This document appears to be a service report related to a federal contract opportunity for cooling tower replacement at a VA facility. The report details the current operating conditions of the cooling tower, including water chemistry parameters and recent maintenance performed on the chlorine monitoring and control system. It indicates that Legionella testing results were satisfactory. The related federal contract opportunity is Solicitation Number 36C25524R0070 for "N041--589A6-24-402, COOLING TOWER REPLACEMENT (VA-24-00061267)" issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. The solicitation appears to be for the replacement of a cooling tower at a VA facility in Leavenworth, Kansas. No additional details about the requirements, response dates, pricing, or set-asides are provided in the given information.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Cooling Tower

Conductivity (umhos) 1987 1400 - 2200 pH 8.71 8 - 9

Polymer (FAU) 122 70 - 150

Free Chlorine, ppm 0.30

0.1 - 0.5

Opening Comment Pyxis free chlorine monitoring & control panel is now functional.

• Thank you Don for mounting and getting set up. I landed wiring today and the bleach pump is now being controlled via the new control unit.

• New sensor was calibrated to match my field free chlorine test (0.30 ppm).

• Current setpoints:

◦ Bleach pump ON = 0.19 ppm

◦ Bleach pump OFF = 0.20 ppm

• I have a very tight deadband set in an effort to maintain tight control and consistency. As ambient temperatures increase, we can start to slowly bump up the free chlorine target setpoint.

• As discussed with Don, the setpoint can be adjusted on the Prominent controller.

◦ From the ‘Home’ screen — Select ‘Menu”

◦ Select ‘Adjust Setpoints’

◦ Select ‘Biotrol 12.5’

◦ Adjust accordingly and exit to home screen

• Legionella Testing

◦ Great Legionella results on our last round of testing — Final report previously sent

◦ I will send an invite as a reminder for the beginning of June

Thank you guys and please don’t hesitate to contact me if you have any questions.

Chad Mayes Kurita America, Inc.

(913) 424-8106

Service Report Wednesday, April 3, 2024 3:30 PM CDT

VA Leavenworth Steam Plant Facilities 4101 4th Street Trafficway Leavenworth KS 66048

(913) 682-2000

Report Number: 21125320 Recorded By: Chad Mayes

(913) 424-8106 c.mayes@kurita-water.com

On-Site Time: 12:30 PM CDT to 2:45 PM CDT

Chiller Plant - Chiller Tests