N1. THE CONTRACTOR SHALL PROVIDE OUTLET BOXES AND

1"C. TO ABOVE NEAREST ACCESSIBLE CEILING FOR ALL

NURSE CALL DEVICE LOCATIONS. ALL NURSE CALL

DEVICE LOCATIONS SHALL BE COORDINATED WITH THE

FINAL DRAWINGS FROM THE NURSE CALL SYSTEM

SUPPLIER. COORDINATE ALL REQUIREMENTS WITH THE

NURSE CALL SYSTEM SUPPLIER. MOUNTING HEIGHT FOR

EMERGENCY BATH STATIONS SHALL BE PER AIA

GUIDELINES.

NURSE CALL

H1. DO NOT ROUTE BRANCH CIRCUITS OR FEEDERS

ABOVE OR BELOW IMAGING ROOMS BECAUSE OF

POSSIBLE ELECTROMAGNETIC INTERFERENCE.

H2. BOND PANELBOARDS SERVING THE SAME PATIENT

CARE VICINITY WITH #6 AWG MINIMUM COPPER

CONDUCTOR PER NEC ARTICLE 517. THIS INCLUDES

NORMAL AND ESSENTIAL PANELBOARDS AND

ESSENTIAL PANELBOARDS FED FROM DIFFERENT

TRANSFER SWITCHES.

H3. THE GROUNDING SYSTEM IN PATIENT CARE AREAS

SHALL BE TESTED BY VOLTAGE AND IMPEDANCE

MEASUREMENTS PER NFPA 99 REQUIREMENTS.

H4. MEDICAL GAS ALARM CABLING SHALL BE PROVIDED

AND INSTALLED BY THE ELECTRICAL CONTRACTOR.

VERIFY ALL REQUIREMENTS WITH THE MEDICAL GAS

SUPPLIER. ALL MEDICAL GAS CABLING SHALL BE IN

CONDUIT.

H5. COORDINATE ALL BOX ROUGH-IN AND PATHWAY

REQUIREMENTS FOR SOUND SYSTEMS IN OPERATING

ROOMS WITH THE EQUIPMENT SUPPLIER

H6. REFER TO THE SPECIFICATIONS FOR REQUIREMENTS

ON COLOR CODING BOXES AND/OR CONDUIT

ACCORDING TO THE SPECIFIC BRANCH OF THE

ESSENTIAL ELECTRICAL SYSTEM.

H7. REFER TO THE SPECIFICATIONS FOR REQUIREMENTS

ON COLOR CODING OF NAMEPLATES ACCORDING TO

THE SPECIFIC BRANCH OF THE ESSENTIAL ELECTRICAL

SYSTEM.

H8. THIS IS A LIFE SAFETY BUILDING WHICH MEANS IT

SHALL REMAIN REASONABLY OPERATIONAL IN THE

CASE OF A SEISMIC EVENT. REFER TO THE

SPECIFICATIONS FOR SPECIFIC REQUIREMENTS ON

EQUIPMENT BRACING.

H9.

H10.

H11. REFER TO MANUFACTURER DRAWINGS FOR ALL

IMAGING EQUIPMENT REQUIREMENTS, INCLUDING

BUT NOT NOT LIMITED TO CIRCUIT BREAKER SIZE,

CABLE TRAY, DUCTS, CONDUITS, CABLES,

CONDUCTORS, EPO SWITCHES, AND ALL DEVICES

REQUIRED FOR A COMPLETE INSTALLATION.

H12.

H13. DIGITAL CLOCK WITH INTEGRAL TIMER SHALL BE

SIMPLEX #6303-9103 CLOCK WITH #6303-9202 CONTROL

STATION OR APPROVED EQUAL. PROVIDE 120V.

POWER TO CLOCK AND CONTROL WIRING FROM

CLOCK TO CONTROL STATION AS REQUIRED.

H14.

FOR ISOLATION PANEL CIRCUITS, USE 1" MINIMUM EMT

CONDUIT ROUTED AS DIRECT AS POSSIBLE. MAXIMUM

OF 2 CIRCUITS PER CONDUIT. REFERENCE

SPECIFICATION SECTION 260527 FOR ADDITIONAL

REQUIREMENTS.

ALL PATIENT CARE AREAS (PATIENT ROOMS AND

SUPPORT SPACES) SHALL HAVE TWO GROUND

PATHS PER N.E.C. ARTICLE 517.

THE LIFE SAFETY BRANCH AND THE CRITICAL BRANCH

OF THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE KEPT

ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND

EQUIPMENT AND SHALL NOT ENTER THE SAME

RACEWAY, BOXES, OR CABINETS WITH EACH OTHER OR

OTHER WIRING PER N.E.C. ARTICLE 517.

DIGITAL CLOCK SHALL BE SIMPLEX #6334-9125 WITH #

6334-9802 MOUNTING BRACKET AND #6334-9803

HARNESS ASSEMBLY OR APPROVED EQUAL. CLOCK

SHALL BE 120V. WITH 2-1/2" LED (4) DIGIT DISPLAY.

HEALTHCARE

H15. ALL RECEPTACLES SHALL BE HOSPITAL GRADE.

T1. EACH DATA, TELEPHONE, VIDEO, OR OTHER SYSTEMS

OUTLET REQUIRES 1"C. WITH PULL ROPE STUBBED 6"

ABOVE NEAREST ACCESSIBLE CEILING UNLESS

OTHERWISE NOTED ON PLANS. CONDUITS STUBBED

UP ABOVE CEILINGS SHALL BE TURNED OUT 90

DEGREES. PROVIDE INSULATED BUSHINGS ON ALL

CONDUITS. LABEL CONDUIT TO IDENTIFY ITS

INTENDED USE (I.E. TELEPHONE, DATA, ETC.).

COMMUNICATION / DATA

T2. RUN CABLES CONTINUOUS FROM JACK TO

ASSOCIATRD SYSTEM PATCH PANEL IN CONDUIT,

CABLE TRAY, OR J-HOOKS PER THE PLANS AND

SPECIFICATIONS. NUMBER BESIDE CABLE

SYMBOL INDICATES QUANTITY OF CABLES

REQUIRED PER HOME RUN.

T3. PROVIDE QUANTITY AND TYPE OF JACKS PER THE

DRAWINGS, SPECIFICATIONS AND DETAILS. PROVIDE

JACK AND CABLE LABELING PER THE SPECIFICATIONS.

F1. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED

PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION.

DEVICES SHOWN INDICATE DESIGN INTENT AND SHALL

BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER SHALL

PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR

DEVICES REQUIRED BY THE AUTHORITY HAVING

JURISDICTION.

F2. FIELD VERIFY LOCATIONS OF AREA SMOKE DETECTORS

AND HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF

A HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT

AIR FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN

36" OF THE TIP OF A CEILING FAN BLADE. SMOKE

DETECTORS FOR DOOR RELEASE SHALL BE LOCATED

ON THE CENTER LINE OF THE DOOR AND A MAXIMUM OF

5 FEET FROM THE DOOR. THE MINIMUM DISTANCE FROM

THE DOOR IS THE DEPTH OF THE WALL SECTION ABOVE

THE DOOR, BUT NOT LESS THAN 12".

F4. LABEL REMOTE ALARM INDICATOR FOR DUCT

MOUNTED SMOKE DETECTORS (I.E. RTU-=1 SUPPLY,

RTU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT

DETECTORS SHOULD BE LOCATED IN THE AREA

BETWEEN 6 AND 10 DUCT EQUIVALENT DIAMETERS

OF STRAIGHT, UNITERRUPTED DUCTWORK. DUCT

DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD

BE LOCATED BETWEEN THE LAST INLET OR OUTLET

UPSTREAM OF THE DAMPER AND THE FIRST INLET

OR OUTLET DOWNSTREAM OF THE DAMPER.

F3. FAN SHUTDOWN RELAY WIRING SHALL BE LOCATED

WITHIN 3 FEET OF THE FAN CONTROLS AND THE WIRING

TO THE RELAY SHALL BE MONITORED.

F5. PROVIDE 120V POWER AND FUSTAT FOR EACH

FIRE/SMOKE DAMPER. INTERLOCK WITH FIRE ALARM

CONTROL PANEL TO CLOSE THE FIRE/SMOKE DAMPER

UPON ANY ALARM AT THE FIRE ALARM CONTROL PANEL

AND TO SHUTDOWN THE ASSOCIATED MECHANICAL UNIT.

FIRE ALARM

1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE

LATEST EDITION OF THE NATIONAL ELECTRICAL CODE

(NEC) & THE AMERICANS WITH DISABILITIES ACT (ADA).

2. REFER TO RELATED ARCHITECTURAL, MECHANICAL,

STRUCTURAL, AND CIVIL DRAWINGS FOR RELATED

INFORMATION.

3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE

DRAWINGS.

4. E.C. SHALL REFER TO MECHANICAL DRAWINGS AND

SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED

WITH WIRING AND CONNECTION OF INTERLOCKING AND

CONTROLS OF MECHANICAL UNITS AND THERMOSTAT

LOCATIONS.

5. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO

MINIMIZE CUTTING OF BRICK OR BLOCK.

6. ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS

OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON

THE JOB PRIOR TO ROUGH-IN.

7. CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND

WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS

REQUIRED.

8. WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON

THE PLANS, THE LARGER CONDUCTOR SIZE SHALL BE

USED THROUGHOUT THE LENGTH OF THE CIRCUIT,

INCLUDING NEUTRAL AND GROUND.

9. "CT" INDICATED ADJACENT TO DEVICE INDICATES DEVICE

MOUNTED ABOVE BACKSPLASH OF COUNTER TOP.

VERIFY EXACT HEIGHT WITH ARCHITECTURAL PLANS AND

ELEVATIONS.

10. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME

RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE

CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY

BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE

CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE

MARKED OR LABELED TO INDICATE WHICH CIRCUIT THEY

ARE ASSOCIATED WITH. SEE SPECIFICATION SECTION

"LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND

CABLES" FOR ADDITIONAL INFORMATION.

12. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE

WITH PANEL DESIGNATION AND CIRCUIT NUMBER

USING CLEAR THERMAL TRANSFER (ELECTRONIC

DYMO) LABELS WITH 1/8" HIGH BLACK LETTERS (OR

CONTRASTING COLOR IF COVERPLATES ARE BLACK OR

BROWN). LABELS SHALL BE SUITABLE FOR

INDOOR/OUTDOOR USE. LABEL THE BACK OF EACH

LIGHT SWITCH COVERPLATE WITH PANEL DESIGNATION

AND CIRCUIT NUMBER USING A FINE BLACK

PERMANENT MARKER.

11. JUNCTION BOX OR RECEPTACLE FOR DRINKING FOUNTAINS

SHALL BE LOCATED BEHIND THE EQUIPMENT SKIRT UNLESS

OTHERWISE NOTED. COORDINATE CONNECTION TYPE AND

LOCATION WITH EQUIPMENT PROVIDED.

13. PROVIDE 18" LONG (MIN.) CONDUIT SLEEVES THRU ALL

WALLS WHERE CABLES ARE INDICATED OR REQUIRED TO

PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS.

SIZE CONDUIT FOR CABLES INSTALLED. AT CABLE TRAYS,

PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH OF

CABLE TRAY. MAXIMUMS SHALL BE:

1"C. = 10 CABLES

2 1/2"C. = 20 CABLES

3"C. = 30 CABLES

4"C. = 50 CABLES

14. LOCATE CABLE TRAYS 6" ABOVE CEILING. OFFSET TRAY

UP AND OVER LIGHT FIXTURES AND DUCTWORK (FIELD

VERIFY AND PROVIDE AS REQUIRED). IF PHYSICALLY

IMPOSSIBLE TO RUN CABLE TRAY UP AND OVER, THEN

PROVIDE CABLE SUPPORT HOOKS FROM STRUCTURE

ABOVE, SIZED AND RATED FOR INSTALLED CABLES PLUS

25% SPARE.

15. PROVIDE DIMMER PER THE SPECIFICATIONS.

COORDINATE DIMMER TYPE AND WIRING WITH

ASSOCIATED LIGHT FIXTURE DIMMING REQUIREMENTS (I.E.

3-WIRE, O-10V, ELECTRONIC OR MAGNETIC LOW VOLTAGE,

ETC.) OR WITH LIGHTING CONTROL SYSTEM PROPRIETARY

REQUIREMENTS (I.E. LUTRON, nLIGHT, DALI, ETC.) AS

NECESSARY. 3-WIRE DIMMERS SHALL BE PROVIDED WITH

A DEDICATED NEUTRAL FOR EACH CONTROL ZONE. 0-10V

DIMMERS SHALL BE PROVIDED WITH DIM/ON/OFF

CONTROL. COORDINATE PHASE CONTROL OF LED

DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.)

WITH LIGHT FIXTURE MANUFACTURER'S

RECOMMENDATIONS. LOW VOLTAGE CONTROL WIRING IS

NOT SHOWN ON PLANS FOR CLARITY, BUT SHALL BE

PROVIDED AS REQUIRED.

- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -

- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -

GENERAL NOTES

PEN WEIGHT LEGEND

LIGHT FIXTURE TO BE REMOVED

EXISTING LIGHT FIXTURE TO REMAIN

NEW LIGHT FIXTURE

DUPLEX GROUNDED REC TO BE REMOVED

EXISTING DUPLEX GROUNDED REC TO REMAIN

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK

SOLID LINES ARE NEW TO BE INSTALLED

NEW DUPLEX GROUNDED RECEPTACLE

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT

SOLID LINES ARE EXISTING TO REMAIN

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK

DASHED LINES ARE EXISTING TO BE REMOVED

LIGHT FIXTURE TO BE RELOCATED

DUPLEX GROUNDED REC TO BE RELOCATED

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT

DASHED LINES ARE EXISTING TO BE RELOCATED

SECURITY

WALL M

E

W

W

B

K KEY PAD

SECURITY BEAM DETECTOR

GLASS BREAK SENSOR

CARD READER

MAGNETIC LOCK

ELECTRIC DOOR STRIKE

DOOR POSITION SWITCH

DOOR LOCK & POSITION SWITCHDOOR RELEASE BUTTON

CCTV CAMERA - FIXED

CCTV CAMERA - FIXED

CCTV CAMERA - PAN/TILT/ZOOM

DURESS

CCTV CAMERA - PAN/TILT/ZOOM

SEC ROOM MOTION DETECTOR

SEC ROOM MOTION DETECTOR

CR

WALL

CEILING

CEILING

REQUEST TO EXIT DEVICEED

WALL/CLG

SEC CORRIDOR MOTION DETECTOR

CEILING

CONDUIT AND WIRING

PHASE CONDUCTORS/

NEUTRAL CONDUCTOR (#12 UON)

EMERGENCY CIRCUIT

CONDUIT RUN PARTIAL CIRCUIT.

