N1. THE CONTRACTOR SHALL PROVIDE OUTLET BOXES AND
1"C. TO ABOVE NEAREST ACCESSIBLE CEILING FOR ALL
NURSE CALL DEVICE LOCATIONS. ALL NURSE CALL
DEVICE LOCATIONS SHALL BE COORDINATED WITH THE
FINAL DRAWINGS FROM THE NURSE CALL SYSTEM
SUPPLIER. COORDINATE ALL REQUIREMENTS WITH THE
NURSE CALL SYSTEM SUPPLIER. MOUNTING HEIGHT FOR
EMERGENCY BATH STATIONS SHALL BE PER AIA
GUIDELINES.
NURSE CALL
H1. DO NOT ROUTE BRANCH CIRCUITS OR FEEDERS
ABOVE OR BELOW IMAGING ROOMS BECAUSE OF
POSSIBLE ELECTROMAGNETIC INTERFERENCE.
H2. BOND PANELBOARDS SERVING THE SAME PATIENT
CARE VICINITY WITH #6 AWG MINIMUM COPPER
CONDUCTOR PER NEC ARTICLE 517. THIS INCLUDES
NORMAL AND ESSENTIAL PANELBOARDS AND
ESSENTIAL PANELBOARDS FED FROM DIFFERENT
TRANSFER SWITCHES.
H3. THE GROUNDING SYSTEM IN PATIENT CARE AREAS
SHALL BE TESTED BY VOLTAGE AND IMPEDANCE
MEASUREMENTS PER NFPA 99 REQUIREMENTS.
H4. MEDICAL GAS ALARM CABLING SHALL BE PROVIDED
AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
VERIFY ALL REQUIREMENTS WITH THE MEDICAL GAS
SUPPLIER. ALL MEDICAL GAS CABLING SHALL BE IN
CONDUIT.
H5. COORDINATE ALL BOX ROUGH-IN AND PATHWAY
REQUIREMENTS FOR SOUND SYSTEMS IN OPERATING
ROOMS WITH THE EQUIPMENT SUPPLIER
H6. REFER TO THE SPECIFICATIONS FOR REQUIREMENTS
ON COLOR CODING BOXES AND/OR CONDUIT
ACCORDING TO THE SPECIFIC BRANCH OF THE
ESSENTIAL ELECTRICAL SYSTEM.
H7. REFER TO THE SPECIFICATIONS FOR REQUIREMENTS
ON COLOR CODING OF NAMEPLATES ACCORDING TO
THE SPECIFIC BRANCH OF THE ESSENTIAL ELECTRICAL
SYSTEM.
H8. THIS IS A LIFE SAFETY BUILDING WHICH MEANS IT
SHALL REMAIN REASONABLY OPERATIONAL IN THE
CASE OF A SEISMIC EVENT. REFER TO THE
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS ON
EQUIPMENT BRACING.
H9.
H10.
H11. REFER TO MANUFACTURER DRAWINGS FOR ALL
IMAGING EQUIPMENT REQUIREMENTS, INCLUDING
BUT NOT NOT LIMITED TO CIRCUIT BREAKER SIZE,
CABLE TRAY, DUCTS, CONDUITS, CABLES,
CONDUCTORS, EPO SWITCHES, AND ALL DEVICES
REQUIRED FOR A COMPLETE INSTALLATION.
H12.
H13. DIGITAL CLOCK WITH INTEGRAL TIMER SHALL BE
SIMPLEX #6303-9103 CLOCK WITH #6303-9202 CONTROL
STATION OR APPROVED EQUAL. PROVIDE 120V.
POWER TO CLOCK AND CONTROL WIRING FROM
CLOCK TO CONTROL STATION AS REQUIRED.
H14.
FOR ISOLATION PANEL CIRCUITS, USE 1" MINIMUM EMT
CONDUIT ROUTED AS DIRECT AS POSSIBLE. MAXIMUM
OF 2 CIRCUITS PER CONDUIT. REFERENCE
SPECIFICATION SECTION 260527 FOR ADDITIONAL
REQUIREMENTS.
ALL PATIENT CARE AREAS (PATIENT ROOMS AND
SUPPORT SPACES) SHALL HAVE TWO GROUND
PATHS PER N.E.C. ARTICLE 517.
THE LIFE SAFETY BRANCH AND THE CRITICAL BRANCH
OF THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE KEPT
ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND
EQUIPMENT AND SHALL NOT ENTER THE SAME
RACEWAY, BOXES, OR CABINETS WITH EACH OTHER OR
OTHER WIRING PER N.E.C. ARTICLE 517.
DIGITAL CLOCK SHALL BE SIMPLEX #6334-9125 WITH #
6334-9802 MOUNTING BRACKET AND #6334-9803
HARNESS ASSEMBLY OR APPROVED EQUAL. CLOCK
SHALL BE 120V. WITH 2-1/2" LED (4) DIGIT DISPLAY.
HEALTHCARE
H15. ALL RECEPTACLES SHALL BE HOSPITAL GRADE.
T1. EACH DATA, TELEPHONE, VIDEO, OR OTHER SYSTEMS
OUTLET REQUIRES 1"C. WITH PULL ROPE STUBBED 6"
ABOVE NEAREST ACCESSIBLE CEILING UNLESS
OTHERWISE NOTED ON PLANS. CONDUITS STUBBED
UP ABOVE CEILINGS SHALL BE TURNED OUT 90
DEGREES. PROVIDE INSULATED BUSHINGS ON ALL
CONDUITS. LABEL CONDUIT TO IDENTIFY ITS
INTENDED USE (I.E. TELEPHONE, DATA, ETC.).
COMMUNICATION / DATA
T2. RUN CABLES CONTINUOUS FROM JACK TO
ASSOCIATRD SYSTEM PATCH PANEL IN CONDUIT,
CABLE TRAY, OR J-HOOKS PER THE PLANS AND
SPECIFICATIONS. NUMBER BESIDE CABLE
SYMBOL INDICATES QUANTITY OF CABLES
REQUIRED PER HOME RUN.
T3. PROVIDE QUANTITY AND TYPE OF JACKS PER THE
DRAWINGS, SPECIFICATIONS AND DETAILS. PROVIDE
JACK AND CABLE LABELING PER THE SPECIFICATIONS.
F1. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED
PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION.
DEVICES SHOWN INDICATE DESIGN INTENT AND SHALL
BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER SHALL
PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR
DEVICES REQUIRED BY THE AUTHORITY HAVING
JURISDICTION.
F2. FIELD VERIFY LOCATIONS OF AREA SMOKE DETECTORS
AND HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF
A HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT
AIR FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN
36" OF THE TIP OF A CEILING FAN BLADE. SMOKE
DETECTORS FOR DOOR RELEASE SHALL BE LOCATED
ON THE CENTER LINE OF THE DOOR AND A MAXIMUM OF
5 FEET FROM THE DOOR. THE MINIMUM DISTANCE FROM
THE DOOR IS THE DEPTH OF THE WALL SECTION ABOVE
THE DOOR, BUT NOT LESS THAN 12".
