About this file

36C25519R0057 0001 Drawings- Remodel 5th Floor-Vol 5.pdf

View the file

Other files

File Type Posted
36C25519R0057-0004001.pdf PDF
36C25519R0057-0004000.docx DOCX document
36C25519R0057-0003001.pdf PDF
36C25519R0057-0003000.docx DOCX document
36C25519R0057-0002002.pdf PDF
36C25519R0057-0002001.pdf PDF
36C25519R0057-0002003.pdf PDF
36C25519R0057-0002000.docx DOCX document
36C25519R0057-0001007.pdf PDF
36C25519R0057-0001004.pdf PDF
36C25519R0057-0001003.pdf PDF
36C25519R0057-0001002.pdf PDF
36C25519R0057-0001006.pdf PDF
36C25519R0057-0001000.docx DOCX document
36C25519R0057-0001001.pdf PDF
36C25519R0057-009.pdf PDF
36C25519R0057-003.pdf PDF
36C25519R0057-008.pdf PDF
36C25519R0057-010.pdf PDF
36C25519R0057-011.pdf PDF
36C25519R0057-002.pdf PDF
36C25519R0057-006.pdf PDF
36C25519R0057-012.pdf PDF
36C25519R0057-004.pdf PDF
36C25519R0057-005.pdf PDF
36C25519R0057-007.pdf PDF
36C25519R0057-001.docx DOCX document
36C25519R0057-000.docx DOCX document
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:1

P

M

E-001

ELECTRICAL NOTES AND

SYMBOLS

DDC KTN

SPECIAL OUTLETS

MARK DESCRIPTION

FBC MULTI-SERVICE FLOOR BOX: PROVIDE WITH (1) 120V. 20A. DUPLEX RECEPTACLE AND PROVISIONS FOR TELECOMMUNICATIONS VIA (1) 1-1/4" PULLROPE ROUTED TO THE NEAREST ACCESSIBLE CEILING. VERIFY COVER TO BE

COMPATIBLE WITH FLOOR FINISH. COLOR TO BE VERIFIED WITH ARCHITECT.

P OVERHEAD PROJECTOR: PROVIDE 120V. 20A. DUPLEX RECEPTACLE, (1) DATA, (1) HDMI CABLE ROUTED TO A/V CABINET.

FLUSH MOUNT RECEPTACLE IN CEILING TILE.

PB PROJECTOR BOARD WALL BOX: PROVIDE AND INSTALL FLUSH MOUNTED WALL BOX WITH (1) 120V., 20A. DUPLEX RECEPTACLE AND PROVISIONS FOR TELECOMMUNICATIONS/AUDIO-VISUAL CONNECTION VIA (1) 1" CONDUIT WITH PULLROPE AND (1) 1-1/2" CONDUIT WITH PULLROPE RESPECTIVELY. BOX SHALL BE PROVIDED WITH ALL WHITE COVER AND ALL DEVICE OPENINGS/COVERS AS NEEDED FOR A COMPLETE INSTALLATION. LOCATE BOX AT 60" AFF. VERIFY

EXACT LOCATION BEFORE INSTALLATION.

PO TELE-POWER POLE: PROVIDE TWO COMPARTMENT ALUMINUM SERVICE POLE. THE SERVICE POLE SHALL BE MADE OF EXTRUDED ALUMINUM, .05" THICK. THE HEIGHT OF THE SERVICE POLE SHALL EXTEND 1' ABOVE CEILING ELEVATION.

PROVIDE 3/4" NPT KNOCKOUTS FOR FLEXIBLE DATA CONNECTION TO WORKSTATIONS. PROVIDE KNOCKOUTS FOR FLEXIBLE POWER CONNECTIONS TO WORKSTATIONS. CAT6 CABLES TO BE ROUTED TO DATA RACK LOCATED IN I.T.

551. TERMINATE CABLES ON ASSOCIATED EQUIPMENT AS REQUIRED.

SM SOUND MASKING CONTROLLER: PROVIDE WITH (1) 120V. 20A. DUPLEX RECEPTACLE FOR CAMBRIDGE SOUND MANAGEMENT "QT100" CONTROL MODULE. PROVIDE CAT6 CABLE FROM THE CONTROLLER TO THE FIRST EMITTER IN THE OPEN OFFICE. COORDINATE EXACT LOCATION OF CONTROLLER WITH OWNER PRIOR TO INSTALLATION.

WAPS WIRELESS ACCESS POINT: PROVIDE CAT-6 DROP WITH 10'-0" EXCESS CABLE COILED ABOVE THE CEILING. TERMINATE TO 8P8C CONNECTOR WAP PROVIDED AND INSTALLED BY GOVERNMENT. CLINICAL WIRELESS DROPS (GREEN CABLES), AND GUEST WIRELESS DROPS (PINK CABLES) TO BE LEFT IN PLACE AND COILED ABOVE CEILING THROUGHOUT DEMO TO BE REUSED. SERVICE LOOP SHALL BE SUPPORTED FROM STRUCTURE AND SHALL NOT REST

ON CEILING TILE. COORDINATE EXACT LOCATION WITH C.O.R.

Revisions: Date:

01/28/2019

NOT IN CONTRACT

W

WAPS

WAPS

DAS WAPS

WAPS

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

D D D

DDD

D

D

D

D D D

DD

D D

DD

D D

DD

D

D D

D

D D

DD

D D D

DD

D D

E

D

D D

D

D D

D

D D

D

D

D D D D D D D D

D D D

D D D

D

DDDD

D D

D D D D

D

D D

D

DD

D D

DD

D

D

D

D

D

D D

D D

D

D D

DD

LP5-G5-120VC

LP5-G5-120VN

PROJECTOR

SCREEN

PROJECTOR

SCREEN

PROJECTOR

LP5-L4-277VN

LP5-L4-120VN

LP5-H9-277VN

LP5-H9-120VE

LP5-H9-277VE

LP5-H9-120VN

T5-L4-120VC

D

D

D

D

D D D

D

D

D

D1

LENEL SECURITY

CABINET

D3

511513518522526528

512C 512B

514A

526A 524 519 513A 511A

512516517520521523

523A

525527

531A

534A

537A

536A

530C 530A

530B

564A

501B501C

PROJECTOR

D1

D4

D4

D7

D

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE

OPTION TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES,

RECEPTACLES, LIGHTS, PANELS, ETC. NOT BEING USED IN THE

FINISHED WORK. COORDINATE WITH OWNER PRIOR TO STARTING

DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT

AND MATERIALS BEING REMOVED.

2. CONDUIT THAT IS BEING REMOVED SHALL BE TERMINATED AT THE

PANEL OR JUNCTION BOX WHEN SPECIFIED.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT FOR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN. PROVIDE PATCHING

IN SPACES REQUESTED BY THE VA.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

9. EXISTING 2x2 CREE LIGHT FIXTURES SHALL BE GIVEN TO THE VA. REFER

TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE INFORMATION.

