E-148D

Office A-107

Office A-108

Office A-105

Office A-106

Office A-102

Office A-103

Voluntary Service Chief B-117A

Observation A-114

Group Therapy A-113

Chief A-111

Stairs

Corridor A-100

Vestibule

Secretary A-110

Ambulatory Care Pharmacy

A-119

Controlled Substance A-122

Flammable Storage

A-125

Stretcher/Exam A-101

Staff Lounge E-144

Pharmacy Office A-126 Waiting

A-119A

Head Nurse E-146

Patient E-148A

Patient E-148B

Linen A-109

Isol Patient E-148

Nurse Station E-142

Toilet D-102

E-151

Stairs

Pharmacy Waiting A-120

Police Office

EKG

A-129C

Vitals Triage A-133

Vitals Triage A-119B

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

GENERAL NOTES

1. THIS SHEET IS INCLUDED AS A COURTESY AND SHOWS APPROXIMATE LOCATIONS OF

EXISTING SPACES AND PARTITIONS ON THE FLOOR BELOW THE AREA OF WORK TO ASSIST

THE CONTRACTOR IN COORDINATING AND SCHEDULING THE ABOVE CEILING WORK WITH

THE COR. ACCURACY OF THIS PLAN IS NOT GUARANTEED AS IT WAS DRAWN FROM THE

BEST AVAILABLE AS-BUILT DRAWINGS PROVIDED BY THE OWNER. CONTRACTOR TO VISIT

THE SITE TO CONFIRM EXISTING CONDITIONS.

2. WITH THE EXCEPTION OF ABOVE CEILING WORK AND REPAIR OR REPLACEMENT OF CEILING

AND RELATED SYSTEMS, NO NEW WORK IS TO OCCUR ON THIS FLOOR EXCEPT AS

NECESSARY TO INSTALL THE WORK AT THE SECOND FLOOR.

3. ANY DAMAGES OR DISRUPTIONS TO THE EXISTING CONSTRUCTION ON THIS FLOOR AS A

RESULT OF INSTALLING WORK FOR THE SECOND FLOOR SHALL BE REPAIRED AND

COORDINATED WITH THE COR.

CEILING AREAS TO BE DISRUPTED TO

INSTALL / MODIFY ABOVE CEILING

CONSTRUCTION

LEGEND

NOTE

SOME AREAS OF THE FIRST FLOOR SUCH AS PHARMACY AND OTHER AREAS ARE

PARTICULARLY SENSITIVE TO DISRUPTION. THEY WILL REQUIRE CLOSE COORDINATION WITH

THE COR TO IDENTIFY THE AVAILABLE TIMES AND LENGTH OF DISRUPTION THAT WILL BE

ACCEPTABLE TO MINIMIZE DOWN-TIME IN THESE AREAS. SOME AFTER-HOURS WORK SHOULD

BE ANTICIPATED AND CAREFULLY SCHEDULED WITH THE COR. TEMPORARY RE-ROUTING OF

PLUMBING MAY BE REQUIRED TO MINIMIZE DISRUPTION OF SERVICES TO THE THIRD FLOOR

ABOVE THE WORK AREA UNTIL THE PERMANENT PLUMBING SYSTEM IS IN PLACE.

THIS FLOOR PLAN ILLUSTRATES THE GENERAL LAYOUT OF AREAS ON THE FIRST FLOOR BELOW

THE SECOND FLOOR WARD 2A AREA WHERE THE BULK OF DEMOLITION AND CONSTRUCTION

WILL BE OCCURRING. AS THIS DRAWING WAS CREATED FROM THE BEST AVAILABLE DRAWINGS

OF THIS AREA AT THAT TIME, SOME DIFFERENCES TO THE LAYOUT SHOULD BE EXPECTED AS

THERE HAS BEEN SOME MINOR RENOVATION WORK THAT HAS OCCURRED SINCE THE DRAWING

WAS CREATED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

8/

/2

5:

:5

PM

A102

FIRST FLOOR PLAN

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

1/8" = 1'-0"A102 1 First Floor Plan

Revisions: Date:

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

F F

G G

H H

E E

D D

C C

B B

A A

18'

- 0

20'

- 0

20'

- 0

25'

- 0

20'

- 0

25'

- 0

20'

- 0

20'