F4. LABEL REMOTE ALARM INDICATOR FOR DUCT
MOUNTED SMOKE DETECTORS (I.E. RTU-=1 SUPPLY,
RTU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT
DETECTORS SHOULD BE LOCATED IN THE AREA
BETWEEN 6 AND 10 DUCT EQUIVALENT DIAMETERS
OF STRAIGHT, UNITERRUPTED DUCTWORK. DUCT
DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD
BE LOCATED BETWEEN THE LAST INLET OR OUTLET
UPSTREAM OF THE DAMPER AND THE FIRST INLET
OR OUTLET DOWNSTREAM OF THE DAMPER.
F3. FAN SHUTDOWN RELAY WIRING SHALL BE LOCATED
WITHIN 3 FEET OF THE FAN CONTROLS AND THE WIRING
TO THE RELAY SHALL BE MONITORED.
F5. PROVIDE 120V POWER AND FUSTAT FOR EACH
FIRE/SMOKE DAMPER. INTERLOCK WITH FIRE ALARM
CONTROL PANEL TO CLOSE THE FIRE/SMOKE DAMPER
UPON ANY ALARM AT THE FIRE ALARM CONTROL PANEL
AND TO SHUTDOWN THE ASSOCIATED MECHANICAL UNIT.
FIRE ALARM
1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE
(NEC) & THE AMERICANS WITH DISABILITIES ACT (ADA).
2. REFER TO RELATED ARCHITECTURAL, MECHANICAL,
STRUCTURAL, AND CIVIL DRAWINGS FOR RELATED
INFORMATION.
3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE
DRAWINGS.
4. E.C. SHALL REFER TO MECHANICAL DRAWINGS AND
SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED
WITH WIRING AND CONNECTION OF INTERLOCKING AND
CONTROLS OF MECHANICAL UNITS AND THERMOSTAT
LOCATIONS.
5. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO
MINIMIZE CUTTING OF BRICK OR BLOCK.
6. ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS
OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON
THE JOB PRIOR TO ROUGH-IN.
7. CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND
WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS
REQUIRED.
8. WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON
THE PLANS, THE LARGER CONDUCTOR SIZE SHALL BE
USED THROUGHOUT THE LENGTH OF THE CIRCUIT,
INCLUDING NEUTRAL AND GROUND.
9. "CT" INDICATED ADJACENT TO DEVICE INDICATES DEVICE
MOUNTED ABOVE BACKSPLASH OF COUNTER TOP.
VERIFY EXACT HEIGHT WITH ARCHITECTURAL PLANS AND
ELEVATIONS.
10. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME
RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE
CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY
BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE
CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE
MARKED OR LABELED TO INDICATE WHICH CIRCUIT THEY
ARE ASSOCIATED WITH. SEE SPECIFICATION SECTION
"LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND
CABLES" FOR ADDITIONAL INFORMATION.
12. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE
WITH PANEL DESIGNATION AND CIRCUIT NUMBER
USING CLEAR THERMAL TRANSFER (ELECTRONIC
DYMO) LABELS WITH 1/8" HIGH BLACK LETTERS (OR
CONTRASTING COLOR IF COVERPLATES ARE BLACK OR
BROWN). LABELS SHALL BE SUITABLE FOR
INDOOR/OUTDOOR USE. LABEL THE BACK OF EACH
LIGHT SWITCH COVERPLATE WITH PANEL DESIGNATION
AND CIRCUIT NUMBER USING A FINE BLACK
PERMANENT MARKER.
11. JUNCTION BOX OR RECEPTACLE FOR DRINKING FOUNTAINS
SHALL BE LOCATED BEHIND THE EQUIPMENT SKIRT UNLESS
OTHERWISE NOTED. COORDINATE CONNECTION TYPE AND
LOCATION WITH EQUIPMENT PROVIDED.
13. PROVIDE 18" LONG (MIN.) CONDUIT SLEEVES THRU ALL
WALLS WHERE CABLES ARE INDICATED OR REQUIRED TO
PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS.
SIZE CONDUIT FOR CABLES INSTALLED. AT CABLE TRAYS,
PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH OF
CABLE TRAY. MAXIMUMS SHALL BE:
1"C. = 10 CABLES
2 1/2"C. = 20 CABLES
3"C. = 30 CABLES
4"C. = 50 CABLES
14. LOCATE CABLE TRAYS 6" ABOVE CEILING. OFFSET TRAY
UP AND OVER LIGHT FIXTURES AND DUCTWORK (FIELD
VERIFY AND PROVIDE AS REQUIRED). IF PHYSICALLY
IMPOSSIBLE TO RUN CABLE TRAY UP AND OVER, THEN
PROVIDE CABLE SUPPORT HOOKS FROM STRUCTURE
ABOVE, SIZED AND RATED FOR INSTALLED CABLES PLUS
25% SPARE.
15. PROVIDE DIMMER PER THE SPECIFICATIONS.
COORDINATE DIMMER TYPE AND WIRING WITH
ASSOCIATED LIGHT FIXTURE DIMMING REQUIREMENTS (I.E.
3-WIRE, O-10V, ELECTRONIC OR MAGNETIC LOW VOLTAGE,
ETC.) OR WITH LIGHTING CONTROL SYSTEM PROPRIETARY
REQUIREMENTS (I.E. LUTRON, nLIGHT, DALI, ETC.) AS
NECESSARY. 3-WIRE DIMMERS SHALL BE PROVIDED WITH
A DEDICATED NEUTRAL FOR EACH CONTROL ZONE. 0-10V
DIMMERS SHALL BE PROVIDED WITH DIM/ON/OFF
CONTROL. COORDINATE PHASE CONTROL OF LED
DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.)
WITH LIGHT FIXTURE MANUFACTURER'S
RECOMMENDATIONS. LOW VOLTAGE CONTROL WIRING IS
NOT SHOWN ON PLANS FOR CLARITY, BUT SHALL BE
PROVIDED AS REQUIRED.
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
GENERAL NOTES
PEN WEIGHT LEGEND
LIGHT FIXTURE TO BE REMOVED
EXISTING LIGHT FIXTURE TO REMAIN
NEW LIGHT FIXTURE
DUPLEX GROUNDED REC TO BE REMOVED
EXISTING DUPLEX GROUNDED REC TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
SOLID LINES ARE NEW TO BE INSTALLED
NEW DUPLEX GROUNDED RECEPTACLE
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT
SOLID LINES ARE EXISTING TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
DASHED LINES ARE EXISTING TO BE REMOVED
LIGHT FIXTURE TO BE RELOCATED
DUPLEX GROUNDED REC TO BE RELOCATED
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT
DASHED LINES ARE EXISTING TO BE RELOCATED
SECURITY
WALL M
E
W
W
B
K KEY PAD
SECURITY BEAM DETECTOR
GLASS BREAK SENSOR
CARD READER
MAGNETIC LOCK
ELECTRIC DOOR STRIKE
DOOR POSITION SWITCH
DOOR LOCK & POSITION SWITCHDOOR RELEASE BUTTON
CCTV CAMERA - FIXED
CCTV CAMERA - FIXED
CCTV CAMERA - PAN/TILT/ZOOM
DURESS
CCTV CAMERA - PAN/TILT/ZOOM
SEC ROOM MOTION DETECTOR
SEC ROOM MOTION DETECTOR
CR
WALL
CEILING
CEILING
REQUEST TO EXIT DEVICEED
WALL/CLG
SEC CORRIDOR MOTION DETECTOR
CEILING
CONDUIT AND WIRING
PHASE CONDUCTORS/
NEUTRAL CONDUCTOR (#12 UON)
EMERGENCY CIRCUIT
CONDUIT RUN PARTIAL CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CDT RUN 2#12 & 1#12 GRD.- 1/2"C.