10. EXISTING CONDUIT AND CABLE FOR VOICE/DATA SHALL BE CUT BACK TO

EXISTING I.T. CLOSET 551.

11. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:2

P

M

ED101

PHASE 1 - DEMOLITION FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 1 - DEMOLITION FLOOR PLAN

# KEYED NOTES:

D1 RELOCATE AND REINSTALL EQUIPMENT AS SHOWN ON SYSTEMS

PLANS. EXTRA EQUIPMENT TO BE GIVEN BACK TO VA STAFF.

D3 EXISTING LENEL SECURITY CABINET TO BE REMOVED AND

REINSTALLED IN I.T. CLOSET 551 DURING PHASE 1. REFER TO

DRAWING EY101.

D4 RELOCATE AND REINSTALL EQUIPMENT AS SHOWN ON POWER

PLANS. EXTRA EQUIPMENT TO BE GIVEN BACK TO VA STAFF.

D7 EXISTING VIDEO TELECONFERENCING EQUIPMENT TO BE REMOVED

AND REINSTALLED DURING PHASE 2 CONSTRUCTION.

Revisions: Date:

W

TV

W

WAPS

TV

WAPS

PROJECTOR

SCREEN

PROJECTOR

SCREEN

PROJECTOR

SCREEN

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

D

D

D D

DD

D

D

D D D

D

D

DD

D

RD

D D

D

D

R D

DR

D

D

D

D D

D

D

DD

D D

D D

D

D

D

D D

D D

D D

D

D D

D

D

D D

D

D

D

D

D

D D

D

D

D

D D D

D

D

D D

D D D D

D D

D

DD

DD

D

D

D

D

D DDD

D DD

D

DD

D

D

D D

D

D6D6

D6

D6

D

PROJECTOR

SCREEN

D2D2

PROJECTOR PROJECTOR

P

D1

LP5-L4-120VN

LP5-L4-277VN

T5-L4-120VC

LP5-H9-277VN

LP5-H9-120VN

LP5-H9-120VE

LP5-H9-277VE

R

R

D4

D4 D4

D4

PROJECTOR

501A

534A

537A

536 536A

OPEN OFFICE

WORK AT THIS AREA

TO BE DONE AT

NIGHT/ON WEEKENDS

STAIR 2

501B501C

HOUSEKEEPING CLOSET

501A

STORAGE

STAIR 1

STAIR 2

IT CLOSET

SIMULATION TRAINING

ROOM

CLASSROOM

CLASSROOM

VAM TRAINING ROOM

MEDICAL MEDIA ROOM

COMPUTER TRAINING

ROOM

SCHEDULER TRAINING

ROOM

OPEN OFFICE

OPEN OFFICE

CORRIDOR

C58

CLASSROOM

ELEVATOR LOBBY

MEN

OFFICE

CORRIDOR

C57

FREIGHT ELEVATOR LOBBY

CONTROL ROOM

554A

ELEC

545A

OPEN OFFICE

COPY ALCOVE

STORAGE

547A

CORRIDOR

C55

CORRIDOR

C51 D

DD

DAS

DDD

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE

OPTION TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES,

RECEPTACLES, LIGHTS, PANELS, ETC. NOT BEING USED IN THE

FINISHED WORK. COORDINATE WITH OWNER PRIOR TO STARTING

DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT

AND MATERIALS BEING REMOVED.

2. CONDUIT THAT IS BEING REMOVED SHALL BE TERMINATED AT THE

PANEL OR JUNCTION BOX WHEN SPECIFIED.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT FOR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN. PROVIDE PATCHING

IN SPACES REQUESTED BY THE VA.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

9. EXISTING 2x2 CREE LIGHT FIXTURES SHALL BE GIVEN TO THE VA. REFER

TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE INFORMATION.

10. EXISTING CONDUIT AND CABLE FOR VOICE/DATA SHALL BE CUT BACK TO

EXISTING I.T. CLOSET 551.

11. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:2

P

M

ED102

PHASE 2 - DEMOLITION FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 2 - DEMOLITION FLOOR PLAN

# KEYED NOTES:

D1 RELOCATE AND REINSTALL EQUIPMENT AS SHOWN ON SYSTEMS

PLANS. EXTRA EQUIPMENT TO BE GIVEN BACK TO VA STAFF.

D2 EXISTING EQUIPMENT TO BE REMOVED AND GIVEN BACK TO VA

STAFF.

D4 RELOCATE AND REINSTALL EQUIPMENT AS SHOWN ON POWER

PLANS. EXTRA EQUIPMENT TO BE GIVEN BACK TO VA STAFF.

D6 RELOCATE AND REINSTALL EQUIPMENT IN SIMULATION TRAINING

ROOM 554 AS SHOWN ON SYSTEMS PLANS.

Revisions: Date:

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

D D

D D

D D

D

LP5-H9-277VN

LP5-H9-120VN

LP5-H9-120VE

LP5-H9-277VE

LP5-L4-120VNLP5-L4-277VN

T5-L4-120VC

ELEC

FAC

501B501C

HOUSEKEEPING CLOSET

501A

STORAGE

STAIR 1

STAIR 2

IT CLOSET

SIMULATION TRAINING

ROOM

CLASSROOM

CLASSROOM

VAM TRAINING ROOM

MEDICAL MEDIA ROOM

COMPUTER TRAINING

ROOM

557SCHEDULER TRAINING

ROOM

OPEN OFFICE

OPEN OFFICE

CORRIDOR

C58

CLASSROOM

ELEVATOR LOBBY

MEN

OFFICE

CORRIDOR

C57

FREIGHT ELEVATOR LOBBY

CONTROL ROOM

554A

ELEC

545A

OPEN OFFICE

COPY ALCOVE

STORAGE

547A

CORRIDOR

C51

CONFERENCE ROOM

CONFERENCE ROOM

STAFF BREAKROOM

OFFICE

LACTATION ROOM

WOMEN

MEN

CORRIDOR

C53

OFFICE

CONFERENCE ROOM

OFFICE

OFFICE

OPEN OFFICE

OPEN OFFICE

STORAGE

OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CORRIDOR

C54

ELEC

514A

ELEC

512C

ELEC

512B

COPY ALCOVE

520A

OPEN OFFICE

COPY ALCOVE

OPEN OFFICE

CORRIDOR

C55

D D

D

DD D

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE

OPTION TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES,

RECEPTACLES, LIGHTS, PANELS, ETC. NOT BEING USED IN THE

FINISHED WORK. COORDINATE WITH OWNER PRIOR TO STARTING

DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT

AND MATERIALS BEING REMOVED.