- 0

J J

A301

A301

Treatment

Treatment

Treatment

Student Room

Conference / Multipurpose

Patient Toilet 234 Treatment

Treatment

Splint Fabrication

Yoga/Tai Chi Room

CVT Room

OT Gymnasium

Staff Workroom

Staff Workroom

PT Gymnasium

Housekeeping

Vestibule

Storage

Rec Supervisor

Rec Gym

Elevator

Womens Restroom

Vestibular Rehab

UV Treatment

Treatment

Mobility Storage

Mobility

Storage

Cube Stations

Office Supply

Chief

Stair

Reception

Waiting Area

Supervisor

Cardio/Pulmonary

Sub-Wait

Patient Toilet 214Treatment

Treatment

Break Room

Female Staff RR

EMG

Male Staff RR 231 Supervisor

EMG

Mechanical

Elect

Storage

Stair

Mens Restroom

Existing Elevators

Stair

Elec / Storage Room

Provider Workroom

Treatment

Treatment

Treatment

Scales

Nursing Workroom

Storage

Lymphedema/CVT

Clean Supply

Medication

Telecommunications

Chute

AO Office

Staff Toilet

ADL

Waiting

MAS

Gym Storage

Priv Treatment

Priv Treatment

Priv Treatment

Corridor 200A

Corridor 200B

Corridor 200C

Corridor 200D

Toilet

Janitor

20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 24' - 10" 15' - 2" 20' - 0" 20' - 0" 20' - 0" 19' - 11 1/2" 20' - 0" 22' - 0"

Corridor 200B

Corridor 200D

Janitor

Storage

A104

A105

A106

A106

Vestibule 249A

Vestibule 249B

Corridor 200GCorridor

200E

Corridor 200F

Corridor 200H

Corridor 200H

G3 G2 G2 G2 G2 G2 G2

E2

G3 G3

H G2

G2

E2

H

H

E

G2

G2

G2 G3 G2 G2 G3 G2 G2 E2 E2

G2

M

G2B2I

E2

IB2

G2

G2G2G2B2G2G2

G2

G2

G2

G2

G2

G2

G2

G2 E2 M

J2 E2

E2

G2 G2B2

H

G2 G2

G2 G3

G2

I

G2 G2

E2

I

E2

G2

E

G2

G2

G2

G2

G2

I

H

E

M2

M2

M2

M2

M2

M2

M2 M2

M2

M2

Fire Alarm 269.1

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

A6

D

E2

E2s

E

B

F

G2

G3

H

I

Ia

M2

J2

M

1/8" = 1'-0"A103 1 Second Floor Plan − Overall

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

9/

/2

:0 5:

A

M

A103

SECOND FLOOR PLAN

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

Revisions: Date:

KEY PLAN

2/A106

2/A106

1/A105 1/A104

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

ANA

Signage Types

F F

E E

D D

C C

A2011A201 2

A201 8

1a

200c

1c

OT Gymnasium

Staff Workroom

Staff Workroom

PT Gymnasium

Housekeeping

Vestibule

Storage

Rec Supervisor

Rec Gym

Elevator

Womens Restroom

Vestibular Rehab

UV Treatment

Treatment

Mobility Storage

Mobility 277Storage

Cube Stations

Waiting Area

Supervisor

Storage

Stair

Mens Restroom

ADL

Waiting

MAS

Gym Storage

Priv Treatment

Priv Treatment

Priv Treatment

Corridor 200A

Corridor 200B Corridor

200C Corridor

200D

Toilet

200b

0a

Corridor 200D

A401

A401

25'

- 0

20'

- 0

25'

- 0

A20117 16

A203

FEC

FEC

15' - 2" 20' - 0" 20' - 0" 20' - 0" 19' - 11 1/2" 20' - 0"

7' - 7 1/2" 4 7/8" 9 5/8" 7' - 0" 7 1/4" 7' - 6 3/4" 1' - 11 1/4" 4 7/8" 8' - 0" 4 7/8" 8' - 2 3/4" 4 7/8" 7 3/8" 7' - 4 5/8" 4 7/8" 10' - 2 1/2" 4 7/8" 1' - 7 1/8" 14' - 3 1/16" 4 7/8" 5' - 4 1/16" 19' - 6 3/4" 7 1/2"

8' - 4 3/4" 1' - 2 1/2"

10' - 2"