OR CDT RUN AS NOTED ON PLAN
CDT RUN 2#12 & 1#12 GRD.- 3/4"C.
OR CDT RUN AS NOTED ON PLAN
CLG/WALL
MASTER/SLAVE FIXTURE WHIP
CONDUIT HOME RUN, 2 CIRCUITS.
4#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 3 CIRCUITS.
6#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#10 & 1#10 GRD.
#10
GROUND CONDUCTOR (#12 UON)
CONDUIT HOME RUN, 2 CIRCUITS
SWITCH LEGS (#12 UON)
CEILING
CLG/WALL
CLG/WALL
EARTH/
FLOOR
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
LOW VOLTAGE WIRING CLG/WALL
MISC. EQUIPMENT CONNECTION
CONDUIT SEAL OFF
AUDIO-VISUAL
CEILINGCEILING MOUNTED SPEAKER
CLOCK/SPEAKER (SYSTEM CLOCK)
WALL MOUNTED SPEAKER
DIGITAL CLOCK WITH TIMER
(GEN NOTE H14)
WALL
PA/SOUND SYSTEM W/RACK/SHELF'PACP' FLOOR/WALL
WALL
SYSTEM CLOCK
(A=ANALOG, D=DIGITAL)
WALL
WALL
VOLUME CONTROL
BELL
CALL SWITCH 46"AFF
MICROPHONE OUTLET
WALL
46"AFF
BOTTOM 80"
V
FIRE ALARM
46"AFFFIRE ALARM MANUAL STATION
DUCT SMOKE DETECTOR &
FIRE/ SMOKE DAMPER (GEN
NOTES F4 & F5)
FIRE ALARM VISUAL SIGNAL
FIRE ALARM HORN
DUCT SMOKE DETECTOR
(GEN NOTE F4)
IONIZATION AREA SMOKE
DETECTOR (GEN NOTE F2)
PHOTO ELECTRIC AREA SMOKE
DETECTOR (GEN NOTE F2)
F.A. RELAY (GEN NOTE F3)R
CH CHIME
DUCTWORK
CEILING
FIRE ALARM CONTROL PANEL'FACP'
FIRE SPRINKLER ALARM BELL
WALL
BOTTOM 80"
COMB. F.A. HORN & VISUAL SIGNAL
BOTTOM 80"
BOTTOM 80"
FIRE ALARM SPEAKER
COMB FA SPEAKER & VISUAL SIGNAL
FIRE ALARM REMOTE ANNUNCIATOR'FAAP' WALL
COMB FA HORN & VISUAL SIGNAL
FSD DUCTWORK
WALL
WALL
WALL
BOTTOM 80"
FIRE SPRINKLER TAMPER SWITCHT
ELECTROMAGNETIC DOOR HOLDER
FIRE SPRINKLER WATER FLOW SWW
HEAT DETECTOR (GEN NOTE F2)H
SPRKLR RSR
M
C FIRE ALARM CONTROL MODULE
FIRE ALARM MONITOR MODULE
FIRE ALARM SPEAKER
FIRE SPRINKLER PRESSURE SWITCHP
FIRE ALARM SPEAKER
CEILING
WALL
WALL
SPRKLR RSR
SA
NC PATIENT STATION (GEN NOTE N3)
WALL'NCCP' NC CONTROL PANEL
NC PRESENCE STATION
NC STAFF ASSIST STATION
WITHOUT AUDIO
NC DUTY STATION
CEILINGNC ZONE LIGHT
E
X
S
N
46" AFF
NC STAFF STATION W/ AUDIO
P
NC AUXILIARY JACKA
NC BED INTERFACE UNIT 46" AFF
NC MASTER STATION
BI
DESKTOPNC
CLG/WALLNC VISUAL SIGNAL
NC CODE BLUE STATION 46" AFFB
NC EMERGENCY BATH STATION
46" AFF
46" AFF
46" AFF
46" AFF
46" AFF
NURSE CALL
1-VOICE OUTLET & JACK (GEN
NOTES T1 & T3)
1-VOICE/1-DATA OUTLET &
JACKS (GEN NOTES T1 & T3)
1-DATA OUTLET & JACK (GEN
NOTES T1 & T3)
18"AFF
CABLE TV OR VIDEO OUTLET &
CONNECTOR (GEN NOTES T1 & T3)
1-VOICE/2-DATA OUTLETS &
JACKS (GEN NOTES T1 & T3)
2-VOICE/2-DATA OUTLETS & JACKS
(GEN NOTES T1 & T3)
1-VOICE/3-DATA OUTLETS &
JACKS (GEN NOTES T1 & T3)
4-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
2-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
3-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF 18"AFF
18"AFF
18"AFF
COMMUNICATION / DATA
VIDEO COAX CABLE HOME RUN
FIBER OPTIC CABLE HOME RUN
(MULTI MODE)
FIBER OPTIC CABLE HOME RUN
(SINGLE MODE)
DATA UTP CABLE HOME RUN
VOICE UTP CABLE HOME RUN GEN NOTE T2
GEN NOTE T2
GEN NOTE T2
GEN NOTE T2
GEN NOTE T22
POWER
DUPLEX GROUNDED RECEPTACLE
FUSTAT BUSS #SSY
SPECIAL DEVICE (AS NOTED)
JUNCTION BOX - 1-GANG
DOUBLE DUPLEX GROUNDED REC
GROUND FAULT DUPLEX REC
DUPLEX GROUNDED RECEPTACLE
SINGLE GROUNDED RECEPTACLE
DUPLEX GRD REC BOTTOM SWITCHD
GRD FAULT DOUBLE DUPLEX REC
18" AFF
A
ELECTRICAL DISTRIBUTION EQUIP
EQUIPMENT - SEE EQUIPMENT
CONNECTION SCHEDULE
x-x x-x
CONDUIT SLEEVE (GEN NOTE 13)
CABLE TRAY (GEN NOTE 14)
FEEDER DESIGNATION
M MANUAL STARTER
CIRCUIT BREAKER
DISCONNECT SWITCH
M MOTOR
PLUGMOLD SURFACE RACEWAY
S
18" AFF
18" AFF
CEILING
18" AFF
18" AFF
18" AFF
FLOOR/WALL
72" TO TOP
WALL
JUNCTION BOX - 2-GANG
PLUG LOAD SENSOR CEILING
HANDICAP DOOR PUSHBUTTON 36" AFF
RELAY
PUSHBUTTON (1-BUTTON, 2-BUTTON)
BOX MOUNTED TRANSFORMER
46" AFF
CONTACTOR
METER
STARTER OR ATS (AS NOTED)
COMBINATION STARTER/DISC
BUSDUCT PLUG
THERMOSTAT/TEMP SENSOR 46" AFF
SPECIAL OUTLET (SEE
SCHEDULE OR AS NOTED)
BRANCH CIRCUIT PANEL AND
PANEL DESIGNATION
J
A
F
A
TS
H
P
1J
C
T
R
2D
1D
2M
SWITCHES (KEYED, PILOT, TIMER)
INDICATES SWITCHING SCHEME
EMERGENCY BATTERY LIGHT FIXT
LIGHT FIXTURE & FIXTURE LETTER