2. CONDUIT THAT IS BEING REMOVED SHALL BE TERMINATED AT THE

PANEL OR JUNCTION BOX WHEN SPECIFIED.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT FOR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN. PROVIDE PATCHING

IN SPACES REQUESTED BY THE VA.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

9. EXISTING 2x2 CREE LIGHT FIXTURES SHALL BE GIVEN TO THE VA. REFER

TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE INFORMATION.

10. EXISTING CONDUIT AND CABLE FOR VOICE/DATA SHALL BE CUT BACK TO

EXISTING I.T. CLOSET 551.

11. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:3

P

M

ED103

PHASE 3 - DEMOLITION FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 3 - DEMOLITION FLOOR PLAN

Revisions: Date:

OPEN OFFICE

CLASSROOM

CORRIDOR

C57

CLASSROOM

OFFICE

MEN

MEDICAL MEDIA ROOM

IT CLOSET

STAIR 1

OPEN OFFICE

ELEVATOR LOBBY

NOT IN CONTRACT

C53BBBB

HOUSEKEEPING CLOSET

501A

STAIR 2

STORAGE

CLASSROOM

CORRIDOR

C58

SCHEDULER TRAINING

ROOM

SIMULATION TRAINING

ROOM

VAM TRAINING ROOM

COMPUTER TRAINING

ROOM

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

S1 S1

S1 S1

S1

S1

S1

S1

S1 S1 S1 S1 S1 S1 S1 S1

S1 S1

S1

S1

S1

S1

S1S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1S1

S1

S1

S1

S1

S1S1

S1 S1

S1S1

S1 S1

S1 S1 S1

S1 S1

W2

S1

S1

S1

S1 S1S1

S1 S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

X1X2

X1 b b b b b b b b a a a a a a

S1

NL

NL

NL

NL

NL

U2

U2

ELEC

545A

FREIGHT ELEVATOR LOBBY

L1

S1 S1

S1S1

S1 S1

L1

S1

S1

S1

S1

S1

S1

S1 S1 S1

S1S1

S1

S1 S1 S1

S1S1S1

S1 S1 S1

S1S1S1

S1

E a b a b

S2

S2

S1 b b

X1

X1

L3

LP5-L4-277VN:5

LP5-L4-277VN:3

LP5-L4-277VN:7

STORAGE

547A

CORRIDOR

C51

CORRIDOR

C55

OPEN OFFICE

CONTROL ROOM

554A

ELEV 1

512C

511513518522526528

512C 512B

514A

526A 524 519 513A 511A

516517520521523

523A

525527

531A

534A

537A

536A

530C 530A

530B

564A

501B501C

NL

LP5-L4-277VN:3

LP5-H9-277VE:19

L10L10 b

L8

L8

L8 L8

L8

L8

S1 S1S1S1

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb

S2

S2 a a

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING TO

MATCH THE RATING OF THE WALL.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

6. REFER TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE

INFORMATION.

7. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:4

P

M

EL101

PHASE 1 - LIGHTING FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 1 - LIGHTING FLOOR PLAN

# KEYED NOTES:

L1 CONNECT TO EXISTING AREA LIFE SAFETY CIRCUIT.

L3 PROVIDE CONNECTION TO FUTURE LIGHT FIXTURES IN PHASE 3.

L8 PROVIDE INTERLOCK BETWEEN LOCAL OCCUPANCY SENSORS PER

MANUFACTURERS REQUIREMENTS.

L10 INSTALL 3-WAY DIMMER TO CONTROL LIGHTS IN ADJACENT

CLASSROOM. LABEL THE FACEPLATE OF DIMMER TO SAY “LIGHTS IN

OTHER ROOM”.

Revisions: Date:

OPEN OFFICE

517 OFFICE

LACTATION ROOM

ELEC

512C

ELEC

512B

CORRIDOR

C53

ELEC

514A

CONFERENCE ROOM

CONFERENCE ROOM

STAFF BREAKROOM

OFFICE

OFFICE

OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CONFERENCE ROOM

OPEN OFFICE

MEN

WOMEN

CORRIDOR

C54

CORRIDOR

C55

OFFICE

STORAGE

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

S1

S1

S1

S1

S1 S1 S1 S1 S1 S1 S1 S1

S1 S1

S1

S1S1

S1S1S1S1S1

S1 S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1S1

S1

S1

S1

S1 S1

S1

S1

S1 S1

S1

S1 S1

S1 S1 S1

S1 S1

S1 S1

W2

W2

W2

W2

S1

S1 S1

S1

S1

S1S1

S1

S1

S1

S1S1

S1S1 S1

X2

X1X2

S1 S1

S1 S1

S1 S1 S1

S1S1

S1

S1

S1

S1

S1

NL

NL

NLNL

NL

NL NL

U2

U2

U2

U2

L1

NL

NL

S1 S1

S1S1

S1 S1

S1

S1

S1

W2

W2

LP5-H9-277VN:5

STAIR 2

COPY ALCOVE

520A

OPEN OFFICE

COPY ALCOVE

OPEN OFFICE

FREIGHT ELEVATOR LOBBY

501 HOUSEKEEPING CLOSET

501A

ELEVATOR LOBBY

500CORRIDOR

C51

OPEN OFFICE

CORRIDOR

C55

COPY ALCOVE

MEN

OFFICE

OPEN OFFICE

OPEN OFFICE

SCHEDULER TRAINING

ROOM

CORRIDOR

C57

ELEC

545A

CLASSROOM

CLASSROOM

CORRIDOR

C58

CLASSROOM

STORAGE

CONTROL ROOM

554A

SIMULATION TRAINING

ROOM

VAM TRAINING ROOM

COMPUTER TRAINING

ROOM

IT CLOSET

STORAGE

547A

STAIR 1

MEDICAL MEDIA ROOM

534A

537A

536 536A

501B501C

S1 S1 S1

S1 S1 b b b b bb a a a a a a a a a a a b b bb b b b b

S1

S1

U2

LP5-H9-277VE:19

HB

L8 L8

L8

L8

L8

L8

L8

L8

L8

NL

L11

L11

L11

LP5-H9-277VE:19

LP5-L4-277VN:5 LP5-L4-277VN:5

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb

X1 X2

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING TO

MATCH THE RATING OF THE WALL.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

6. REFER TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE

INFORMATION.

7. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:5

:5

P

M

EL102

PHASE 2 - LIGHTING FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 2 - LIGHTING FLOOR PLAN

# KEYED NOTES:

L1 CONNECT TO EXISTING AREA LIFE SAFETY CIRCUIT.

L8 PROVIDE INTERLOCK BETWEEN LOCAL OCCUPANCY SENSORS PER

MANUFACTURERS REQUIREMENTS.

L11 PROVIDE CONNECTION TO EXISTING LIGHT FIXTURE DURING PHASE 2

CONSTRUCTION.

