This document outlines a federal contract opportunity for corrections to a sprinkler system. The solicitation number is 36C25222B0007 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. The opportunity is for Project 537-16-102A which involves corrections to an existing sprinkler system. No other details are provided in the document regarding response dates, pricing terms, set asides, incumbent contractors, or work requirements.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Jesse Brown Veteran’s Hospital Project 537-16-102A Sprinkler Corrections Field Report 10-02-2019 Areas of concern Building 40 – Basement
1 – Typical piping in ceiling of crawl space. Corrosion on piping, condensate everywhere.
3 – Condensation on piping throughout much of space
2 – Existing Jockey Pump
Field Report 12-09-2019
Building 40 – 2nd Floor
1 – 2nd Floor Stairwell 2 – Standpipe and Hose Valve in stairwell
3 – Floor Control Valve and Pressure gauge in Stairwell 4 – Close up of hose valve in stairwell
5 – Rusted piping and fittings to sprinkler head 6 – Rusted fitting to sprinkler head
7 – Rusted fitting to sprinkler head 8 – Rusted fitting to sprinkler head
9 – Rusted fittings to sprinkler head
Field Report 12-11-2019
10 – 2nd Floor Stairwell 11 – Standpipe and Hose Valve in stairwell, fittings rusted
12 – Floor Control Valve and Pressure gauge in Stairwell 13 – Close up of hose valve in stairwell
Field Report 12-11-2019
14 – Rusted fittings to sprinkler head 15 – Approximately 15 feet of rusty piping
Field Report 10-03-2019
Building 40 – 3rd Floor
1 – Insufficient sprinkler coverage under ductwork 2 – Missing sprinkler coverage under ductwork
3 – Missing sprinkler coverage under ductwork 4 – Missing sprinkler coverage under ductwork
5 – Missing sprinkler coverage under ductwork 6 – Missing sprinkler coverage under ductwork
7 – Missing sprinkler coverage under ductwork 8 – Missing sprinkler coverage under ductwork
9 – Missing sprinkler coverage under ductwork 10 – Missing sprinkler coverage under ductwork
11 – Missing sprinkler coverage under ductwork 12 – Missing sprinkler coverage under ductwork
13 – Sprinkler and light in conflict. Coverage 14 – Sprinkler support hanger for high pressure zone. This is not typical on floors with pressures over 125 psi.
15 – Improper sprinkler installation – cut insulation in ductwork for sprinkler clearance.
16 – 3rd floor Hose Valve – Chicago threads
Building 40 – 4th Floor
1 – Rusted fittings on piping. 2 – Sprinkler piping corroding from leaking mechanical unit.
3 – Sprinkler main in stairwell – Not properly fire sealed 4 – Fire riser and Sprinkler control valve.
5 – Sprinkler main not fire sealed to stairwell 6 – Sprinkler pressure valve for system
7 – Sprinkler control valve 8 – Multiple fire sealant used for penetration
9 – Sprinkler cover plate missing – stuffed with gloves 10 – Exposed sprinkler head with cover plate missing
Building 40 – 5th Floor
1 – Sprinkler head close to electrical equipment 2 – Proper bracing of sprinkler pipe. (not typical)
3 – Item removed from project 4 – Fire riser and Sprinkler control valve.
5 – Pressure valve on sprinkler main – greater than 100 psi 6 – Massive corrosion on sprinkler main and threaded outlet
7 – Sprinkler control valve and pressure gauge in stairwell 8 – Sprinkler main penetration through wall – properly done.
9 – Sprinkler pressure gauge – greater than 100 psi.
Field Report 10-17-2019
Building 40 – 6th Floor
1 – Sprinkler Standpipe and Hose Valve in stairwell 2 – Control Valve and Pressure Gauge on sprinkler supply to 6th floor
3 – Closer image of Pressure Gauge in stairwell 4 – Item removed from project
5 – Item removed from project 6 – Rust on reducer to sprinkler head
7 – Mechanical piping corroded 8 – Rusting of fittings and corrosion on Reducer
9 – Standpipe 6th floor stairwell 10 – Pressure gauge in th floor stairwell
11 – Pipe penetration in 6th floor stairwell wall 12 – no hanger bracing support on branchline, end of line
13 – No sprinkler end of lane hanger support 14 – Wall penetration not fire sealed – stuffed with paper.
15 – Wires taped to sprinkler piping 16 – Wires taped to sprinkler piping
17 – Unusual exterior piping corrosion 18 – Alternate view of piping corrosion
19 – Item removed from project
Building 40 – 7th Floor
1 – Vandal resistant access panels on 7th floor. 2 – vandal resistant sprinkler heads, insulation too close to head
3 – Skylights missing sprinkler heads 4 – Skylights missing sprinkler heads
5 – Non insulated vandal resistant sprinkler head 6 – Head located too close to wall. Minimum 4” to center.
7 – Full room view of sprinkler too close to wall. 8 – 7th Floor stairwell
9 – Hose Valve in stairwell 10 – Hole in ceiling, taped over
11 – Rusted coupling 12 – Reducer rusted
13 – No hangers on sprinkler piping 14 – Alternate view no hangers on sprinkler piping
15- Alternate view no hangers on sprinkler piping 16 – Alternate view no hangers on sprinkler piping
17 – Cavity adjacent to skylight – room for piping and sprinkler head
18 – 7th Floor Stairwell – Stair information missing. Stair 13
19 – Hose valve in stairwell 20 – Pressure Gauge in Stairwell
21 – Standpipe in stairwell 22 – Rusty fittings on standpipe in stairwell
23 – 7th Floor Stairwell 24 – Control Valve and Pressure Gauge in Stairwell
25 – Hose Valve in stairwell 26 – Top of standpipe – 7th Floor Stairwell
27 – Pressure gauge at top of standpipe – 100 psi.
Building 40 – 8th Floor
1 – PH Standpipe riser - Corroded 2 – PH Stairwell Riser fittings corroded
3 – Rusted fitting in penthouse 4 – Hanger to sprinkler head greater than 36”
5 – Sprinkler fitting rusted 6 – Sprinkler fitting rusted
7 – Sprinkler fitting rusted 8 – sprinkler fitting rusted
9 – Standpipe and hose valve 8th Floor Stairwell 10 – Control Valve in stairwell
11 – Pressure Gauge in stairwell 12 – Standpipe up to Roof in stairwell
| 10-02-2019 - Building 40 - Lower Level Field Report |
| 12-09-2019 - Building 40 - 2nd Floor Field Report |
| 12-11-2019 - Building 40 - 2nd Floor Field Report |
| 10-03-2019 - Building 40 - 3rd Floor Field Report |
| 10-03-2019 - Building 40 - 4th Floor Field Report |
| 10-03-2019 - Building 40 - 5th Floor Field Report |
| 10-17-2019 - Building 40 - 6th Floor Field Report |
| 12-09-2019 - Building 40 - 7th Floor Field Report |
| 10-17-2019 - Building 40 - 8th Floor Field Report |