This document outlines a federal contract opportunity for corrections to a sprinkler system. The solicitation number is 36C25222B0007 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. The opportunity is for Project 537-16-102A which involves corrections to an existing sprinkler system. No other details are provided in the document regarding response dates, pricing terms, set asides, incumbent contractors, or work requirements.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Jesse Brown Veteran’s Hospital Project 537-16-102A Sprinkler Corrections Field Report 10-02-2019 Areas of concern Building 1 – Basement
1 – Incoming Fire Service main – Corroded and Rusted 3 – Corrosion on valves
2 – Zip tie connecting sprinkler pipe to conduit 4 – Elbow rusted
5 – Severe condensation and Rust on fittings 7 – Elbows rusted
6 – Piping rusting 8 – Couplings rusting
9 – Condensation and couple rusting 11 – Couplings and fitting rusting
10 – Elbow fitting rusting 12 – Fittings rusting
13 – Piping and fittings rusting 15 – Piping rusting
14 – Alternate view – Pipe rusting 16 – Severe condensation build up
17 – Rusting at mechanical tee and elbow 19 – Sprinkler piping to elevator pit not painted.
18 – Fire Piping penetration- Not Fire Sealed
20 – Block of wood used to separate piping & conduit
21 – non-rising stem, unlocked valve on fire main 23 – Severe condensation on all piping in space. Apparent
Steam line leak.
22 – Sprinkler piping to elevator pit not painted. 24 – Rusting fittings
Field Report 10-17-2019
Building 1 – 2nd Floor
1 – 2nd Floor Stairwell 2 – 2nd Floor Standpipe and hose valve
3 – 2nd Floor Stairwell control valve and pressure gauge 4 – Transition from CPVC in corridor to steel pipe.
5 – piping sleeve not properly used. Not installed in wall. 6 – Flex drop sprinkler used in tight to fit spaces
7 – Corroded piping outside room 2444 8 – Transition from CPVC to thinwall piping
9 – Exit from room blocked 10 – Stair exit blocked
11 – No sprinkler coverage in exit stairwell 12 – Storage placed in exit stair landing
13 – Chemical drain piping improperly installed back sloped 14 – Leaking drain piping corroding sprinkler fitting
Field Report 10-18-2019
15 – Rusted piping and fittings in mechanical room 16 – Rusted fittings and sprinkler piping
17 – Sprinkler Standpipe and Hose Valve in stairwell 18 – Sprinkler standpipe and control valve in stairwell
19 – Sprinkler piping through stair wall 20 – Inspector’s test drain valve
21 – CPVC piping through wall – poor fire sealant installation
22 – CPVC piping to thinwall transistion
23 – Steel piping fire sealed 24 – Sprinkler head obstructed by light
25 – Sprinkler head obstructed by heater 26 – Stairwell 2nd floor
27 – Standpipe & hose valve in 2nd floor stairwell 28 – Hose valve mounted 5’-0” above floor
29 – Sprinkler control valve – 2nd floor stairwell 30 – Sprinkler line penetration through stairwell wall
31 – Transition from steel sprinkler main to CPVC in corridor
32 – Sprinkler head obstructed by storage – less than 18”
33 – Sprinkler head obstructed by storage – less than 18” 34 – Leaking sanitary piping above ceiling
35 – Thinwall piping used as transition 36 – Sprinkler piping and fitting rusted and corroded
37 – Thinwall piping used as transition 38 – 2nd Floor Stairwell
39 – Stairwell standpipe and hose valve 40 – Stairwell floor control valve and pressure valve
41 – CPVC piping hanger spacing too far, pipe sagging 42 – CPVC piping used as hanger support
43 – Tape and Plastic used to contain leak 44 – Fire sealant on piping remaining, no wall.
45 – 2nd Floor Stairwell standpipe and hose valve 46 – Pressure gauge and control valve in stairwell
Building 1 – 3rd Floor
1 – Hanger Rod rusted 2 – CPVC piping through rated wall – Poor fire stopping
3 – 3rd floor stairwell 4 – 3rd floor standpipe, hose valve and control valve in stairwell
5 – 3rd floor Hose valve in stairwell 6 – Pressure gauge on sprinkler supply to floor – shut down
7 – Control valve shut off 8 – Sprinkler obstructed
9 – Sprinkler piping rusting 10 – 3rd Floor standpipe in stairwell
11 – 3rd floor control valve in stairwell 12 – Pressure gauge in stairwell, wall penetration
13 – Sprinkler coverage obstructed – Need another head 14 – 3rd Floor standpipe
15 – Control valve in stairwell 16 – Pressure gauge in stairwell
17 – Sprinkler coverage missing in drywall ceiling 18 – CPVC piping burnt on exterior. Pipe to be replaced
19 – Corridor to toilet room missing sprinkler coverage
Field Report 10-22-2019
20 – Sprinkler head not installed under ductwork 21 – Sprinkler head to freezer – dry bulb type
22 – Sprinkler head in cooler - rusted 23 – Alternate view – Rusted sprinkler head in cooler
24 – Rusted sprinkler head in cooler 25 – Sprinkler head installed above drop ceiling
26 – Access panel above drop ceiling blocked 27 – Sprinkler head obstructed by piping, completely blocked
28 – Sprinkler piping transition from CPVC to Steel 29 – 3rd Floor Stairwell
30 – Standpipe, control valve and hose valve in stairwell 31 – Pressure gauge in stairwell
32 – Sprinkler head against wall in stairwell 33 – Alternate view – Sprinkler head against wall
34 – 3rd Floor stairwell 35 – Standpipe, control valve and hose valve in stairwell
36 – Control valve located close to floor in stairwell 37 – Pressure gauge in stairwell
38 – Sprinkler head rusted in freezer 39 – Sprinkler head in freezer rusted / Opening exposed
Field Report 10-21-2019
Building 1 – 4th Floor
1 – 4th Floor stairwell 2 – Standpipe and Control valve in stairwell
3 – Pressure gauge in stairwell 4 – Hose valve in stairwell
5 – CPVC piping used as hanger support for light 6 – Corrosion grease from mechanical equipment on sprinkler piping
7 – Sprinkler upright in unfinished room 8 – Missing/removed sprinkler head – not enough protection
9 – Sprinkler transition from CPVC to steel. Steel pipe corroded.
10 – Corrosion debris on sprinkler piping?
11 – Sprinkler elbow and piping rusting 12 – 4th floor stairwell
13 – Standpipe, hose valve and control valve in stairwell 14 – Pressure Gauge in stairwell
15 – Sprinkler piping running through ductwork insulation 16 – Dry Pendant sprinkler head into cooler
17 – Sprinkler head cut into ceiling exposed 18 – Wire zip tied to sprinkler piping
19 – Fire Door exit 4th floor 20 – 4th Floor Stairwell
21 – Standpipe, hose valve in stairwell 22 – Control valve in stairwell
23 – Pressure Gauge in stairwell 24 – Hose valve coated in paint
| 10-02-2019 - Building 1 - Lower Level Field Report |
| 10-17-2019 - Building 1 - 2nd Floor Field Report |
| 10-18-2019 - Building 1 - 2nd Floor Field Report |
| 10-18-2019 - Building 1 - 3rd Floor Field Report |
| 10-22-2019 - Building 1 - 3rd Floor Field Report |
| 10-21-2019 - Building 1 - 4th Floor Field Report |
| 10-22-2019 - Building 1 - 4th Floor Field Report |
| 10-22-2019 - Building 1 - 5th Floor Field Report |
| 10-22-2019 - Building 1 - 6th Floor Field Report |
| 11-01-2019 - Building 1 - 6th Floor Field Report |
| 11-01-2019 - Building 1 - 7th Floor Field Report |
| 12-09-2019 - Building 1 - 7th Floor Field Report |
| 11-05-2019 - Building 1 - 8th Floor Field Report |
| 12-09-2019 - Building 1 - 8th Floor Field Report |
| 11-13-2019 - Building 1 - 9th Floor Field Report |
| 11-05-2019 - Building 1 - 10th Floor Field Report |
| 12-09-2019 - Building 1 - 10th Floor Field Report |
| 12-11-2019 - Building 1 - 11th Floor Field Report |
File details come from the government source that posted it. Updated .