S02 SOW_Att15c_578-25-003 100 perc Bid Drawings_Part 3of5 DRAFT.pdf

PDF 270 KB Posted

Attached to
Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
Solicitation number
36C25225R0036
Issued by

About this file

These are fire protection design drawings for the Elevator Replacement Project at the Hines VA Hospital in Hines, Illinois. The drawings, issued as 100% Bid Documents on 01/24/2025, provide detailed fire protection specifications for the machine room floor plan, including sprinkler head guard details, fire protection symbols, and general notes. Key requirements include installing sprinkler head guards on all existing sprinkler heads in the elevator machine room, demolishing existing sidewall sprinklers, and ensuring compliance with multiple NFPA standards and building codes. The drawings are part of a comprehensive elevator renovation project for Building 200, which involves modernizing passenger and service elevators while maintaining hospital operations.

The fire protection drawings specify technical requirements such as maintaining fire and smoke-rated wall integrity, providing U.L. approved penetration drawings, and coordinating fire protection system installation with electrical contractors. The project is classified under NAICS Code 238290, set aside for service-disabled veteran-owned small businesses, with an estimated construction value between $10-20 million. The contractor will be responsible for complete installation, including submittals, reviews, quality assurance, and closeout within 730 calendar days from the Notice to Proceed.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N.T.S.

2 5/8" [67 mm]

2 5/8" [67 mm]

3" [75 mm]

3" [75 mm]

EXISTING

SPRINKLER

HEAD

SPRINKLER HEAD GUARD

EXISTING

SPRINKLER

HEAD

WITH UPRIGHT SPRINKLER WITH PENDENT SPRINKLER

1 SPRINKLER HEAD GUARD DETAIL

(E)

2"

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

PIPE RISE

PIPE DROP

PIPE TEE

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

Room

INVERT: -105' - 1"

1/8" / 12" SLOPE

FIRE PROTECTION SYMBOLS

FIRE PROTECTION OTHER

FIRE PROTECTION DRY

FIRE PROTECTION PRE-ACTION

FIRE PROTECTION WET

Ø DIAMETER

ABV ABOVE

AFF ABOVE FINISHED FLOOR

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

CAP CAPACITY

CLG CEILING

D DEGREE

DN DOWN

ELEC ELECTRICAL

F FAHRENHEIT

FDC FIRE DEPARTMENT CONNECTION

FPM FEET PER MINUTE

FT FOOT/FEET

GAL GALLON

GPM GALLONS PER MINUTE

HYD HYDRANT

IN INCH

INV INVERT

LB POUND

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

MISC MISCELLANEOUS

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PSI POUNDS PER SQUARE INCH

REC RECESSED

RM ROOM

SF SQUARE FOOT/FEET

SP STANDPIPE

SP STATIC PRESSURE

TYP TYPICAL

UG UNDERGROUND

ABBREVIATIONS

PIPE ACCESSORY TAGS

BALANCING VALVE

1/4 TURN BALL VALVE

CHECK VALVE

UPRIGHT SPRINKLER HEAD

PENDENT SPRINKLER HEAD

DRY SPRINKLER HEAD

CAP

SIDEWALL SPRINKLER HEAD

EXTENDED COVERAGE SIDEWALL

SPRINKLER HEAD

RECESSED SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

ALARM CHECK VALVE

DRY PIPE VALVE

INDICATING BUTTERFLY

VALVE

OS&Y VALVE PREACTION VALVE

POST INDICATOR VALVE

RISER

THRUST BLOCK

VALVE NONRISING STEM

DRY SIDEWALL SPRINKLER HEAD

DRY EXTENDED COVERAGE SIDEWALL

SPRINKLER HEAD

EXISTING SPRINKLER HEAD

GENERAL NOTES

FIRE PROTECTION NOTES

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER

DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS

SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.

FREESTANDING SIAMESE

DEPARTMENT FIRE

CONNECTION

PRESSURE REDUCING

VALVE

SINGLE FIRE DEPARTMENT

CONNECTION

SIAMESE FIRE CONNECTION

DEPARTMENT

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF

WORK TO BE PROVIDED (FURNISHED AND INSTALLED) UNDER THIS

CONTRACT. DRAWINGS SHOULD NOT BE SCALED.

4. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR

INSTALLATION OF WORK UNDER THIS CONTRACT. DISMANTLE AND

REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING

AND THE LOCATION OF INSTALLATION.

5. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND

SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED

AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

6. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART

OF THE TOTAL PROJECT COST.

7. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS,

PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH

RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.

REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.

8. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE

OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR

CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL

TIMES DURING CONSTRUCTION.

9. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

10.THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT

SUBMITTALS FOR ALL PRODUCTS USED ON PROJECT.

11.THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE

CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE

REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR

HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC

DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT

RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR

OMISSIONS IN HIS OR HER SUBMITTAL DATA.

12.THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M

MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION.

MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL

NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA,

EQUIPMENT SHOP DRAWINGS, SPARE PARTS DATA, ETC. PROVIDE AN INDEX

AND ASSOCIATED DIVIDERS.

13.CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF

CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP

AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET

IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND

CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE

TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION

COMPLETION.

14.IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND

UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT

LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS

ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING ANY WORK,

THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS,

VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR

ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR

DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF

NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND

MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN

CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.

A.THE SYSTEM SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S

SPECIFICATIONS AND RECOMMENDATIONS AND AS PER REQUIREMENTS OF

ALL FEDERAL VA AUTHORITIES, NFPA, AND FACTORY MUTUAL.

B. THIS CONTRACTOR SHALL COORDINATE PHASING OF SPRINKLER WORK

WITH THE GENERAL CONTRACTOR PRIOR TO STARTING WORK.

C.REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION

REGARDING SPRINKLER HEAD LOCATION AND PIPE, UNLESS NOTED

OTHERWISE.

D. DIVISION 21 CONTRACTOR SHALL COORDINATE WITH THE ELECTRICAL

CONTRACTOR FOR PROPER INSTALLATION OF THE FIRE PROTECTION

SYSTEMS ALARM DEVICES INVOLVED WITH FIRE SPRINKLER SYSTEM.

E. THE CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS AS

REQUIRED TO ENSURE AN APPROVED FIRE PROTECTION SYSTEM AT NO

ADDITIONAL COST TO THE OWNER.

F. SHOW ALL ROOM NUMBERS ON SHOP DRAWING PLANS.

LIMIT OF DEMOLITION

2. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL,

STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY

THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN

THESE ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT

REQUIREMENTS SHALL GOVERN.

3. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE

REQUIREMENTS:

· VA TECHNICAL INFORMATION LIBRARY (TIL)

· INTERNATIONAL BUILDING CODE (IBC) 2024

· INTERNATIONAL EXISTING BUILDING CODE 2024

· INTERNATIONAL MECHANICAL CODE 2024

· INTERNATIONAL PLUMBING CODE 2024

· INTERNATIONAL ENERGY CONSERVATION CODE 2024

· INTERNATIONAL FIRE CODE 2024

· NFPA 1-2024, THE UNIFORM FIRE CODE

· NFPA 101-2024, THE LIFE SAFETY CODE

· NFPA 51B-2024, STANDARD FOR FIRE PREVENTION DURING WELDING,

CUTTING AND OTHER HOT WORK

· NFPA 13-2022, STANDARD FOR THE INSTALLATION OF SPRINKLER

SYSTEMS

· NFPA 70-2023, NATIONAL ELECTRICAL CODE

· NFPA 90A-2024, STANDARD FOR THE INSTALLATION OF AIR

CONDITIONING AND VENTING SYSTEMS.

· NFPA 99-2024, STANDARD FOR HEALTH CARE FACILITIES

· NFPA 241-2022, STANDARD FOR SAFEGUARDING CONSTRUCTION,

ALTERATION AND DEMOLITION OPERATIONS.

FP-W

FP-PA

FP-O

FP-D

D

D D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Architect:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP Engineer: Elevator Consultant:

MES GROUP LERCH BATES

550 N. REO STREET SUITE 203

TAMPA, FL 33609

813.289.4700

216 S. JEFFERSON STREET

SUITE LL2

CHICAGO, IL 60661

312.256.1010

30% SCHEMATIC DESIGN 06/20/2024

60% DESIGN DEVELOPMENT 08/12/2024

90% QAQC REVIEW 09/23/2024

90% CONSTRUCTION DOCUMENTS 10/02/2024

100% QAQC REVIEW 10/25/2024

100% BID DOCUMENTS 01/20/2025

100% BID DOCUMENTS - REVISED BASE BID 01/24/2025

A u to d e s k D o c s /1

.6

.1

V A

H in e s E le v a to r

R e p la c e m e n t/

.6

.1

H in e s E le v a to rs M

E P

R

.r v t

/2

/2

:1

:4

A

M

F000

FIRE PROTECTION TITLE SHEET

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

ELEVATOR REPLACEMENT

5000 5TH AVE, HINES, IL 60141

578-25-003

01/24/2025 NPS PBJ

100% BID DOCUMENTS

FULLY SPRINKLERED

FIRE PROTECTION SHEET INDEX

F000 FIRE PROTECTION TITLE SHEET

FP116 MACHINE ROOM FLOOR PLAN - FIRE PROTECTION

FIRE RATING LEGEND

1 HOUR FIRE WALL

2 HOUR FIRE WALL

Revisions: Date:

Date Signed: 01/24/2025 License Expires: 02/28/2027

A. EXISTING EQUIPMENT, PIPING, SPRINKLER HEADS, AND ASSOCIATED

COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND

ARE PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND

COORDINATE WITH EXACT LOCATIONS, ELEVATIONS, SIZES, NUMBER OF

SPRINKLER HEADS, AND CONDITIONS OF EXISTING COMPONENTS.

B. FIRE PROTECTION PIPING SHALL NOT BE LOCATED OR ROUTED ABOVE ANY

ELECTRICAL EQUIPMENT. DRAIN PANS SHALL BE PROVIDED WHERE

NECESSARY TO PREVENT ANY DAMAGE TO EQUIPMENT.

FIRE PROTECTION GENERAL NOTES

1. GUARDS SHALL BE PROVIDED ON ALL EXISTING SPRINKLER HEADS

(PENDENT, UPRIGHT, AND SIDEWALL) LOCATED IN ELEVATOR MACHINE

ROOM. CONTRACTOR SHALL FIELD VERIFY EXACT NUMBER OF SPRINKLER

HEADS IN SPACE PRIOR TO ORDERING GUARDS. ALL EXISTING SPRINKLER

HEAD GUARDS SHALL BE REPLACED WITH NEW GUARDS.

2. EXISTING SIDEWALL SPRINKLER SHALL BE DEMOLISHED COMPLETELY. ALL

ASSOCIATED FIRE SPRINKLER BRANCH PIPING SHALL BE DEMOLISHED

COMPLETELY BACK TO LIMIT OF DEMOLITION SHOWN ON DRAWING. CAP

AND SEAL.

FIRE PROTECTION KEYNOTES -

H I J

ENGINEERING MECHANICAL

ROOM

OPEN TO BELOW

OPEN TO BELOW

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(E) 2" FP-W

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Architect:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP Engineer: Elevator Consultant:

MES GROUP LERCH BATES

550 N. REO STREET SUITE 203

TAMPA, FL 33609

813.289.4700

216 S. JEFFERSON STREET

SUITE LL2

CHICAGO, IL 60661

312.256.1010

30% SCHEMATIC DESIGN 06/20/2024

60% DESIGN DEVELOPMENT 08/12/2024

KEY PLAN

NO SCALE

N

90% QAQC REVIEW 09/23/2024

90% CONSTRUCTION DOCUMENTS 10/02/2024

100% QAQC REVIEW 10/25/2024

100% BID DOCUMENTS 01/20/2025

100% BID DOCUMENTS - REVISED BASE BID 01/24/2025

A u to d e s k D o c s /1

.6

.1

V A

H in e s E le v a to r

R e p la c e m e n t/

.6

.1

H in e s E le v a to rs M

E P

R

.r v t

/2

/2

:1

:4

A

M

FP116

MACHINE ROOM FLOOR PLAN -

FIRE PROTECTIONGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

ELEVATOR REPLACEMENT

5000 5TH AVE, HINES, IL 60141

578-25-003

01/24/2025 NPS PBJ

100% BID DOCUMENTS

FULLY SPRINKLERED

N

SCALE: 1/4" = 1'-0"FP116

1 MACINE ROOM FLOOR PLAN - FIRE PROTECTION

Revisions: Date:

Date Signed: 01/24/2025 License Expires: 02/28/2027