This file contains a draft elevator study documenting the existing conditions of elevators in Building 200 at the Hines VA Hospital. The study details eight traction elevators, including five passenger elevators (P1-P5) and three service elevators (S6-S8), with capacities ranging from 4,000 to 5,000 lbs and traveling at 600 fpm. The elevators are equipped with Motion Control Engineering (MCE) controllers built in 2000, Montgomery DC gearless machines likely installed in the 1960s, and various components from Hollister Whitney, including governors, rope grippers, and guide assemblies.
The documentation indicates the elevator equipment is in poor to average condition and operating at its useful life expectancy. The survey recommends budgeting for modernization, estimating approximately per unit, with a modernization process taking 18-20 weeks per unit. Key components requiring replacement include controllers, machines, governors, door operating equipment, guide assemblies, elevator safeties, hall and car fixtures, and safety buffers. The survey also notes additional issues such as sprinkler placement, machine room environmental conditions, and door fire ratings that may need attention during modernization.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SouthCo Services, LLC | 1-877-611-5511 4
Building 200 Traction Units
Previous Elevator Survey by South Co
Issue #21 -- OPEN (2/2) Penthouse S6/S7/S8 and P1/P2/P3/P4/P5 Guide Wheel
MP field survey
SouthCo Services, LLC | 1-877-611-5511 4
Rope Grippers
SouthCo Services, LLC | 1-877-611-5511 5
Governor
Issue #19 -- OPEN (2/3)
Governor and Governor Control Box
Issue #19 -- OPEN (3/3)
Governor
Issue #18 -- OPEN (2/2)
Sprinklers located directly above elevator equipment, may need to be rearranged per code
Issue #21 -- OPEN (2/2)
Controller is Microprocessor Type
Issue #19 -- OPEN (2/3)
Issue #19 -- OPEN (3/3)
Hoist "Ropes" measured at 5/8"
Issue #18 -- OPEN (2/2) Penthouse S6/S7/S8 and P1/P2/P3/P4/P5 Gearless type Machine
Issue #10 -- OPEN (2/3)
Issue #10 -- OPEN (3/3)
Issue #7 -- OPEN (2/2) Elevator Number P4/P5 Field Photos
Issue #5 -- OPEN (2/3)
Elevator Number S6/S7/S8 Field Photos
Issue #5 -- OPEN (3/3) Elevator Number S6/S7/S8 Field Photos
Issue #7 -- OPEN (2/2)
Issue #5 -- OPEN (2/3)
Issue #5 -- OPEN (3/3)