46" AFF
A
A
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
STRIP LIGHT FIXTURE & FIXT LETTERA
A
A
A
1 RELAY PIR SENSOR
PIR SENSOR
2 RELAY PIR SENSOR
DUAL TECHNOLOGY SENSOR
1 RELAY DUAL TECH SENSOR
2 RELAY DUAL TECH SENSOR
M
D DIMMER (SEE GENERAL NOTE 15)
ON/OFF SWITCH
S
PC PHOTOCELL
CLG/WALL
CLG/WALL
46" AFF
46" AFFSSS
SSS
S a, b, c
CEILING
CEILING
CEILING
WALL
CEIL/WALL
WALL
CEILING
CEIL/WALL
46" AFF
46" AFF
46" AFF
46" AFF
46" AFF
2 3 4
K P T
LIGHTING, SWITCHES AND SENSORS
SWITCHES (1-POLE, 2-POLE,
3-WAY, 4-WAY)
EXIT SIGN (SHADING DENOTES
EXIT FACE SIDE)
FIXTURE WITH SHADED LAMP(S)
ON EMERGENCY POWER
WALLCOMB EXIT SIGN/EM BATTERY LIGHT
SP SWITCHING POWER PACK
SE UL924 SWITCHING POWER PACK
DP DIMMING POWER PACK
DE UL924 DIMMING POWER PACK
46" AFF
ON/OFF/0-10V DIMMING SWITCH
S
46" AFF
DUAL TECH ON/OFF SENSOR
S
46" AFF
16-SCENE WALL CONTROLLER
S
46" AFF
DUAL TECH ON/OFF/0-10V DIM SW
S
46" AFF
LOW VOLTAGE SWITCH
S
A
A
A
A A
LIGHT FIXTURE & FIXTURE LETTERA POLEA
AV AV SYSTEM/LIGHTING INTERFACE
NIGHT LIGHT - WIRE AHEAD OF
ABBREVIATIONS
NL
EM
WP
CT
UON
ON EMERGENCY POWER
WEATHERPROOF
COUNTERTOP (SEE GEN. NOTE 9)
UNLESS OTHERWISE NOTED
ABOVE FINISHED FLOORAFF
AFG ABOVE FINISHED GRADE
WALLW
CONTROLS
DRINKING FOUNTAIN -
SEE GENERAL NOTE 11
DF
GENERAL NOTES
SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
E-001
ELECTRICAL LEAD SHEET
Wichita, Kansas
SMS JLW04-27-2018
SHEET INDEX
NUMBER SHEET TITLE
E-001 ELECTRICAL LEAD SHEET
ED100 ELECTRICAL DEMOLITION PLAN - LOWER LEVEL
ED102 ELECTRICAL DEMOLITION PLAN - SECOND FLOOR
ED103 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR
ED103.3 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 3
ED103.4 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 4
EL102 ELECTRICAL LIGHTING PLAN - SECOND FLOOR
EL103 ELECTRICAL LIGHTING PLAN - THIRD FLOOR
EL103.3 ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 3
EL103.4 ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 4
EL501 ELECTRICAL LIGHTING DETAILS
EL601 ELECTRICAL LIGHTING SCHEDULE
EP100 ELECTRICAL POWER PLAN - LOWER LEVEL
EP102 ELECTRICAL POWER PLAN - SECOND FLOOR
EP103 ELECTRICAL POWER PLAN - THIRD FLOOR
EP103.3 ELECTRICAL POWER PLAN - THIRD FLOOR - BID ITEM 3
EP103.4 ELECTRICAL POWER PLAN - THIRD FLOOR - BID ITEM 4
EP501 ELECTRICAL POWER DETAILS
EP601 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION
EP602 ELECTRICAL ONE-LINE DIAGRAM - NEW CONSTRUCTION
EP603 ELECTRICAL POWER SCHEDULES
EY102 ELECTRICAL SYSTEMS PLAN - SECOND FLOOR
EY103 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR
EY103.3 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR - BID ITEM 3
EY103.4 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR - BID ITEM 4
EY501 ELECTRICAL SYSTEMS DETAILS
SPECIAL OUTLETS
MARK DESCRIPTION
OM OMNICELL/PYXIS LOCATION. PROVIDE FSR #PWB-200 RECESSED WALL
BOX. PROVIDE (1) 20A. 120V. DUPLEX GROUNDED RECEPTACLE AND
(2) DATA OUTLETS. PROVIDE MATCHING COVERPLATE AND ALL
ASSOCIATED MOUNTING HARDWARE. MOUNT AT 42" AFF.
PD POWERED DOOR OPERATOR.
PL PATIENT LIFT CONNECTION. PROVIDE DUPLEX RECEPTACLE IN
LOCKABLE ENCLOSURE ABOVE CEILING. SIZE LOCKABLE ENCLOSURE
AS REQUIRED BY PATIENT LIFT EQUIPMENT. VERIFY EXACT LOCATION
OF LIFT MOTOR WITH SUPPLIER PRIOR TO INSTALLATION.
PTV PATIENT TV LOCATION. PROVIDE DUPLEX RECEPTACLE, COAX DROP,
DATA DROP, AND NURSE CALL CONTROL INTERFACE IN RECESSED
ENCLOSURE. PROVIDE FSR #PWB-250 RECESSED WALL BOX. ROUTE
1-1/4" CONDUIT TO ABOVE ACCESSIBLE CEILING FOR ROUTING OF
LOW VOLTAGE CABLING. PROVIDE (1) 120V 20A DUPLEX RECEPTACLE,
(1) CAT-6 DATA RECEPTACLE, (1) CATV F-TYPE CONNECTOR, AND
NURSE CALL INTERFACE. PROVIDE COVERPLATE AND ALL
ASSOCIATED MOUNTING HARDWARE. MOUNT AT 68" A.F.F.
COORDINATE MOUNTING HEIGHT AND LOCATIONWITH PATIENT TV
MOUNT SO THAT RECESSED WALL BOX IS COMPLETELY HIDDEN
BEHIND TV.
U COMBINATION DUPLEX RECEPTACLE AND USB CHARGING
RECEPTACLE WITH 5A, 5V OUTPUT. PROVIDE HUBBEL #USB20AC OR
APPROVED EQUAL WITH 120V, 20A DUPLEX RECEPTACLES, (1) USB
TYPE-A RECEPTACLE, (1) USB TYPE-C RECEPTACLE.
No. Description Date
23475234752347523475 04/26/2018
1-1 1-2 1-3
1-4
1-6
1-7
1-9
1-10 1-11 1-12
1-13
1-151-16
1-18
1-20 1-21 1-25
1-27
1-28 1-29 1-30
1-31
1-A
1-B
1-C
1-D
1-E
1-F
1-G 1-H
1-I
1-J
1-M
1-N
1-Q
1-T
1-U
1-V
1-W
1-X
1-R
1-23
1-5
1-3A
1-3B
1-26
1A-1 1A-2 1A-3
1A-A
1A-B
1A-C
1A-D
1-AHU-1
(E) 1-RF1
ED100
B
(E) 1-SA1
(E) 1-AFM1
(E) 1-SH1
(E) 1-AFM2
EXISTING PANEL '1-B-EM' TO REMAIN.
PANEL SERVES AIR HANDLING UNIT
FANS AND PUMPS
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK.
EE7819
EE44491
EE7908A
EE8602
EMD-1A
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
ED100
ELECTRICAL DEMOLITION PLAN - LOWER
LEVEL
Wichita, Kansas
SMS JLW04-27-2018
1/8" = 1'-0" A
ELECTRICAL DEMOLITION PLAN - LOWER LEVEL
N 4' 8' 16'
1/8" = 1'-0"
0'
PLAN INCLUDED FOR REFERENCE. DEMOLITION OF
MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT,
CONDUCTORS, DISCONNECTING MEANS, ETC. IS THE
EXTENT OF DEMOLITION WORK.
1/4" = 1'-0" B
ENLARGED BASEMENT ENGINEERING ROOM 2' 4' 8'0'
1/4" = 1'-0"
N
No. Description Date
1-6
1-7
1-9
1-10 1-11 1-12
1-13
1-16
1-18
1-20 1-21 1-25
1-D
1-E
1-F
1-G
1-H
1-J
1-M
1-U
1-X
1-23
1-5
1-3A
1-3B
REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,
DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL
EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND
DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.
1-2W-EM
1-2W
SHADED AREA NOT IN
SCOPE OF WORK
EXISTING PANELBOARD TO BE REMOVED. ALL EXISITNG CONDUIT
AND CIRCUITING SHALL BE REMOVED. PANELBOARD INCOMING
FEEDER SERVES PANELBOARD ON LEVEL ABOVE. COORDINATE
REMOVAL OF PANELBOARD IN ORDER TO MAINTAIN POWER TO
PANEL ON LEVEL ABOVE AND MINIMIZE DOWNTIME (TYPICAL OF 2).
EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND
DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES
DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED
BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR
EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
EXISTING TELECOM
CLOSET
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK. SECOND FLOOR KEY PLAN
N
PHASE 1 PROJECT
STORAGE
237-1
HSKPG
239-1
STOR
237A-1
RESPIRATORY THERAPY
OFFICE
243-1
245-1
STAIRS
2-STAIR-C
ELEV.
2-ELEV
HEMODIALYSIS EXAM
ROOM
200-1
ICU WAITING ROOM
286-1
SLEEP
286A-1
RR
285-1
STUDY ROOM
284-1
BREAK ROOM
250-1
CORRIDOR
2-CORR-1
GUEST ROOM
227-1
GUEST ROOM
226-1
TELEHEALTH
225-1
NURSE OFFICE
224-1
ASSOCIATE DIRECTOR ICU
222-1
RR
226A-1
HEMODIALYSIS STORAGE
201-1
SPEECH THERAPY OFFICE
202-1
OFFICE
203-1
BREAK AND LOCKER ROOM
204-1
OFFICE
205-1
RR
222A-1
RR
206-1
ELEC
207-1
EDUCATION STORAGE
208-1
OFFICE
209-1
EDUCATION OFFICE
210A-1
EDUCATION OFFICE
210-1
CHAPEL
211-1
TOILET
212-1
EUCHARISTIC CHAPEL
213-1
215A-1
STORE
214-1
CHAPLAIN OFFICE
215-1
CHAPLAIN PASTORAL CARE
OFFICE
216-1
CHAPLAIN OFFICE
216B-1
216A-1
SIMULATION LAB
217-1
STORE
218-1
VISUAL IMPAIRMENT
SERVICES
219-1
OFFICE
220-1
RR
220A-1
OFFICE
221-1
STAIRS
2-STAIR-W
TELECOM
223-1
CORRIDOR
2-CORR-W
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
ED102
ELECTRICAL DEMOLITION PLAN - SECOND
FLOOR
Wichita, Kansas
SMS JLW04-27-2018
1/4" = 1'-0" A
ELECTRICAL DEMOLITION PLAN - SECOND FLOOR
N
2' 4' 8'0'
1/4" = 1'-0"
No. Description Date
1-6
1-7
1-9
1-10 1-11 1-12
1-13 1-18
1-D
1-E
1-F
1-G
1-H
1-J
1-M
1-N
1-Q
1-T
1-U
1-V
1-X
1-23
1-5
1-3A
1-3B
REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,
DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL
EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND
DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.
1-3W
1-3W-EM
SHADED AREA NOT IN
SCOPE OF WORK
EXISTING PANELBOARD TO BE REMOVED. ALL EXISITNG CONDUIT
AND CIRCUITING SHALL BE REMOVED.
EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND
DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES
DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED
BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR
EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK. THIRD FLOOR KEY PLAN
PHASE 1
N
NURSE STATION
313B-1
PATIENT ROOM
310-1
PATIENT ROOM
317-1
RR
319A-1
OBSERVATION
318-1
PATIENT ROOM
319-1
PATIENT ROOM
320-1
NURSE OFFICE
320A-1
HSKPG
316-1
CLEAN LINEN
315-1
MEDICAL ROOM 1
314B-1
STAIRS
3-STAIR-W
RESIDENTS OFFICE
314-1
PATIENT ROOM
313-1
TOILET
311A-1
TOILET
313A-1
RR
312-1
MEN'S
308-1
ELEC
307-1
STAFF RR
306-1
PATIENT ROOM
309-1
PATIENT ROOM
311-1
CLEAN SUPPLY
305-1
SPD STORAGE
304-1
PATIENT ROOM
303-1
PATIENT ROOM
302-1
NURSE OFFICE
301-1
EMPLOYEE LOUNGE
300-1
PATIENT ROOM
327-1
PATIENT ROOM
325-1
STORAGE
324-1PATIENT ROOM
323-1
PATIENT ROOM
321-1
TELECOM
322-1
RR
321A-1
RR
326-1
RR
325A-1
EQUIPMENT STORAGE
381-1
RECEPTION
380-1
VENDING
379-1
PATIENT ROOM
377-1
STAIRS
3-STAIR-C
IRM
345-1
RN OFFICE
343-1
HSKPG
339-1
TOILET
338-1
LOCKER ROOM
337-1
TELCOM
344-1
ELEV.
3-ELEV
CORRIDOR
3-CORR-W
CORRIDOR
3-CORR-C
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
ED103
ELECTRICAL DEMOLITION PLAN - THIRD
FLOOR
Wichita, Kansas
SMS JLW04-27-2018
1/4" = 1'-0" A
ELECTRICAL DEMOLITION PLAN - THIRD FLOOR 2' 4' 8'0'
1/4" = 1'-0"
N
No. Description Date
THIRD FLOOR KEY PLAN
PHASE 1
N
1-1 1-2 1-3
1-4
1-6
1-7
1-9
1-10 1-11 1-12
1-13 1-18
1-D
1-E
1-F
1-G
1-H
1-J
1-M
1-N
1-Q
1-T
1-U
1-V
1-X
1-23
1-5
1-3A
1-3B
REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,
DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL
EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND
DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.
SHADED AREA NOT IN
SCOPE OF WORK
1-3W-EM
1-3W
EXISTING PANELBOARD AND ALL CIRCUITS AND ASSOCIATED
CONDUITS FED FROM THIS PANEL TO BE REMOVED. CIRCUITS
ON THIS FLOOR THAT ARE TO REMAIN BY BID ITEM SHALL BE
FED FROM NEW PANELBOARD. SEE NEW CONSTRUCTION
FLOOR PLANS FOR ADDITIONAL INFORMATION.
SHADED AREA NOT IN
SCOPE OF WORK
EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND
DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES
DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED
BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR
EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK.
NURSE STATION
313B-1
PATIENT ROOM
310-1
PATIENT ROOM
317-1
RR
319A-1
OBSERVATION
318-1
PATIENT ROOM
319-1
PATIENT ROOM
320-1
NURSE OFFICE
320A-1
HSKPG
316-1
CLEAN LINEN
315-1
MEDICAL ROOM 1
314B-1
STAIRS
3-STAIR-W
RESIDENTS OFFICE
314-1
PATIENT ROOM
313-1
TOILET
311A-1
TOILET
313A-1
RR
312-1
MEN'S
308-1
ELEC
307-1
STAFF RR
306-1
PATIENT ROOM
309-1
PATIENT ROOM
311-1
CLEAN SUPPLY
305-1
SPD STORAGE
304-1
PATIENT ROOM
303-1
PATIENT ROOM
302-1
NURSE OFFICE
301-1
EMPLOYEE LOUNGE
300-1
PATIENT ROOM
327-1
PATIENT ROOM
325-1
STORAGE
324-1PATIENT ROOM
323-1
PATIENT ROOM
321-1
TELECOM
322-1
RR
321A-1
RR
326-1
RR
325A-1
EQUIPMENT STORAGE
381-1
RECEPTION
380-1
VENDING
379-1
PATIENT ROOM
377-1
STAIRS
3-STAIR-C
IRM
345-1
RN OFFICE
343-1
HSKPG
339-1
TOILET
338-1
LOCKER ROOM
337-1
TELCOM
344-1
ELEV.
3-ELEV
CORRIDOR
3-CORR-W
CORRIDOR
3-CORR-C
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
ED103.3
ELECTRICAL DEMOLITION PLAN - THIRD
FLOOR - BID ITEM 3
Wichita, Kansas
Checker Author04-27-2018
2' 4' 8'0'
1/4" = 1'-0"
N
1/4" = 1'-0" A
ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 3
No. Description Date
THIRD FLOOR KEY PLAN
PHASE 1
N
1-1 1-2 1-3
1-4
1-6
1-7
1-9
1-10 1-11 1-12
1-13 1-18
1-D
1-E
1-F
1-G
1-H
1-J
1-M
1-N
1-Q
1-T
1-U
1-V
1-X
1-23
1-5
1-3A
1-3B
REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,
DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL
EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND
DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.
SHADED AREA NOT IN
SCOPE OF WORK
SHADED AREA NOT IN
SCOPE OF WORK
1-3W
1-3W-EM
EXISTING PANEL TO
REMAIN (TYPICAL)
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK.
NURSE STATION
313B-1
PATIENT ROOM
310-1
PATIENT ROOM
317-1
RR
319A-1
OBSERVATION
318-1
PATIENT ROOM
319-1
PATIENT ROOM
320-1
NURSE OFFICE
320A-1
HSKPG
316-1
CLEAN LINEN
315-1
MEDICAL ROOM 1
314B-1
STAIRS
3-STAIR-W
RESIDENTS OFFICE
314-1
PATIENT ROOM
313-1
TOILET
311A-1
TOILET
313A-1
RR
312-1
MEN'S
308-1
ELEC
307-1
STAFF RR
306-1
PATIENT ROOM
309-1
PATIENT ROOM
311-1
CLEAN SUPPLY
305-1
SPD STORAGE
304-1
PATIENT ROOM
303-1
PATIENT ROOM
302-1
NURSE OFFICE
301-1
EMPLOYEE LOUNGE
300-1
PATIENT ROOM
327-1
PATIENT ROOM
325-1
STORAGE
324-1PATIENT ROOM
323-1
PATIENT ROOM
321-1
TELECOM
322-1
RR
321A-1
RR
326-1
RR
325A-1
EQUIPMENT STORAGE
381-1
RECEPTION
380-1
VENDING
379-1
PATIENT ROOM
377-1
STAIRS
3-STAIR-C
IRM
345-1
RN OFFICE
343-1
HSKPG
339-1
TOILET
338-1
LOCKER ROOM
337-1
TELCOM
344-1
ELEV.
3-ELEV
CORRIDOR
3-CORR-W
CORRIDOR
3-CORR-C
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
ED103.4
ELECTRICAL DEMOLITION PLAN - THIRD
FLOOR - BID ITEM 4
Wichita, Kansas
Checker Author04-27-2018
2' 4' 8'0'
1/4" = 1'-0"
N
1/4" = 1'-0" A
ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 4
No. Description Date
D
D
D
M
M
D
M
D
D
D
D
D
D
D
D
D
D
D
DD
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
M
M
DD
D D
M
M
D
D
D
D
D
M
PATIENT ROOM
221-1
TOILET
220-1
SOILED UTILITY
218-1
TOILET
217-1
PATIENT ROOM
216-1
AIRBORNE INFECTION ISO.
PATIENT ROOM
214-1
TOILET
213-1
PATIENT ROOM
211-1
TOILET
209-1
PATIENT ROOM
208-1
PATIENT ROOM
204-1
BARIATRIC PATIENT ROOM
202-1
PATIENT ROOM
233-1
PATIENT ROOM
234-1
PATIENT ROOM
236-1
TOILET
232-1
ANTE RM
215-1
CHARTING
206-1
TOILET
238-1
RECEPTION
241-1
NURSE STATION
224-1
EXIST. STAIRS
2-STAIR-W
TOILET
210-1
TOILET
203-1
TOILET
205-1
CORR
200-1
CORR
201-1
CORR
212-1
CORR
219-1
CORR
207-1
STAFF TOILET
222-1 SB
HA
HA
HA
HA HA
ST
ST
L1
L2 a c a a b b d a b c d f,g f,g e
HS
HA
h j h h j
SV
KA
KA
KA
KA
KA
KA
KA
KA
KA KA KA KA KA KA
KA KA KA KA
KA
KA
KA
K2F
K2 b
NL a
NL
a
NL
a
NL
a
NL
a
NL
a
NL
a
NL
a
NL
a a NL a
SV
SB
HA
HA HAHA
HA
HS
SB
HA
HA
HA
HA
HA
HA
HS SV
SB
HA HA
HA HA
HA
SV
HS
HA
HA
SV
HS
SB
HA HA HA
HA
HA
SV
HA HS
SB
HA HA HA
HASB
SV
HA
HS
SV
HA
HS
HA
HA
HA
SB
HA
SV
SV
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
HA
HA
SB
HA
HA
HA
HA
HA
SB
HAHA
HA
HA
HS
HA
HS
KA
KA
KA
KAKA
KA
NL
a NL
N4
CLEAN UTILITY
231-1
MEDICATION
230-1
CLEAN LINEN
201B-1
NOURISH.