Revisions: Date:

CORRIDOR

C56

OFFICE

WOMEN

OFFICE

OFFICE

NOT IN CONTRACT

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

S1 S1

S1S1

S1 S1

S1 S1

S1S1

S1 S1

S1

S1

S1

S1

W2

S1

S1S1

S1

S1

S1

S1 S1

S1

X2 X2

X1

S1

R

R

NL

NL

NL

NL

S1

S1

NL

STAIR 2

ELEC

512C

ELEC

512B

ELEC

514A

CORRIDOR

C53

CORRIDOR

C54

COPY ALCOVE

520A

OFFICE

OFFICE

OFFICE

STAFF BREAKROOM

CONFERENCE ROOM

CONFERENCE ROOM

LACTATION ROOM

OFFICE

OPEN OFFICE

MEN

WOMEN

OPEN OFFICE

CORRIDOR

C55

CONFERENCE ROOM

OFFICE

COPY ALCOVE

STORAGE

OFFICE

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

OPEN OFFICE

OPEN OFFICE

SCHEDULER TRAINING

ROOM

ELEC

545A

CORRIDOR

C57

CLASSROOM

CLASSROOM

IT CLOSET

STORAGE

547A

MEDICAL MEDIA ROOM

OPEN OFFICE

CORRIDOR

C51

ELEVATOR LOBBY

FREIGHT ELEVATOR LOBBY

HOUSEKEEPING CLOSET

501A

CLASSROOM

STORAGE

CONTROL ROOM

554A

CORRIDOR

C58

COMPUTER TRAINING

ROOM

VAM TRAINING ROOM

SIMULATION TRAINING

ROOM

MEN

COPY ALCOVE

501B501C

LP5-H9-277VE:19

L8

L8

LP5-L4-277VN:7

L8

L8

LP5-L4-277VN:5

L8

L8

LP5-L4-277VN:5

L8

LP5-L4-277VN:3

FFaGHJKLMMbN La Ja Hb Ga

4.1

5.4

6.2

6.7

Jb

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING TO

MATCH THE RATING OF THE WALL.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

6. REFER TO LIGHT FIXTURE SCHEDULE ON EL601 FOR MORE

INFORMATION.

7. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:1

P

M

EL103

PHASE 3 - LIGHTING FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 3 - LIGHTING FLOOR PLAN

# KEYED NOTES:

L8 PROVIDE INTERLOCK BETWEEN LOCAL OCCUPANCY SENSORS PER

MANUFACTURERS REQUIREMENTS.

Revisions: Date:

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:1

P

M

EL501

ELECTRICAL LIGHTING

DETAILS

DDC KTNRevisions: Date:

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:1

P

M

EL601

LIGHT FIXTURE SCHEDULE

DDC KTNRevisions: Date:

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

TO MATCH THE RATING OF THE WALL.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

7. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE-

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

8. PROVIDE ALL ISOLATED GROUND CIRCUITS WITH INDIVIDUAL NEUTRAL

CONDUCTORS AND EQUIPMENT GROUND CONDUCTORS.

9. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

OPEN OFFICE

CLASSROOM

CORRIDOR

C57

CLASSROOM

OFFICE

541 MEN

MEDICAL MEDIA ROOM

IT CLOSET

STAIR 1

OPEN OFFICE

ELEVATOR LOBBY

NOT IN CONTRACT

C53BBBB

HOUSEKEEPING CLOSET

501A

STAIR 2

STORAGE

CLASSROOM

CORRIDOR

C58

SCHEDULER TRAINING

ROOM

SIMULATION TRAINING

ROOM

VAM TRAINING ROOM

COMPUTER TRAINING

ROOM

CT

CT

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

P

P

P

P

P3

P2

P3

P2

P2

P3

P2

P3

ELEC

545A

FREIGHT ELEVATOR LOBBY

LP5-L4-277VN

LP5-L4-120VN

T5-L4-120VC

CONTROL ROOM

554A

60"

MONITOR

72"

CT

P4

PB

PB

PB

PO

LP5-L4-120VN:7

LP5-L4-120VN:9

LP5-L4-120VN:11

LP5-L4-120VN:13

LP5-L4-120VN:15

LP5-L4-120VN:17 LP5-L4-120VN:27

LP5-L4-120VN:29

LP5-L4-120VN:31

LP5-L4-120VN:33

LP5-L4-120VN:35

LP5-L4-120VN:37

LP5-L4-120VN:39

LP5-L4-120VN:41

LP5-L4-120VN:43

LP5-L4-120VN:47

LP5-L4-120VN:55

LP5-L4-120VN:65

LP5-L4-120VN:59

LP5-L4-120VN:63LP5-L4-120VN:2

LP5-L4-120VN:4

LP5-L4-120VN:8

LP5-L4-120VN:10

LP5-L4-120VN:12

LP5-L4-120VN:14

LP5-L4-120VN:16

LP5-L4-120VN:18

LP5-L4-120VN:26

LP5-L4-120VN:32

LP5-L4-120VN:28

LP5-L4-120VN:34

LP5-L4-120VN:36

LP5-L4-120VN:38

LP5-L4-120VN:40

LP5-L4-120VN:42

LP5-L4-120VN:44

LP5-L4-120VN:67

LP5-L4-120VN:69

STORAGE

547A

CORRIDOR

C55

Room 512A

CORRIDOR

C51

511513518522526528

512C 512B

514A

526A 524 519 513A 511A

516517520521523

523A

525527

531A

534A

537A

536A

530C 530A

530B

564A

501B501C

LP5-L4-120VN:3

LP5-L4-120VN:5

COPIERCOPIER

COPY ALCOVE

546 SM

LP5-L4-120VN:72

CT

CT

CT

DF

DF

P11

LP5-L4-120VN:74

LP5-G5-120VC

LP5-G5-120VN

P10

LP5-L4-120VN:80

LP5-L4-120VN:71,75,81,83

PRINTER

UC FRIDGE

P9P9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:2

P

M

EP101

PHASE 1 - POWER FLOOR

PLAN

DDC KTN

KEYED NOTES:

P2 PROVIDE 120V. CONNECTION TO MOTORIZED SCREEN AND

ASSOCIATED CONTROL WIRING AS REQUIRED. COORDINATE EXACT

LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.

P3 PROVIDE CONTROL SWITCH IN LOCATION AS INDICATED FOR

MOTORIZED SCREEN.

P4 PROVIDE DUPLEX RECEPTACLE AT 6” BELOW CEILING FOR

RECHARGEABLE BATTERY ON TRACK MOUNTED PATIENT LIFT.

VERIFY EXACT LOCATION BEFORE INSTALLATION.

P9 PROVIDE 120V CONNECTION TO SKYFOLD PARTITION CONTROLLER.

P10 PROVIDE JUNCTION BOX FOR SKYFOLD PARTITION POWER SUPPLY.

COORDINATE SIZE OF BACKBOX WITH MANUFACTURER PRIOR TO

INSTALLATION.