2#12 & 1#12 GRD. - 1/2"C.

CDT RUN 2#12 & 1#12 GRD.- 1/2"C.

OR CDT RUN AS NOTED ON PLAN

CDT RUN 2#12 & 1#12 GRD.- 3/4"C.

OR CDT RUN AS NOTED ON PLAN

CLG/WALL

MASTER/SLAVE FIXTURE WHIP

CONDUIT HOME RUN, 2 CIRCUITS.

4#12 & 1#12 GRD. - 1/2"C.

CONDUIT HOME RUN, 1 CIRCUIT.

2#12 & 1#12 GRD. - 1/2"C.

CONDUIT HOME RUN, 3 CIRCUITS.

6#12 & 1#12 GRD. - 1/2"C.

CONDUIT HOME RUN, 1 CIRCUIT.

2#10 & 1#10 GRD.

#10

GROUND CONDUCTOR (#12 UON)

CONDUIT HOME RUN, 2 CIRCUITS

SWITCH LEGS (#12 UON)

CEILING

CLG/WALL

CLG/WALL

EARTH/

FLOOR

CLG/WALL

CLG/WALL

CLG/WALL

CLG/WALL

CLG/WALL

LOW VOLTAGE WIRING CLG/WALL

MISC. EQUIPMENT CONNECTION

CONDUIT SEAL OFF

AUDIO-VISUAL

CEILINGCEILING MOUNTED SPEAKER

CLOCK/SPEAKER (SYSTEM CLOCK)

WALL MOUNTED SPEAKER

DIGITAL CLOCK WITH TIMER

(GEN NOTE H14)

WALL

PA/SOUND SYSTEM W/RACK/SHELF'PACP' FLOOR/WALL

WALL

SYSTEM CLOCK

(A=ANALOG, D=DIGITAL)

WALL

WALL

VOLUME CONTROL

BELL

CALL SWITCH 46"AFF

MICROPHONE OUTLET

WALL

46"AFF

BOTTOM 80"

V

FIRE ALARM

46"AFFFIRE ALARM MANUAL STATION

DUCT SMOKE DETECTOR &

FIRE/ SMOKE DAMPER (GEN

NOTES F4 & F5)

FIRE ALARM VISUAL SIGNAL

FIRE ALARM HORN

DUCT SMOKE DETECTOR

(GEN NOTE F4)

IONIZATION AREA SMOKE

DETECTOR (GEN NOTE F2)

PHOTO ELECTRIC AREA SMOKE

DETECTOR (GEN NOTE F2)

F.A. RELAY (GEN NOTE F3)R

CH CHIME

DUCTWORK

CEILING

FIRE ALARM CONTROL PANEL'FACP'

FIRE SPRINKLER ALARM BELL

WALL

BOTTOM 80"

COMB. F.A. HORN & VISUAL SIGNAL

BOTTOM 80"

BOTTOM 80"

FIRE ALARM SPEAKER

COMB FA SPEAKER & VISUAL SIGNAL

FIRE ALARM REMOTE ANNUNCIATOR'FAAP' WALL

COMB FA HORN & VISUAL SIGNAL

FSD DUCTWORK

WALL

WALL

WALL

BOTTOM 80"

FIRE SPRINKLER TAMPER SWITCHT

ELECTROMAGNETIC DOOR HOLDER

FIRE SPRINKLER WATER FLOW SWW

HEAT DETECTOR (GEN NOTE F2)H

SPRKLR RSR

M

C FIRE ALARM CONTROL MODULE

FIRE ALARM MONITOR MODULE

FIRE ALARM SPEAKER

FIRE SPRINKLER PRESSURE SWITCHP

FIRE ALARM SPEAKER

CEILING

WALL

WALL

SPRKLR RSR

SA

NC PATIENT STATION (GEN NOTE N3)

WALL'NCCP' NC CONTROL PANEL

NC PRESENCE STATION

NC STAFF ASSIST STATION

WITHOUT AUDIO

NC DUTY STATION

CEILINGNC ZONE LIGHT

E

X

S

N

46" AFF

NC STAFF STATION W/ AUDIO

P

NC AUXILIARY JACKA

NC BED INTERFACE UNIT 46" AFF

NC MASTER STATION

BI

DESKTOPNC

CLG/WALLNC VISUAL SIGNAL

NC CODE BLUE STATION 46" AFFB

NC EMERGENCY BATH STATION

46" AFF

46" AFF

46" AFF

46" AFF

46" AFF

NURSE CALL

1-VOICE OUTLET & JACK (GEN

NOTES T1 & T3)

1-VOICE/1-DATA OUTLET &

JACKS (GEN NOTES T1 & T3)

1-DATA OUTLET & JACK (GEN

NOTES T1 & T3)

18"AFF

CABLE TV OR VIDEO OUTLET &

CONNECTOR (GEN NOTES T1 & T3)

1-VOICE/2-DATA OUTLETS &

JACKS (GEN NOTES T1 & T3)

2-VOICE/2-DATA OUTLETS & JACKS

(GEN NOTES T1 & T3)

1-VOICE/3-DATA OUTLETS &

JACKS (GEN NOTES T1 & T3)

4-DATA OUTLETS & JACKS (GEN

NOTES T1 & T3)

2-DATA OUTLETS & JACKS (GEN

NOTES T1 & T3)

3-DATA OUTLETS & JACKS (GEN

NOTES T1 & T3)

18"AFF

18"AFF

18"AFF

18"AFF

18"AFF

18"AFF 18"AFF

18"AFF

18"AFF

COMMUNICATION / DATA

VIDEO COAX CABLE HOME RUN

FIBER OPTIC CABLE HOME RUN

(MULTI MODE)

FIBER OPTIC CABLE HOME RUN

(SINGLE MODE)

DATA UTP CABLE HOME RUN

VOICE UTP CABLE HOME RUN GEN NOTE T2

GEN NOTE T2

GEN NOTE T2

GEN NOTE T2

GEN NOTE T22

POWER

DUPLEX GROUNDED RECEPTACLE

FUSTAT BUSS #SSY

SPECIAL DEVICE (AS NOTED)

JUNCTION BOX - 1-GANG

DOUBLE DUPLEX GROUNDED REC

GROUND FAULT DUPLEX REC

DUPLEX GROUNDED RECEPTACLE

SINGLE GROUNDED RECEPTACLE

DUPLEX GRD REC BOTTOM SWITCHD

GRD FAULT DOUBLE DUPLEX REC

18" AFF

A

ELECTRICAL DISTRIBUTION EQUIP

EQUIPMENT - SEE EQUIPMENT

CONNECTION SCHEDULE

x-x x-x

CONDUIT SLEEVE (GEN NOTE 13)

CABLE TRAY (GEN NOTE 14)

FEEDER DESIGNATION

M MANUAL STARTER

CIRCUIT BREAKER

DISCONNECT SWITCH

M MOTOR

PLUGMOLD SURFACE RACEWAY

S

18" AFF

18" AFF

CEILING

18" AFF

18" AFF

18" AFF

FLOOR/WALL

72" TO TOP

WALL

JUNCTION BOX - 2-GANG

PLUG LOAD SENSOR CEILING

HANDICAP DOOR PUSHBUTTON 36" AFF

RELAY

PUSHBUTTON (1-BUTTON, 2-BUTTON)

BOX MOUNTED TRANSFORMER

46" AFF

CONTACTOR

METER

STARTER OR ATS (AS NOTED)

COMBINATION STARTER/DISC

BUSDUCT PLUG

THERMOSTAT/TEMP SENSOR 46" AFF

SPECIAL OUTLET (SEE

SCHEDULE OR AS NOTED)

BRANCH CIRCUIT PANEL AND

PANEL DESIGNATION

J

A

F

A

TS

H

P

1J

C

T

R

2D

1D

2M

SWITCHES (KEYED, PILOT, TIMER)

INDICATES SWITCHING SCHEME

EMERGENCY BATTERY LIGHT FIXT

LIGHT FIXTURE & FIXTURE LETTER

46" AFF

A

A

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

STRIP LIGHT FIXTURE & FIXT LETTERA

A

A

A

1 RELAY PIR SENSOR

PIR SENSOR

2 RELAY PIR SENSOR

DUAL TECHNOLOGY SENSOR

1 RELAY DUAL TECH SENSOR

2 RELAY DUAL TECH SENSOR

M

D DIMMER (SEE GENERAL NOTE 15)

ON/OFF SWITCH

S

PC PHOTOCELL

CLG/WALL

CLG/WALL

46" AFF

46" AFFSSS

SSS

S a, b, c

CEILING

CEILING

CEILING

WALL

CEIL/WALL

WALL

CEILING

CEIL/WALL

46" AFF

46" AFF

46" AFF

46" AFF

46" AFF

2 3 4

K P T

LIGHTING, SWITCHES AND SENSORS

SWITCHES (1-POLE, 2-POLE,

3-WAY, 4-WAY)

EXIT SIGN (SHADING DENOTES

EXIT FACE SIDE)

FIXTURE WITH SHADED LAMP(S)

ON EMERGENCY POWER

WALLCOMB EXIT SIGN/EM BATTERY LIGHT

SP SWITCHING POWER PACK

SE UL924 SWITCHING POWER PACK

DP DIMMING POWER PACK

DE UL924 DIMMING POWER PACK

46" AFF

ON/OFF/0-10V DIMMING SWITCH

S

46" AFF

DUAL TECH ON/OFF SENSOR

S

46" AFF

16-SCENE WALL CONTROLLER

S

46" AFF

DUAL TECH ON/OFF/0-10V DIM SW

S

46" AFF

LOW VOLTAGE SWITCH

S

A

A

A

A A

LIGHT FIXTURE & FIXTURE LETTERA POLEA

AV AV SYSTEM/LIGHTING INTERFACE

NIGHT LIGHT - WIRE AHEAD OF

ABBREVIATIONS

NL

EM

WP

CT

UON

ON EMERGENCY POWER

WEATHERPROOF

COUNTERTOP (SEE GEN. NOTE 9)

UNLESS OTHERWISE NOTED

ABOVE FINISHED FLOORAFF

AFG ABOVE FINISHED GRADE

WALLW

CONTROLS

DRINKING FOUNTAIN -

SEE GENERAL NOTE 11

DF

GENERAL NOTES

SYMBOL

SYMBOL LIST

DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING SYMBOL

SYMBOL LIST

DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

E-001

ELECTRICAL LEAD SHEET

Wichita, Kansas

SMS JLW04-27-2018

SHEET INDEX

NUMBER SHEET TITLE

E-001 ELECTRICAL LEAD SHEET

ED100 ELECTRICAL DEMOLITION PLAN - LOWER LEVEL

ED102 ELECTRICAL DEMOLITION PLAN - SECOND FLOOR

ED103 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR

ED103.3 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 3

ED103.4 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 4

EL102 ELECTRICAL LIGHTING PLAN - SECOND FLOOR

EL103 ELECTRICAL LIGHTING PLAN - THIRD FLOOR

EL103.3 ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 3

EL103.4 ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 4

EL501 ELECTRICAL LIGHTING DETAILS

EL601 ELECTRICAL LIGHTING SCHEDULE

EP100 ELECTRICAL POWER PLAN - LOWER LEVEL

EP102 ELECTRICAL POWER PLAN - SECOND FLOOR

EP103 ELECTRICAL POWER PLAN - THIRD FLOOR

EP103.3 ELECTRICAL POWER PLAN - THIRD FLOOR - BID ITEM 3

EP103.4 ELECTRICAL POWER PLAN - THIRD FLOOR - BID ITEM 4

EP501 ELECTRICAL POWER DETAILS

EP601 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION

EP602 ELECTRICAL ONE-LINE DIAGRAM - NEW CONSTRUCTION

EP603 ELECTRICAL POWER SCHEDULES

EY102 ELECTRICAL SYSTEMS PLAN - SECOND FLOOR

EY103 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR

EY103.3 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR - BID ITEM 3

EY103.4 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR - BID ITEM 4

EY501 ELECTRICAL SYSTEMS DETAILS

SPECIAL OUTLETS

MARK DESCRIPTION

OM OMNICELL/PYXIS LOCATION. PROVIDE FSR #PWB-200 RECESSED WALL

BOX. PROVIDE (1) 20A. 120V. DUPLEX GROUNDED RECEPTACLE AND

(2) DATA OUTLETS. PROVIDE MATCHING COVERPLATE AND ALL

ASSOCIATED MOUNTING HARDWARE. MOUNT AT 42" AFF.

PD POWERED DOOR OPERATOR.

PL PATIENT LIFT CONNECTION. PROVIDE DUPLEX RECEPTACLE IN

LOCKABLE ENCLOSURE ABOVE CEILING. SIZE LOCKABLE ENCLOSURE

AS REQUIRED BY PATIENT LIFT EQUIPMENT. VERIFY EXACT LOCATION

OF LIFT MOTOR WITH SUPPLIER PRIOR TO INSTALLATION.

PTV PATIENT TV LOCATION. PROVIDE DUPLEX RECEPTACLE, COAX DROP,

DATA DROP, AND NURSE CALL CONTROL INTERFACE IN RECESSED

ENCLOSURE. PROVIDE FSR #PWB-250 RECESSED WALL BOX. ROUTE

1-1/4" CONDUIT TO ABOVE ACCESSIBLE CEILING FOR ROUTING OF

LOW VOLTAGE CABLING. PROVIDE (1) 120V 20A DUPLEX RECEPTACLE,

(1) CAT-6 DATA RECEPTACLE, (1) CATV F-TYPE CONNECTOR, AND

NURSE CALL INTERFACE. PROVIDE COVERPLATE AND ALL

ASSOCIATED MOUNTING HARDWARE. MOUNT AT 68" A.F.F.

COORDINATE MOUNTING HEIGHT AND LOCATIONWITH PATIENT TV

MOUNT SO THAT RECESSED WALL BOX IS COMPLETELY HIDDEN

BEHIND TV.

U COMBINATION DUPLEX RECEPTACLE AND USB CHARGING

RECEPTACLE WITH 5A, 5V OUTPUT. PROVIDE HUBBEL #USB20AC OR

APPROVED EQUAL WITH 120V, 20A DUPLEX RECEPTACLES, (1) USB

TYPE-A RECEPTACLE, (1) USB TYPE-C RECEPTACLE.

No. Description Date

23475234752347523475 04/26/2018

1-1 1-2 1-3

1-4

1-6

1-7

1-9

1-10 1-11 1-12

1-13

1-151-16

1-18

1-20 1-21 1-25

1-27

1-28 1-29 1-30

1-31

1-A

1-B

1-C

1-D

1-E

1-F

1-G 1-H

1-I

1-J

1-M

1-N

1-Q

1-T

1-U

1-V

1-W

1-X

1-R

1-23

1-5

1-3A

1-3B

1-26

1A-1 1A-2 1A-3

1A-A

1A-B

1A-C

1A-D

1-AHU-1

(E) 1-RF1

ED100

B

(E) 1-SA1

(E) 1-AFM1

(E) 1-SH1

(E) 1-AFM2

EXISTING PANEL '1-B-EM' TO REMAIN.

PANEL SERVES AIR HANDLING UNIT

FANS AND PUMPS

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

EE7819

EE44491

EE7908A

EE8602

EMD-1A

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

ED100

ELECTRICAL DEMOLITION PLAN - LOWER

LEVEL

Wichita, Kansas

SMS JLW04-27-2018

1/8" = 1'-0" A

ELECTRICAL DEMOLITION PLAN - LOWER LEVEL

N 4' 8' 16'

1/8" = 1'-0"

0'

PLAN INCLUDED FOR REFERENCE. DEMOLITION OF

MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT,

CONDUCTORS, DISCONNECTING MEANS, ETC. IS THE

EXTENT OF DEMOLITION WORK.

1/4" = 1'-0" B

ENLARGED BASEMENT ENGINEERING ROOM 2' 4' 8'0'

1/4" = 1'-0"

N

No. Description Date

1-6

1-7

1-9

1-10 1-11 1-12

1-13

1-16

1-18

1-20 1-21 1-25

1-D

1-E

1-F

1-G

1-H

1-J

1-M

1-U

1-X

1-23

1-5

1-3A

1-3B

REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,

DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL

EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND

DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.

1-2W-EM

1-2W

SHADED AREA NOT IN

SCOPE OF WORK

EXISTING PANELBOARD TO BE REMOVED. ALL EXISITNG CONDUIT

AND CIRCUITING SHALL BE REMOVED. PANELBOARD INCOMING

FEEDER SERVES PANELBOARD ON LEVEL ABOVE. COORDINATE

REMOVAL OF PANELBOARD IN ORDER TO MAINTAIN POWER TO

PANEL ON LEVEL ABOVE AND MINIMIZE DOWNTIME (TYPICAL OF 2).

EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND

DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES

DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED

BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR

EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE

PROTECTED DURING DEMOLITION.

EXISTING TELECOM

CLOSET

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK. SECOND FLOOR KEY PLAN

N

PHASE 1 PROJECT

STORAGE

237-1

HSKPG

239-1

STOR

237A-1

RESPIRATORY THERAPY

OFFICE

243-1

245-1

STAIRS

2-STAIR-C

ELEV.

2-ELEV

HEMODIALYSIS EXAM

ROOM

200-1

ICU WAITING ROOM

286-1

SLEEP

286A-1

RR

285-1

STUDY ROOM

284-1

BREAK ROOM

250-1

CORRIDOR

2-CORR-1

GUEST ROOM

227-1

GUEST ROOM

226-1

TELEHEALTH

225-1

NURSE OFFICE

224-1

ASSOCIATE DIRECTOR ICU

222-1

RR

226A-1

HEMODIALYSIS STORAGE

201-1

SPEECH THERAPY OFFICE

202-1

OFFICE

203-1

BREAK AND LOCKER ROOM

204-1

OFFICE

205-1

RR

222A-1

RR

206-1

ELEC

207-1

EDUCATION STORAGE

208-1

OFFICE

209-1

EDUCATION OFFICE

210A-1

EDUCATION OFFICE

210-1

CHAPEL

211-1

TOILET

212-1

EUCHARISTIC CHAPEL

213-1

215A-1

STORE

214-1

CHAPLAIN OFFICE

215-1

CHAPLAIN PASTORAL CARE

OFFICE

216-1

CHAPLAIN OFFICE

216B-1

216A-1

SIMULATION LAB

217-1

STORE

218-1

VISUAL IMPAIRMENT

SERVICES

219-1

OFFICE

220-1

RR

220A-1

OFFICE

221-1

STAIRS

2-STAIR-W

TELECOM

223-1

CORRIDOR

2-CORR-W

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

ED102

ELECTRICAL DEMOLITION PLAN - SECOND

FLOOR

Wichita, Kansas

SMS JLW04-27-2018

1/4" = 1'-0" A

ELECTRICAL DEMOLITION PLAN - SECOND FLOOR

N

2' 4' 8'0'

1/4" = 1'-0"

No. Description Date

1-6

1-7

1-9

1-10 1-11 1-12

1-13 1-18

1-D

1-E

1-F

1-G

1-H

1-J

1-M

1-N

1-Q

1-T

1-U

1-V

1-X

1-23

1-5

1-3A

1-3B

REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,

DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL

EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND

DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.

1-3W

1-3W-EM

SHADED AREA NOT IN

SCOPE OF WORK

EXISTING PANELBOARD TO BE REMOVED. ALL EXISITNG CONDUIT

AND CIRCUITING SHALL BE REMOVED.

EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND

DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES

DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED

BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR

EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE

PROTECTED DURING DEMOLITION.

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK. THIRD FLOOR KEY PLAN

PHASE 1

N

NURSE STATION

313B-1

PATIENT ROOM

310-1

PATIENT ROOM

317-1

RR

319A-1

OBSERVATION

318-1

PATIENT ROOM

319-1

PATIENT ROOM

320-1

NURSE OFFICE

320A-1

HSKPG

316-1

CLEAN LINEN

315-1

MEDICAL ROOM 1

314B-1

STAIRS

3-STAIR-W

RESIDENTS OFFICE

314-1

PATIENT ROOM

313-1

TOILET

311A-1

TOILET

313A-1

RR

312-1

MEN'S

308-1

ELEC

307-1

STAFF RR

306-1

PATIENT ROOM

309-1

PATIENT ROOM

311-1

CLEAN SUPPLY

305-1

SPD STORAGE

304-1

PATIENT ROOM

303-1

PATIENT ROOM

302-1

NURSE OFFICE

301-1

EMPLOYEE LOUNGE

300-1

PATIENT ROOM

327-1

PATIENT ROOM

325-1

STORAGE

324-1PATIENT ROOM

323-1

PATIENT ROOM

321-1

TELECOM

322-1

RR

321A-1

RR

326-1

RR

325A-1

EQUIPMENT STORAGE

381-1

RECEPTION

380-1

VENDING

379-1

PATIENT ROOM

377-1

STAIRS

3-STAIR-C

IRM

345-1

RN OFFICE

343-1

HSKPG

339-1

TOILET

338-1

LOCKER ROOM

337-1

TELCOM

344-1

ELEV.

3-ELEV

CORRIDOR

3-CORR-W

CORRIDOR

3-CORR-C

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

ED103

ELECTRICAL DEMOLITION PLAN - THIRD

FLOOR

Wichita, Kansas

SMS JLW04-27-2018

1/4" = 1'-0" A

ELECTRICAL DEMOLITION PLAN - THIRD FLOOR 2' 4' 8'0'

1/4" = 1'-0"

N

No. Description Date

THIRD FLOOR KEY PLAN

PHASE 1

N

1-1 1-2 1-3

1-4

1-6

1-7

1-9

1-10 1-11 1-12

1-13 1-18

1-D

1-E

1-F

1-G

1-H

1-J

1-M

1-N

1-Q

1-T

1-U

1-V

1-X

1-23

1-5

1-3A

1-3B

REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,

DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL

EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND

DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.

SHADED AREA NOT IN

SCOPE OF WORK

1-3W-EM

1-3W

EXISTING PANELBOARD AND ALL CIRCUITS AND ASSOCIATED

CONDUITS FED FROM THIS PANEL TO BE REMOVED. CIRCUITS

ON THIS FLOOR THAT ARE TO REMAIN BY BID ITEM SHALL BE

FED FROM NEW PANELBOARD. SEE NEW CONSTRUCTION

FLOOR PLANS FOR ADDITIONAL INFORMATION.

SHADED AREA NOT IN

SCOPE OF WORK

EXISITNG TELECOM CLOSET TO REMAIN. ALL COMPONENTS, CABLING, AND

DEVICES WITHIN THIS CLOSET HALL REMAIN. ALL CABLING WHICH SERVES

DEVICES OR EQUIPMENT WITHIN THE DEMOLITION AREA SHALL BE REMOVED

BACK TO THE TELECOM CLOSET. ALL CABLING WHICH SERVES DEVICES OR

EQUIPMENT OUTSIDE OF THE AREA OF DEMOLITION SHALL REMAIN AND BE

PROTECTED DURING DEMOLITION.

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

NURSE STATION

313B-1

PATIENT ROOM

310-1

PATIENT ROOM

317-1

RR

319A-1

OBSERVATION

318-1

PATIENT ROOM

319-1

PATIENT ROOM

320-1

NURSE OFFICE

320A-1

HSKPG

316-1

CLEAN LINEN

315-1

MEDICAL ROOM 1

314B-1

STAIRS

3-STAIR-W

RESIDENTS OFFICE

314-1

PATIENT ROOM

313-1

TOILET

311A-1

TOILET

313A-1

RR

312-1

MEN'S

308-1

ELEC

307-1

STAFF RR

306-1

PATIENT ROOM

309-1

PATIENT ROOM

311-1

CLEAN SUPPLY

305-1

SPD STORAGE

304-1

PATIENT ROOM

303-1

PATIENT ROOM

302-1

NURSE OFFICE

301-1

EMPLOYEE LOUNGE

300-1

PATIENT ROOM

327-1

PATIENT ROOM

325-1

STORAGE

324-1PATIENT ROOM

323-1

PATIENT ROOM

321-1

TELECOM

322-1

RR

321A-1

RR

326-1

RR

325A-1

EQUIPMENT STORAGE

381-1

RECEPTION

380-1

VENDING

379-1

PATIENT ROOM

377-1

STAIRS

3-STAIR-C

IRM

345-1

RN OFFICE

343-1

HSKPG

339-1

TOILET

338-1

LOCKER ROOM

337-1

TELCOM

344-1

ELEV.

3-ELEV

CORRIDOR

3-CORR-W

CORRIDOR

3-CORR-C

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

ED103.3

ELECTRICAL DEMOLITION PLAN - THIRD

FLOOR - BID ITEM 3

Wichita, Kansas

Checker Author04-27-2018

2' 4' 8'0'

1/4" = 1'-0"

N

1/4" = 1'-0" A

ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 3

No. Description Date

THIRD FLOOR KEY PLAN

PHASE 1

N

1-1 1-2 1-3

1-4

1-6

1-7

1-9

1-10 1-11 1-12

1-13 1-18

1-D

1-E

1-F

1-G

1-H

1-J

1-M

1-N

1-Q

1-T

1-U

1-V

1-X

1-23

1-5

1-3A

1-3B

REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, FEEDERS,

DEVICES, CIRCUITING, CONDUIT, LIGHTING, MECHANICAL

EQUIPMENT CONNECTIONS, NURSE CALL, FIRE ALARM, PHONE AND

DATA, ETC. WITHIN HATCHED AREA UNLESS OTHERWISE NOTED.

SHADED AREA NOT IN

SCOPE OF WORK

SHADED AREA NOT IN

SCOPE OF WORK

1-3W

1-3W-EM

EXISTING PANEL TO

REMAIN (TYPICAL)

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

NURSE STATION

313B-1

PATIENT ROOM

310-1

PATIENT ROOM

317-1

RR

319A-1

OBSERVATION

318-1

PATIENT ROOM

319-1

PATIENT ROOM

320-1

NURSE OFFICE

320A-1

HSKPG

316-1

CLEAN LINEN

315-1

MEDICAL ROOM 1

314B-1

STAIRS

3-STAIR-W

RESIDENTS OFFICE

314-1

PATIENT ROOM

313-1

TOILET

311A-1

TOILET

313A-1

RR

312-1

MEN'S

308-1

ELEC

307-1

STAFF RR

306-1

PATIENT ROOM

309-1

PATIENT ROOM

311-1

CLEAN SUPPLY

305-1

SPD STORAGE

304-1

PATIENT ROOM

303-1

PATIENT ROOM

302-1

NURSE OFFICE

301-1

EMPLOYEE LOUNGE

300-1

PATIENT ROOM

327-1

PATIENT ROOM

325-1

STORAGE

324-1PATIENT ROOM

323-1

PATIENT ROOM

321-1

TELECOM

322-1

RR

321A-1

RR

326-1

RR

325A-1

EQUIPMENT STORAGE

381-1

RECEPTION

380-1

VENDING

379-1

PATIENT ROOM

377-1

STAIRS

3-STAIR-C

IRM

345-1

RN OFFICE

343-1

HSKPG

339-1

TOILET

338-1

LOCKER ROOM

337-1

TELCOM

344-1

ELEV.

3-ELEV

CORRIDOR

3-CORR-W

CORRIDOR

3-CORR-C

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

ED103.4

ELECTRICAL DEMOLITION PLAN - THIRD

FLOOR - BID ITEM 4

Wichita, Kansas

Checker Author04-27-2018

2' 4' 8'0'

1/4" = 1'-0"

N

1/4" = 1'-0" A

ELECTRICAL DEMOLITION PLAN - THIRD FLOOR - BID ITEM 4

No. Description Date

D

D

D

M

M

D

M

D

D

D

D

D

D

D

D

D

D

D

DD

D

D

D

D

D

D

D

D

D

D

D D

D

D

D

D

D

M

M

DD

D D

M

M

D

D

D

D

D

M

PATIENT ROOM

221-1

TOILET

220-1

SOILED UTILITY

218-1

TOILET

217-1

PATIENT ROOM

216-1

AIRBORNE INFECTION ISO.

PATIENT ROOM

214-1

TOILET

213-1

PATIENT ROOM

211-1

TOILET

209-1

PATIENT ROOM

208-1

PATIENT ROOM

204-1

BARIATRIC PATIENT ROOM

202-1

PATIENT ROOM

233-1

PATIENT ROOM

234-1

PATIENT ROOM

236-1

TOILET

232-1

ANTE RM

215-1

CHARTING

206-1

TOILET

238-1

RECEPTION

241-1

NURSE STATION

224-1

EXIST. STAIRS

2-STAIR-W

TOILET

210-1

TOILET

203-1

TOILET

205-1

CORR

200-1

CORR

201-1

CORR

212-1

CORR

219-1

CORR

207-1

STAFF TOILET

222-1 SB

HA

HA

HA

HA HA

ST

ST

L1

L2 a c a a b b d a b c d f,g f,g e

HS

HA

h j h h j

SV

KA

KA

KA

KA

KA

KA

KA

KA

KA KA KA KA KA KA

KA KA KA KA

KA

KA

KA

K2F

K2 b

NL a

NL

a

NL

a

NL

a

NL

a

NL

a

NL

a

NL

a

NL

a a NL a

SV

SB

HA

HA HAHA

HA

HS

SB

HA

HA

HA

HA

HA

HA

HS SV

SB

HA HA

HA HA

HA

SV

HS

HA

HA

SV

HS

SB

HA HA HA

HA

HA

SV

HA HS

SB

HA HA HA

HASB

SV

HA

HS

SV

HA

HS

HA

HA

HA

SB

HA

SV

SV

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

HA

HA

SB

HA

HA

HA

HA

HA

SB

HAHA

HA

HA

HS

HA

HS

KA

KA

KA

KAKA

KA

NL

a NL

N4

CLEAN UTILITY

231-1

MEDICATION

230-1

CLEAN LINEN

201B-1

NOURISH.

227-1

EQUIP. STOR.

229-1

ELECT.

228-1

KA

KA KA

KA

KA

b b b NL c

3a

3a d e e e e d d d d d dK4

K4

K4

K4

K4

N4

KA

HL HL

HA

KA

H4

H4

H4

H4

H4

H4 H4

H4

H4

H4

HA

KA

HA

HA

HL HL

HL HL

HL HL

HA

HA

HL

HA

HL

HA

HA

HA

HA

HA

HL HL

HA

HLHL

HL

HL

HA

HA

HA

HL

HL

HA

HAHA

HL

HL

KA

e

SV

HA

e e a a a

SHADED AREA NOT IN

SCOPE OF WORK

b h h j h jb d d a a a a a a b c e f,g e e f,g c b a c c a a f,g e e f,g e a a b d d hj h b h j a c c a a b d d f,g e e ef,g f,g e e e f,g a d d c c a a b a b a h j h b h j c c d df,ge ee f,g a a a a a b b b j h h j h h j b h j h b aaaa d d e e f,ge f,g c c b a d d h j b j h h a b a e e e f,g f,g a c c a a b c c a a a b a f,g e e f,ge b a h j h j h b h h j b jh b dd c a c a b a ef,g e e f,g a a

ST

KA

H4 H4

H4

H4

H4

H4

X1

X1

X1

X1

X2

X2

X1

X1 h b h j a b b b c c c c c c c c c c

L1 L2

L2L1

L1L2

L1L2

L2

L1

L2 L1

L2L1

L1

L2

L1

L2

X1 X1

L3 h j

L3

L3

U1

U1 U1

U1

U2

U1

U1

U2 U2 U2

U2

U2

L4

KA

a

L3

L4

L3

L3

L3

L4

L3

L3

L3

L4

L4 L4

L4

L4

1-EL-2W

1-2W

1-EC-2W

U1

U1

U1

U1

L4

L4

1-EC-2W:2

1-2W:2

1-2W:2

1-2W:2

1-2W:2

1-2W:2

HSKPG

240-1

1-EL-2W:2

1-2W:4

1-2W:6

1-EC-2W:4

1-2W:6

1-2W:6

1-2W:6

1-2W:6

1-2W:6

1-2W:6

1-EC-2W:4

1-EC-2W:4

1-EC-2W:2

1-EC-2W:2

1-EC-2W:2

1-EC-2W:4

1-EC-2W:6

1-EC-2W:6

1-EC-2W:6

1-EC-2W:6

CLOSET

207A-1

U2

U1

U2

U2

U2U1

U2

U2

U2

U2

U2U2 U1

U2U1

U1U2

L4L4

L4

U2

U2

L4

L4

U1U2

L4

L4

U2

U1

L4

L4 U1

U2

L4

U2 U1

L4

U2

U1 L4

L4

SECOND FLOOR KEY PLAN

N

PHASE 1 PROJECT

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF

ONE HOUR.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

EL102

ELECTRICAL LIGHTING PLAN - SECOND

FLOOR

Wichita, Kansas

SMS JLW04-27-2018

1/4" = 1'-0" A

ELECTRICAL LIGHTING PLAN - SECOND FLOOR

N

2' 4' 8'0'

1/4" = 1'-0"

KEYED NOTES:

L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH

FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF

FIXTURE ‘SB’.

L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE

LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE

CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM

PILLOW SPEAKER.

L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN

MANUFACTURED HEADWALL UNIT.

L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE

CIRCUIT BELOW.

No. Description Date

M

M

DD

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

DD

D

D

D

D

D

D

D

D D

D

D D

D

M

M

D

D

D

M

PATIENT RM

316-1

TOILET

317-1

SOILED UTILITY

319-1

STORAGE

320-1

TOILET

321-1

PATIENT RM

322-1

TOILET

310-1

TOILET

309-1

PATIENT RM

308-1

BARIATRIC PATIENT ROOM

302-1

PATIENT RM

304-1

TOILET

305-1

HSKPG

324-1

TOILET

335-1

PATIENT ROOM

334-1

PATIENT ROOM

336-1

TOILET

337-1

EQUIP. STOR.

338-1

EQUIP. ALCOVE

300-1

NURSE STATION

325-1

HALL

307-1

HALL

301-1

HALL

326-1

HALL

339-1

HALL

312-1

CHARTING

306-1

STAFF TOILET

323-1

TOILET

313-1

ANTE RM

318-1

KAKA

KAKAKAKAKAKAKAKA

KA

KA

KA

KA

KA

KA

KA

K2

KA

KA

K2F K2

K2 b a

NL

a

NL

a a

NL

NL

NL a a NL a a NL a NL

K4

K4

HS

HA

HA

SB

HA HA

SB

SV

HS

HA HA

HA

HA

HAHA

SB

HA

HA HA

HA

HA

SV

HA

HS

SB

SV

HS

HA

HA

HA

SB

SV

HS

HA

HA

SB

SV

HS

HA

HA

SV

HS

HA

HAHA

SB

HA

HA

HS

SB

SV

HA HS

SB

HA

HA

STST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

KA

KA

KA

KA

KA

N4

K4

K4

K4

K4

K4

K4

N4 c c c

3a c

3a a

NL

HA HA HA

KA

HLHL

HA

HAHA

HL HL

HAHA

SV

ST

HL

HL

HA

HL

HL

HA

HL HL

HA

HL

HL

HA

HA

HAHA

HA

HA

HA

HA

HA

HL HL

HA HA

HA HA

HA

H4 H4

H4

H4

H4

H4

HL HL

HA

HL HL

KA

1-3W b b b b b b a

SHADED AREA NOT IN

SCOPE OF WORK

X1

KA

X1

X2

X1

X2

X1

H4 b

CLOSET

307A-1

HA

HA

a b c ca a e e f,g f,g e a a b h d d j j h h a b d d b h j j h h b a a a e e f,g e f,g c c b a a a b a a b a d d f,g ee f,g e c c jh h b h j d dc c aa f,g ee f,g e a b a b a h j h b h j c cd de f,g f,g e e a a a a a b b h j b h h j j h b h j h b a a a a b c c a d d f,g e e f,g e h h b j b h j d d a a a c ce ee f,g f,g b a a c a c b h b a j h j h b e e f,ge f,g a ef,g e e f,g aaca a b c d d b b jh h h j

1-EC-3W1-EM-3W

a

1-EL-2W:4

CLEAN UTILITY

330-1

CLEAN UTILITY

330-1

CLEAN UTILITY

330-1

1-EC-3W:2

1-EC-3W:2

1-3W:4

1-3W:4

1-3W:2

1-3W:4

1-EC-3W:2

1-EC-3W:4

1-3W:6

1-3W:6

1-EC-3W:4

1-3W:6

1-EC-3W:4

1-3W:6

1-EC-3W:4

1-EC-3W:6

1-3W:6

1-3W:6

1-EC-3W:6

1-3W:6

1-EC-3W:6

1-EC-3W:6

1-3W:6

L2 L1

L3

ELECT.

328-1

U2

U1

U1

U1

L4

L4

L4

U1

U1

U2

L4

L4

U2

U1 L4

L4 b

U2

U1

U2

U2

L4

L4

L4

SV

U1

U2

U1U2

H4

H4 H4 b b

U2

U1 L4

L2

L1

L3

U1

U2

U2

U1U2

L1

L2

L3

U1 U2

L4

L4

L4

L4

L4

U2 U1

L4

U1 U2

U1

U2

L4

L4 U1

U2

L4

U2

L1

L3

L2

L1

L2L3

L1

L3

L2

L3

L2

L1

L1

L2 L3

HA

a

L1

L3 L2

THIRD FLOOR KEY PLAN

PHASE 1

N

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF

ONE HOUR.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

EL103

ELECTRICAL LIGHTING PLAN - THIRD

FLOOR

Wichita, Kansas

SMS JLW04-27-2018

1/4" = 1'-0" A

ELECTRICAL LIGHTING PLAN - THIRD FLOOR 2' 4' 8'0'

1/4" = 1'-0"

N

KEYED NOTES:

L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH

FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF

FIXTURE ‘SB’.

L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE

LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE

CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM

PILLOW SPEAKER.

L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN

MANUFACTURED HEADWALL UNIT.

L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE

CIRCUIT BELOW.

No. Description Date

D

D

D

D

D

D

D

D

D

M

M

D

D

D

D D

M

D D

M

M

D

D

D

D

D

D

D

D

D D

D

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF

ONE HOUR.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN. THIRD FLOOR KEY PLAN

PHASE 1

N

PATIENT RM

316-1

TOILET

317-1

SOILED UTILITY

319-1

STORAGE

320-1

TOILET

321-1

PATIENT RM

322-1

BARIATRIC PATIENT ROOM

302-1

PATIENT RM

304-1

TOILET

305-1

HSKPG

324-1

TOILET

335-1

PATIENT ROOM

334-1

PATIENT ROOM

336-1

TOILET

337-1

EQUIP. STOR.

338-1

EQUIP. ALCOVE

300-1

NURSE STATION

325-1

HALL

307-1

HALL

301-1

HALL

326-1

HALL

339-1

HALL

312-1

CHARTING

306-1

STAFF TOILET

323-1

TOILET

313-1

ANTE RM

318-1

KAKA

KAKAKA

a a NL a NL

K4

K4

HS

HA

HA

SB

HA HA

ST SV

ST

HL

HL

HA

HA

HA

HA

SHADED AREA NOT IN

SCOPE OF WORK

X1

KA

X1

CLOSET

307A-1 a b c ca a e e f,g f,g e a a b h d d j j h h a b a

1-EL-2W:4

CLEAN UTILITY

330-1

CLEAN UTILITY

330-1

CLEAN UTILITY

330-1

1-EC-3W:2

1-EC-3W:2

1-3W:4

1-3W:2

1-3W:4

1-EC-3W:2

1-EC-3W:4

1-3W:6

1-3W:6

1-EC-3W:4

1-EC-3W:6

1-3W:6

1-3W:6

1-EC-3W:6

1-3W:6

1-EC-3W:6

1-EC-3W:6

1-3W:6

ELECT.

328-1

L4

L4

L4

U1L4

L4

SB

HLHL

HAHAHA

HA

HA HA

ST

ST

HA

HS SV

U1

KA

KA

KA

SV

ST

HA HS

ST

HAHAHAHA

HA

SB

KA KAKA

KA

KA

SV

ST

HA

HS

ST

HAHA

HAHA

SB

HL HL

HA

U1

U1

KA

KA

X1

KAKA

KA

H4

H4

H4 H4

H4

H4

H4

H4

H4

N4

H4 KA

KA

K4

X1

K4

K4

K4

K4

K4

U2

KAKA

KA

X2

KA

K2

HA

SV

HS

HA

ST

ST

HA

HA

HA

HL

HA

HAHA

HL

SB

N4

X2

HL HL

e e f,g f,g ee b a c a a d a hj h b a

NL

a c a a a b h b h j d h j a b c ef,g f,g e a b h j d c a

NL

a b b b b b bb b b b a

NL

NL a a NL b a c a a f,g e e a a b h h j h j d d c

3a b c cc c b h h j j h b b a aa add f,g c e e e f,g c a

NL

U2

KA

KA

SV

HS

HA

ST

STHA

HA

HA

SB

HL HL

K2F K2

K2

HS

HA

SV

ST

ST

HA

HA HAHAHA

SB

HL HL

h h j j h b b a c c b a a f,g e e e f,g j h h b h j b aac d a f,g ee a c b a d ef,g

SHADED AREA NOT IN

SCOPE OF WORK

L4

L4

L4

U2

U1

U2

U2

U1U2

U2

U2 U1

U1 U2

U1

U2 U1

U2

U1 U2

U2 U1

L4

L4

L4

L4

L4

L4

U2

U1

U2

L4

L4 3a

1-3W:4

NL

L1 L2

L3

L1

L3 L2

L2

L1

L3

L2L1

L3

L2

L1 L3 f,g e

L1

L2

L3

L1

L2

L3

1-3W 1-EC-3W1-EM-3W

Drawing Title Project Title

Date

Location

Checked

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

589A7-17-203

Robert J. Dole VA Medical Center

RENOVATE WARDS FOR PATIENT

PRIVACY PHASE 1, B1

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA

142 N. MOSELY ST

WICHITA, KANSAS

EL103.3

ELECTRICAL LIGHTING PLAN - THIRD

FLOOR - BID ITEM 3

Wichita, Kansas

Checker Author04-27-2018

2' 4' 8'0'

1/4" = 1'-0"

N

1/4" = 1'-0" A

ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BID ITEM 3

# KEYED NOTES:

L1 PROVIDE LOW VOLTAGE BUMP-UP, BUMP-DOWN TOGGLE SWITCH

FOR CONTROL OF AMBIENT AND EXAM LIGHTING PORTIONS OF

FIXTURE ‘SB’.

L2 DIMMER SWITCH FOR CONTROL OF READING CAN LIGHTS. PROVIDE

LOW VOLTAGE RELAY AS REQUIRED AND INTERLOCK WITH NURSE

CALL FOR MANUAL ON/OFF CONTROL OF LIGHT FIXTURES FROM

PILLOW SPEAKER.

L3 INSTALL LOW VOLTAGE SWITCH AND DIMMER SWITCH IN

MANUFACTURED HEADWALL UNIT.

L4 CONNECT UNDERCABINET LIGHT FIXTURE TO 120V RECEPTACLE

CIRCUIT BELOW.

No. Description Date

D

D

PATIENT ROOM

336-1

TOILET

337-1

EQUIP. STOR.

338-1

EQUIP. ALCOVE

300-1

HALL

339-1

KAKA

KAKAKA

NL

NL

K4

K4

HS

HA

HA

SB

HA HA

ST SV

ST

HL

HL

HA

HA

HA

HA

SHADED AREA NOT IN

SCOPE OF WORK

X1

KA

X1 a b c ca a e e f,g f,g e a a b h d d j j h h a b

U1L4

SHADED AREA NOT IN

SCOPE OF WORK

1-3W-EM

1-3W L4

U2 U1

L3

L1

L2

L8

L7

L6

L5

THIRD FLOOR KEY PLAN

PHASE 1

N

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE…