S06 - 537-16-102A Construction Plans IFC - Photos - 6.pdf

PDF 12 MB Posted

Attached to
Z1DA--537-16-102A Corrections to Sprinkler System
Solicitation number
36C25222B0007
Issued by

About this file

This document summarizes a federal contract solicitation for corrections to a sprinkler system. The solicitation number is 36C25222B0007 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 for Project 537-16-102A. The opportunity type is listed as a solicitation for corrections to an existing sprinkler system located at a Veterans Affairs medical facility. No other details are provided regarding response dates, pricing terms, set asides, incumbent contractors, or work requirements.

View the file

Other files

File Type Posted
S06 - 537-16-102A Construction Plans IFC - Photos - 4.pdf PDF
36C25222B0007 0013.docx DOCX document
36C25222B0007 0012.docx DOCX document
S06 - 537-16-102A Construction Plans IFC - Photos - 5.pdf PDF
S06 - 537-16-102A Construction Plans IFC - Photos - 7.pdf PDF
S06 - 537-16-102A Construction Plans IFC - Photos - 2.pdf PDF
S06 - 537-16-102A Construction Plans IFC - Photos - 1.pdf PDF
36C25222B0007 0011.docx DOCX document
S06 - 537-16-102A Construction Plans IFC - Photos - 4.pdf PDF
S06 - 537-16-102A Construction Plans IFC - Photos - 3.pdf PDF
S06 - 537-16-102A Construction Plans Issued for Bid and Construction 02_11_2022 - (1).pdf PDF
S06 - 537-16-102A Construction Plans Issued for Bid and Construction 02_11_2022 - (2).pdf PDF
S06 - VA Responses to RFIs.pdf PDF
S06 - Wage Determination 01_14_2022.pdf PDF
36C25222B0007 0010.docx DOCX document
S06 - 537-16-102A Specifications Issued for Bid and Construction 02_03_2022.pdf PDF
36C25222B0007 0009.docx DOCX document
36C25222B0007 0008.docx DOCX document
36C25222B0007 0007.docx DOCX document
S06 - Campus Floor Plan 1 of 2.pdf PDF
S06 - Pre-Bid Site Visit Attendance Sheet - 1-14-22.pdf PDF
S06 - Record Drawings 1 of 8.pdf PDF
S06 - Pre-Bid Site Visit Attendance Sheet - 1-5-22.pdf PDF
36C25222B0007 0006.docx DOCX document
S06 - Attachments 0006.zip ZIP file
36C25222B0007 0005.docx DOCX document
537-16-102A Construction Plans IFC 08302020-2.pdf PDF
537-16-102A Construction Plans IFC 08302020 - 2.pdf PDF
36C25222B0007 0004.docx DOCX document
537-16-102A Construction Plans IFC 08302020 - 1.pdf PDF
S06 - Record Drawings 4 of 8.pdf PDF
36C25222B0007 0003.docx DOCX document
S06 - Record Drawings 8 of 8.pdf PDF
S06 - Record Drawings 5 of 8.pdf PDF
S06 - Record Drawings 7 of 8.pdf PDF
S06 - Record Drawings 6 of 8.pdf PDF
S06 - Attachments 0002.zip ZIP file
36C25222B0007 0002.docx DOCX document
36C25222B0007 0001.docx DOCX document
S06 - Attachments 0001.zip ZIP file
S02 - 537-16-102A Specifications IFC 02082020.pdf PDF
S02 - 537-16-102A Construction Plans IFC 08302020.pdf PDF
S02 - VHA Sup Con Req for Combatting COVID-19.pdf PDF
S02 - Statement of Work.pdf PDF
S02 - Wage Determination as of 12_3_21.pdf PDF
36C25222B0007.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Jesse Brown Veteran’s Hospital Project 537-16-102A Sprinkler Corrections Field Report 01-15-2020 Areas of concern Full Campus – 1st Floor

1 – Bed Tower 1st Floor Stairwell 2 – Bed Tower 1st Floor Stairwell

3 – Bed Tower 1st Floor Stairwell 4 – Bed Tower 1st Floor Stairwell

5 – Bed Tower 1st - Hose Valve & Riser in stairwell 6 – Bed Tower 1st – Control Valve & Riser in stairwell

7 – Bed Tower 1st – Pressure Gauge in stairwell 8 – Bed Tower 1st – Control Valve & Pressure Gauge in stairwell

9 – Bed Tower 1st – Copper Piping corroded. Sprinkler fitting rusted. Replace damaged piping.

10 – Bed Tower 1st – Sprinkler fitting rusted. Replace piping.

11 – Bed Tower 1st – Sprinkler fitting rusted. Replace fitting. 12 – Bed Tower 1st – Sprinkler fitting rusted. Replace ftting.

13 – Bed Tower 1st – Escutcheon opening too large. Patch hole.

14 – Ogden 1st – Tapered Drop rusted, replace with standard drop and reducing fitting.

15 – Ogden 1st Floor stairwell 16 – Ogden 1st - Hose Valve & Riser in stairwell

17 – Ogden 1st - Hose Valve in corridor 18 – Ogden 1st – Tapered Drop rusted, replace with

19 – Ogden 1st – Sprinkler needed in drywall ceiling.

Concealed head too close to drop.

20 – Ogden 1st – Tapered Drop rusted, replace with

21 – Ogden 1st – Tapered Riser rusted, replace with standard riser and reducing fitting.

22 – Ogden 1st – Sprinkler riser and dry pipe valve for MRI sprinklers. Closet not marked.

23 – Bed Tower 1st Floor stairwell 24 – Bed Tower 1st - Hose Valve & Riser in stairwell

25 – Bed Tower 1st – Control Valve & Pressure Gauge in

26 – Damon 1st – Sprinkler head farther than 9’-0” from back wall. Move sprinkler 2’-0” close to wall.

27 – Damon 1st Floor stairwell 28 – Damon 1st - Hose Valve & Riser in stairwell

29 – Damon 1st – Control Valve & Pressure Gauge in

30 – Damon 1st Floor stairwell

31 – Damon 1st – Control Valve & Riser in stairwell 32 – Damon 1st – Control Valve & Riser in stairwell

Field Report 01-17-2020

33 – Damon 1st – Sprinkler piping rusted. About 4’-6” length. 34 – Damon 1st – Sprinkler piping rusted. About 4’-6” length.

35 – Damon 1st – Sprinkler fitting rusted. 36 – Damon 1st – Sprinkler piping and fittings rusted.

37 – Damon 1st – Sprinkler piping rusted. About 4’-6” length. 38 – Damon 1st – Drain pan connected to sprinkler piping. .

39 – Damon 1st – Sprinkler hanger rod bent. Replace. 40 – Damon 1st – Sprinkler not located under ductwork.

41 – Damon 1st – Sprinkler coverage in garage Not on dry system. Provide new Dry pipe valve for space.

42 - Damon 1st – Sprinklers blocked by ceiling elevation change.

43 – Damon 1st – Sprinkler coverage missing under roll up doors. Provide additional heads

44 – Damon 1st – Rusted Tee. Replace fitting.

45 – Damon 1st – Head not within 8” of ceiling. CPVC exposed in tele closet. Not permitted.

46 – Damon 1st – Rusted Tee. Replace fitting.

47 – Damon 1st – Rusted fittings. Replace fitting. 48 – Damon 1st – Rusted fittings. Replace fitting.

49 - Damon 1st –Sprinkler head rusted. Surrounding ceiling has water damage. Replace head.

50 - Damon 1st – Sidewall head obstructed by drain line.

Relocate head or add head on opposite side of pipe

51 – Damon 1st Floor stairwell 52 – Damon 1st - Hose Valve & Riser in stairwell

53 – Damon 1st – Control Valve & Pressure Gauge in

54 – Damon 1st – Lower stairwell missing sprinkler protection. Provide additional coverage.

55 – Damon 1st – Sprinkler fitting rusted. Replace fitting. 56 – Damon 1st – Crawlspace access does not include any sprinkler coverage.

57 – Damon 1st – Crawlspace access does not include any

58 – Damon 1st – Crawlspace access does not include any

59 – Damon 1st Floor stairwell 60 – Damon 1st - Hose Valve & Riser in stairwell

61 – Damon 1st - Hose Valve & Riser in stairwell 62 – Damon 1st – Control Valve & Pressure Gauge in

63 – Atrium 1st – Sprinkler head too far from door. Move to 7’-6” from door.

64 – Atrium 1st – Alcoves do not have sprinkler heads.

(6 locations) Install new heads in each alcove.

65 – Atrium 1st – Alcoves do not have sprinkler heads.

(6 locations) Install new heads in each alcove.

66 – Atrium 1st – Location of control valve above ceiling.

67 – Atrium 1st – Location of control valve above ceiling. 68 – Atrium 1st – Location of control valve above ceiling.

69 – Taylor 1st – Sprinkler fitting rusted. Replace fitting. 70 – Taylor 1st – Sprinkler piping and fitting rusted. Replace with new.

71 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

72 – Taylor 1st – Sprinkler piping connected to conduit with wire. Remove and support sprinkler piping with hanger

73 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

74 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

75 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

76 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

77 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

78 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

79 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

80 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

81 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

82 – Taylor 1st – Sprinkler piping and fitting rusted. Replace

01-15-2020 -Full Campus Level 01 Field Report