135°

3' - 1 13/16" 8' - 8 11/16" 5' - 0" 10 1/2" 4' - 0" 4' - 5" 4' - 0" 5' - 0" 3' - 2" 4' - 0" 10 1/2"

4' - 0" 7' - 11 1/2" 1' - 4" 3' - 0" 10' - 5" 4 7/8" 2' - 0" 6' - 0" 10' - 4 1/4" 4' - 0" 2' - 5 3/8" 5"

3' - 10" 11' - 2 3/4" 4' - 0" 6 1/4"

9' - 10 1/4" 4' - 0" 1' - 3 3/4" 40' - 0" 2' - 4" 4' - 0" 8' - 5" 5' - 3" 17' - 6 1/8" 7' - 4 3/4" 4' - 0" 2' - 0" 3' - 0" 6' - 0 5/8"

4 7/8" 6' - 8 1/2" 15' - 2" 6' - 6 7/8" 4 7/8" 12' - 0" 4 7/8" 11' - 10 1/8" 4 7/8" 8' - 4 3/8" 20' - 0" 6' - 6 3/8" 7 1/4" 11' - 9 5/8" 4 7/8" 10' - 9 5/8" 4 7/8" 9' - 4 7/8"

5' - 5"

4' - 0"

6' - 4 7

/8" 4' -

0" 5' -

2 1 /8"

1' - 2 3

/4" 4' -

0" 1' -

4 7 /8"

4' - 0"

9' - 9"

4 7 /8"

8' - 0"

4 7 /8"

15'

- 9

5/8

13'

- 7

3/8

4 7 /8"

5' -

3/4

4 5 /8"

4 7 /8"

6' -

3/4

4 7 /8"

2' - 0"

8' - 0"

4' - 0"

8' - 0"

9 1 /2"

1' - 10 1/4"

1' -

1/4

20'

- 7

3/8

4 7 /8"

8" 9' -

0" 14'

- 3 3/4

6' - 6 7/8" 5' - 10 7/8" 4' - 0" 5' - 9" 4' - 0" 5' - 4 7/8" 8' - 4 3/8"

KINETRON

WEIGHT

RACKS

EXERCISE MATEXERCISE MAT

EXERCISE MAT

EXERCISE MAT

TREATMENT

TABLE

TREATMENT

TABLE

TREATMENT

TABLE

TREATMENT

TABLE

DYNAVISION

COPIER COPIER

ST

AT

ION

AR

Y B

IKE

ST

AT

ION

AR

Y B

IKE

ST

AT

ION

AR

Y B

IKE

ST

AT

ION

AR

Y B

IKE

SC

I-F

IT B

IKE

COLD PACHOT PAC

ICE

MACHCO

LD

PA

C

HO

T P

AC

PARALLEL BARS

CEILING MOUNTED PATIENT LIFT SYSTEM

CEILING MOUNTED

SINGLE TRACK

PATIENT LIFT SYSTEM

CEILING MOUNTED PATIENT LIFT SYSTEM

NU

ST

EP

NU

ST

EP

EXERCISE RAMP

TR

EA

DM

ILL

WEIGHT

CART

TH

ER

AP

Y S

HE

LF

BTE

w / DATA EISOMETER

ENDORPHIN EXERCISE MAT

PULLEY

RICKSHAW

REBANDER

FLUIDS

TREATMENT TABLE

BIKE

ROWING MACHINE

BOW

FLEX

CARD

TABLE

TV

D3R

C3S

A1

C3

C3S

C3S

D3R

D3R

D3RD6R

D3R

C3A

C6S

D3R

C3A

C3A

C3A

C3S

A3

C6S

A3

D3R

C3S

C3S

A3

A3

C3A

C6

D3R

C3A

C3A

C6

C3A

A6A3

A2 A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

C6S

C3A

C3S

C3S

C3A C3S

E3R

A2

C3A

D3R

D3R

TUB

A2026

A20122

FEC

FEC

A201 15

A2

7' - 2"

4' - 0"

5' - 0 1

/2" 8' -

0"

A2

A2

1' - 10 1/4"

1' -

1/4

A2

D3R

C3S

E3R

A2 A2A2A2 A2

A2

A2

A2

A2

A2

A2 A2

A2 A2 A2 A2 A2 A2 A2 A0

A2

A2

A3

C3S

D3R

C6

C6

C3A

C3SC3SC3S C3S

A2

A2

A2

A2

E3R

E3R

D6R

C3S C3A

C3

A202

WALL MOUNTED

SMART TV CFCI

** * * * *A2 * cg cg cg cg cg cg cg cg cg cg cg cg cg cg cgcg cg cg cgcgcgcgcgcgcgcgcgcgcg cg cg cg cgcg cg cg cg cgcg cg cg cg cgcg cg cg cgcg cg cg cg cg cg cg cg cg cg cg

A3D3R

A202 1011

A20115

OPP

A2025 4

A2043

A2

A3

C2

A2 cg cg cg cg

A20214

EJ

EJ

EJ

EJ

1" EXPANSION JOINT

NE

W

FL

OO

RIN

G

EX

IST

ING

FL

OO

RIN

G

TO

RE

MA

IN

A2*

D3R

A0

A2

A2 *

1b

REPLACE EXISTING METAL PANEL

WITH MATCHING SPANDREL GLASS

EXP JT

A501

A501

A501

WALL MIRROR, GC TO

COORDINATE OPENINGS

TO ACCOMMODATE

OUTLETS & SWITCHES

WALL MIRROR

WALL MIRROR

WALL MIRROR

WALL MIRROR

A20117 16 sim

FEC

FEC

9.1

Fire Alarm 269.1

A204

A20419

A204 14

A20416

A301

251d

1111 Louisiana 26th Floor Houston, TX 77002

713.665.5665 phone . eypae.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

5190 Canal Boulevard, Suite 201 New Orleans, LA 70124 (504)835-8013

LACHIN

Architects, apc

Architecture . Planning . Project Management

C :\R ev it

L oc al \V

A In pa tie nt W ar d

2A _l ac hi n-ar ch ite ct s.

rv t

9/

/2

:0 6:

A

M

A104

LARGE SCALE PLAN

Michael G. Lachin

Renovate Ward 2A

1500 E. Woodrow Wilson Dr. Jackson, MS 39216

586-18-101

August 18, 2020 PF BB

FINAL SUBMISSION

1/4" = 1'-0"A104 1 Large Scale Plan − East

Revisions: Date:

KEY PLAN

* TERMINATE WALLS AT UNDERSIDE OF

WINDOW SILL, SEE DETAIL 2/A301

M

IC

HAEL G.

HCAL

IN

REG ISTE RED ARCHITECT

STATE OF

ISIUOL

713.665.5665 phone . eypae.com

F F

E E

D D

C C

A2013

A201

A201

A2019

25'

- 0

20'

- 0

25'

- 0

9b

Treatment

Treatment

Treatment

Student Room

Conference / Multipurpose

Patient Toilet 234 Treatment

Treatment

Splint Fabrication

OT Gymnasium

Storage

Cube Stations

Waiting Area

Supervisor

Cardio/Pulmonary

Sub-Wait

Patient Toilet

Treatment

Treatment

Break Room

Female Staff RR

EMG

Male Staff RR 231 Supervisor

EMG

Mechanical

Elect

Storage

Provider Workroom

Treatment

Treatment

Treatment

Scales

Nursing Workroom

Storage

Lymphedema/CVT

Clean Supply

Medication

Telecommunications

Chute

ADL

Corridor 200B

251d

9a

20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 24' - 10"

A401

A401

A401

A401

A401

A201 21

A201

A201 4

A201

A2016

A203

FEC

FEC

FEC

FEC

Storage

14'

- 5

1/2

4 7 /8"

6" 3' -

0" 6' -

7 5 /8"

3' - 8 1

/16

4' - 0"

1' - 4 7

/8" 4' -

0" 6' -

1/8

1' -

4 9 /16

4' -

0" 15'

- 2 7/1

6" 4' -

0" 4 3

/8"

6' - 0"

4 7 /8"

3' - 8 3

/4" 8' -

2 1 /16

4 7

/8" 11'

- 5 1/8

5 1

1/1 6"

4 7 /8"

11'

- 1

0 1 3/1

6" 4 7

/8" 11'

- 9

/16

6" 6"

6"

15'

- 7

1/4

7 1 /4"

8' - 0"

7 1 /4"

11'

- 2

4 7

/8" 8' -

7 3 /8"

4 5 /8"

4 7 /8"

8' - 0"

4 7 /8"

8' -

4 7

/8" 6' -

6 3 /4"

16' - 11 1/2" 4 7/8" 2' - 7 5/8" 5' - 4 3/8" 4 7/8" 8' - 0" 4 7/8" 5' - 9 7/8" 2' - 2 1/8" 4 7/8" 8' - 0 1/2" 4 7/8" 8' - 0" 11 5/8" 8' - 0 1/2" 10' - 8 1/4" 4 7/8" 10 3/8"

9' - 1 5/8" 4 7/8" 10' - 5 1/2" 8' - 2 1/4" 4 7/8" 7' - 0" 4 7/8" 7' - 7 1/2"

10' - 7 1/4" 7 1/4" 5' - 9" 4' - 2 1/16" 4' - 0" 10 1/2" 4' - 0" 7' - 11 1/4" 4' - 0" 10 1/2" 4' - 0" 8' - 0 9/16" 4' - 0" 6 7/8" 8' - 0" 3' - 0 3/4" 5' - 0" 4' - 6" 4' - 7 5/8" 4' - 0" 11' - 4 3/8" 2' - 10 7/16" 4' - 0" 5' - 6 1/2"

8' - 0" 9 1/2" 28' - 2" 4' - 0" 1' - 4 7/8" 4' - 0" 2' - 5 1/8" 11' - 2 1/2" 8' - 0" 9 1/2" 9' - 0" 3' - 6" 3' - 0" 3' - 0" 1' - 6" 1' - 0" 4' - 0" 19' - 10"

9 1/2" 9' - 6 7/8" 5' - 0 1/2" 4 7/8" 4' - 11 3/4" 12' - 8" 4 7/8" 6' - 11 1/8" 10' - 9 5/8" 4 7/8"

15'

- 7

1/4

7 1 /4"

8' - 0"

4 7 /8"

20'

- 9

1/4

4 7 /8"

8' - 0"

4 7 /8"

15'

- 9

5/8

4 7/8" 9' - 0" 4 7/8" 3' - 10 5/8" 4 7/8"

5' - 6 1/2" 7' - 0 1/4" 11' - 10 1/8" 4 7/8"

6' - 8 1/2"

6' - 4 7/8" 3' - 0" 2' - 1 1/8" 3' - 0" 5' - 6" 14' - 8 1/4" 3' - 0" 2' - 3 3/4" 11' - 2 1/2" 5' - 1 3/8" 3' - 0" 1' - 4 7/8" 3' - 0" 7' - 5 3/4" 11 1/2" 4' - 0" 4' - 9 15/16" 4 7/8" 7' - 11 3/16"

9 1/2" 4' - 5 3/8" 4' - 0" 11' - 6 5/8" 11' - 1 9/16" 4' - 0" 4' - 2" 4' - 0" 1' - 3 5/16" 4' - 0" 9' - 6 7/16" 4' - 0" 1' - 4 7/8" 4' - 0" 9' - 8 3/8" 4' - 0" 6 7/8" 8' - 0" 4 7/8" 14' - 7 11/16"

9' - 4" 4 7/8"

10' - 7 3/4" 15' - 8 5/16" 8' - 6 1/8" 9' - 0" 4 7/8" 6' - 4 11/16" 2' - 7 5/16" 4 7/8" 9' - 7 1/2" 4 7/8" 6' - 11 7/16" 1' - 4 9/16"

C3A

C3S

C6S

C3S

C3A

D3R

D3R

C3S D3R

C6S

D3R

C3S

C3A C3S

C3A

C6S

C3A

C3A

C3A

C6S

C3A

D3R

C3A C3S

C3S

C3S

A3

D3R

D3R

C6S

C3A

C3A

C6S

C3A

C3A

C3A

C3S

C6S

C3SC3A

C3S

C3A

C3A

C3S

C3S

C3S

A3

C3S

A0

A0

A0

A0

A2

A2

A2

A2

A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

A2

C3S

C3A

C3S

C3S

A2

A2

C3A

C3A

A3

C3A

A3

A3

D3R

C3S

C3A D3R

C3A A1

A1

C3S

C6S

D6R

C6S D3R

C6SC6S

C3S

C6S

E3R

E3R

D3R

A401

Corridor 200E

Corridor 200F

Corridor 200H

Corridor 200G

M8

M8 M8

M8

D…