This document provides details for a federal contract opportunity with the Department of Veterans Affairs to renovate Building 131-4A for patient safety at a Veterans Affairs medical center. The solicitation number is 36C25222B0008 and it seeks to award a contract to renovate the building to improve emergency operations capabilities. Offerors should respond by the specified due date to provide construction services to upgrade the facility. The opportunity is designated for full and open competition among qualified vendors.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:1
P
M
556-17-002
GI001
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGCOVER SHEET
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
CAMPUS AERIAL PHOTO
LOCATION MAP
COORDINATION NOTES
INDEX OF DRAWINGS
PROJECT
3001 GREEN BAY ROAD
NORTH CHICAGO, IL 60064
556-17-002
RENOVATE BUILDING 131-4A WING
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE CENTER (FHCC)
THE CONTRACTOR SHALL PREPARE COORDINATION DRAWINGS. SUCH DRAWINGS SHALL BE ARRANGED AND DESIGNED THROUGH AND FROM COORDINATION WITH ALL OTHER MAJOR AND MINOR SUBCONTRACTORS.
THE CONTRACTOR AT THEIR OWN EXPENSE SHALL PREPARE A THREE-DIMENSIONAL COORDINATION MODEL AND PRODUCE TWO-DIMENSIONAL COORDINATION DRAWINGS FROM MODEL, SPECIFICALLY CREATED BY THE
CONTRACTOR FOR THIS PROJECT.
MODEL SHALL INCLUDE AND DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO: ALL DUCTWORK; ALL AIR DISTRIBUTION; MECHANICAL EQUIPMENT; MECHANICAL PIPING; FIRE PROTECTION PIPING; ALL PLUMBING PIPING;
CABLE TRAYS (WITH ELEVATIONS NOTED); LIGHTING FIXTURES (WHEN CEILING MOUNTED); CEILING GRID AND CEILING HEIGHT; COLUMNS, BEAMS AND JOISTS (WITH ELEVATIONS MARKED); FIRE ALARM DEVICES AND SPEAKERS (WHERE CEILING MOUNTED); ELECTRICAL CONDUITS LARGER THAN 2-INCH DIAMETER; ELECTRICAL BUSWAY AND REQUIRED CLEARANCES; EQUIPMENT PROVIDED BY OTHERS THAT PROTRUDE INTO CEILING CAVITIES OR IMPEDE THE LOCATION OR ACCESS TO ABOVE CEILING PIPING, DUCTWORK OF OTHER EQUIPMENT. SECTIONS SHALL BE CUT THROUGH AREAS SHOWING MATERIALS AND SYSTEMS OF ALL CONTRACTS.
IF THERE ARE ANY COORDINATION ISSUES THAT CANNOT BE RESOLVED BY THE GC’S COORDINATION DRAWING PREPARER, THE GC SHALL SUBMIT RFI TO THE VA.
CONTRACTOR SHALL PERFORM CLASH DETECTION ON ALL MODELED ELEMENTS AND RESOLVE CLASHES AMONGST TRADES.
NOTE THAT ROUGH-IN / FABRICATION CANNOT BEGIN UNTIL COORDINATION MODEL AND DRAWINGS HAVE BEEN APPROVED. ANY MATERIAL, EQUIPMENT, SYSTEMS, ETC., PROCUREMENT OR INSTALLATION COMMENCED PRIOR TO APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK AND MAY HAVE TO BE MODIFIED, MOVED AND/OR RECONFIGURED AT NO INCREASE IN CONSTRUCTION TIME OR MONIES TO BE BURDENED BY THE GOVERNMENT. BOTH MODEL AND DRAWINGS ARE TO BE MADE A PART OF COORDINATION DRAWING SUBMISSION TO GOVERNMENT AND DESIGNER. ENSURE THAT ALL SUB-CONTRACTORS ARE RESPONSIBLE FOR
COORDINATION ACROSS ENTIRE SET OF CONSTRUCTION DOCUMENTS.
PROJECT
SITE
FIRE ALARM
FA001 GENERAL NOTES AND SCHEDULES
FA101 FOURTH FLOOR FIRE ALARM PLAN
FA102 ROOF AND PENTHOUSE FLOOR FIRE ALARM PLAN
FIRE PROTECTION
FX001 GENERAL NOTES & LEGENDS
FD101 FOURTH FLOOR PLAN - FIRE PROTECTION DEMOLITION
FX101 FOURTH FLOOR PLAN - FIRE PROTECTION
FX102 ROOF & PENTHOUSE FLOOR - FIRE PROTECTION
PLUMBING
PL001 GENERAL NOTES, LEGENDS, & SCHEDULES
PD101 FOURTH FLOOR PLAN - PLUMBING DEMOLITION
PL101 FOURTH FLOOR PLAN - WASTE
PL102 FOURTH FLOOR PLAN - DOMESTIC WATER
PL501 PLUMBING DETAILS
PL701 PLUMBING RISER DIAGRAMS
MECHANICAL
MH001 GENERAL NOTES & LEGENDS
MD101 FOURTH FLOOR - ENLARGED - MECHANICAL DEMOLITION PLAN
MH101 FOURTH FLOOR - ENLARGED - MECHANICAL DUCTWORK PLAN
MP101 FOURTH FLOOR - ENLARGED - MECHANICAL PIPING PLAN
MH301 SECTIONS & ELEVATIONS
MH401 ROOF AND PENTHOUSE - PARTIAL - TEMPORARY MECHANICAL PLANS
MH402 ROOF AND PENTHOUSE - PARTIAL - MECHANICAL PLANS
MH501 DETAILS
MH502 DETAILS
MH503 DETAILS
MH601 SCHEDULES
MI701 CONTROLS SCHEMATICS
MI702 CONTROLS POINTS
ELECTRICAL
EG001 GENERAL NOTES AND SCHEDULES
ED101 FOURTH FLOOR DEMOLITION PLAN - ELECTRICAL
ED102 PENTHOUSE FLOOR DEMOLITION PLAN - ELECTRICAL
EL101 FOURTH FLOOR LIGHTING PLAN
EL102 PENTHOUSE LIGHTING PLAN
EP101 FOURTH FLOOR POWER PLAN
EP102 PENTHOUSE FLOOR POWER PLAN
EY101 FOURTH FLOOR SYSTEMS PLAN
EY102 FOURTH FLOOR SYSTEMS PLAN - CABLE TRAY
EP501 ELECTRICAL DETAILS
EP502 ELECTRICAL DETAILS
EP601 ELECTRICAL RISER DIAGRAM
EP701 PANEL SCHEDULES
EP702 ELECTRICAL EQUIPMENT SCHEDULE
GENERAL
GI001 COVER SHEET
GI002 EQUIPMENT MOUNTING LEGEND
GI003 ACCESSIBILITY LEGEND
GI101 FOURTH FLOOR LIFE SAFETY PLAN
GI200 BID DEDUCT ALTERNATES
GI201 BID DEDUCT ALTERNATE PLANS
GI501 PROJECT-WIDE PARTITION TYPES AND STANDARD DETAILS
LS-5 BUILDING 131 FOURTH FLOOR
GENERAL CONDITIONS
GC100 GROUND FLOOR INFECTION CONTROL (ICRA) PLAN
GC103 FOURTH FLOOR INFECTION CONTROL (ICRA) PLAN
ARCHITECTURAL
AS101 ARCHITECTURAL SITE PLAN
AI001 NOTES AND LEGEND
AI002 ARCHITECTURAL ABBREVIATIONS
AD052 FOURTH FLOOR DEMOLITION PLAN
AE100 FOURTH FLOOR OVERALL PLAN
AE102 FOURTH FLOOR PLAN - ENLARGED
AE103 FOURTH FLOOR DIMENSION PLAN
AE104 FOURTH FLOOR WALL TYPES PLAN
AE105 FOURTH FLOOR LEVELING PLAN
AE106 FOURTH FLOOR REFLECTED CEILING PLAN
AE107 THIRD FLOOR REFLECTED CEILING PLAN
AE108 PENTHOUSE FLOOR PLAN - TEMPORARY AHU
AE109 PENTHOUSE FLOOR PLANS
AE110 PENTHOUSE ROOF PLAN
AE400 TYPICAL AND ENLARGED PLANS
AE401 INTERIOR ELEVATIONS
AE402 PARTIAL BUILDING SECTIONS
AE403 INTERIOR ELEVATIONS
AE404 BUILDING SECTIONS
AE511 INTERIOR DETAILS
AE512 INTERIOR DETAILS
AE515 CASEWORK DETAILS
AE601 DOOR SCHEDULE
AE602 WINDOW ELEVATIONS AND TYPES
AE603 WINDOW DETAILS
INTERIOR
AF100 FOURTH FLOOR FINISH PLAN
AF500 THRESHOLD DETAILS
AF501 WALL PROTECTION / SIGNAGE TYPES
AF502 SIGNAGE TYPES CONSTRUCTION DETAILS
AF601 ROOM FINISHES SCHEDULE
AF602 INTERIOR MATERIALS LEGEND
EQUIPMENT
QH101 ENLARGED FOURTH FLOOR EQUIPMENT PLAN
QH102 ENLARGED EQUIPMENT PLANS
QH103 ENLARGED EQUIPMENT PLANS
QH601 EQUIPMENT SCHEDULE
PROJECT DESCRIPTION
THE PROJECT RENOVATES APPROXIMATELY 10,096 SQUARE FEET OF EXISTING FOURTH FLOOR INTERIOR SPACE FOR INPATIENT MENTAL HEALTH SERVICES. PROJECT CONSTRUCTS A NEW LAYOUT AND RENOVATION
FOR APPROXIMATELY 10,096 GROSS SQUARE FEET (GSF) OF LOCKED INPATIENT MENTAL HEALTH SPACE, WITH THE GOAL OF PROMOTING A SAFE AND RECOVERY-ORIENTED ENVIRONMENT. THE PROJECT CREATES A
NON-INSTITUTIONAL, HOME LIKE ENVIRONMENT WHILE IMPLEMENTING SAFETY AND ANTI-LIGATURE FEATURES.
TO SERVE THESE OBJECTIVES, THE PROJECT GUTS AND RENOVATES BUILDING 131 UNIT 4A. THE NEW DESIGN PROVIDES 16 NEW PATIENT BEDS, DISTRIBUTED AS 4 DOUBLE PATIENT ROOMS AND 8 SINGLE PATIENT
ROOMS. THIS PROJECT ALSO PROVIDES SECLUSION ROOM, DINING/GROUP ROOM, DAY ROOM, CONSULT/FAMILY ROOM, AND QUIET ROOM. STAFF SUPPORT SPACES INCLUDE CONFERENCE/TEAM ROOM, CLEAN UTILITY, AND SOILED UTILITY. TREATMENT ROOMS INCLUDE EXAM, INTERVIEW/TRIAGE, AND MEDS/NOURISHMENT ROOMS. THIS PROJECT FURNISHES APPROPRIATE NEW BUILDING UTILITY INFRASTRUCTURE TO ACCOMMODATE
INPATIENT AND CLINICAL NEEDS. THIS PROJECT ALSO INCLUDES REPLACING THE EXISTING MECHANICAL AIR HANDLER SERVING 4A, 3A, AND 2A.
LASTLY, THIS PROJECT PROVIDES NEW SECURITY INFRASTRUCTURE FOR THE EXISTING SALLY PORT, SO CARD READERS WILL OPEN THE SALLY PORT DOORS FROM 4A AND 4C NURSE STATIONS.
1. PRODUCTS TO BE FURNISHED BY VA AND INSTALLED BY GC:
A. SEE SHEET QH601 FOR COMPLETE LIST.
2. NAME BRAND OR EQUAL ITEMS TO BE FURNISHED AND INSTALLED BY GC.
A. THE DOOR SWITCH LIGATURE RESISTANT OVER-THE-DOOR ALARMS BY CAM-
DEX SECURITY CORPORATION.
B. WICKET DOORS: CECO MEDALLION BH-PRA
C. KENNON SOFT SUICIDE DOORS
D. YASKAWA VARIABLE FREQUENCY DRIVES
E. WHITEHALL LIGATURE RESISTANT CORTERRA™ BASIN ADA COMPLIANT
MODEL WH3775
F. INTERSAN BY AQUADESIGN MANUFACTURING CEILING SHOWER HEAD
G. WILLOUGHBY INDUSTRIES - BEHAVIORAL HEALTH PRODUCTS LIGATURE-
RESISTANT TOILET
H. FIRECLAY TILE RIPPLE
I. FIRECLAY TILE MAGNOLIA W/ BLACK PATINE
NAME BRAND OR EQUAL ITEMS:
SCHEDULE OF BID ITEMS
BID DEDUCT ALTERNATE 1: REMOVE INTERIOR RENOVATION WORK IN CONFERENCE ROOM/TEAM A406.
BID DEDUCT ALTERNATE 2: REMOVE INTERIOR RENOVATION WORK AND PLUMBING FIXTURE REPLACEMENTS IN TOILET VISITOR A407 AND TOILET STAFF A408B.
BID DEDUCT ALTERNATE 3: REMOVE INTERIOR RENOVATION WORK AND PLUMBING FIXTURES IN DINING/GROUP A436 AND CONSULT FAMILY A437.
2. NAME BRAND OR EQUAL ITEMS TO BE FURNISHED AND INSTALLED BY GC
(CONTINUED).
J. ALC CONTROLS
K. BELIMO VALVES AND ACTUATORS.
L. SIMPLEX 4100 SERIES FIRE ALARM
M. LENEL 2020 SYSTEMS PACS SYSTEM
N. LYNX PC BASED DURESS SYSTEM
O. ASCOM TELLIGENCE NURSE CALL
P. FLEXIMOUNTS A04 FULL MOTION ARTICULATING TV WALL MOUNT
BRACKET
Q. CENDREX PFI-HS.
43 41 I-94
I-94
LOT A
LOT B
LOT T
206 205
LOT D
GREEN HOMES
202 201
LOT J
LOT G
135LOT H
133CA
LOT C
133EF
XX = BUILDING NUMBER
N
S
W E
PROJECT
SITE
N
S
W E
COORDINATION OF MECHANICAL WORK:
ALL WORK PROVIDING TEMPORARY SERVICE TO THE SECOND AND THIRD FLOORS
MUST BE COMPLETE AND INSTALLED BEFORE DEMOLITION OF MECHANICAL
EQUIPMENT IN THE PENTHOUSE. ACTIVATION OF TEMPORARY AHU SERVICE TO
EXISTING MUST BE COORDINATED WITH COR BEFORE BEGINNING.
DURING AHU TRANSITIONS, A 4-HOUR MAXIMUM DURATION IS ALLOWED WHERE
BUILDING IS WITHOUT ACTIVE HVAC. TRANSITIONS MUST BE PERFORMED ON
WEEKENDS ONLY.
BID ITEM 1, BASE BID: THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TOOLS, LABOR, MATERIALS, EQUIPMENT, PERMITS, LICENSE, AND SUPERVISION FOR “RENOVATE BUILDING 131-4A WING" PROJECT NUMBER 556-17-002, LOCATED AT THE CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE CENTER (FHCC), NORTH CHICAGO, IL. IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. WORK INCLUDES, BUT IS NOT LIMITED TO, GENERAL DEMOLITION AND PREPARATION, CONSTRUCTION, PLUMBING, HVAC, AND ELECTRICAL.
3. OWNER FURNISHED AND INSTALLED NAME BRAND ITEMS REQUIRING GC
COORDINATION DURING CONSTRUCTION:
A. SMARTBOARD 7000R PRO SERIES
Revision Number Revisions: Date:
Jonathan Carr
Digitally signed by Jonathan Carr Date: 2021.09.17 17:28:45-04'00'
1' - 6"
CUBICLE CURTAIN OR
WALL EDGE WHERE
OCCURS
HAND SANITIZER
(WHERE OCCURS)
CLOCK
4"
T O
B T
M
4"
TIME ELAPSED
CLOCK
FIRE ALARM
PULL AT DOOR
F
TYPICAL SIGNAGE /
STROBE AT DOOR
4"
4" 7" 1' - 0"
TYPICAL LOCATION AT DOORDOMELIGHT
WALL MTD
TYPICAL NURSE CALL
DOMELIGHT CEILING
MTD
TACKBOARD
SURFACE MTD
MARKERBOARD
SURFACE MTD
HANGING BIN
SYSTEM
TYPICAL JANITOR CLOSET
SIDEWALL ELEVATION - 2
TYPICAL JANITOR CLOSET
Z0559
SIDEWALL ELEVATION - 2
ROD & SHELF
FLOORING BASE
REFER TO FINISH SCHEDULE
FOR TYPE AND HEIGHT
DEVICE PROXIMITY
GUIDELINES
ALIGN TOP OF CLOCK
WITH TOP OF DOOR
SHIFT DEVICES TOWARDS
DOOR FRAME WHERE ALL
DEVICES DO NOT OCCUR
ALIGN TOP OF ALL
DEVICES, TYP IN ALL
LOCATIONS
6" 6"
5" 5"
4" 4"
EQ EQ
3' - 0"
T O
P O
F T
A C
K B
O A
R D
3' - 0"
"TRACK SYSTEMS
SEE EQUIPMENT
DRAWINGS
6"
MOP RACK
2' - 4"
CHEMICAL DISPENSER
EYE WASH
MOP RACK
2' - 4"
4"
A C
C E
S S
IB
L E
CORNER GUARD
BASE
FINISH FLOOR
HIGH
MEDIUM
LOW
NOTE: ALIGN
LOW / HIGH DEVICES
AT CENTER LINE,
TYP. THROUGHOUT
WHERE DEVICES
ARE IN CLOSE
PROXIMITY
" EQ EQ
S
ID
E W
A L L
T O
P O
F M
A R
K E
R B
O A
R D
EQ EQ
4"
MIRROR
MIRROR
T
O G
L A
S S
TYP GRAB BAR
CENTER
ON LAV.
UNO
FOLD DOWN
SHOWER SEAT
SPECIMEN
PASS THRU - 200
FIRE EXTINGUISHER
CAB
FEC
T O
P O
F E
X T
IN
G
U
IS
H E
R
M A
X
CORNER OR
EDGE OF
WALL
1' - 10"
OR CENTER ON WALL
6' WIDE OR LESS
COAT HOOK
(AT DOOR)
TOWEL HOOKS
SURFACE MTD
COAT HOOK
SURFACE MTD
EQ EQ
APRON RACK
X3150
SURFACE
MTD
OTOSCOPE
M4200
SURFACE
MTD
TO ALIGN W SS
PNL @ SINKS
CONT
BLKG
NO ELEC, OUTLETS
WITHIN THE
DASHED
CLEARANCE AREA
1' - 3"
SPHYGMOMANOMETER
M4100
SURFACE MTD
GLOVE
DISPENSER
SURFACE MTD
HAND SANITIZER
NIC SURFACE MTD
PAPER TOWEL DISP
PTD-2, SURFACE MTD
BY OWNER
BABY CHANGING
STATION
RECESSED
PAPER TOWEL
DISP, PTD-1,
RECESSED
DISPENSER
OUTLET
RECEPTACL
E
HAND DRYER
HD-1
SURFACE MTD
SEAT COVER DISP, (SCD)
RECESSED
CENTER ON
TOILET
FIXTURE
SOAP DISH
SD-2, SURFACE MTD
BY OWNER
EQ EQ
SOAP DISH SHELF
RECESSED
SAN NAP RECEPTACLE
SN-1
SURFACE MTD
TOILET PAPER DISP
TPD-3
SURFACE MTD
1' - 7"
2' - 6" TO C OF CLOSEST WALL
FF
FF
FF
FF
FF
FF
SHARPS
DISPOSAL
SURFACE MTD
MARKER/TACK
BOARD
3' - 0"
SHOWER
HEAD/CONTROL
9"
1' - 3" 1' - 3" 6"
TYP TOILET AT FLIP UP
SCD, GB-FL, NC
(BACKWALL ELEVATION)
SEAT
COVER DISP
(WHERE
OCCURS)
M
IN
M A
X
EQ EQ
TYPICAL LAV
(SIDEWALL ELEVATION)
CLINICAL SINK
M
IN
M A
X
M
IN
MIN
8"
6" MAX
2' - 0"
PAPER
TOWEL
DISPENSER
REFER TO FINISH
SCHEDULE FOR
DECORATIVE FINISH
THICKNESS
ACCOUNTED FOR IN
CLEAR DIM.
M
IN
M A
X
1' - 3"
ALIGN BOTTOM OF
MIR, SD, AND PTD
REFER TO FIXTURE
SCHEDULE FOR LAV
TYPES AND DETAILS
SOAP DISPENSER
30" X 48" CLEAR
FLOOR SPACE
REQUIRED
TYPICAL LAV
MR, SD & PTD
(BACKWALL ELEVATION)
1' - 5"
THERMOSTAT AT
EDGE OF WALL OR
CORNER
UC LIGHT SWITCH
LOCATION AT SIDE
WALL
GENERAL WALL DEVICES
M A
X
S
U R
F A
C E
S
U R
F A
C E
4"
DOOR OPERATOR
PUSH PLATE
DR - OP - PSH
DOOR OPERATOR
CARD READER
DR - OP - CR
ELECTRICAL
PANEL
HANDRAIL
WHERE
OCCURS
CL CL
S/SA
E M
E R
G E
N C
Y
P O
W E
R O
F F
D U
P L E
X
F
IR
E A
L A
R M
P U
L L
T H
E R
M O
S T
A T
/T H
E R
M
IS
T O
R
S W
IT
C
H
D O
U B
L E
S W
IT
C
H
W A
L L P
H O
N E
W A
L L P
H O
N E
J A
C K
WALL CABINETS
ALIGN
BASE
CABINETS
D U
P L E
X
Q U
A D
V O
IC
E
D
A T
A
V
R E
C E
P T
A C
L E
S W
IT
C
H
D U
P L E
X
Q U
A D
V O
IC
E
D
A T
A
S W
IT
C
H
D U
P L E
X
Q U
A D
V O
IC
E
D
A T
A
V
R E
C E
P T
A C
L E
C A
B L E
B E
D
F
IR
E H
O R
N
4"
6"
FF
GENERAL WALL DEVICES
AT WORK SURFACE
NURSE CALL DEVICES
ES
ET
P A
T
IE
N T
T O
IL
E
T
S
A T
IO
N
NP BS
B E
D S
T A
T U
S
P A
T
IE
N T
S
T A
F F
A
S
IS
T
J
A C
K S
T A
T
IO
N
D U
T Y
S T
A T
IO
N
P A
T
IE
N
H O
W
R
A T
IO
N
1' - 7"
TYP HC TOILET DEVICES
TPD & SN
(SIDEWALL ELEVATION)
S
ID
E W
A L L
1' - 0" 2' - 0"
TYP HC TOILET DEVICES
SCD & GB
(BACKWALL ELEVATION)
T V
D U
P L E
X
D
T A
C
A B
L E
D U
C T
S M
O K
T E
C T
IN
IC
A T
L
M P
T O
B T
M
ND
SCHEDULED CEILING
SCHEDULED
WALL FINISH
TOILET PARTITION
(WHERE OCCURS)
TPD
SANITARY NAPKIN
DISPENSER
(WMS ONLY)
ALIGN
SCHEDULED CEILING
SCHEDULED
WALL FINISH
TOILET
PARTITION
LINE OF WALL'S FINISHED
FACE, REFER TO FINISH
SCHEDULE FOR
DECORATIVE FINISH
THICKNESS ACCOUNTED
FOR
IN CLEAR DIMENSION
REFER TO TOILET
ACCESSORIES
SCHEDULE FOR
MIRROR TYPES
NURSE CALL
SEAT
COVER
DISPENSER
(WHERE
OCCURS)
CEILING
L
CONTINUOUS
BLOCKING
CONTINUOUS
BLOCKING
CONTINUOUS
BLOCKING
CONTINUOUS
BLOCKING,
TYPICAL.
SCHEDULED CEILING
1' - 7"
WATER FOUNTAIN
M A
X
BOTTLE FILLING
STATION, AS
REQUIRED
" 3
SHOWER HEAD IN CEILING
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
NORTH LEGEND
PLAN
NORTH
TRUE
NORTH
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
KEY PLAN
RENOVATION
AREA
BUILDING 131 - 4TH FLOOR
A B C
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:1
P
M
556-17-002
GI002
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGEQUIPMENT MOUNTING LEGEND
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
1/4" = 1'-0" F1
EQUIPMENT MOUNTING LEGEND
2'0 4' 8'
1. FOR FINISH PLANS REFER TO AF100 SERIES SHEETS. FOR
WALL PROTECTION TYPES AND CORNER GUARDS SEE
SHEET AF501.
2. FOR TOILET ACCESSORIES, REFER TO QH100 SERIES
SHEETS, AND QH601 SHEETS.
3. FOR LOCATIONS / TYPES OF NURSE CALL DEVICES AND
RELATED EQUIPMENT SEE EY100 SERIES SHEETS .
4. TYPICAL MOUNTING HEIGHTS: MOUNT ITEMS AT HEIGHTS
ABOVE FLOOR LEVELS AS SHOWN ON THIS SHEET,
UNLESS OTHERWISE NOTED ON INTERIOR ELEVATIONS
OR OTHER DRAWINGS. NOTIFY ARCHITECT OF POTENTIAL
CONFLICTS PRIOR TO PURCHASE OR INSTALLATION.
5. FIRE RATED PARTITIONS: WHERE ITEMS ARE RECESSED
INTO FIRE RATED PARTITIONS, PROVIDE CONTINUOUS
FIRE-RATED CONSTRUCTION BEHIND AND ALL AROUND
ITEMS.
6. WHERE MANUAL FLUSH VALVE IS INSTALLED FOR TOILET,
MOUNT THE FLOW CONTROL TO THE OPEN SIDE OF THE
STALL OR TOILET ROOM.
GENERAL SHEET NOTES
Revision Number Revisions: Date:
Jonathan Carr
Digitally signed by Jonathan Carr
17:28:46-04'00'
SIZE OF CIRCULAR WHEELCHAIR
TURNING SPACE
5' - 0"
1' - 0" 3' - 0" 1' - 0"
" 5
5' - 0"
12" MIN
M A
X
M
IN
M A
X
MIN.
3' - 0"
MIN
2' - 8"
CLEAR WIDTH OF AN
ACCESSIBLE ROUTE CLEAR WIDTH AT TURN
M
IN
3' - 6" MIN
X<48"
X 3' - 6" MIN
12" MIN
M A
X
A
F F
12" MIN
12" MIN
M
IN
C L
E A
R
MIN
6"
M A
X
CLEARANCE
6" MAX TOE
C L E
A R
A N
C E
M A
X T
O E
MIN CLEAR
36"
A
F F
2" CLEAR
A
F F
36"
3' - 6"5' - 0"
M
IN
2' - 6" MIN
4' - 0"
5' - 0" MIN
M
IN
M
IN
3' - 0" MIN
M
IN
5' - 0" MIN
MIN CLEAR
36"
A
F F
MIN CLEAR
3' - 0"
3' - 9"
C U
R B
A
F F
A
F F
3' - 6"
A
F F
MIN CLEAR
36"
CLEAR
2"
1 - 1/4 MIN. - 2" MAX 2 1/4" MIN.
66" MIN
M
IN
4" MAX
M
IN
16" - 18"
66" MIN
M
IN
4" MAX
M
IN
16" - 18"
M
IN
18" MIN
2' - 8" MIN
.0
0°
2' - 8" MIN 2' - 8" MIN
3' - 0"
1' - 0" MIN
M
IN
36" MIN 5
M
IN
42" MIN
2' - 6" MIN
M
IN 1
T O
S P
R O
U T
M A
X
5' - 0"
X
4"
X
X
M A
X
X
M A
X
X > 12"
M
IN
X > 12"
M
IN
M A
X
20" MAX
M A
X
M A
X
M A
X
M A
X
20" - 25"
M A
X
M
IN
10" MAX 3
M A
X
M A
X
24" MAX
M A
X
M A
X
M
IN
24" MIN
M
IN
24" MIN
M
IN
22" MIN 24" MIN5
M
IN
24" MIN
M
IN
M A
X
M A
X
4' - 0" 4' - 0"
MAX
1' - 0"
MAX
1' - 0"
M
IN
M
IN
18" 18"
42" MIN
16" 16"
32" MIN
M
IN
M A
X
1' - 4"
SIZE OF T - SHAPE WHEELCHAIR
TURNING SPACE
FORWARD APPROACH CLEAR
FLOOR SPACE
PARALLEL APPROACH CLEAR
FLOOR SPACE
PASSING SPACE
MANEUVERING CLEARANCE FOR A
FORWARD APPROACH TO AN ALCOVE
MANEUVERING CLEARANCE FOR A
PARALLEL APPROACH TO AN ALCOVE
LIMITS OF PROTRUDING OBJECTS REDUCED VERTICAL CLEARANCE
SINGLE POST - MOUNTED
PROTRUDING OBJECT
MULTIPLE POST - MOUNTED
PROTRUDING OBJECT
UNOBSTRUCTED
FORWARD REACH
UNOBSTRUCTED
SIDE REACH
20" MAX OBSTRUCTED
HIGH FORWARD REACH
10" MAX OBSTRUCTED
HIGH SIDE REACH
20" -25" MAX OBSTRUCTED
HIGH FORWARD REACH
24" MAX OBSTRUCTED
HIGH SIDE REACH
CLEAR WIDTH OF
HINGED DOOR
CLEAR WIDTH OF
SLIDING DOOR
FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE
* NOTE: WHERE CLOSER AND LATCH ARE
PROVIDED
HINGE APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE
LATCH APPROACH, PUSH SIDE W/
CLOSER LATCH APPROACH, PULL SIDE
HINGE APPROACH W/ LATCH
CLOSER W/ LATCH CLOSER
LATCH APPROACH, PUSH SIDE LOCATION OF VISION PANEL
HARDWARE
TWO DOORS IN SERIES TWO DOORS IN SERIES
DRINKING FOUNTAIN SPOUT
LOCATION: FORWARD
APPROACH
DRINKING FOUNTAIN SPOUT
LOCATION: PARALLEL
APPROACH
CLEARANCES FOR
AMBULATORY ACCESSIBLE
WATER CLOSET
CLEARANCES FOR
STANDARD
WATER CLOSET
CLEARANCES FOR
ACCESSIBLE
URINALS
CLEARANCES FOR WALL - HUNG
WHEELCHAIR ACCESSIBLE
WATER CLOSET
CLEARANCES FOR FLOOR -
MOUNTED WHEELCHAIR
ACCESSIBLE WATER CLOSET
TOILET COMPARTMENT
TOE CLEARANCE
TOE CLEARANCES FOR WALL- HUNG
WHEELCHAIR ACCESSIBLE WATER CLOSET
TOP / BOTTOM HANDRAIL EXTENSIONS,
AND HEIGHT AT EXTERIOR STAIRS
TOP / BOTTOM HANDRAIL EXTENSIONS,
AND HEIGHT AT EXTERIOR RAMPS
HANDRAIL CLEARANCE AND CROSS SECTION
16" 16"
32" MIN
F.F.
CLEAR
2"
MIN CLEAR
36"
A
F F
36"
2" CLEAR
A F
F
C L E
A R
M A
X
A
F F
M A
X
CLEAR WIDTH OF
FOLDING DOOR
12" + T
3' - 0" 1' - 0"
1' - 0" 4' - 0"
TURNING SPACE
17" MIN 6" MAX
M A
X
C L E
A R
M
IN
M A
X
MIN
11"
17" - 25"
M
IN
8" MIN
TOE CLEARANCE KNEE CLEARANCE
M
IN
M
IN
ADA SINK APRONADA SINK APRON
NOT DRAWN TO SCALE (N.T.S.)
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
LIFE SAFETY LEGEND
NORTH LEGEND
PLAN
NORTH
TRUE
NORTH
EXISTING PARTITION /
BARRIER - WALL TO REMAIN
EXISTING PARTITION /
BARRIER - WALL TO BE
REMOVED
NEW PARTITION / BARRIER - WALL
PARTITION LEGEND
NO RATING
SMOKE RESISTIVE PARTITION - NON RATED
1 HOUR FIRE BARRIER
1 HOUR FIRE/SMOKE BARRIER
2 HOUR FIRE BARRIER
2 HOUR FIRE/ SMOKE BARRIER
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
KEY PLAN
RENOVATION
AREA
BUILDING 131 - 4TH FLOOR
A B C
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:1
P
M
556-17-002
GI003
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGACCESSIBILITY LEGEND
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
1/4" = 1'-0" F3
ACCESSIBILITY LEGEND
GENERAL SHEET NOTES
1. ALL ACCESSIBILITY DETAILS COMPLY WITH FEDERAL
ABAAS AND THE VA BARRIER FREE DESIGN GUIDE,
PG-18-13.
2. DETAILS ARE PROVIDED FOR REFERENCE ONLY. THESE
DETAILS SHOW MINIMUM REQUIREMENTS. REFER TO
ARCHITECTURAL DRAWINGS FOR ACTUAL DIMENSIONS.
WHERE NOTHING IS INDICATED ON OTHER DRAWINGS,
GC IS TO REFER TO THESE DETAILS.
3. ADDITIONAL REQUIREMENTS ARE SHOWN ON OTHER
SHEETS IN CONSTRUCTION DOCUMENTS, THIS SHEET
DOES NOT REPRESENT ALL REQUIREMENTS.
4. NOTIFY ARCHITECT OF CONFLICTS BETWEEN THIS
SHEET AND OTHER SHEETS.
5. REINFORCING SHALL BE PROVIDED AND INSTALLED AT
ALL WALL MOUNTED EQUIPMENT PER WALL BACKING
DETAILS.
2'0 4' 8'
Revision Number Revisions: Date:
Jonathan Carr
Digitally signed by Jonathan Carr
17:28:46-04'00'
EXIT SEPARATION: 105'-1"
APPLICABLE CODES IN ORDER OF PRECEDENCE:
VETERANS AFFAIRS "FIRE PROTECTION DESIGN MANUAL"
NFC CODES CURRENT ADDITIONS
OCCUPANCY CLASSIFICATION:
MAIN USE: NEW HEALTHCARE,
NFPA 101 CHAPTER 18.
SECONDARY USES: N/A
HIGH-RISE / NOT HIGH-RISE: NOT HIGH-RISE ( 3.3.36.7 )
NO. OF STORIES ( EXISTING / RENOVATE / PERMITTED ):
CONSTRUCTION TYPE LIMITATIONS: NFPA 101 TABLE 18.1.6.1
BUILDING HEIGHT (FT) LIMITATIONS ( PROPOSED / PERMITTED ): >NO CHANGE / 4
STORIES / UNLIMITED
MINIMUM CONSTRUCTION CLASSIFICATION,
RELEVANT FIRE RESISTANCE RATINGS PER NFPA TABLE A.8.2.1.2:
FIRE SEPARATION DISTANCE > 30'-0"
CONSTRUCTION ELEMENT
REQUIRED RATING
UL DESIGNPER CLASSIFICATION
NOTED ABOVE (IF APPLICABLE)
EXTERIOR NON-BEARING WALLS 0
BEAMS, GIRDERS, TRUSSES, AND ARCHES 2
[SUPPORTING MORE THAN ONE FLOOR]
COLUMNS [SUPPORTING MORE THAN ONE
FLOOR]
MAX. PERMITTED AREA
RENOVATION TOTAL
AUTOMATIC QUICK RESPONSE HEAD SPRINKLERS THROUGHOUT: YES
PER VA FIRE PROTECTION DESIGN MANUAL (2018, P.23 (K)), SEE FIRE PROTECTION
DRAWINGS FOR FURTHER CLARIFICATION
NFPA 101 (2018) 18.3.7.1 - MAX SMOKE COMPARTMENT PERMITTED = 22,500 SQFT
NFPA 101 (2018) 18.3.7.1 - MAX TRAVEL DISTANCE WITHIN SMOKE BARRIER = 200 FT
COMMON PATH OF TRAVEL 75 FT MAX
STANDPIPE SYSTEM: NO
SEPARATION OF USES: NO (INCIDENTAL USE OCCUPANCIES)
AREA INCREASE DUE TO OPEN SPACE: N/A
AREA INCREASE FOR SPRINKLER SYSTEM: N/A
FLOOR AREA (SF) LARGEST FLOOR ( PROPOSED / PERMITTED BY CONSTRUCTION TYPE):
UL
TOTAL PERMITTED FLOOR AREA WITH AREA INCREASES: N/A
ELECTRICAL SUPERVISION OF AUTOMATIC SPRINKLER SYSTEMS:
YES ( 9.7.2 )
ELECTRICAL SUPERVISION OF BUILDING ALARM AND FIRE DETECTION DEVICES:
YES ( 9.6.2 )
FIRE DEPARTMENT NOTIFICATION VIA APPROVED MONITORING OF FIRE SUPPRESSION,
DEECTION AND ALARM DEVICES: YES ( 9.6.4 )
FIRE ALARM SYSTEM SOUNDS AN AUDIBLE AND VISIBLE ALARM IN A CONSTANTLY ATTENDED
RECEIVING STATION WITHIN ADJACENT BUILDING 1 (ON CAMPUS): YES (9.6.7 )
BUILDING FIRE COMMAND CENTER: NO
SEISMIC AND WIND LOADING:
PER VA H-18-8 SEISMIC DESIGN MANUAL, P. 15 - SEISMIC BRACING IS REQUIRED (HIGH
SEISMICALLY ACTIVE ZONE).
OCCUPANCY CALCULATION
EXISTING SMOKE COMPARTMENT ZONE 4A
(RENOVATED AREA)
7,320 SQFT
PER NFPA 101 2018 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
NEW HEALTHCARE 120 SQFT / PERSON
TOTAL AREA / SQFT
PER PERSON
7,320 SQFT / 120 SQFT /
PERSON = 61 OCCUPANTS
BASED ON THE OCCUPANT LOAD CALCULATIONS BELOW THE COMBINED OCCUPANT LOAD
CAN SAFELY EGRESS OUT ANY EGRESS COMPONENT AS SHOWN.
GENERAL FIRE PROTECTION NOTES:
1. THE VETERANS AFFAIRS "FIRE PROTECTION DESIGN MANUAL" REQUIRES THE
FOLLOWING:
- THE FIRE PROTECTION DESIGN IS TO BE BASED ON THE LATEST EDITIONS OF THE
NATIONAL FIRE CODES (NFC) AT THE DATE OF AWARD OF THE CONTRACT TO THE
ARCHITECTURAL / ENGINEERING FIRM. 2018 NFPA 101 LIFE SAFETY CODE IS
IMPLEMENTED.
- FIRE PROTECTION FEATURES NOT ADDRESSED BY THE NFC ARE TO BE DESIGNED TO
COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE (IBC). 2018
IBC IS IMPLEMENTED.
BUILDING 131: CODE SUMMARY
TYPE 1A (3-3-2) FULLY SPRINKLERED
INTERIOR NON-BEARING WALLS 0
FLOOR / CEILING ASSEMBLIES 2
ROOF / CEILING ASSEMBLIES 1 1/2
NO CHANGE - ADDITION TO MATCH EXISTING BUILDING HEIGHT
RENOVATION AREA + EXISTING TO REMAIN =
8,536 + 08,536 GSF =
NO CHANGE TO EXISTING SMOKE
COMPARTMENT BOUNDARIES, TOTAL (NSF)
TOTAL NUMBER OF OCCUPANTS PER ZONE
ZONE 4A ZONE 4B 7,320 SQFT 61 OCCUPANTS
NET SQUARE
FOOTAGE (NSF)
NFPA 101 (2018) 18.2.5.2 - DEAD END CORRIDOR 30 FT MAX
ZONE 4A 7,344 SQFT
ZONE 4B 1,216 SQFT
RENOVATION AREA
UNLIMITED
6 STORIES
IBC GROUP I-2
EXISTING SMOKE COMPARTMENT ZONE 4B
991 SQFT +
225 SQFT
EXISTING SMOKE COMPARTMENT ZONE 4B
(RENOVATED AREA) [WITHIN 4B NO CHANGE]
7,344 SQFT 7,344 SQFT / 120 SQFT /
PERSON = 62 OCCUPANTS
7,344 SQFT 62 OCCUPANTS
COLUMNS [SUPPORTING ONE FLOOR] 2
PATIENT ROOM
A414
BRNP1
TOILET
A414A
TSPM1
TOILET
A415A
TSPM1
PATIENT ROOM
A415
BRNP1
PATIENT ROOM
A412
BRNP1
CORRIDOR
C4-4
TOILET
A411A
TSPM1
PATIENT ROOM
A411
BRNP1
INTER/TRIA
A410
OFDC2
MEDS/NOUR
A409
MEDP1
NURSE STA & WORK
A408
NSTA1 / WRCH1
TLT VISITOR
A407
TNPG1
TLT STAFF
A408B
TNPG1
CONF/TEAM
A406
CFR02
CLEAN UT
A417
UCCL1
EXAM
A416
EXRG3
PATIENT ROOM
A418
BRNP2
TOILET
A418A
TSPM1
TOILET
A419A
TSPM1
PATIENT ROOM
A419
BRNP2
SOILED / SOILED LINEN
A420
USCL1 / UTLC1
PATIENT ROOM
A421
BRNP2
TOILET
A421A
TSPM1
TOILET
A423A
TSPM1
STOR
A422
SRSE1
PATIENT ROOM
A423
BRNP2
SECLUSION
A424
BRNP5
SEC TLT
A424B
TSPM1
SEC ANTE
A424A
BRNP6
STAIR NO.
C4-5A
HAC
A425
JANC1
LAUN
A432
NULR1
ELECTRICAL
A431
CLOSET
A433
PATIENT ROOM
A430
BRNP1
TOILET
A430A
TSPM1
TOILET
A429A
TSPM1
PATIENT ROOM
A429
BRNP1
PATIENT ROOM
A427
BRNP1
TOILET
A427A
TSPM1
TOILET
A426A
TSPM1
PATIENT ROOM
A426
BRNP1
QUIET ROOM
A434
OFDC2
DAY ROOM
A435
DAYR1
TV CLOSET
A435A
DINING/GROUP
A436
FSCD1 / OPMH1
CONSULT FAMILY
A437
OFDC2
CLEAN LINEN
A428
LCCL1
CORRIDOR
C4-5
STOR RM
A413
SRS01
TOILET
A412A
TSPM1
UNIT CLERK
A467B
SERVICE LOBBY
A438
PROJECT LIMITS
PROJECT LIMITS
P R
O J
E C
T L
IM
IT
S
P R
O J
E C
T L
IM
IT
S
CAPACITY
FACTOR
ACTUAL CAPACITY
CLEAR
WIDTH (IN.)
0.234
CAPACITY
FACTOR
ACTUAL CAPACITY
CLEAR
WIDTH (IN.)
0.288
BOTTLE FILLING
STATION
CORRIDOR
C4-6
1 5 8 10 11 13 17122 4 6 7 9 1414.7.6.4.
D
E
L
N
O
G
I
J
M e
F
EXISTING - EXIT SIGN - LIT FACES
INDICATED BY SHADING
NEW - FIRE EXTINGUISHER
CABINET LOCATION
EGRESS TRAVEL PATH
TD: TRAVEL DISTANCE
CPOT: COMMON PATH OF TRAVEL DISTANCE
EXISTING - FIRE EXTINGUISHER
CABINET LOCATION
INDICATES AREA NOT IN
SCOPE OF WORK
NEW - EXIT SIGN - LIT FACES
INDICATED BY SHADING
CAPACITY
FACTOR
ACTUAL CAPACITY
CLEAR
WIDTH (IN.)
0.288
EGRESS CAPACITY CALCULATION
CLEAR WIDTH
CAPACITY FACTOR
NUMBER OF OCCUPANTS
NFPA 1 –FIRE CODE, 2018 EDITION
NFPA 10 – PORTABLE FIRE EXTINGUISHERS, 2018 EDITION
NFPA 13 – STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
NFPA 14 - STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2019 EDITION NFPA 20 - STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION, 2019 EDITION
NFPA 54 - NATIONAL FUEL GAS CODE, 2018 EDITION
NFPA 70 – NATIONAL ELECTRICAL CODE, 2020 EDITION
NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION
NFPA 80 - STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, 2019 EDITION
NFPA 90A - STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2018 EDITION NFPA 90B - STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING SYSTEMS, 2018 EDITION NFPA 96 - STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, 2017 EDITION
NFPA 99 - HEALTH CARE FACILITIES CODE, 2018 EDITION
NFPA 101 - LIFE SAFETY CODE, 2018 EDITION
NFPA 105 - STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER OPENING PROTECTIVES, 2019 EDITION
NFPA 110 - STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS, 2019 EDITION
NFPA 241 - STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, 2019 EDITION ASHRAE 90.1 - ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS, 2016 EDITION
ASHRAE 170 - VENTILATION OF HEALTH CARE FACILITIES, 2017 EDITION
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
LIFE SAFETY LEGEND
NORTH LEGEND
PLAN
NORTH
TRUE
NORTH
EXISTING PARTITION /
BARRIER - WALL TO REMAIN
EXISTING PARTITION /
BARRIER - WALL TO BE
REMOVED
NEW PARTITION / BARRIER - WALL
PARTITION LEGEND
NO RATING
SMOKE RESISTIVE PARTITION - NON RATED
1 HOUR FIRE BARRIER
1 HOUR FIRE/SMOKE BARRIER
2 HOUR FIRE BARRIER
2 HOUR FIRE/ SMOKE BARRIER
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
KEY PLAN
RENOVATION
AREA
BUILDING 131 - 4TH FLOOR
A B C
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:1
P
M
556-17-002
GI101
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGFOURTH FLOOR LIFE SAFETY PLAN
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
1/8" = 1'-0" F1
FOURTH FLOOR LIFE SAFETY PLAN
GENERAL SHEET NOTES
A. FOR GENERAL PROJECT NOTES, SEE SHEET AI001.
2'0 4' 8'
SYMBOLS LEGEND
EXISTING CONCRETE
EXISTING CONCRETE
EXISTING CONCRETE
EXISTING CONCRETE
EXISTING CONCRETE
APPLICABLE CODES
2. PENTHOUSE STEEL STRUCTURE (COLUMNS, BEAMS, AND DECK) IS 2-HOUR PROTECTED
STEEL. WHERE FIREPROOFING IS DISTURBED DURING NEW CONSTRUCTION ACTIVITIES,
REPAIR FIREPROOFING WITH LIKE AND COMPATIBLE MATERIAL. USE UL P701 AND X854 AS
BASIS OF DESIGN FOR REPAIRING STEEL FIREPROOFING.
SEE NOTE BELOW
FOR PENTHOUSE
Revision Number Revisions: Date:
YES
6 STORIES, 1 RENOVATED
Jonathan Carr
Digitally signed by Jonathan Carr
17:28:47-04'00'
PATIENT ROOM
A414
TOILET
A414A
TOILET
A415A
PATIENT ROOM
A415
PATIENT ROOM
A412
CORRIDOR
C4-4
TOILET
A411A
PATIENT ROOM
A411
INTER/TRIA
A410 MEDS/NOUR
A409
NURSE STA & WORK
A408
TLT VISITOR
A407
TLT STAFF
A408B
CONF/TEAM
A406
CLEAN UT
A417
EXAM
A416
PATIENT ROOM
A418
TOILET
A418A
TOILET
A419A
PATIENT ROOM
A419
SOILED / SOILED LINEN
A420
PATIENT ROOM
A421
TOILET
A421A
TOILET
A423A
STOR
A422
PATIENT ROOM
A423
SECLUSION
A424
SEC TLT
A424B SEC ANTE
A424A
STAIR NO.
C4-5A
HAC
A425
LAUN
A432
ELECTRICAL
A431
CLOSET
A433
PATIENT ROOM
A430
TOILET
A430A
TOILET
A429A
PATIENT ROOM
A429
PATIENT ROOM
A427
TOILET
A427A
TOILET
A426A
PATIENT ROOM
A426
QUIET ROOM
A434
DAY ROOM
A435
TV CLOSET
A435A
DINING/GROUP
A436
CONSULT FAMILY
A437
CLEAN LINEN
A428
CORRIDOR
C4-5
CORRIDOR
C4-3
STOR RM
A413
TOILET
A412A
UNIT CLERK
A467B
SERVICE LOBBY
A438
PROJECT LIMITS
PROJECT LIMITS
P R
O J
E C
T L
IM
IT
S
P R
O J
E C
T L
IM
IT
S
ALC CC
A408A
CORRIDOR
C4-6
02.60
02.61
02.61
02.62
02.62
GI201
F2
GI201
F5
GI201
F8
1 5 8 10 11 13 17122 4 6 7 9 1414.7.6.4.
D
E
L
N
G
I
J
M e
F
BID DEDUCT 1BID DEDUCT 2
BID DEDUCT 3
AE403 F2
AE403
F4
F6
GI201
D8
GI201
D2
GI201
D5
AE401F4
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
LIFE SAFETY LEGEND
NORTH LEGEND
PLAN
NORTH
TRUE
NORTH
EXISTING PARTITION /
BARRIER - WALL TO REMAIN
EXISTING PARTITION /
BARRIER - WALL TO BE
REMOVED
NEW PARTITION / BARRIER - WALL
PARTITION LEGEND
NO RATING
SMOKE RESISTIVE PARTITION - NON RATED
1 HOUR FIRE BARRIER
1 HOUR FIRE/SMOKE BARRIER
2 HOUR FIRE BARRIER
2 HOUR FIRE/ SMOKE BARRIER
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
KEY PLAN
RENOVATION
AREA
BUILDING 131 - 4TH FLOOR
A B C
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:2
P
M
556-17-002
GI200
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGBID DEDUCT ALTERNATES
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
1/8" = 1'-0" F2
BID DEDUCT ALTERNATES
4'0 8' 16'
- SHEET KEYNOTES
GENERAL SHEET NOTES
02.60 DEDUCT ALTERNATE 1: REMOVE INTERIOR RENOVATION
WORK IN CONFERENCE / TEAM ROOM A406 AND ASSOCIATED
WORK.
02.61 DEDUCT ALTERNATE 2: REMOVE INTERIOR RENOVATION
WORK AND PLUMBING FIXTURE REPLACEMENTS IN TOILET
VISITOR A407 AND TOILET STAFF A408B.
02.62 DEDUCT ALTERNATE 3: REMOVE INTERIOR RENOVATION
WORK IN DINING / GROUP ROOM A436, CONSULT FAMILY A437
AND PLUMBING FIXTURE.
A. FOR GENERAL NOTES AND SYMBOLS LEGENDS SEE SHEET
AI001.
Revision Number Revisions: Date:
Jonathan Carr
Digitally signed by Jonathan Carr
17:28:47-04'00'
DINING/GROUP
A436
CONSULT FAMILY
A437
02.62
02.62
10 11 1312
G
I
F
IF DEDUCT ALTERNATE 3 IS
TAKEN, REMOVE TEMPORARY
ANTE ROOM WALLS AT
COMPLETION OF WORK.
RETURN FLOOR, WALL, AND
CEILING FINISHES TO ORIGINAL
STATE AND CLEAN BEFORE
FINAL INSPECTION.
DEDUCT ALTERNATE #3
AE403 F2
AE403
F4
F6
TLT VISITOR
A407
TLT STAFF
A408B
02.61
02.61
DEDUCT ALTERNATE #2
L
J
CONF/TEAM
A406
02.60
DEDUCT ALTERNATE #1
DINING/GROUP
A436
10 11 12
L
I
J
EXISTING DOORS TO BE
DEMOLISHED AND INFILLED
WITH STUDS AND WALL BOARD
TO FLUSH WITH ADJACENT
SURFACE. INTERIOR FINISHES
TO REMAIN AS EXISTING. PAINT
BOTH SIDES OF WALL ALONG
COLUMN LINE "J" AND BETWEEN
COLUMN LINES "11" AND "12".
REPLACE WALL BASE ON BOTH
SIDES OF NORTH WALL.
THIS WALL AND ITS FINISHES
REMAIN AS NEW CONSTRUCTION
IF DEDUCT 1 IS ACCEPTED.
INSTALL NEW ACT RUNNER
ALONG THIS WALL.
10 11 12
L
J
DEDUCT ALTERNATE 1:
NO WORK IN THIS AREA
DEMOLITION AND REMOVAL OF
EXISTING DOORS REMAIN IN
BASE BID AND ARE NOT PART
OF DEDUCT ALTERNATE 1.
GROUP ROOM
L
J
VISITOR TOILET
STAFF TOILET
417R
IF DEDUCT ALTERNATE 2 IS
TAKEN, PROTECT DOORS,
FIXTURES, AND FINISHES
DURING CONSTRUCTION.THIS WALL FACE IS
EXCLUDED FROM
DEDUCT. INSTALL NEW
FINISHES ON THIS WALL
FACE, AS REQUIRED BY
BASE BID.
THIS WALL FACE IS
EXCLUDED FROM DEDUCT.
INSTALL NEW FINISHES ON
THIS WALL FACE, AS
REQUIRED BY BASE BID.
02.78
10 11 1312
G
I
F
PROTECT EXISTING MURAL
DURING CONSTRUCTION
INSTALL TEMPORARY
PROTECTION BOARD ON
EXISTING FLOORING
DINING
A436
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED DRAWN
DRAWING TITLE
APPROVED
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
LIFE SAFETY LEGEND
NORTH LEGEND
PLAN
NORTH
TRUE
NORTH
EXISTING PARTITION /
BARRIER - WALL TO REMAIN
EXISTING PARTITION /
BARRIER - WALL TO BE
REMOVED
NEW PARTITION / BARRIER - WALL
PARTITION LEGEND
NO RATING
SMOKE RESISTIVE PARTITION - NON RATED
1 HOUR FIRE BARRIER
1 HOUR FIRE/SMOKE BARRIER
2 HOUR FIRE BARRIER
2 HOUR FIRE/ SMOKE BARRIER
HARRELL DESIGN GROUP PC
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
704-814-1346
POC: LEE HARRELL PE, LEED AP, QCxP
PRESIDENT
KEY PLAN
RENOVATION
AREA
BUILDING 131 - 4TH FLOOR
A B C
COPYRIGHT © 2021
h d g fs s v r\
U s e rF o ld e rR e d ir e c ts
\k b e n to n \D o c u m e n ts \R e v it
B a c k u p \1
A R
C H k b e n to n h a rr e lld g .c o m
.r v t
/1
/2
:1
:2
P
M
556-17-002
GI201
DWJCSEPTEMBER 17, 2021
CAPTAIN JAMES A. LOVELL FEDERAL HEALTH CARE
CENTER (FHCC)
RENOVATE BUILDING 131-4A WINGBID DEDUCT ALTERNATE PLANS
CONSTRUCTION
DOCUMENTS 100%
HDG PROJECT: 19030
1/8" = 1'-0" F8
BID DEDUCT ALTERNATE 3 NEW
WORK PLAN
1/8" = 1'-0" F5
BID DEDUCT ALTERNATE 2 NEW
WORK PLAN
1/8" = 1'-0" F2
BID DEDUCT ALTERNATE 1 NEW
WORK PLAN
1/8" = 1'-0" D2
BID DEDUCT ALTERNATE 1
DEMOLITION PLAN
1/8" = 1'-0" D5
BID DEDUCT ALTERNATE 2
DEMOLITION PLAN
1/8" = 1'-0" D8
BID DEDUCT ALTERNATE 3
DEMOLITION PLAN
4'0 8' 16'
4'0 8' 16'
4'0 8' 16'
4'0 8' 16'
4'0 8' 16'
4'0 8' 16'
- SHEET KEYNOTES
GENERAL SHEET NOTES
02.60 DEDUCT ALTERNATE 1: REMOVE INTERIOR RENOVATION
WORK IN CONFERENCE / TEAM ROOM A406 AND ASSOCIATED
WORK.
02.61 DEDUCT ALTERNATE 2: REMOVE INTERIOR RENOVATION
WORK AND PLUMBING FIXTURE REPLACEMENTS IN TOILET
VISITOR A407 AND TOILET STAFF A408B.
02.62 DEDUCT ALTERNATE 3: REMOVE INTERIOR RENOVATION
WORK IN DINING / GROUP ROOM A436, CONSULT FAMILY A437
AND PLUMBING FIXTURE.
02.78 SEE DEMOLITION PLAN SHEET AD052 FOR EXTENTS OUTSIDE
OF ALTERNATE LIMITS.
NOTES:
1. EXISTING CEILING AND APPURTENANCES REMAIN.
2. ON NORTH WALL ALONG CENTERLINE J BETWEEN
CENTERLINES 11 AND 12, INSTALL NEW SWITCHES
AND POWER AS INDICATED ON ELECTRICAL
DRAWINGS. THE NORTH WALL IS EXCLUDED FROM
DEDUCTALTERNATE 1.
3. CONNECT NEW SWITCHES TO EXISTING DEVICES IN
EXISTING CEILING IN ROOM A406.
A. WHERE EXISTING FINISHES REMAIN, PROTECT EXISTING
FINISHES DURING CONSTRUCTION. USE TEMPORARY
PROTECTION BOARD ON FLOORING.
EXISTING CEILING TO REMAIN NEW CEILING
EXISTING CEILING
TO REMAIN
NEW CEILING
Revision Number Revisions: Date:
Jonathan Carr
Digitally signed by Jonathan Carr
17:28:48-04'00'
SCHEDULED PARTITION
WALL AND FINISH
VARIES
SCHEDULED TILE, SEAL POROUS
TILE, AND GROUT (SEE
MANUFACTURER'S INSTRUCTIONS)
5/8" GYPSUM WALL BOARD,
PAINT AS SCHEDULED
"J" CASING BEAD
8' - 4" A.F.F. U.N.O (SEE ELEVATIONS)
LINE OF CEILING, SEE REFLECTED
CEILING PLANS FOR INFORMATION
TILE COUNCIL ASSOCIATION
TILE SETTING METHOD (TCA) W243
EPOXY GROUT, SEAL POROUS
TILE, AND GROUT (SEE
MANUFACTURER'S INSTRUCTIONS)
LATEX-PORTLAND CEMENT
BOND MORTAR
FULL HEIGHT TILE
AT WALL CONDITION
T1
SCHEDULED PARTITION
WALL AND FINISH
(EXISTING WALL)
SCHEDULED TILE, SEAL POROUS TILE,
AND GROUT (SEE MANUFACTURER'S
INSTRUCTIONS)
5/8" GYPSUM WALL BOARD,
PAINT AS SCHEDULED
"J" CASING BEAD
8' - 4" A.F.F. U.N.O (SEE ELEVATIONS)
LINE OF CEILING, SEE
REFLECTED CEILING PLANS
FOR INFORMATION
EPOXY GROUT, SEAL POROUS
TILE, AND GROUT (SEE
MANUFACTURER'S INSTRUCTIONS)
LATEX-PORTLAND CEMENT
BOND MORTAR
TILE COUNCIL ASSOCIATION
TILE SETTING METHOD (TCA) W243
FULL HEIGHT TILE
OVER EXISTING CONDITIONS
T2
SEAL SMOKE TIGHT (105.3,
105.4, 105.7, 105.8, 105.10)
105.1 5/8" GWB ON 4" METAL STUDS.
105.2 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT
INSULATION.
105.3 5/8" GWB ON 4" METAL STUDS,SEALED SMOKE TIGHT.
105.4 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT
INSULATION, SEALED SMOKE TIGHT.
105.5 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
105.6 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION.
105.7 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS,
SEALED SMOKE TIGHT.
105.8 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION, SEALED SMOKE
TIGHT.
105.9 5/8" GWB ON 8" METAL STUDS, SEALED SMOKE TIGHT.
105.10 2 LAYERS 5/8" GWB ON 4" METAL STUDS, WITH
ACOUSTICAL BATT INSULATION, SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER UNIT
(105.5, 105.6, 105.7, 105.8)
5/8" GYPSUM BOARD
(105.1, 105.2,105.10)
4" METAL STUDS AT 16"
O.C. (105.1 - 105.8)
SEAL SMOKE TIGHT (105.3,
105.4, 105.7, 105.8,105.10)
METAL TRACK FASTENED
TO STRUCTURE
METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(105.2, 105.4, 105.8,105.10)
SEAL SMOKE TIGHT
(101.2, 101.4, 101.7,101.10, 101.12, & 101.14)
101.1 5/8" GWB ON 7/8" METAL HAT CHANNEL.
101.2 5/8" GWB ON 7/8" METAL HAT CHANNEL, SEALED SMOKE TIGHT.
101.3 5/8" GWB ON 1-1/2" METAL HAT CHANNEL.
101.4 5/8" GWB ON 1-1/2" METAL HAT CHANNEL, SEALED SMOKE TIGHT.
101.5 5/8" GWB ON 1" Z FURRING CHANNEL.
101.6 5/8" GWB ON 1" Z FURRING CHANNEL WITH RIGID INSULATION.
101.7 5/8" GWB ON 1" Z FURRING CHANNEL, SEALED SMOKE TIGHT.
101.8 5/8" GWB ON 2" Z FURRING CHANNEL.
101.9 5/8" GWB ON 2" Z FURRING CHANNELWITH RIGID INSULATION.
101.10 5/8" GWB ON 2" Z FURRING CHANNEL, SEALED SMOKE TIGHT.
101.11 5/8" CEMENTITIOUS BACKER UNIT ON 7/8" METAL HAT CHANNEL.
101.12 5/8" CEMENTITIOUS BACKER UNIT ON 7/8" METAL HAT CHANNEL,
SEALED SMOKE TIGHT.
101.13 5/8" CEMENTITIOUS BACKER UNIT ON 1-1/2" METAL HAT CHANNEL.
101.14 5/8" CEMENTITIOUS BACKER UNIT ON 1-1/2" METAL HAT CHANNEL,
SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER UNIT
(101.11, 101.12. 101.13, & I01.14)
5/8" GYPSUM BOARD
(101.1 - 101.10)
7/8" METAL HAT CHANNELS.
(101.1, & 101.2)
SEAL SMOKE TIGHT (103.2, 103.3)
RIGID INSULATION
(101.6, & 101.9)
1-1/2" METAL HAT CHANNELS.
(101.3, & 101.4)
1" Z FURRING CHANNELS
(101.5, 101.6, & 101.7)
2" Z FURRING CHANNELS
(101.8, 101.9, & 101.10)
SEAL SMOKE TIGHT
(100.2, 100.4, 100.6)
100.1 1/4" GWB LAMINATED TO EXIST WALL SURFACE.
100.2 1/4" GWB LAMINATED TO EXIST WALL SURFACE, SEALED
SMOKE TIGHT.
100.3 5/8" GWB LAMINATED TO EXIST WALL SURFACE.
100.4 5/8" GWB LAMINATED TO EXIST WALL SURFACE,
SEALED SMOKE TIGHT.
100.5 5/8" CEMENTITIOUS BACKER UNIT LAMINATED TO EXIST
WALL SURFACE.
100.6 5/8" CEMENTITIOUS BACKER UNIT LAMINATED TO EXIST
WALL SURFACE, SEALED SMOKE TIGHT.
100.7 5/8" GWB LAMINATED TO ALIGN FLUSH WALL SURFACE.
1/4" GWB LAMINATED
(100.1, 100.2)
5/8" GWB LAMINATED
(100.3, 100.4)
SEAL SMOKE TIGHT
(100.2, 100.4, 100.6)
5/8" CEMENTITIOUS BACKER
UNIT LAMINATED (100.5, 100.6)
LINE OF EXISTING
WALL SURFACE
SEAL SMOKE TIGHT
(104.3, 104.4, 104.7, 104.8)
104.1 5/8" GWB ON 3 5/8" METAL STUDS.
104.2 5/8" GWB ON 3 5/8" METAL STUDS WITH ACOUSTICAL BATT INSULATION.
104.3 5/8" GWB ON 3 5/8" METAL STUDS, SEALED SMOKE TIGHT.
104.4 5/8" GWB ON 3 5/8" METAL STUDS WITH ACOUSTICAL BATT INSULATION,
SEALED SMOKE TIGHT.
104.5 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL STUDS.
104.6 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL STUDS WITH
ACOUSTICAL BATT INSULATION.
104.7 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL STUDS, SEALED
SMOKE TIGHT.
104.8 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL STUDS WITH
ACOUSTICAL BATT INSULATION, SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER UNIT
(104.5, 104.6, 104.7, 104.8)
5/8" GYPSUM BOARD
(104.1, 104.2)
3 5/8" METAL STUDS
AT 16" O.C.
SEAL SMOKE TIGHT
(104.3, 104.4, 104.7, 104.8)
3 5/8" METAL TRACK
FASTENED TO STRUCTURE
3 5/8" METAL TRACK
FASTENED TO STRUCTURE
ACOUSTICAL BATT INSULATION
(104.2, 104.4, 104.8)
SEAL SMOKE TIGHT (106.3,
106.4, 106.7, 106.8, 106.13)
106.1 5/8" GWB ON 4" METAL STUDS.
106.2 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT INSULATION.
106.3 5/8" GWB ON 4" METAL STUDS, SEALED SMOKE TIGHT.
106.4 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT INSULATION, SEALED
SMOKE TIGHT.
106.5 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
106.6 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS WITH ACOUSTICAL BATT
INSULATION.
106.7 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS, SEALED SMOKE TIGHT.
106.8 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS WITH ACOUSTICAL BATT
INSULATION, SEALED SMOKE TIGHT.
106.9 5/8" GWB ON 2.5" METAL STUDS.
106.10 5/8" GWB ON 8" METAL STUDS WITH ACOUSTICAL BATT INSULATION, SEALED
SMOKE TIGHT.
106.11 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT INSULATION. SPOT WELD
EXPANDED METAL (9-GAUGE ) EVERY 6 INCHES TO VERTICAL AND HORIZONTAL
METAL SUPPORTS OF 16-GAUGE THICKNESS PERMANENTLY ATTACHED TO
CONCRETE SLAB AND UNDERSIDE OF DECK.
106.12 5/8" GWB ON 6" METAL STUDS WITH ACOUSTICAL BATT INSULATION
106.13 2 LAYERS 5/8" GWB ON 4" METAL STUDS, WITH ACOUSTICAL BATT INSULATION,
SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER UNIT,
EACH SIDE (106.5, 106.6, 106.7, 106.8)
5/8" GWB BOARD, EACH SIDE
(106.1, 106.2, 106.13)
4" METAL STUDS AT 16" O.C. (106.1 - 106.8,
106.13)
SEAL SMOKE TIGHT (106.3,
106.4, 106.7, 106.8, 106.13)
METAL TRACK FASTENED
TO STRUCTURE
METAL TRACK FASTENED TO STRUCTURE
ACOUSTICAL BATT INSULATION
(106.2, 106.4, 106.8)
107.1 5/8" GWB TYPE X ON 4" METAL STUDS.
107.2 5/8" ABUSE RESISTANTGWB TYPE X ON 4" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
107.3 5/8" ABUSE RESISTANTGWB TYPE X ON 4" METAL
STUDS WITH ACOUSTICAL BATT INSULATION. SMOKE
BARRIER
5/8" GWB BOARD, EACH
SIDE
4" METAL STUDS
AT 16" O.C.
4" METAL TRACK FASTENED
TO STRUCTURE
4" METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(107.2)
UL DESIGN U419
1 - HOUR RATED ASSEMBLY
FIRE RATED SEALANT
(RED COLOR)
108.1 5/8" GWB TYPE X ON 4" METAL STUDS.
108.2 5/8" GWB TYPE X ON 4" METAL STUDS WITH ACOUSTICAL BATT
INSULATION.
(2 LAYERS) 5/8" GWB BOARD,
EACH SIDE WITH STAGGERED
SEAMS
4" METAL STUDS
AT 16" O.C.
4" METAL TRACK FASTENED
TO STRUCTURE
4" METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(108.2)
UL DESIGN U419
2 - HOUR RATED ASSEMBLY
FIRE RATED SEALANT
(RED COLOR)
FIRE RATED SEALANT
(RED COLOR)
FIRE RATED SEALANT
(RED COLOR)
110.1 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
110.2 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION.
5/8" CEMENTITIOUS
BACKER UNIT, EACH SIDE
4" METAL STUDS
AT 16" O.C.
4" METAL TRACK FASTENED
TO STRUCTURE
4" METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT
INSULATION (110.2)
UL DESIGN U442
1 - HOUR RATED ASSEMBLY
FIRE RATED SEALANT
(RED COLOR)
FIRE RATED SEALANT
(RED COLOR)
109.1 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
109.2 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION.
109.3 5/8" CEMENTITIOUS BACKER UNIT (TILE SIDE ONLY) ON 4"
METAL STUDS WITH ACOUSTICAL BATT INSULATION,
SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER
UNIT, EACH SIDE
4" METAL STUDS
AT 16" O.C.
4" METAL TRACK FASTENED
TO STRUCTURE
4" METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(109.2)
ACOUSTICAL SEALANT
ACOUSTICAL SEALANT
SCHEDULED TILE,
SEE FINISHES
SCHEDULED TILE,
SEE FINISHES
NON-RATED TYPICAL WALL
113.1 5 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL FOR
FILL, REBAR, AND TYPICAL HEADER DETAIL.
113.2 7 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL FOR
FILL, REBAR, AND TYPICAL HEADER DETAIL.
113.3 11 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL
FOR FILL, REBAR, AND TYPICAL HEADER DETAIL.
5 5/8 CONCRETE
MASONRY UNIT (113.1)
STAGGERED STEEL
ANGLES, SEE STRUCTURAL
FOR INFORMATION
7 5/8 CONCRETE
MASONRY UNIT (113.2)
11 5/8 CONCRETE
MASONRY UNIT (113.3)
114.1 5 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL FOR
FILL, REBAR, AND TYPICAL HEADER DETAIL.
114.2 7 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL FOR
FILL, REBAR, AND TYPICAL HEADER DETAIL.
114.3 11 5/8 CONCRETE MASONRY UNIT, SEE STRUCTURAL FOR
FILL, REBAR, AND TYPICAL HEADER DETAIL.
5 5/8 CONCRETE
MASONRY UNIT (114.1)
STAGGERED STEEL
ANGLES, SEE STRUCTURAL
FOR INFORMATION
7 5/8 CONCRETE
MASONRY UNIT (114.2)
11 5/8 CONCRETE
MASONRY UNIT (114.3)
FILL ANNUALAR SPACE WITH
FIRE RATED MATERIAL
EQUAL TO UL DESIGNATION
UL DESIGN U618
2 - HOUR RATED ASSEMBLY
NOTE: REBAR AND FILL NOT SHOWN SEE STRUCTURAL DRAWINGS
NOTE: REBAR AND FILL NOT SHOWN SEE STRUCTURAL DRAWINGS
9 GAUGE HORZONTAL
LADDER REINFORCING
EVERY OTHER COURSE, UON.
9 GAUGE HORZONTAL
LADDER REINFORCING
EVERY OTHER COURSE, UON.
SEAL SMOKE TIGHT
(103.3, 103.4, 103.7, 103.8)
103.1 5/8" GWB ON 2 1/2" METAL STUDS.
103.2 5/8" GWB ON 2 1/2" METAL STUDS WITH ACOUSTICAL BATT INSULATION.
103.3 5/8" GWB ON 2 1/2" METAL STUDS, SEALED SMOKE TIGHT.
103.4 5/8" GWB ON 2 1/2" METAL STUDS WITH ACOUSTICAL BATT INSULATION,
SEALED SMOKE TIGHT.
103.5 5/8" CEMENTITIOUS BACKER UNIT ON 2 1/2" METAL STUDS.
103.6 5/8" CEMENTITIOUS BACKER UNIT ON 2 1/2" METAL STUDS WITH
ACOUSTICAL BATT INSULATION.
103.7 5/8" CEMENTITIOUS BACKER UNIT ON 2 1/2" METAL STUDS, SEALED
SMOKE TIGHT.
103.8 5/8" CEMENTITIOUS BACKER UNIT ON 2 1/2" METAL STUDS WITH
ACOUSTICAL BATT INSULATION, SEALED SMOKE TIGHT.
103.9 5/8" GWB ON 4" METAL STUDS WITH ACOUSTICAL BATT INSULATION.
SPOT WELD EXPANDED METAL (9-GAUGE ) EVERY 6 INCHES TO
VERTICAL AND HORIZONTAL METAL SUPPORTS OF 16- GAUGE
THICKNESS PERMANENTLY ATTACHED TO CONCRETE SLAB AND
UNDERSIDE OF DECK.
5/8" CEMENTITIOUS BACKER UNIT
(103.5, 103.6, 103.7, 103.8)
5/8" GYPSUM BOARD
(103.1, 103.2)
2 1/2" METAL STUDS AT
16" O.C.
SEAL SMOKE TIGHT
(103.3, 103.4, 103.7, 103.8)
METAL TRACK FASTENED
TO STRUCTURE
METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(103.2, 103.4, 103.8)
NON-RATED TILE ASSEMBLY
NON-RATED CMU
SEAL SMOKE TIGHT
(102.3, 102.4, 102.7, 102.8)
102.1 5/8" GWB ON 1 5/8" METAL STUDS.
102.2 5/8" GWB ON 1 5/8" METAL STUDS WITH ACOUSTICAL BATT INSULATION.
102.3 5/8" GWB ON 1 5/8" METAL STUDS, SEALED SMOKE TIGHT.
102.4 5/8" GWB ON 1 5/8" METAL STUDS WITH ACOUSTICAL BATT
INSULATION, SEALED SMOKE TIGHT.
102.5 5/8" CEMENTITIOUS BACKER UNIT ON 1 5/8" METAL STUDS.
102.6 5/8" CEMENTITIOUS BACKER UNIT ON 1 5/8" METAL STUDS WITH
ACOUSTICAL BATT INSULATION.
102.7 5/8" CEMENTITIOUS BACKER UNIT ON 1 5/8" METAL STUDS, SEALED
SMOKE TIGHT.
102.8 5/8" CEMENTITIOUS BACKER UNIT ON 1 5/8" METAL STUDS WITH
ACOUSTICAL BATT INSULATION, SEALED SMOKE TIGHT.
5/8" CEMENTITIOUS BACKER UNIT
(102.5, 102.6, 102.7, 102.8)
5/8" GYPSUM BOARD
(102.1, 102.2)
1 5/8" METAL STUDS
AT 16" O.C.
SEAL SMOKE TIGHT
(102.3, 102.4, 102.7, 102.8)
1 5/8" METAL TRACK
FASTENED TO STRUCTURE
1 5/8" METAL TRACK
FASTENED TO STRUCTURE
ACOUSTICAL BATT INSULATION
(102.2, 102.4, 102.8)
111.1 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL
STUDS.
111.2 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
111.3 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
111.4 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION.
5/8" CEMENTITIOUS BACKER
UNIT, ONE SIDE
4" METAL STUDS AT 16"
O.C. (111.3, 111.4)
METAL TRACK FASTENED
TO STRUCTURE
METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT
INSULATION (111.2, 111.3)
ACOUSTICAL SEALANT
ACOUSTICAL SEALANT
SCHEDULED TILE,
SEE FINISHES
NON-RATED TILE ASSEMBLY - ONE SIDE
5/8" GWB ONE SIDE
TILE CONDITIONS
3 5/8" METAL STUDS AT
16" O.C. (111.1, 111.2)
112.1 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL
STUDS.
112.2 5/8" CEMENTITIOUS BACKER UNIT ON 3 5/8" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
112.3 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS.
112.4 5/8" CEMENTITIOUS BACKER UNIT ON 4" METAL STUDS
WITH ACOUSTICAL BATT INSULATION.
5/8" CEMENTITIOUS
BACKER UNIT, ONE SIDE
4" METAL STUDS AT 16" O.C.
(112.3, 112.4)
METAL TRACK FASTENED TO
STRUCTURE
METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT
INSULATION (112.2, 112.3)
FIRE RATED SEALANT
(RED COLOR)
SCHEDULED TILE,
SEE FINISHES
5/8" GWB ONE SIDE
3 5/8" METAL STUDS AT 16"
O.C. (112.1, 112.2)
UL DESIGN U442
1 - HOUR RATED ASSEMBLY - ONE SIDE
FIRE RATED SEALANT
(RED COLOR)
UL DESIGN U415
SYSTEM A
1 - HOUR RATED ASSEMBLY
2 - HOUR RATED ASSEMBLY
FIRE RATED SEALANT
(RED COLOR)
FIRE RATED SEALANT
(RED COLOR)
STEEL J RUNNER
1" SHAFT
LINER PANEL
5/8" GWB BOARD TYPE X
(116.1, 116.2, 116.3)
CH STUDS 2.5" @ 24"
O.C. (116.1, 116.4)
STEEL J RUNNER
116.1 CH 2.5" STUDS AT 24" O.C.
116.2 CH 4" STUDS AT 24" O.C.
116.3 CH 6" STUDS AT 24" O.C.
116.4 2 LAYERS OF 5/8" ON 2.5" CH STUDS AT 24" O.C.
(2-HR RATED ASSEMBLY)
CH STUDS 4" @ 24" O.C.
(116.2)
CH STUDS 6" @ 24" O.C.
(116.3)
115.1 5/8" GWB TYPE X ON 2.5" METAL STUDS.
115.2 5/8" ABUSE RESISTANT GWB TYPE X ON 2.5" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
115.3 5/8" ABUSE RESISTANT GWB TYPE X ON 3 5/8" METAL
STUDS.
115.4 5/8" ABUSE RESISTANT GWB TYPE X ON 3 5/8" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
115.5 5/8" ABUSE RESISTANT GWB TYPE X ON 4" METAL
STUDS.
115.6 5/8" ABUSE RESISTANT GWB TYPE X ON 4" METAL
STUDS WITH ACOUSTICAL BATT INSULATION.
115.7 5/8" ABUSE RESISTANT GWB TYPE X ON 4" METAL
STUDS WITH ACOUSTICAL BATT INSULATION, SMOKE
BARRIER.
2 LAYERS 5/8" GWB
BOARD TYPE X
3 5/8" METAL STUDS AT
16" O.C. (115.3, 115.4)
METAL TRACK FASTENED
TO STRUCTURE
METAL TRACK FASTENED
TO STRUCTURE
ACOUSTICAL BATT INSULATION
(115.2, 115.4, 115.6)
UL DESIGN V497
1 - HOUR RATED ASSEMBLY
FIRE RATED SEALANT
(RED COLOR)
FIRE RATED SEALANT
(RED COLOR)
2.5" METAL STUDS AT
16" O.C. (115.1, 115.2)
4" METAL STUDS AT
16" O.C. (115.5, 115.6)
WHERE APPLICABLE SEE TILE
CONDITIONS SUFFIX -T1, -T2, OR -T3
8" METAL STUDS AT
16" O.C. (105.9)
2.5" METAL STUDS AT 16" O.C. (106.9)
8" METAL STUDS AT
16" O.C. (106.10)
WALL TAG SUFFIX TILE CONDITIONS (WHERE
APPLICABLE) WALL TAGS I.E., 100.7T3
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRETE SLAB
EDGE OF B.O.
STRUCTURE
EDGE OF T.O.
CONCRET…