P11 PROVIDE 120V CONNECTION TO JUNCTION BOX ABOVE ACCESSIBLE

CEILING TO SERVE MECHANICAL TERMINAL UNIT CONTROLS. ALL

CONTROL WIRING TO BE DONE BY THE TCC. REFER TO MECHANICAL

DRAWINGS FOR EXACT LOCATION OF TERMINAL UNITS.

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 1 - POWER FLOOR PLAN

Revisions: Date:

OPEN OFFICE

OFFICE

LACTATION ROOM

ELEC

512C

ELEC

512B

CORRIDOR

C53

ELEC

514A

CONFERENCE ROOM

CONFERENCE ROOM

STAFF BREAKROOM

OFFICE

OFFICE

OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CONFERENCE ROOM

OPEN OFFICE

MEN

WOMEN

CORRIDOR

C54

CORRIDOR

C55

OFFICE

STORAGE

CORRIDOR

C51

CT

CT

REF.

ICE MACH.

VENDING

CT

CT

NOT IN CONTRACT

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

CT

CT

CT

FBC

FBC

FBC FBC FBC

P P

P2

P3 P3

P2

LP5-H9-120VE

LP5-H9-277VN

LP5-H9-277VE

LP5-H9-120VN

LP5-L4-120VNLP5-L4-277VN

T5-L4-120VC

UC FRIDGE

PO

84"

LP5-H9-120VN:1

LP5-H9-120VN:5

LP5-H9-120VN:7

LP5-H9-120VN:11

STAIR 2

LP5-H9-120VN:13

LP5-H9-120VN:15

LP5-H9-120VN:17

LP5-H9-120VN:19

LP5-H9-120VN:21

LP5-H9-120VN:23

LP5-H9-120VN:25

LP5-H9-120VN:27

LP5-H9-120VN:29

LP5-H9-120VN:31

LP5-H9-120VN:33

LP5-H9-120VN:35

LP5-H9-120VN:37

LP5-H9-120VN:39

LP5-H9-120VN:41

LP5-H9-120VN:45

LP5-H9-120VN:47

LP5-H9-120VN:49

LP5-H9-120VN:53

LP5-H9-120VN:59

LP5-H9-120VN:63

LP5-H9-120VN:65

LP5-H9-120VN:71

LP5-H9-120VN:73

LP5-H9-120VN:75

LP5-H9-120VN:4

LP5-H9-120VN:77

LP5-H9-120VN:12

LP5-H9-120VN:18

LP5-H9-120VN:20

LP5-H9-120VN:22

LP5-H9-120VN:28

LP5-H9-120VN:28

LP5-H9-120VN:30

OPEN OFFICE

FREIGHT ELEVATOR LOBBY

HOUSEKEEPING CLOSET

501A

OPEN OFFICE

OPEN OFFICE

SCHEDULER TRAINING

ROOM

CORRIDOR

C57

COPY ALCOVE

CORRIDOR

C55

MEN

MEDICAL MEDIA ROOM

OPEN OFFICE

ELEVATOR LOBBY

IT CLOSET

STORAGE

547A

STAIR 1

552 CLASSROOM

STORAGE

CORRIDOR

C58

COMPUTER TRAINING

ROOM

VAM TRAINING ROOM

556SIMULATION TRAINING

ROOM

CONTROL ROOM

554A

CLASSROOM

CLASSROOM

ELEC

545A

COPY ALCOVE

520A

OPEN OFFICE

COPY ALCOVE

534A

537A

536 536A

LP5-H9-120VN:76

LP5-H9-120VN:76

P7P7

P7

P7

P7

P7

P7

P8

P8 P7P7

P7P7

P7P7

501B501C

LP5-H9-120VN:8

PO

LP5-H9-120VN:78

P11

LP5-H9-120VN:80

PRINTER

P5

P5

LP5-L4-120VN:82

PRINTER

LP5-H9-120VN:46,48,54,58

LP5-H9-120VN:62,64,66

LP5-H9-120VN:79

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

TO MATCH THE RATING OF THE WALL.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

7. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE-

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

8. PROVIDE ALL ISOLATED GROUND CIRCUITS WITH INDIVIDUAL NEUTRAL

CONDUCTORS AND EQUIPMENT GROUND CONDUCTORS.

9. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:3

P

M

EP102

PHASE 2 - POWER FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 2 - POWER FLOOR PLAN

# KEYED NOTES:

P2 PROVIDE 120V. CONNECTION TO MOTORIZED SCREEN AND

ASSOCIATED CONTROL WIRING AS REQUIRED. COORDINATE EXACT

LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.

P3 PROVIDE CONTROL SWITCH IN LOCATION AS INDICATED FOR

MOTORIZED SCREEN.

P5 PROVIDE 120V CONNECTION TO MOTORIZED DOOR OPERATOR.

PROVIDE CONNECTION OF MOTORIZED DOOR OPERATOR TO

HANDWAVE SENSOR. ROUGH-IN AND CONNECT AS REQUIRED BY

EQUIPMENT MANUFACTURER. PROVIDE AND INSTALL ALL CONDUIT,

BOXES, AND WIRING AS REQUIRED BY EQUIPMENT MANUFACTURER.

P7 PROVIDE 120V CONNECTION TO PLUMBING FIXTURE SENSOR.

COORDINATE EXACT LOCATION WITH MECHANICAL PRIOR TO

ROUGH-IN.

P8 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING

MEANS TO ALL PLUMBING SENSORS IN ROOM.

P11 PROVIDE 120V CONNECTION TO JUNCTION BOX ABOVE ACCESSIBLE

CEILING TO SERVE MECHANICAL TERMINAL UNIT CONTROLS. ALL

CONTROL WIRING TO BE DONE BY THE TCC. REFER TO MECHANICAL

DRAWINGS FOR EXACT LOCATION OF TERMINAL UNITS.

Revisions: Date:

OFFICE

WOMEN

OFFICE

OFFICE

NOT IN CONTRACT

CT

N Mb M La L K Ja J Hb H Ga G Fa F

6.7

6.2

5.4

4.1

Jb

LP5-H9-277VN

LP5-H9-120VN

LP5-H9-120VE

LP5-H9-277VE

LP5-L4-120VNLP5-L4-277VN

T5-L4-120VC

PO

PO

LP5-H9-120VN:60

LP5-L4-120VN:64

LP5-L4-120VN:48

LP5-L4-120VN:56

LP5-L4-120VN:58 LP5-L4-120VN:62

VAM TRAINING ROOM

COMPUTER TRAINING

ROOM

CORRIDOR

C58

CONTROL ROOM

554A

SIMULATION TRAINING

ROOM

CLASSROOM

CLASSROOM

CORRIDOR

C57

COPY ALCOVE

MEDICAL MEDIA ROOM

IT CLOSET

STORAGE

547A

STAIR 1

CLASSROOM

STORAGE

ELEVATOR LOBBY

CORRIDOR

C51

OPEN OFFICE

WOMEN

FREIGHT ELEVATOR LOBBY

HOUSEKEEPING CLOSET

501A

OPEN OFFICE

OFFICE

LACTATION ROOM

STAIR 2

ELEC

512C

ELEC

512B

CORRIDOR

C54

CORRIDOR

C53

ELEC

514A

CONFERENCE ROOM

CONFERENCE ROOM

STAFF BREAKROOM

OFFICE

OFFICE

MEN

CORRIDOR

C55

OPEN OFFICE

OPEN OFFICE

OFFICE

COPY ALCOVE

STORAGE

OPEN OFFICE

CONFERENCE ROOM

OPEN OFFICE

532OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

501B501C

P11

LP5-L4-120VN:84

LP5-H9-120VN:70,74

LP5-L4-120VN:46,66

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

TO MATCH THE RATING OF THE WALL.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

7. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE-

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

8. PROVIDE ALL ISOLATED GROUND CIRCUITS WITH INDIVIDUAL NEUTRAL

CONDUCTORS AND EQUIPMENT GROUND CONDUCTORS.

9. NOT ALL PLAN NOTES MAY APPLY TO THIS SHEET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:4

P

M

EP103

PHASE 3 - POWER FLOOR

PLAN

DDC KTN

0' 4' 8' 12' 1/8" = 1'-0"

PHASE 3 - POWER FLOOR PLAN

Revisions: Date:

PANEL K

PHASE B: RED

PHASE C: BLUE

PHASE A: BLACK

42,000 A.I.C. WITH

120/208V.,3∅,4W.

1/4"

1/8"

1/8" 1/8"

1/4"

3/8"

GROUND: GREEN

NEUTRAL: WHITE

ISO.GRD.: GRN/YEL

22KA BREAKERS AND1/4"

CLASS 'J' FUSES1/4"

1/4"

1/4"

FED FROM DP:**1/4"

1/8"

1/4"

1/4"

PANEL K

PHASE B: RED

PHASE C: BLUE

PHASE A: BLACK

10,000 A.I.C.

120/208V.,3∅,4W.

1/4"

1/8"

1/8" 1/8"

1/4"

3/8"

GROUND: GREEN

NEUTRAL: WHITE

RTU #1

LPJ 200AMP

SERVES

1/8"

1/4" RTU-1

SERVES

ISO.GRD.: GRN/YEL

FED FROM DP:**1/4"

FED FROM DP:**1/4"

CRITICAL BRANCH1/4"

1/4" CRITICAL BRANCH

CRITICAL BRANCH1/4"

NOTE: SEE SPECIFICATION SECTION 260500 FOR NAME PLATE

COLOR REQUIREMENTS.

SERIES RATED

BRANCH CIRCUIT/DISTRIBUTION PANELBRANCH CIRCUIT/DISTRIBUTION PANEL

DISCONNECT SWITCH

CONTROL CENTER BREAKER/SWITCH

SWITCHBOARD/DISTRIBUTION PANEL/MOTOR

METAL STUD

CONDUITS

RECEPTACLE

EQUIPMENT GROUND

CONDUCTOR

GROUND SCREW ON

WIRING DEVICE

GROUND SCREW IN

OUTLET BOX

CONDUIT

4 SQUARE OUTLET BOX

DRYWALL

PLASTER RING

PLASTER RING

RECEPTACLE

OUTLET BOX SECURED

TO BOX SUPPORT

GROUND SCREW IN

OUTLET BOX

WIRE NUT (TYP.)

STUD TO STUD BOX

SUPPORT, B-LINE #BB2

SERIES OR EQUAL.

NEUTRAL

CONDUCTORS

HOT CONDUCTORS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:4

P

M

EP501

ELECTRICAL POWER DETAILS

DDC KTN

NO SCALE

TYPICAL HEALTHCARE NAMEPLATES

NO SCALE

TYPICAL RECEPTACLE MOUNTING DETAIL

Revisions: Date:

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

PANELBOARD: LP5-L4-277VN

480Y/277 VOLTS, 3 PHASE, 4 WIRE

100 AMP MLO, SURFACE MTD.

65000 AIC LABELEDW/GRD. BUS

1 EXISTING LOAD A 2SPARSPARE120

3 3446 LGHT LTG: NORTH ROOMS 1 20 B 4SPARSPARE120

5 1212 LGHT LTG: OPEN OFFICE 1 20 C 6SPARSPARE120

7 945 LGHT LTG: CORRIDOR 1 20 A 8SPARSPARE120

9 SPAR SPARE 1 20 B 10SPARSPARE120

11 SPAR SPARE 1 20 C 12SPACE

13 SPAR SPARE 1 20 A 14SPACE

15 SPAR SPARE 1 20 B 16SPACE

17 SPAR SPARE 1 20 C 18SPACE

19 EXISTING LOAD A 20EXISTING LOAD

21 SPACE B 22SPACE

23 SPACE C 24SPACE

25 SPACE A 26SPACE

27 SPACE B 28SPACE

29 SPACE C 30SPACE

31 SPACE A 32SPACE

33 SPACE B 34SPACE

35 SPACE C 36SPACE

37 SPACE A 38SPACE

39 SPACE B 40SPACE

41 SPACE C 42SPACE

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

PANELBOARD: LP5-H9-277VN

208Y/120 VOLTS, 3 PHASE, 4 WIRE

30 AMP MLO, SURFACE MTD.

50000 AIC LABELEDW/GRD. BUS

1 EXISTING LOAD A 2EXISTING LOAD

3 EXISTING LOAD B 4SPARSPARE120

5 1212 LGHT LTG: SOUTH AREA 1 20 C 6SPARSPARE120

7 SPAR SPARE 1 20 A 8SPARSPARE120

9 SPAR SPARE 1 20 B 10SPARSPARE120

11 SPAR SPARE 1 20 C 12SPACE

13 SPAR SPARE 1 20 A 14SPACE

15 SPACE B 16SPACE

17 SPACE C 18SPACE

19 SPACE A 20SPACE

21 SPACE B 22SPACE

23 SPACE C 24SPACE

25 SPACE A 26SPACE

27 SPACE B 28SPACE

29 SPACE C 30SPACE

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

PANELBOARD: LP5-H9-277VE

480Y/277 VOLTS, 3 PHASE, 4 WIRE

50 AMP MAIN BKR, SURFACE MTD.

50000 AIC LABELEDW/GRD. BUS

1 EXISTING LOAD A 2EXISTING LOAD

3 EXISTING LOAD B 4SPARSPARE120

5 EXISTING LOAD C 6SPARSPARE120

7 EXISTING LOAD A 8SPARSPARE120

9 EXISTING LOAD B 10SPACE

11 EXISTING LOAD C 12SPACE

13 EXISTING LOAD A 14SPACE

15 EXISTING LOAD B 16SPACE

17 EXISTING LOAD C 18SPACE

19 860 LGHT LTG: EM LIGHTS 1 20 A 20SPACE

21 SPAR SPARE 1 20 B 22SPACE

23 SPAR SPARE 1 20 C 24SPACE

25 SPAR SPARE 1 20 A 26SPACE

27 SPACE B 28SPACE

29 SPACE C 30SPACE

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

PANELBOARD: LP5-H9-120VN

208Y/120 VOLTS, 3 PHASE, 4 WIRE

225 AMP MLO, SURFACE MTD.

65000 AIC LABELEDW/GRD. BUS

1 500 POWR RM 511 PROJECTOR SCREEN 1 20 A 2EXISTING LOAD

3 EXISTING LOAD B 4720RCPTREC: RM 513120

5 720 RCPT REC: RM 511 PROJECTOR 1 20 C 6EXISTING LOAD

7 720 RCPT REC: RM 511 1 20 A 8360RCPTREC: RM 513120

9 EXISTING LOAD B 10EXISTING LOAD

11 900 RCPT REC: RM 511/C53 1 20 C 12800RCPTREC: RM 513 UC FRIDGE120

13 540 RCPT REC: RM 511 FLOOR 1 20 A 14EXISTING LOAD

15 500 POWR RM 515 PROJECTOR SCREEN 1 20 B 16EXISTING LOAD

17 900 RCPT REC: RM 515 1 20 C 18900RCPTREC: RM 516120

19 900 RCPT REC: RM 515 1 20 A 20900RCPTREC: RM 517120

21 360 RCPT REC: RM 515 FLOOR 1 20 B 22900RCPTREC: RM 517120

23 360 RCPT REC: RM C53 1 20 C 24EXISTING LOAD

25 1200 RCPT REC: RM 518 VENDING 1 20 A1 26EXISTING LOAD

27 1200 RCPT REC: RM 518 VENDING 1 20 B1 281500POWRRM 519/533 HANDWAVE120

29 720 RCPT REC: RM 518 1 20 C 30720RCPTREC: RM 519/533120

31 1200 RCPT REC: RM 518 REF 1 20 A1 32EXISTING LOAD

33 800 RCPT REC: RM 518 ICE MAKER 1 20 B1 34EXISTING LOAD

35 900 RCPT REC: RM 522 1 20 C 36EXISTING LOAD

37 900 RCPT REC: RM 521 1 20 A 38EXISTING LOAD

39 900 RCPT REC: RM 520 1 20 B 40EXISTING LOAD

41 1500 RCPT REC: RM 520A PRINTER 1 20 C 42EXISTING LOAD

43 EXISTING LOAD A 44EXISTING LOAD

45 1080 RCPT REC: RM 523 1 20 B 461500POWRRM 524 WORKSTATIONS120

47 900 RCPT REC: RM 525 1 20 C 481500POWRRM 524 WORKSTATIONS120

49 1080 RCPT REC: RM 526 1 20 A 50EXISTING LOAD

51 EXISTING LOAD B 52EXISTING LOAD

53 1080 RCPT REC: RM 526 1 20 C 541500POWRRM 524 WORKSTATIONS120

55 EXISTING LOAD A 56EXISTING LOAD

57 EXISTING LOAD B 581500POWRRM 524 WORKSTATIONS120

59 1080 RCPT REC: RM 528/530 1 20 C 60900RCPTREC: RM 531120

61 EXISTING LOAD A 621500POWRRM 531 WORKSTATIONS120

63 1500 RCPT REC: RM 527 PRINTER 1 20 B 641500POWRRM 531 WORKSTATIONS120

65 720 RCPT REC: RM 529 1 20 C 661500POWRRM 531 WORKSTATIONS120

67 EXISTING LOAD A 68EXISTING LOAD

69 EXISTING LOAD B 701500POWRRM 531 WORKSTATIONS120

71 720 RCPT REC: RM 529 1 20 C 72EXISTING LOAD

73 1080 RCPT REC: RM 532 1 20 A 741500POWRRM 531 COPIER120

75 1080 RCPT REC: RM 532 1 20 B 761000POWRRM 519/533 PLUMBING FIXT.120

77 900 RCPT REC: RM 523/524 1 20 C 78360RCPTREC: RM 531120

79 1200 POWR DISPOSAL BREAKROOM 518 1 20 A 80500POWRTERMINAL UNIT CONTROLS120

81 EXISTING LOAD B 82EXISTING LOAD

83 EXISTING LOAD C 84EXISTING LOAD

GFCI BREAKER SHALL PROVIDE GROUND FAULT EQUIPMENT PROTECTION PER NEC.1

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

PANELBOARD: LP5-L4-120VN

208Y/120 VOLTS, 3 PHASE, 4 WIRE

225 AMP MLO, SURFACE MTD.

65000 AIC LABELEDW/GRD. BUS

1 1000 POWR FIRE SMOKE DAMPERS 1 20 A 2720RCPTREC: RM 555/C58120

3 900 RCPT REC: RM 544 COMPUTERS 1 20 B 4500POWRRM 553 PROJECTOR SCREEN120

5 600 RCPT REC: RM 544 COMPUTERS 1 20 C 6EXISTING LOAD

7 600 RCPT REC: RM 544 COMPUTERS 1 20 A 8720RCPTREC: RM 553 PROJECTOR120

9 720 RCPT REC: RM 545 PROJECTOR 1 20 B 10200RCPTRM 553 SMART BOARD120

11 200 RCPT RM 545 SMART BOARD 1 20 C 12720RCPTREC: RM 553120

13 500 POWR RM 545 PROJECTOR SCREEN 1 20 A 14900RCPTREC: RM 547120

15 720 RCPT REC: RM 545 1 20 B 16800RCPTRM 547 FRIDGE120

17 720 RCPT REC: RM 550 1 20 C 181500RCPTRM 547 PRINTER120

19 EXISTING LOAD A 20EXISTING LOAD

21 EXISTING LOAD B 22EXISTING LOAD

23 EXISTING LOAD C 24EXISTING LOAD

25 EXISTING LOAD A 26720RCPTREC: RM 547120

27 720 RCPT REC: RM 550 PROJECTOR 1 20 B 281080RCPTREC: RM 539120

29 500 POWR RM 550 PROJECTOR SCREEN 1 20 C 30EXISTING LOAD

31 200 RCPT RM 550 SMART BOARD 1 20 A 321080RCPTREC: RM 539120

33 540 RCPT REC: RM 554A 1 20 B 341080RCPTREC: RM 539120

35 720 RCPT REC: RM 554 1 20 C 361600RCPTREC: DRINKING FOUNTAIN C55120 1

37 540 RCPT REC: RM 554 1 20 A 38800RCPTREC: RM 546 COPIER120

39 720 RCPT REC: RM 556 1 20 B 40800RCPTREC: RM 546 COPIER120

41 540 RCPT REC: RM 557 1 20 C 42900RCPTREC: RM 541120

43 1200 RCPT REC: RM 557 COMPUTERS 1 20 A 44540RCPTREC: RM 542/546/C57120

45 EXISTING LOAD B 461500POWRRM 534 WORKSTATIONS120

47 1200 RCPT REC: RM 557 COMPUTERS 1 20 C 481080RCPTREC: RM 534/535120

49 EXISTING LOAD A 50EXISTING LOAD

51 EXISTING LOAD B 52EXISTING LOAD

53 EXISTING LOAD C 54EXISTING LOAD

55 1200 RCPT REC: RM 557 COMPUTERS 1 20 A 56900RCPTREC: RM 537120

57 EXISTING LOAD B 58900RCPTREC: RM 536120

59 720 RCPT REC: RM 557 PROJECTOR 1 20 C 60EXISTING LOAD

61 EXISTING LOAD A 62720RCPTREC: RM 538/C51/C56120

63 500 POWR RM 557 PROJECTOR SCREEN 1 20 B 64540RCPTREC: RM 531/534120

65 540 RCPT REC: RM 557 1 20 C 661500POWRRM 534 WORKSTATIONS120

67 720 RCPT REC: RM 540 1 20 A 68EXISTING LOAD

69 720 RCPT REC: RM 540 1 20 B 70EXISTING LOAD

71 1500 POWR RM 540 WORKSTATIONS 1 20 C 72200POWRSOUND MASKING CONTROL120

73 EXISTING LOAD A 74500POWRTERMINAL UNIT CONTROLS120

75 1500 POWR RM 540 WORKSTATIONS 1 20 B 76EXISTING LOAD

77 EXISTING LOAD C 78EXISTING LOAD

79 EXISTING LOAD A 801000POWRRM 550/545 PARTITION120

81 1500 POWR RM 540 WORKSTATIONS 1 20 B 82540RCPTREC: 27/C54120

83 1500 POWR RM 540 WORKSTATIONS 1 20 C 84500POWRTERMINAL UNIT CONTROLS120

GFCI BREAKER SHALL PROVIDE GROUND FAULT EQUIPMENT PROTECTION PER NEC.1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 -

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone 828-315-9962 www.atriaxgroup.com

GLMV Architecture 1525 E. Douglas Wichita, KS 67211 Phone 316-265-9367

PEC Professional Engineering Consultants, PA 303 S. Topeka Wichita, KS 67202 Phone 316-262-2691

589A4-18-187REMODEL 5TH FLOOR

COLUMBIA, MO

JANUARY 28, 2019

BID DOCUMENTS

C U s e rs

\k ri s .n o n d o rf

\D o c u m e n ts

\1

-0

-M

A S

T E

R E

L E

C -R

K ri s .N o n d o rf p e c

.c o m

.r v t

/2

/2

:0

:5

P

M

EP601

ELECTRICAL SCHEDULES

DDC KTN

PANELBOARD: LP5-L4-277VN

CONNECTED KVA: DEMAND CONT. SIZING AMPS:

PH-A PH-B PH-C TOTAL FACTOR KVA FACT TOTAL PH-A PH-B PH-C

Lighting 0.9 3.4 1.2 5.6 1.0 5.6 1.25 8.4 4.3 15.6 5.5 Spare 0.2 1.1 1.0 1.3 1.3 1.3 1.3

TOTAL KVA: 0.9 3.4 1.2 5.6 6.7 TOTAL AMPS: PH-A PH-B PH-C

TOTAL AMPS: 3.0 12.0 4.0 6.7 9.7 5.6 16.9 6.8

PANELBOARD: LP5-H9-277VN

CONNECTED KVA: DEMAND CONT. SIZING AMPS:

PH-A PH-B PH-C TOTAL FACTOR KVA FACT TOTAL PH-A PH-B PH-C

Lighting 0.0 0.0 1.2 1.2 1.0 1.2 1.25 4.2 0.0 0.0 12.6 Spare 0.2 0.2 1.0 0.7 0.7 0.7 0.7

TOTAL KVA: 0.0 0.0 1.2 1.2 1.5 TOTAL AMPS: PH-A PH-B PH-C

TOTAL AMPS: 0.0 0.0 10.0 3.4 4.9 0.7 0.7 13.3

PANELBOARD: LP5-H9-277VE

CONNECTED KVA: DEMAND CONT. SIZING AMPS:

PH-A PH-B PH-C TOTAL FACTOR KVA FACT TOTAL PH-A PH-B PH-C

Lighting 0.9 0.0 0.0 0.9 1.0 0.9 1.25 1.2 3.9 0.0 0.0 Spare 0.2 0.2 1.0 0.2 0.2 0.2 0.2

TOTAL KVA: 0.9 0.0 0.0 0.9 1.0 TOTAL AMPS: PH-A PH-B PH-C

TOTAL AMPS: 3.0 0.0 0.0 1.0 1.4 4.1 0.2 0.2

Revisions: Date:

PANELBOARD: LP5-H9-120VN

CONNECTED KVA: DEMAND CONT. SIZING AMPS:

PH-A PH-B PH-C TOTAL FACTOR KVA FACT TOTAL PH-A PH-B PH-C

Receptacles 8.9 8.5 15.1 10.0 1.0 10.0 (First 10000VA at 1.0 + remainder at 0.5) 22.5 0.5 11.3

> 1.0 59.0 48.4 46.5 82.2

Power 5.2 9.0 4.5 18.7 1.0 18.7 1.0 51.9 43.3 75.0 37.5 Spare 0.2 8.0 1.0 22.2 22.2 22.2 22.2

TOTAL KVA: 14.1 17.5 19.6 51.2 47.9 TOTAL AMPS: PH-A PH-B PH-C

TOTAL AMPS: 117.0 146.0 163.0 142.2 133.1 113.9 143.7 141.9

PANELBOARD: LP5-L4-120VN

CONNECTED KVA: DEMAND CONT. SIZING AMPS:

PH-A PH-B PH-C TOTAL FACTOR KVA FACT TOTAL PH-A PH-B PH-C

Receptacles 11.6 11.0 11.0 10.0 1.0 10.0 (First 10000VA at 1.0 + remainder at 0.5) 23.6 0.5 11.8

> 1.0 60.5 62.5 59.4 59.7

Power 3.0 5.5 5.7 14.2 1.0 14.2 1.0 39.4 25.0 45.8 47.5 Spare 0.2 7.2 1.0 20.0 20.0 20.0 20.0

TOTAL KVA: 14.6 16.5 16.7 47.8 43.2 TOTAL AMPS: PH-A PH-B PH-C

TOTAL AMPS: 121.0 137.0 140.0 132.7 119.9 107.5 125.2 127.2

SYSTEMS PLAN NOTES:

1. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF…