This document outlines a federal contract opportunity for corrections to a sprinkler system. The solicitation number is 36C25222B0007 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 for Project 537-16-102A. The opportunity type is a solicitation for corrections to an existing sprinkler system located at a Veterans Affairs facility. No other details are provided in the document regarding response dates, pricing terms, set asides, or incumbent contractors.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Jesse Brown Veteran’s Hospital Project 537-16-102A Sprinkler Corrections Field Report 10-02-2019 Areas of concern Building 11 – Basement Level
1 – Cutting Grease on Fitting, old galvanized pipe. Painting scraped off
3 – Cutting Grease on Fitting
2 – Fire Alarm Wiring not connected. Not sure if existing was not removed or not, or if not connected to system.
4 – Fire Alarm Wiring not connected. Not sure if existing was not removed or not, or if not connected to system.
Field Report 10-02-2019
Building 11 – Basement Level
5 – Severe rust on pipe and fitting. Paint chipping off. Galv Piping.
7 – Severe rust on pipe and fitting. Paint chipping off. Galv Piping.
8 – Extra Valve, no tamper switch, not locked open.
6 – Rust on old hanger location. 9 – Fitting and pipe joint rusting. Galv Pipe. Paint chipping.
Field Report 12-11-2019
Building 11A – 1st Floor
1 – 1st Floor Stairwell 2 – Standpipe riser and Hose valve in Stairwell. Replace hose valve per SOW
Field Report 11-06-2019
Building 11A – 2nd Floor
1 – Unattached hanger 2 – Elbow rusted
Field Report 11-14-2019
Building 11A – 3rd Floor
1 – Sprinkler and escutcheon falling out - Replace 2 – Sprinkler and escutcheon falling out - Replace
3 – Sprinkler and escutcheon are crooked - Correct
Building 11A – 3rd Floor
4 – Sprinkler heads located greater than 9’-0” from wall.
Add additional sprinklers or relocate existing heads to meet code spacing requirements.
Building 11A – 4th Floor
1 – Item removed from project 2 – Crooked escutcheon and sprinkler - Correct
3 – Rusty Elbow – Replace with new 4 – Sprinkler obstructed by exit sign
Building 11A – 4th Floor
5 – Leak
Building 11A – 5th Floor
1 – Sprinkler is obstructed - Relocate 2 – Fitting rusted shut from leaking – water stains present -
Replace
3 – Sprinkler and escutcheon are crooked - Correct 4 – Rusted fittings – Replace with new
5 - Rusted pipe and fittings – Replace with new 6 – Rusted fitting – Replace with new
7 – 5th Floor Stairwell 8 – Standpipe and Fire Hose Valve in Stairwell
9 – Close up of hose valve, replace per SOW
Field Report 12-10-2019
Building 11A – 6th Floor
1 – 6th Floor Stairwell 2 – Floor Control valve, Pressure Valve in Stairwell
3 – Fire hose valve in stairwell 4 – Thinwall piping down to head.
5 – Rusted fitting to sprinkler head. Replace fitting 6 – Rusted elbow and tee to sprinkler. Replace fittings.
7 – 6th Floor Stairwell 8 – Hose valve in stairwell
9 – Old hose valve in stairwell, Replace per SOW 10 – 6th Floor Stairwell
11 – Fire hose valve in stairwell 12 – weld-o-let rusted. Replace connection
13 – 6th Floor stairwell 14 – Hose valve in stairwell
15 – Hose valve to be replaced per SOW 16 – Firewall penetration not sealed in stairwell
17 – Sprinkler main penetration rusted, firewall sealant damaged. Replace damaged piping, reseal opening.
18 – Sprinkler fitting rusted, replace fitting.
Building 11A – 7th Floor
1 – 7th Floor Stairwell 2 – Fire hose valve in stairwell
3 – Pressure gauge at top of riser in stairwell 4 – Closer look at Fire hose valve to be replaced per SOW.
5 – Tee starting to rust 6 – Elbow and reducer rusting, replace fittings
7 – Sprinkler head coated with something. Replace head 8 – Thinwall piping down to sprinkler
9 – 7th Floor Stairwell 10 – Fire Hose valve in stairwell
11 – Pressure gauge at top of riser in stairwell 12 – Close up of fire hose valve, to be replaced per SOW
13 – Sprinkler head piping down to head rusting, replace piping
14 – Sprinkler head crystalizing on head, frame and bulb.
Replace head.
15 – Sprinkler piping missing hanger, add hanger. 16 – 7th Floor stairwell
17 – Fire hose valve and pressure gauge at top of riser 18 – Close up of hose valve. Replace per SOW.
19 – Rusted reducing tee and elbow to be replaced 20 – Dry pendant sprinkler head in cooler to be replaced.
21 – 7th Floor Stairwell 22 – Standpipe Riser and Hose Valve in stairwell. Hose valve to be replaced per SOW
23 – Standpipe riser and locked OS&Y valve for future floor control zone.
Field Report 12-09-2019
Building 11A – 8th Floor
1 – Insulation on sprinkler piping to be repaired 2 – Missing sprinkler protection under ductwork
3 – Drain valve 4 – Tee fitting corroded, replace with new.
5 – 8th Floor Stairwell 6 – Floor control valve in stairwell
7 – Floor control valve, pressure gauge and hose valve in stairwell
8 – Sprinklers missing over area in mechanical room. Provide 2 heads 9 – Fire hose valve in stairwell, to be replaced per
SOW
10 – Drain elbow rusted in stairwell, replace valve.
| 10-02-2019 - Building 11 - Lower Level Field Report |
| 12-11-2019 - Building 11A - 1st Floor Field Report |
| 11-06-2019 - Building 11A - 2nd Floor Field Report |
| 11-14-2019 - Building 11A - 3rd Floor Field Report |
| 12-11-2019 - Building 11A - 3rd Floor Field Report |
| 11-14-2019 - Building 11A - 4th Floor Field Report |
| 11-14-2019 - Building 11A - 5th Floor Field Report |
| 12-11-2019 - Building 11A - 5th Floor Field Report |
| 12-10-2019 - Building 11A - 6th Floor Field Report |
| 12-10-2019 - Building 11A - 7th Floor Field Report |
| 12-11-2019 - Building 11A - 7th Floor Field Report |
| 12-09-2019 - Building 11A - 8th Floor Field Report |
| 12-11-2019 - Building 11A - 8th Floor Field Report |
File details come from the government source that posted it. Updated .