227-1
EQUIP. STOR.
229-1
ELECT.
228-1
KA
KA KA
KA
KA
b b b NL c
3a
3a d e e e e d d d d d dK4
K4
K4
K4
K4
N4
KA
HL HL
HA
KA
H4
H4
H4
H4
H4
H4 H4
H4
H4
H4
HA
KA
HA
HA
HL HL
HL HL
HL HL
HA
HA
HL
HA
HL
HA
HA
HA
HA
HA
HL HL
HA
HLHL
HL
HL
HA
HA
HA
HL
HL
HA
HAHA
HL
HL
KA
e
SV
HA
e e a a a
SHADED AREA NOT IN
SCOPE OF WORK
b h h j h jb d d a a a a a a b c e f,g e e f,g c b a c c a a f,g e e f,g e a a b d d hj h b h j a c c a a b d d f,g e e ef,g f,g e e e f,g a d d c c a a b a b a h j h b h j c c d df,ge ee f,g a a a a a b b b j h h j h h j b h j h b aaaa d d e e f,ge f,g c c b a d d h j b j h h a b a e e e f,g f,g a c c a a b c c a a a b a f,g e e f,ge b a h j h j h b h h j b jh b dd c a c a b a ef,g e e f,g a a
ST
KA
H4 H4
H4
H4
H4
H4
X1
X1
X1
X1
X2
X2
X1
X1 h b h j a b b b c c c c c c c c c c
L1 L2
L2L1
L1L2
L1L2
L2
L1
L2 L1
L2L1
L1
L2
L1
L2
X1 X1
L3 h j
L3
L3
U1
U1 U1
U1
U2
U1
U1
U2 U2 U2
U2
U2
L4
KA
a
L3
L4
L3
L3
L3
L4
L3
L3
L3
L4
L4 L4
L4
L4
1-EL-2W
1-2W
1-EC-2W
U1
U1
U1
U1
L4
L4
1-EC-2W:2
1-2W:2
1-2W:2
1-2W:2
1-2W:2
1-2W:2
HSKPG
240-1
1-EL-2W:2
1-2W:4
1-2W:6
1-EC-2W:4
1-2W:6
1-2W:6
1-2W:6
1-2W:6
1-2W:6
1-2W:6
1-EC-2W:4
1-EC-2W:4
1-EC-2W:2
1-EC-2W:2
1-EC-2W:2
1-EC-2W:4
1-EC-2W:6
1-EC-2W:6
1-EC-2W:6
1-EC-2W:6
CLOSET
207A-1
U2
U1
U2
U2
U2U1
U2
U2
U2
U2
U2U2 U1
U2U1
U1U2
L4L4
L4
U2
U2
L4
L4
U1U2
L4
L4
U2
U1
L4
L4 U1
U2
L4
U2 U1
L4
U2
U1 L4
L4
SECOND FLOOR KEY PLAN
N
PHASE 1 PROJECT
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF
FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF
ONE HOUR.
4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH
ARCHITECT PRIOR TO ROUGH-IN.
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
EL102
ELECTRICAL LIGHTING PLAN - SECOND
FLOOR
Wichita, Kansas
SMS JLW04-27-2018
1/4" = 1'-0" A
ELECTRICAL LIGHTING PLAN - SECOND FLOOR
N
2' 4' 8'0'
1/4" = 1'-0"
KEYED NOTES:
L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH
FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF
FIXTURE ‘SB’.
L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE
LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE
CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM
PILLOW SPEAKER.
L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN
MANUFACTURED HEADWALL UNIT.
L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE
CIRCUIT BELOW.
No. Description Date
M
M
DD
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
DD
D
D
D
D
D
D
D
D D
D
D D
D
M
M
D
D
D
M
PATIENT RM
316-1
TOILET
317-1
SOILED UTILITY
319-1
STORAGE
320-1
TOILET
321-1
PATIENT RM
322-1
TOILET
310-1
TOILET
309-1
PATIENT RM
308-1
BARIATRIC PATIENT ROOM
302-1
PATIENT RM
304-1
TOILET
305-1
HSKPG
324-1
TOILET
335-1
PATIENT ROOM
334-1
PATIENT ROOM
336-1
TOILET
337-1
EQUIP. STOR.
338-1
EQUIP. ALCOVE
300-1
NURSE STATION
325-1
HALL
307-1
HALL
301-1
HALL
326-1
HALL
339-1
HALL
312-1
CHARTING
306-1
STAFF TOILET
323-1
TOILET
313-1
ANTE RM
318-1
KAKA
KAKAKAKAKAKAKAKA
KA
KA
KA
KA
KA
KA
KA
K2
KA
KA
K2F K2
K2 b a
NL
a
NL
a a
NL
NL
NL a a NL a a NL a NL
K4
K4
HS
HA
HA
SB
HA HA
SB
SV
HS
HA HA
HA
HA
HAHA
SB
HA
HA HA
HA
HA
SV
HA
HS
SB
SV
HS
HA
HA
HA
SB
SV
HS
HA
HA
SB
SV
HS
HA
HA
SV
HS
HA
HAHA
SB
HA
HA
HS
SB
SV
HA HS
SB
HA
HA
STST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
KA
KA
KA
KA
KA
N4
K4
K4
K4
K4
K4
K4
N4 c c c
3a c
3a a
NL
HA HA HA
KA
HLHL
HA
HAHA
HL HL
HAHA
SV
ST
HL
HL
HA
HL
HL
HA
HL HL
HA
HL
HL
HA
HA
HAHA
HA
HA
HA
HA
HA
HL HL
HA HA
HA HA
HA
H4 H4
H4
H4
H4
H4
HL HL
HA
HL HL
KA
1-3W b b b b b b a
SHADED AREA NOT IN
SCOPE OF WORK
X1
KA
X1
X2
X1
X2
X1
H4 b
CLOSET
307A-1
HA
HA
a b c ca a e e f,g f,g e a a b h d d j j h h a b d d b h j j h h b a a a e e f,g e f,g c c b a a a b a a b a d d f,g ee f,g e c c jh h b h j d dc c aa f,g ee f,g e a b a b a h j h b h j c cd de f,g f,g e e a a a a a b b h j b h h j j h b h j h b a a a a b c c a d d f,g e e f,g e h h b j b h j d d a a a c ce ee f,g f,g b a a c a c b h b a j h j h b e e f,ge f,g a ef,g e e f,g aaca a b c d d b b jh h h j
1-EC-3W1-EM-3W
a
1-EL-2W:4
CLEAN UTILITY
330-1
CLEAN UTILITY
330-1
CLEAN UTILITY
330-1
1-EC-3W:2
1-EC-3W:2
1-3W:4
1-3W:4
1-3W:2
1-3W:4
1-EC-3W:2
1-EC-3W:4
1-3W:6
1-3W:6
1-EC-3W:4
1-3W:6
1-EC-3W:4
1-3W:6
1-EC-3W:4
1-EC-3W:6
1-3W:6
1-3W:6
1-EC-3W:6
1-3W:6
1-EC-3W:6
1-EC-3W:6
1-3W:6
L2 L1
L3
ELECT.
328-1
U2
U1
U1
U1
L4
L4
L4
U1
U1
U2
L4
L4
U2
U1 L4
L4 b
U2
U1
U2
U2
L4
L4
L4
SV
U1
U2
U1U2
H4
H4 H4 b b
U2
U1 L4
L2
L1
L3
U1
U2
U2
U1U2
L1
L2
L3
U1 U2
L4
L4
L4
L4
L4
U2 U1
L4
U1 U2
U1
U2
L4
L4 U1
U2
L4
U2
L1
L3
L2
L1
L2L3
L1
L3
L2
L3
L2
L1
L1
L2 L3
HA
a
L1
L3 L2
THIRD FLOOR KEY PLAN
PHASE 1
N
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF
FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF
ONE HOUR.
4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH
ARCHITECT PRIOR TO ROUGH-IN.
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
EL103
ELECTRICAL LIGHTING PLAN - THIRD
FLOOR
Wichita, Kansas
SMS JLW04-27-2018
1/4" = 1'-0" A
ELECTRICAL LIGHTING PLAN - THIRD FLOOR 2' 4' 8'0'
1/4" = 1'-0"
N
KEYED NOTES:
L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH
FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF
FIXTURE ‘SB’.
L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE
LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE
CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM
PILLOW SPEAKER.
L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN
MANUFACTURED HEADWALL UNIT.
L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE
CIRCUIT BELOW.
No. Description Date
D
D
D
D
D
D
D
D
D
M
M
D
D
D
D D
M
D D
M
M
D
D
D
D
D
D
D
D
D D
D
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF
FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF
ONE HOUR.
4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH
ARCHITECT PRIOR TO ROUGH-IN. THIRD FLOOR KEY PLAN
PHASE 1
N
PATIENT RM
316-1
TOILET
317-1
SOILED UTILITY
319-1
STORAGE
320-1
TOILET
321-1
PATIENT RM
322-1
BARIATRIC PATIENT ROOM
302-1
PATIENT RM
304-1
TOILET
305-1
HSKPG
324-1
TOILET
335-1
PATIENT ROOM
334-1
PATIENT ROOM
336-1
TOILET
337-1
EQUIP. STOR.
338-1
EQUIP. ALCOVE
300-1
NURSE STATION
325-1
HALL
307-1
HALL
301-1
HALL
326-1
HALL
339-1
HALL
312-1
CHARTING
306-1
STAFF TOILET
323-1
TOILET
313-1
ANTE RM
318-1
KAKA
KAKAKA
a a NL a NL
K4
K4
HS
HA
HA
SB
HA HA
ST SV
ST
HL
HL
HA
HA
HA
HA
SHADED AREA NOT IN
SCOPE OF WORK
X1
KA
X1
CLOSET
307A-1 a b c ca a e e f,g f,g e a a b h d d j j h h a b a
1-EL-2W:4
CLEAN UTILITY
330-1
CLEAN UTILITY
330-1
CLEAN UTILITY
330-1
1-EC-3W:2
1-EC-3W:2
1-3W:4
1-3W:2
1-3W:4
1-EC-3W:2
1-EC-3W:4
1-3W:6
1-3W:6
1-EC-3W:4
1-EC-3W:6
1-3W:6
1-3W:6
1-EC-3W:6
1-3W:6
1-EC-3W:6
1-EC-3W:6
1-3W:6
ELECT.
328-1
L4
L4
L4
U1L4
L4
SB
HLHL
HAHAHA
HA
HA HA
ST
ST
HA
HS SV
U1
KA
KA
KA
SV
ST
HA HS
ST
HAHAHAHA
HA
SB
KA KAKA
KA
KA
SV
ST
HA
HS
ST
HAHA
HAHA
SB
HL HL
HA
U1
U1
KA
KA
X1
KAKA
KA
H4
H4
H4 H4
H4
H4
H4
H4
H4
N4
H4 KA
KA
K4
X1
K4
K4
K4
K4
K4
U2
KAKA
KA
X2
KA
K2
HA
SV
HS
HA
ST
ST
HA
HA
HA
HL
HA
HAHA
HL
SB
N4
X2
HL HL
e e f,g f,g ee b a c a a d a hj h b a
NL
a c a a a b h b h j d h j a b c ef,g f,g e a b h j d c a
NL
a b b b b b bb b b b a
NL
NL a a NL b a c a a f,g e e a a b h h j h j d d c
3a b c cc c b h h j j h b b a aa add f,g c e e e f,g c a
NL
U2
KA
KA
SV
HS
HA
ST
STHA
HA
HA
SB
HL HL
K2F K2
K2
HS
HA
SV
ST
ST
HA
HA HAHAHA
SB
HL HL
h h j j h b b a c c b a a f,g e e e f,g j h h b h j b aac d a f,g ee a c b a d ef,g
SHADED AREA NOT IN
SCOPE OF WORK
L4
L4
L4
U2
U1
U2
U2
U1U2
U2
U2 U1
U1 U2
U1
U2 U1
U2
U1 U2
U2 U1
L4
L4
L4
L4
L4
L4
U2
U1
U2
L4
L4 3a
1-3W:4
NL
L1 L2
L3
L1
L3 L2
L2
L1
L3
L2L1
L3
L2
L1 L3 f,g e
L1
L2
L3
L1
L2
L3
1-3W 1-EC-3W1-EM-3W
Drawing Title Project Title
Date
Location
Checked
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
589A7-17-203
Robert J. Dole VA Medical Center
RENOVATE WARDS FOR PATIENT
PRIVACY PHASE 1, B1
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA
142 N. MOSELY ST
WICHITA, KANSAS
EL103.3
ELECTRICAL LIGHTING PLAN - THIRD
FLOOR - BID ITEM 3
Wichita, Kansas
Checker Author04-27-2018
2' 4' 8'0'
1/4" = 1'-0"
N
1/4" = 1'-0" A
ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 3
# KEYED NOTES:
L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH
FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF
FIXTURE ‘SB’.
L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE
LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE
CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM
PILLOW SPEAKER.
L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN
MANUFACTURED HEADWALL UNIT.
L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE
CIRCUIT BELOW.
No. Description Date
D
D
PATIENT ROOM
336-1
TOILET
337-1
EQUIP. STOR.
338-1
EQUIP. ALCOVE
300-1
HALL
339-1
KAKA
KAKAKA
NL
NL
K4
K4
HS
HA
HA
SB
HA HA
ST SV
ST
HL
HL
HA
HA
HA
HA
SHADED AREA NOT IN
SCOPE OF WORK
X1
KA
X1 a b c ca a e e f,g f,g e a a b h d d j j h h a b
U1L4
SHADED AREA NOT IN
SCOPE OF WORK
1-3W-EM
1-3W L4
U2 U1
L3
L1
L2
L8
L7
L6
L5
THIRD FLOOR KEY PLAN
PHASE 1
N
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE…