About this file

36C25219B0054 0002 S06 - Amend 0002 Drawings_Part3.pdf

View the file

Other files

File Type Posted
36C25219B0054 0003 36C25219B0054 0003.docx DOCX document
36C25219B0054-0003000.docx DOCX document
36C25219B0054 0002 S06 - Amend 0002 Specs.pdf PDF
36C25219B0054 0002 S06 - Amend 0002 RFIs Answers.docx DOCX document
36C25219B0054 0002 36C25219B0054 0002.docx DOCX document
36C25219B0054 0002 S06 - Amend 0002 Drawings_Part2.pdf PDF
36C25219B0054 0002 S06 - Amend 0002 Drawings_Part1.pdf PDF
36C25219B0054-0002011.docx DOCX document
36C25219B0054-0002009.pdf PDF
36C25219B0054-0002010.pdf PDF
36C25219B0054-0002006.docx DOCX document
36C25219B0054-0002008.pdf PDF
36C25219B0054-0002007.pdf PDF
36C25219B0054 0001 S06 - Wage Determination 07.19.19.pdf PDF
36C25219B0054 0001 36C25219B0054 0001.docx DOCX document
36C25219B0054 0001 S04 - Site Visit Sign In 7-18-19.pdf PDF
36C25219B0054-0001000.docx DOCX document
36C25219B0054-0001002.pdf PDF
36C25219B0054-0001001.pdf PDF
36C25219B0054 Drawings Part1.pdf PDF
36C25219B0054 36C25219B0054_1.docx DOCX document
36C25219B0054 J_A FireStop.pdf PDF
36C25219B0054 J_A 3JCI Controls.pdf PDF
36C25219B0054 Drawings Part2.pdf PDF
36C25219B0054 Drawings Part4.pdf PDF
36C25219B0054 Specifications2 695-18-120.pdf PDF
36C25219B0054 Wage Determinations.pdf PDF
36C25219B0054 Drawings Part3.pdf PDF
36C25219B0054 J_A 3EatonATS.pdf PDF
36C25219B0054-002.pdf PDF
36C25219B0054-010.pdf PDF
36C25219B0054-001.docx DOCX document
36C25219B0054-004.pdf PDF
36C25219B0054-007.pdf PDF
36C25219B0054-003.pdf PDF
36C25219B0054-009.pdf PDF
36C25219B0054-006.pdf PDF
36C25219B0054-008.pdf PDF
36C25219B0054-005.pdf PDF
36C25219B0054 36C25219B0054.docx DOCX document
36C25219B0054-000.docx DOCX document
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT + ENGINEERS:

Office of

Construction and Facilities

Management

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Bancroft AE No.

700 Nicholas Blvd. Suite 300

Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com

Revisions: Date

KEY PLAN:

14-101

100% CONSTRUCTION DOCUMENTS SUBMITTAL - NOT FOR CONSTRUCTION

35% SCHEMATIC DESIGN SUBMITTAL

10-10-2018

95% CONSTRUCTION DOCUMENTS SUBMITTAL

N

100% CONSTRUCTION DOCUMENTS SUBMITTAL

ENGINEERS + CONSULTANTS:

VA CONTRACT NO. VA69D-14-D-0109

65% DESIGN DEVELOPMENT SUBMITTAL

12-07-2018

02-08-2019

04-19-2019

65% DESIGN DEVELOPMENT RESUBMITTAL

01-18-2019

95% CONSTRUCTION DOCUMENTS RESUBMITTAL 03-15-2019

AutoCAD SHX Text

PLAN LEGEND

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text 695-18-120

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

UPGRADE AND REPLACE

AutoCAD SHX Text

VARIOUS MOTOR CONTROL CENTERS

AutoCAD SHX Text 04-19-2019

AutoCAD SHX Text

BUILDING 111 - ELEVENTH FLOOR - FIRE AND LIFE SAFETY PLAN

AutoCAD SHX Text

CZ

AutoCAD SHX Text

JD

AutoCAD SHX Text G311-111

AutoCAD SHX Text

NTS

AutoCAD SHX Text N

AutoCAD SHX Text

BUILDING 111 - ELEVENTH FLOOR - FIRE AND LIFE SAFETY PLAN

AutoCAD SHX Text

AutoCAD SHX Text THIS SHEET MUST BE PRINTED IN COLOR TO IDENTIFY ALL FIRE AND SMOKE BARRIER SEPARATIONS

AutoCAD SHX Text DRAWING PROVIDED BY CLEMENT J. ZABLOCKI VA MEDICAL CENTER FOR INFORMATION PURPOSES ONLY THE VA SHALL NOT BE HELD LIABLE FOR THE ACCURACY OF THESE AS-BUILTS. THE INFORMATION IS DYNAMIC AND MAY CHANGE OVER TIME. THE VA GIVES NO WARRANTY AS TO THE ACCURACY, RELIABILITY, OR COMPLETENESS OF ITS DATA. THESE PLANS ARE INTENDED TO AID IN THE GATHERING OF RELEVANT DATA. ALL LOCATIONS AND INFORMATION SHALL BE FIELD VERIFIED BEFORE USE.

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT + ENGINEERS:

Office of

Construction and Facilities

Management

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Bancroft AE No.

700 Nicholas Blvd. Suite 300

Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com

Revisions: Date

KEY PLAN:

14-101

100% CONSTRUCTION DOCUMENTS SUBMITTAL - NOT FOR CONSTRUCTION

35% SCHEMATIC DESIGN SUBMITTAL

10-10-2018

95% CONSTRUCTION DOCUMENTS SUBMITTAL

N

100% CONSTRUCTION DOCUMENTS SUBMITTAL

ENGINEERS + CONSULTANTS:

VA CONTRACT NO. VA69D-14-D-0109

65% DESIGN DEVELOPMENT SUBMITTAL

12-07-2018

02-08-2019

04-19-2019

65% DESIGN DEVELOPMENT RESUBMITTAL

01-18-2019

95% CONSTRUCTION DOCUMENTS RESUBMITTAL 03-15-2019

111 AND 113

NOTES:

SPECIAL NOTES:

MOUNTING HEIGHTSDEVICE

"A" FT.

LAST ON

CIRCUIT.

FIRST ON

CIRCUIT.

PANELBOARD

1/2 WIRE LENGTH FROM FIRST TO

LAST RECEPTACLE OR LIGHTING

FIXTURE ON CIRCUIT.

PANELBOARD

LAST ON

CIRCUIT.

1/2 WIRE LENGTH FROM FIRST TO

LAST LIGHTING FIXTURE ON

CIRCUIT.

FIRST ON

CIRCUIT.

"B" FT.

"B" FT.

"A" FT.

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text 695-18-120

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

UPGRADE AND REPLACE

AutoCAD SHX Text

VARIOUS MOTOR CONTROL CENTERS

AutoCAD SHX Text 04-19-2019

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

WG

AutoCAD SHX Text

JD

AutoCAD SHX Text E001

AutoCAD SHX Text

1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT VARY. RAISED FLOORS SHALL BE CONSIDERED FINISHED FLOOR. 2. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO CONFORM WITH ARCHITECTURAL REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED. 3. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN VIOLATION OF ADA. 1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL DEVICES. 2. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.

AutoCAD SHX Text

48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD ACCESS).

AutoCAD SHX Text 48" TO CENTERLINE OF BOX MINIMUM (TOILETS). 66" TO CENTERLINE OF BOX MAXIMUM (SHOWERS - LOCATED OUT OF SPRAY AREA).

AutoCAD SHX Text

80" TO CENTERLINE OF DEVICE OR 6" BELOW CEILING, WHICHEVER IS LOWER.

AutoCAD SHX Text

80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" TO TOP.

AutoCAD SHX Text

FIRE ALARM VISUAL ONLY DEVICE OR A COMBINATION AUDIBLE AND VISUAL DEVICE

AutoCAD SHX Text

NOT LESS THAN 90" TO TOP OR 6" BELOW CEILING, WHICH EVER IS HIGHER.

AutoCAD SHX Text

48" TO CENTERLINE OF BOX - NOT MORE THAN 5'-0" FROM EXIT.

AutoCAD SHX Text

54" TO DIAL CENTER (NON-ACCESSIBLE). 48" TO HIGHEST OPERABLE PART (ACCESSIBLE).

AutoCAD SHX Text

12" CEILING TO CENTERLINE OR 7'-0" TO CENTERLINE IF CEILING IS OVER 8'-0".

AutoCAD SHX Text AS NOTED ON DRAWINGS. EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.

AutoCAD SHX Text 16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS. EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.

AutoCAD SHX Text 16" TO BOTTOM OF BOX. EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.

AutoCAD SHX Text 90" TO CENTERLINE OF SIGN OR CENTERED IN WALL AREA BETWEEN TOP OF DOOR AND CEILING.

AutoCAD SHX Text

DISCONNECT SWITCHES, MOTOR STARTERS, MOTOR PUSH BUTTON STATIONS

AutoCAD SHX Text 48" TO CENTERLINE OF BOX. EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET. 2. 480V MOTOR BRANCH CIRCUIT CONDUCTORS SHALL BE #12 AWG IN 3/4" C UNLESS OTHERWISE NOTED. 480V MOTOR BRANCH CIRCUIT CONDUCTORS SHALL BE #12 AWG IN 3/4" C UNLESS OTHERWISE NOTED. 3. SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS FOR TWO MOTORS (MAX.) ARE TO BE COMBINED IN ONE CONDUIT, INCREASE THE SIZE OF CONDUCTORS AND CONDUITS PER NATIONAL ELECTRICAL CODE (NEC), TO COMPENSATE FOR CONDUCTOR DE-RATING. 4. PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT.PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT.

AutoCAD SHX Text

MOUNTING HEIGHTS FOR ELECTRICAL DEVICES

AutoCAD SHX Text

WIRE SIZING TABLE

AutoCAD SHX Text

ELECTRICAL GENERAL NOTES

AutoCAD SHX Text

LIGHT SWITCHES, WALL MOUNTED OCCUPANCY SENSORS

AutoCAD SHX Text

WALL MOUNTED EXIT SIGNS

AutoCAD SHX Text

CEILING MOUNTED EXIT SIGNS

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

SPECIAL OUTLETS OR RECEPTACLES

AutoCAD SHX Text

PLUGMOLD OR WIREMOLD

AutoCAD SHX Text

CLOCK OUTLETS

AutoCAD SHX Text

DATA/COMMUNICATION OR TELEPHONE OUTLETS

AutoCAD SHX Text

TELEPHONE OUTLETS - WALL TYPE

AutoCAD SHX Text

PAY TYPE TELEPHONE OUTLETS

AutoCAD SHX Text

FIRE ALARM MANUAL PULL STATIONS

AutoCAD SHX Text

FIRE ALARM AUDIBLE ONLY DEVICE

AutoCAD SHX Text

WALL MOUNTED REMOTE INDICATOR LIGHT

AutoCAD SHX Text

AREA OF REFUGE TELEPHONE

AutoCAD SHX Text

CALL FOR AID SWITCH WITH PULL CHAIN TO FLOOR

AutoCAD SHX Text

CARD READER

AutoCAD SHX Text

INTERCOM STATION

AutoCAD SHX Text

SOUND SYSTEM VOLUME CONTROL

AutoCAD SHX Text

MICROPHONE OUTLETS

AutoCAD SHX Text

THERMOSTATS

AutoCAD SHX Text

TEMPERATURE/HUMIDITY SENSORS

AutoCAD SHX Text

60" TO CENTER LINE OF BOX.

AutoCAD SHX Text 54" TO HIGHEST OPERABLE PART (SIDE ACCESS). 48" HIGHEST OPERABLE PART (FORWARD ACCESS).

AutoCAD SHX Text

16" TO BOTTOM OF BOX.

AutoCAD SHX Text 54" TO HIGHEST OPERABLE PART (SIDE ACCESS). 48" HIGHEST OPERABLE PART (FORWARD ACCESS).

AutoCAD SHX Text 54" TO HIGHEST OPERABLE PART (SIDE ACCESS). 48" HIGHEST OPERABLE PART (FORWARD ACCESS).

AutoCAD SHX Text

SAME AS TELEPHONE - ACCESSIBLE.

AutoCAD SHX Text

16" TO BOTTOM OF BOX.

AutoCAD SHX Text

80" TO BOTTOM FIXTURE.

AutoCAD SHX Text

60" TO CENTERLINE.

AutoCAD SHX Text

48" MAXIMUM TO COIN SLOT.

AutoCAD SHX Text

IF DISTANCE (A+B) IN FEET IS: (SEE DIAGRAM AT RIGHT)

AutoCAD SHX Text

FOR 120V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

AutoCAD SHX Text USE COPPER WIRE IN METALLIC CONDUIT, AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT AND SIZE CONDUIT ACCORDINGLY.

AutoCAD SHX Text

#12 AWG (MIN.) #10 AWG #8 AWG #6 AWG (MAX.)

AutoCAD SHX Text

FOR 277V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

AutoCAD SHX Text

#12 AWG (MIN.) #10 AWG #8 AWG #6 AWG (MAX.)

AutoCAD SHX Text 0' TO 100' TO 100' 100' 100' TO 175' TO 175' 175' 175' TO 300' TO 300' 300' 300' TO 450'TO 450'450'

AutoCAD SHX Text USE COPPER WIRE IN METALLIC CONDUIT, AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT AND SIZE CONDUIT ACCORDINGLY.

AutoCAD SHX Text

IF DISTANCE (A+B) IN FEET IS: (SEE DIAGRAM AT RIGHT)

AutoCAD SHX Text 0' TO 250' TO 250' 250' 250' TO 400' TO 400' 400' 400' TO 700' TO 700' 700' 700' TO 1000'TO 1000'1000'

AutoCAD SHX Text SEE PROJECT GENERAL NOTES AND OTHER REQUIREMENTS INCLUDING THE LIFE SAFETY AND INFECTION CONTROL REQUIREMENTS LOCATED WITHIN THE GENERAL DRAWINGS SECTION. COMPLY WITH REQUIREMENTS AS THEY ARE A DIRECT PART OF THIS SECTION AND AS IF THEY WERE DIRECTLY INCLUDED AND PROVIDED BELOW. 1. CODES: THE WORK SHALL COMPLY WITH APPLICABLE LOCAL, MUNICIPAL, CODES: THE WORK SHALL COMPLY WITH APPLICABLE LOCAL, MUNICIPAL, STATE AND NATIONAL CODES. WHERE THE CONSTRUCTION DOCUMENTS INDICATE MORE RESTRICTIVE REQUIREMENTS THE CONSTRUCTION DOCUMENTS SHALL GOVERN. HOWEVER, THE CONSTRUCTION DOCUMENTS SHALL NOT BE INTERPRETED AS AUTHORITY TO VIOLATE ANY CODE OR REGULATION. WORK, MATERIAL, AND EQUIPMENT SHALL COMPLY WITH REQUIREMENTS OF THE LATEST EDITIONS AND INTERIM AMENDMENTS OF THE NATIONAL ELECTRICAL CODE (N.E.C.), NATIONAL ELECTRICAL SAFETY CODE, OSHA, AND APPLICABLE FEDERAL, STATE, AND LOCAL LAWS AND ORDINANCES. ELECTRICAL EQUIPMENT PROVIDED UNDER THIS CONTRACT SHALL BE NEW (EXCEPT WHERE OTHERWISE NOTED) AND SHALL BEAR THE MARK OF NATIONALLY RECOGNIZED TESTING LABORATORY, WHEN APPLICABLE. EQUIPMENT OF THE SAME TYPE AND CAPACITY SHALL BE BY THE SAME MANUFACTURER. 2. ELECTRICAL DRAWINGS: THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ELECTRICAL DRAWINGS: THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED. THE LOCATION OF RACEWAY SYSTEM COMPONENTS IS SCHEMATIC. THE EXACT LOCATION OF RACEWAY SYSTEM COMPONENTS SHALL BE DETERMINED BY THE CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL CONFIRM THE DIMENSIONS OF THE ACTUAL EQUIPMENT TO BE SUPPLIED FOR THIS PROJECT, VERIFY CLEARANCES AND ROUGH-INS, AND OBTAIN COR APPROVAL PRIOR TO STARTING WORK. 3. COORDINATION WITH OTHER TRADES: THE ELECTRICAL CONTRACTOR SHALL COORDINATION WITH OTHER TRADES: THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE SET OF GENERAL, ARCHITECTURAL AND ENGINEERING DOCUMENTS AND COORDINATE WITH MECHANICAL, PLUMBING, ARCHITECTURAL, AND OTHER TRADES FOR EXACT DIMENSIONS, CLEARANCES AND ROUGH-IN LOCATIONS. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR 120 VOLT (AND HIGHER) AC POWER TO OTHER TRADES EQUIPMENT AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, CONTROLS, FIRE AND SECURITY SYSTEMS, MOTORIZED DOORS, DAMPERS, LIFTS, AND OTHER SYSTEMS. UNLESS SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH SAFETY DISCONNECT SWITCHES TO MECHANICAL EQUIPMENT. THE CONTRACTOR SHALL CHECK ARCHITECTURAL, STRUCTURAL, AND MECHANICAL TRADES WORK FOR POSSIBLE INTERFERENCE CAUSED BY CONDITIONS IN THE FIELD, 4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, RECEIVING, UNLOADING, UNCRATING, STORING SETTING IN PLACE, AND PROTECTING FROM DAMAGE, VANDALISM, THEFT OR WEATHER DURING CONSTRUCTION FOR NEW EQUIPMENT FURNISHED BY THE ELECTRICAL CONTRACTOR. 5. FIRE STOPPING: PENETRATIONS IN WALLS, FLOORS OR CEILINGS SHALL BE FIRE STOPPING: PENETRATIONS IN WALLS, FLOORS OR CEILINGS SHALL BE SUITABLY CLOSED UP AND SEALED. WHEN NEW CABLES/CONDUITS PENETRATE EXISTING FIRE RATED PENETRATIONS, IT SHALL BE SEALED TO MATCH EXISTING RATING TO ENSURE IT RETAIN EXISTING CONDITIONS. REFER TO SPECIFICATION SECTION 07 84 00 FOR DETAIL INFORMATION. 6. PAINTING: NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO MATCH PAINTING: NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO MATCH THE ADJACENT WALL OR CEILING SURFACE UNLESS THE REQUIRED COLOR CODING IS SPECIFIED. 7. VA FURNISHED EQUIPMENT: EQUIPMENT THAT WILL BE FURNISHED BY THE VA VA FURNISHED EQUIPMENT: EQUIPMENT THAT WILL BE FURNISHED BY THE VA WILL BE INDICATED ON A SCHEDULE OR BE INCLUDED IN SPECIFIC NOTES OR SPECIFICATIONS. THE CONTRACTOR SHALL COORDINATE WITH THE VA/COR FOR DELIVERY SCHEDULES. THE CONTRACTOR IS TO ASSUME THAT ON SITE STORAGE IS NOT BE AVAILABLE WHEN COORDINATING DELIVERY OF EQUIPMENT. THE CONTRACTOR, IN COORDINATION WITH THE VA/COR, WILL INSPECT THE DELIVERY FOR ACCURACY AND SHIPMENT DAMAGE AND ACCEPTING THE EQUIPMENT. THE CONTRACTOR SHALL BE RESPONSIBLE TO STORE, PROTECT, AND ULTIMATELY INSTALL THE EQUIPMENT. 8. ELECTRICAL SERVICE DISRUPTIONS: CONTRACTOR SHALL SUBMIT LOCK ELECTRICAL SERVICE DISRUPTIONS: CONTRACTOR SHALL SUBMIT LOCK OUT/TAG OUT PROCEDURE BEFORE START OF DEMOLITION WORK ON EXISTING MCC AND ELECTRICAL EQUIPMENT UNDER PROJECT SCOPE AND SUBMIT TO COR FOR APPROVAL. REFER TO SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR DETAIL INFORMATION. 9. EQUIPMENT: CONTRACTOR SHALL FURNISH LABOR, MATERIAL, TOOLS, EQUIPMENT: CONTRACTOR SHALL FURNISH LABOR, MATERIAL, TOOLS, EQUIPMENT SERVICES, AND ACCESSORIES FOR COMPLETE INSTALLATION OF ALL ELECTRICAL WORK AS NOTED. 10. MISCELLANEOUS SUPPORTING MEMBERS: ANGLES CHANNELS, AND OTHER MISCELLANEOUS SUPPORTING MEMBERS: ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL, BOLTS OR RODS REQUIRED TO SUPPORT LIGHT FIXTURES, CONDUIT, RACEWAYS, LADDER TRAYS, OR OTHER ELECTRICAL EQUIPMENT OR DEVICES SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO PURCHASING OR ROUGH-IN WORK. 11. SAFETY: CONTRACTOR SHALL TAKE STEPS NECESSARY TO ENSURE THE SAFETY: CONTRACTOR SHALL TAKE STEPS NECESSARY TO ENSURE THE SAFETY OF THE VA'S EMPLOYEES, BUILDING EMPLOYEES AND GUESTS, AS WELL AS THEIR OWN FORCES, BY ADEQUATELY PROTECTING EXPOSED LIVE CONDUCTORS, OR DEVICES THROUGHOUT THE COURSE OF THIS WORK. 12. EQUIPMENT CONNECTIONS: PROVIDE FINAL CONNECTIONS FOR EQUIPMENT EQUIPMENT CONNECTIONS: PROVIDE FINAL CONNECTIONS FOR EQUIPMENT FURNISHED UNDER OTHER DIVISIONS AND FOR VA FURNISHED EQUIPMENT. PROVIDE A FLEXIBLE LIQUID TIGHT CONNECTION TO VIBRATION PRODUCING EQUIPMENT. 13. TEMPORARY LIGHTING, POWER, FIRE, AND SAFETY: PROVIDE TEMPORARY TEMPORARY LIGHTING, POWER, FIRE, AND SAFETY: PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED IN AREAS UNDERGOING WORK DURING CONSTRUCTION. FURNISH AND INSTALL ONE OSHA APPROVED PIGTAIL SOCKET WITH 150-WATT LAMP FOR EVERY 500 SQUARE FEET OF FLOOR SPACE AND A MINIMUM 1 PER ROOM. THE TEMPORARY LIGHTING SHALL BE LEFT IN PLACE UNTIL PERMANENT LIGHTING IS COMPLETELY OPERATIONAL. FURNISH AND INSTALL POWER OUTLETS TO A TOTAL OF ONE FOR EVERY 2000 SQUARE FEET OR PART THEREOF OF FLOOR AREA. THESE SHALL BE 15 AMP, SINGLE PHASE RECEPTACLES FOR EITHER 110 OR 220 VOLTS AS DIRECTED BY THE GENERAL/PRIME CONTRACTOR. COORDINATE FOR ADDITIONAL TEMPORARY POWER REQUIREMENTS WITH OTHER TRADES AND PROVIDE AN ADEQUATE INSTALLATION. COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING CONSTRUCTION AND ALTERATION OPERATIONS. IN ADDITION, OPENINGS IN FIRE RATED SEPARATIONS BETWEEN OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND NON-OPERATIONAL) AREAS SHALL BE SEALED AT THE END OF EACH WORK DAY WITH AN APPROPRIATE FIRE RATED ENCLOSURE OR SEALANT. DO NOT COMPROMISE EXISTING SECURITY OR FIRE ALARM SYSTEMS SERVING THE OCCUPIED OR OPERATIONAL AREAS. DURING CONSTRUCTION THE CONTRACTOR SHALL MAINTAIN ELECTRICAL UTILITIES OF THE BUILDING WITHOUT INTERRUPTION. SHOULD IT BE NECESSARY TO INTERRUPT ANY ELECTRICAL SERVICE OR UTILITY, THE CONTRACTOR SHALL SECURE PERMISSION IN WRITING FROM THE VA/COR FOR SUCH INTERRUPTION AT LEAST 2 WEEKS IN ADVANCE. INTERRUPTION IN SERVICE OR UTILITY SHALL BE MADE WITH THE MINIMUM AMOUNT OF INCONVENIENCE TO THE VA AND SHUT-DOWN TIME SHALL BE ON A PREMIUM TIME/AFTER HOURS BASIS AND INCLUDED IN THE CONTRACTOR'S BID. CONTRACTOR SHALL PROVIDE NECESSARY TEMPORARY LIGHTING AND POWER FOR TRADES DURING CONSTRUCTION AND REMOVE IT AT COMPLETION OF WORK. CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN EACH PHASE OF WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL CITY, STATE, AND FEDERAL SAFETY LAWS (OSHA). 14. FINAL INSPECTION: ITEMS AND WORK SHALL BE TESTED FOR SAFE AND FINAL INSPECTION: ITEMS AND WORK SHALL BE TESTED FOR SAFE AND PROPER OPERATIONS. 15. UPON COMPLETION OF THE WORK, THE ELECTRICAL CONTRACTOR SHALL UPON COMPLETION OF THE WORK, THE ELECTRICAL CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE VA'S PROPERTY, LEAVING THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE WORKING CONDITION. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL OF CARTONS AND DEBRIS FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR INCLUDING EQUIPMENT FURNISHED BY THE VA. THE ABOVE SHALL ALSO APPLY TO EQUIPMENT FURNISHED BY OTHERS AND UNPACKED OR REMOVED FROM CARTON, BY THE CONTRACTOR. 16. WORK IS SEQUENCED INTO PHASES. FOR EACH PHASE, THE CONTRACTOR WORK IS SEQUENCED INTO PHASES. FOR EACH PHASE, THE CONTRACTOR SHALL REVIEW THE DEMOLITION AND CONSTRUCTION PORTION OF EACH PHASE PRIOR STARTING. 17. PHASES WILL INVOLVE TRANSFERRING FEEDER CABLES FROM OLD MOTOR PHASES WILL INVOLVE TRANSFERRING FEEDER CABLES FROM OLD MOTOR CONTROL CENTERS TO NEW PANELS AND/OR MOTOR CONTROL CENTERS. CONTRACTOR SHALL TEST THE FEEDERS FOR REUSABILITY PER SPECIFICATION 26 05 19, SECTION 3.10, ACCEPTANCE CHECKS AND TESTS. 18. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING OVERCURRENT CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY, RELATED CALCULATION AND ANALYSIS AS INDICATED IN SPECIFICATION 26 05 73.

AutoCAD SHX Text

1. EXAMINATION EXAMINATION A. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS FOR VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS FOR DEVICES SHOWN ON DRAWINGS. B. DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION AND EXISTING DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION AND EXISTING RECORD DRAWINGS. REPORT DISCREPANCIES TO OWNER BEFORE DISTURBING EXISTING INSTALLATION. CONTRACTOR SHALL COORDINATE WITH OWNER FOR ANY HIDDEN/UNFORESEEN WORK FOUND AFTER COMMENCEMENT OF WORK THAT NEEDS TO BE REWORKED/RELOCATED TO COMPLETE THE NEW WORK. C. COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING CONDITIONS. D. REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS FOR FOR REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS FOR FOR ANY OTHER ELECTRICAL REQUIREMENTS. 2. PREPARATION PREPARATION A. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. 3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK. A. REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS INDICATED ON THE DRAWINGS AND AS NOTED HEREIN. B. ABANDONED WIRING BACK TO SOURCE OF SUPPLY AND REMOVE ABANDONED WIRING BACK TO SOURCE OF SUPPLY AND REMOVE ABANDONED CONDUIT BACK TO NEAREST ACCESSIBLE JUNCTION BOX FOR ALL EQUIPMENT SHOWN TO BE REMOVED. C. WHERE SOURCE OF SUPPLY IS A PANELBOARD, RE-LABEL PROTECTIVE WHERE SOURCE OF SUPPLY IS A PANELBOARD, RE-LABEL PROTECTIVE DEVICE AS "SPARE". AFTER DEMOLITION IS COMPLETE, SUBMIT REVISED PANELBOARD SCHEDULES INDICATING "SPARES" TO OWNER AND ENGINEER. D. REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. CUT CONDUIT FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES. CONDUIT MAY BE ABANDONED IN WALLS TO REMAIN BUT EXISTING WIRING WITHIN THESE CONDUITS TO BE REMOVED COMPLETELY. E. REMOVE AND DISCONNECT ABANDONED OUTLETS AND ASSOCIATED REMOVE AND DISCONNECT ABANDONED OUTLETS AND ASSOCIATED DEVICES. F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION EQUIPMENT. G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT THAT IS DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT THAT IS NO LONGER IN USE. H. DISCONNECT AND REMOVE ABANDONED LUMINARIES. REMOVE BRACKETS, DISCONNECT AND REMOVE ABANDONED LUMINARIES. REMOVE BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES. I. REMOVE ACCESSIBLE ABANDONED WIRING OR CAP AND LABEL IN JUNCTION REMOVE ACCESSIBLE ABANDONED WIRING OR CAP AND LABEL IN JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE. J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION OF WORK. K. MAINTAIN AND RESTORE, IF INTERRUPTED, CONDUITS AND CONDUCTORS MAINTAIN AND RESTORE, IF INTERRUPTED, CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS. 4. CLEANING, REPAIR, AND REPLACEMENT CLEANING, REPAIR, AND REPLACEMENT A. GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT WILL REMAIN OR ARE TO BE REUSED. B. PANELBOARDS: CLEAN EXPOSED SURFACES AND TIGHTEN ALL ELECTRICAL PANELBOARDS: CLEAN EXPOSED SURFACES AND TIGHTEN ALL ELECTRICAL CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR VACANT POSITIONS. PROVIDE TYPED SCHEDULES SHOWING REVISED CIRCUITING INFORMATION. C. LUMINARIES: REMOVE EXISTING LUMINARIES AS NOTED. LUMINARIES: REMOVE EXISTING LUMINARIES AS NOTED. 5. DISPOSAL DISPOSAL A. OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS THAT HAVE BEEN DEMOLISHED PRIOR TO DISPOSAL OR REMOVAL FROM SITE. B. ANY EQUIPMENT OR MATERIALS NOT WANTED BY THE OWNER SHALL ANY EQUIPMENT OR MATERIALS NOT WANTED BY THE OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND REMOVED FROM SITE. C. CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND REGULATIONS FOR DISPOSAL OF DEMOLISHED MATERIALS AND EQUIPMENT.

GENERAL NOTES - DEMOLITION

1. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR ON THIS

SHEET AND NOT ON THE PLANS.

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE FAULT

CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CB CODE BLUE

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL

PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kAIC KILO AMPERE INTERRUPTING CAPACTITY kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LSIG LONG, SHORT, INSTANTANEOUS GROUND

FAULT PICKUP

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TEMP TEMPORARY

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WQM WATER QUALITY MONITOR

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ELECTRICAL SYMBOLS - DIAGRAM ELECTRICAL SYMBOLS - POWER / DATA PLAN ELECTRICAL SYMBOLS - LIGHTING PLAN

ELECTRONIC SAFETY AND SECURITY SYMBOLS

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER

TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

PANELBOARD

EQUIPMENT TAG

SEE EQUIPMENT SCHEDULE

CABLE AND CONDUIT TAG

SEE SCHEDULE

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

TIME CLOCK

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED

FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.

POWER JUNCTION BOX

TRANSFORMER, PLAN

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

WYE CONNECTION

EARTH GROUND

LADDER CABLE TRAY

PULL BOX

WIREWAY

REGULAR POWER

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER

RECEPTACLE, QUADRAPLEX

LIFE SAFETY POWER

CRITICAL POWER

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS

OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR

AS INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE,

DATA & RECEPTACLE.

VARIABLE FREQUENCY DRIVE

VFD

DOUBLE GANG DEEP AUDIO/VISUAL JUNCTION BOX

SWITCH

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DOOR SWITCH

DM= DIMMER K = KEY OPERATED

LV= LOW VOLTAGE L = LOCK

LM= LOW VOLTAGE MASTER P = WITH PILOT LIGHT

PB= PUSH BUTTON STATION RC= REMOTE CONTROL

T = TIMER OPERATED WP= WEATHER PROOF

X = EXPLOSION PROOF Mo= OCCUPANCY SENSOR

SWITCH, LAMP HOLDER POLE

LIGHT FIXTURE RECESSED ROUND CEILING MOUNTED DOWNLIGHT

LIGHT FIXTURE, RECESSED LED, 2'x4'

LIGHT FIXTURE, RECESSED LED 1'x4'

LIGHT FIXTURE, SURFACE MOUNTED LED, 2'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 1'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, LED EMERGENCY

LIGHT FIXTURE, RECESSED LED, 2'x2'

LIGHT FIXTURE, SURFACE MOUNTED LED

LIGHT TRACK WITH HEADS AS SHOWN

LIGHT FIXTURE, STRIP/INDUSTRIAL LED; LETTER INDICATES TYPE.

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE RECESSED SQUARE CEILING MOUNTED DOWNLIGHT

SWITCH, EXTERIOR PHOTO CELL FOR CONTROL OF EXTERIOR LIGHTING

LIGHTING, UNDERCABINET LIGHT/COVE LIGHT

SWITCH, OCCUPANCY SENSOR REFER TO FIXTURE SCHEDULE FOR TYPE

ALARM, FIRE, MANUAL PULL STATION

ALARM, HORN/LIGHT, ONE ASSEMBLY

ALARM, SPEAKER/LIGHT, ONE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

SMOKE DETECTOR

DETECTOR, SMOKE, FOR DUCT

FIRE ALARM LINE = FA

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

ALARM, HORN, ONE ASSEMBLY

EMERGENCY BATTERY BACK-UP EGRESS LIGHT

CEILING MOUNTED RECEPTACLE FOR PROJECTOR

DOUBLE FACED CEILING OR WALL MOUNTED EXIT SIGN. ARROW INDICATES

DIRECTION

SINGLE FACED CEILING OR WALL MOUNTED EXIT SIGN.

ARROW INDICATES DIRECTION

HOMERUN TO PANELBOARDS. SLASHED LINES INDICATE NUMBER

OF #12 AWG WIRES IN 3/4"C UNLESS OTHERWISE NOTED. LONG

SLASH INDICATES NEUTRAL, LONG SLASH WITH DOT INDICATES

EQUIPMENT GROUND.

THREE PORT TELEPHONE DATA OUTLET - MOUNTED 18" AFF

UNLESS OTHERWISE NOTED.

SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE

COUNTER TOP / COUNTER TOP BACK SPLASH.

NURSE CALL DOME LIGHT-CEILING MOUNTED.

NURSE CALL DOME LIGHT-WALL MOUNTED 54" AFF UNLESS

OTHERWISE NOTED.

NURSE CALL DUTY STATION-MOUNTED 54" AFF UNLESS

OTHERWISE NOTED.

EMERGENCY NURSE CALL.

ALARM, LIGHT/STROBE, ONE ASSEMBLY (WALL MOUNTED)

SPECIAL PURPOSE RECEPTACLE, VOLTAGE, RATING AND

MOUNTING AS NOTED ON PLANS

JUNCTION BOX WITH DISCONNECT SWITCH AND FLEXIBLE CONDUIT

CONNECTION

PP PUSH PLATE (AUTO OPENING DOOR)

DUAL COIL SPEAKER FOR PA AND FIRE ALARM.

BARE COPPER CLASS II STRANDED SIZE MIN

#4/0 LIGHTNING PROTECTION CONDUCTOR

LIGHTNING PROTECTION CLASS II AIR TERMINAL

SIZE 1/2" DIA. X 24" LONG WITH ADAPTER.

EXOTHERMIC GROUND CONNECTION

MECHANICAL GROUND CONNECTION

LIGHTNING PROTECTION SYMBOLS

CONDUIT UP

CONDUIT DOWN

ELECTRICAL SYMBOLS ELECTRICAL ABBREVIATIONS

GENERAL NOTES

P A SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE

COUNTER TOP / COUNTER TOP BACK SPLAH.

CEILING MOUNTED SECURITY CAMERA

WALL MOUNTED CARD READER

C

CR

KEYPAD LOCKKP

AIPHONEAIP

CEILING MOUNTED DOME SECURITY CAMERA

ACCESS CONTROL PANELACP

ROOF POLE MOUNTED SECURITY CAMERA

CAMERA CONTROL PANELCCP

C

REQUEST TO EXITREX

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT + ENGINEERS:

Office of

Construction and Facilities

Management

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Bancroft AE No.

700 Nicholas Blvd. Suite 300

Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com

Revisions: Date

KEY PLAN:

14-101

100% CONSTRUCTION DOCUMENTS SUBMITTAL - NOT FOR CONSTRUCTION

35% SCHEMATIC DESIGN SUBMITTAL

10-10-2018

95% CONSTRUCTION DOCUMENTS SUBMITTAL

N

100% CONSTRUCTION DOCUMENTS SUBMITTAL

ENGINEERS + CONSULTANTS:

VA CONTRACT NO. VA69D-14-D-0109

65% DESIGN DEVELOPMENT SUBMITTAL

12-07-2018

02-08-2019

04-19-2019

65% DESIGN DEVELOPMENT RESUBMITTAL

01-18-2019

95% CONSTRUCTION DOCUMENTS RESUBMITTAL 03-15-2019

111 AND 113

STAB-IN TYPE DEVICE

AutoCAD SHX Text

NCS

AutoCAD SHX Text

NCT

AutoCAD SHX Text J

AutoCAD SHX Text

PB

AutoCAD SHX Text

TC

AutoCAD SHX Text T

AutoCAD SHX Text J

AutoCAD SHX Text

PB

AutoCAD SHX Text A/V

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text S

AutoCAD SHX Text

PC

AutoCAD SHX Text

OCX

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text

DH

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text J

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

FA

AutoCAD SHX Text

PS

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text Y

AutoCAD SHX Text

XX

AutoCAD SHX Text

ELECTRONIC SAFETY AND SECURITY SYMBOLS

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text 695-18-120

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

UPGRADE AND REPLACE

AutoCAD SHX Text

VARIOUS MOTOR CONTROL CENTERS

AutoCAD SHX Text 04-19-2019

AutoCAD SHX Text

SYMBOL LIST

AutoCAD SHX Text

WG

AutoCAD SHX Text

JD

E002

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT + ENGINEERS:

Office of

Construction and Facilities

Management

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Bancroft AE No.

700 Nicholas Blvd. Suite 300

Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com

Revisions: Date

KEY PLAN:

14-101

100% CONSTRUCTION DOCUMENTS SUBMITTAL - NOT FOR CONSTRUCTION

35% SCHEMATIC DESIGN SUBMITTAL

10-10-2018

95% CONSTRUCTION DOCUMENTS SUBMITTAL

N

100% CONSTRUCTION DOCUMENTS SUBMITTAL

ENGINEERS + CONSULTANTS:

VA CONTRACT NO. VA69D-14-D-0109

65% DESIGN DEVELOPMENT SUBMITTAL

12-07-2018

02-08-2019

04-19-2019

65% DESIGN DEVELOPMENT RESUBMITTAL

01-18-2019

95% CONSTRUCTION DOCUMENTS RESUBMITTAL 03-15-2019

111 AND 113

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text 695-18-120

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

UPGRADE AND REPLACE

AutoCAD SHX Text

VARIOUS MOTOR CONTROL CENTERS

AutoCAD SHX Text 04-19-2019

AutoCAD SHX Text

WORK SEQUENCE NOTES

AutoCAD SHX Text

WG

AutoCAD SHX Text

JD

AutoCAD SHX Text E003

AutoCAD SHX Text

GENERAL WORK SEQUENCE NOTES

AutoCAD SHX Text

1. SEQUENCES OF OPERATION LISTED ON THIS SHEET ARE SEQUENCES OF OPERATION LISTED ON THIS SHEET ARE GENERAL SEQUENCES OF CONSTRUCTION FOR THE INSTALLATION OF ELECTRICAL EQUIPMENT LISTED UNDER EACH PHASE FOR THIS PROJECT. THE SEQUENCES ARE MEANT TO BE USED AS A REFERENCE AND ARE NOT INTENDED TO BE A DETAILED STEP BY STEP GUIDE FOR THE INSTALLATION OF ALL EQUIPMENT AND THE TRANSFER OF ALL EXISTING INCOMING FEEDER, LOAD SIDE FEEDER/BRANCH CABLES, AND CONTROL WIRING. CONTRACTOR SHALL REFER TO PLAN DRAWINGS AND SINGLE LINE DIAGRAMS FOR DETAILED SCOPE IN EACH PHASE. 2. CONTRACTOR SHALL PROVIDE A DETAILED SEQUENCE OF CONTRACTOR SHALL PROVIDE A DETAILED SEQUENCE OF CONSTRUCTION, CLEARLY INDICATING ALL OUTAGE, INCLUDING OSHA MANDATED LOCK-OUT TAG-OUT PROCEDURE TO COR FOR APPROVAL PRIOR TO BEGINNING OF WORK FOR EACH PHASE. 3. CONTRACTOR SHALL NOT PERFORM WORK ON ENERGIZED CONTRACTOR SHALL NOT PERFORM WORK ON ENERGIZED EQUIPMENT AND WILL BE IN COMPLIANCE WITH NFPA 70E "ELECTRICAL SAFETY IN THE WORKPLACE". 4. WHILE SIZE AND LOCATION OF NEW WORK AND EQUIPMENT WHILE SIZE AND LOCATION OF NEW WORK AND EQUIPMENT IN EXISTING AREA HAS BEEN INDICATED ON DRAWINGS AS ACCURATELY AS POSSIBLE, CONTRACTOR SHALL ADJUST HIS WORK AS REQUIRED TO AVOID EXISTING UTILITIES, GAS LINES, SEWER, FIRE ALARM, ROOF DRAINS, ACCESS COVERS, AND OTHER STRUCTURES NOT PARTICULARLY SHOWN ON PLAN AT NO ADDITIONAL COST. IN ORDER TO COMPLY WITH NEC ELECTRICAL DEDICATED SPACE AND WORKING CLEARANCE REQUIREMENTS, CONTRACTOR SHALL PROVIDE NECESSARY RELOCATION OF FOREIGN UTILITIES. BEFORE CONSTRUCTION, INSPECT PREMISES, MAKE A DETAILED EXAMINATION OF LOCATIONS WHERE NEW WORK IS TO BE INSTALLED AND EXAMINE EXISTING PIPING, CONDUITS, STRUCTURAL SUPPORTING BEAMS, AND OTHER CONDITIONS. 5. PROVIDE CONFINED SPACE ENTRY POLICIES AS APPLICABLE PROVIDE CONFINED SPACE ENTRY POLICIES AS APPLICABLE AND AS REQUIRED BY OSHA. THESE POLICIES SHALL BE SUBMITTED FOR PRIOR APPROVAL BY COR. 6. PROVIDE NEW PRECAST CONCRETE EQUIPMENT PADS FOR PROVIDE NEW PRECAST CONCRETE EQUIPMENT PADS FOR ALL NEW MOTOR CONTROL CENTERS AND TRANSFORMERS MOUNTED TO FLOORS. PAD SHALL BE 4" THICK AND FASTENED TO EXISTING FLOOR. SEE DETAIL 5/E801. 7. ALL EXISTING EQUIPMENT IS TO REMAIN OPERATIONAL DURING ALL EXISTING EQUIPMENT IS TO REMAIN OPERATIONAL DURING THE CONSTRUCTION PERIOD. ANY TEMPORARY WIRING OR REROUTING OF CIRCUITRY TO ACHIEVE THIS IS BY THE ELECTRICAL CONTRACTOR. SHUTDOWN OF EXISTING SERVICES SHALL ONLY BE PERMITTED UPON WRITTEN APPROVAL FROM THE COR AND THEN ONLY FOR THE DATE AND DURATION AGREED UPON. INCLUDE ALL PREMIUM TIME CHARGES IN THE BASE BID. CONTRACTOR SHALL RESPONSIBLE FOR ENSURING POWER TO TEMPORARY PANEL, TEMPORARY INSTALLATION SHALL BE IN COMPLIANCE WITH NEC ARTICLE 590. 8. IN ORDER TO PERMIT DEMOLITION AND REPLACEMENT OF IN ORDER TO PERMIT DEMOLITION AND REPLACEMENT OF EXISTING MOTOR CONTROL CENTERS WITH NEW MOTOR CONTROL CENTERS OR EXISTING MOTOR CONTROL CENTERS WITH NEW DISTRIBUTION PANELS, CONTRACTOR SHALL FIELD DETERMINE THE CONNECTION POINTS BETWEEN EXISTING INCOMING FEEDER, LOAD SIDE FEEDER/BRANCH AND CONTROL WIRING WITH NEW RESPECTIVE WIRING AND PROVIDE SPLICING IN JUNCTION/PULL BOX AS FIELD CONDITIONS DICTATE.

AutoCAD SHX Text

PHASE 1 WORK SEQUENCE

AutoCAD SHX Text

1. CONTRACTOR SHALL FURNISH AND INSTALL FOLLOWING NEW CONTRACTOR SHALL FURNISH AND INSTALL FOLLOWING NEW EQUIPMENT. REFER TO PHASE 1 SINGLE LINE DIAGRAM FOR SIZES OF VARIOUS NEW EQUIPMENT, CABLES, CONDUITS, AND NEW CIRCUIT BREAKERS. A. PROVIDE CIRCUIT BREAKERS FOR EXISTING PANEL PROVIDE CIRCUIT BREAKERS FOR EXISTING PANEL DH-B02-3 B. PROVIDE REMOTE STARTERS ON TEMPORARY UNISTRUT PROVIDE REMOTE STARTERS ON TEMPORARY UNISTRUT RACK FOR EQUIPMENTS THAT WILL BE MOVED FROM MCC PH-B02-1 C. REPLACE EXISTING MCC EPH-Q-B02-1 WITH NEW REPLACE EXISTING MCC EPH-Q-B02-1 WITH NEW DISTRIBUTION PANEL D. REPLACE EXISTING PANEL EUL-CR-B02-3 WITH NEW REPLACE EXISTING PANEL EUL-CR-B02-3 WITH NEW PANEL E. REPLACE EXISTING TRANSFORMER ECRT-23 WITH NEW REPLACE EXISTING TRANSFORMER ECRT-23 WITH NEW TRANSFORMER F. REPLACE EXISTING ATS-8 WITH NEW ATS REPLACE EXISTING ATS-8 WITH NEW ATS G. REPLACE EXISTING ATS-9 WITH NEW ATS REPLACE EXISTING ATS-9 WITH NEW ATS H. REPLACE EXISTING ATS-10 WITH NEW ATS REPLACE EXISTING ATS-10 WITH NEW ATS I. REPLACE EXISTING ATS-11 WITH NEW ATS REPLACE EXISTING ATS-11 WITH NEW ATS J. REPLACE EXISTING MTS-TSX WITH NEW ATS REPLACE EXISTING MTS-TSX WITH NEW ATS K. REPLACE EXISTING MTS-TSXX WITH PULL BOX REPLACE EXISTING MTS-TSXX WITH PULL BOX L. PROVIDE MTS FOR PNEUMATIC TUBE SYSTEM PROVIDE MTS FOR PNEUMATIC TUBE SYSTEM PHASE 1 REFERENCE DRAWINGS: ED501-111 - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION E501-111 - BUILDING 111 SINGLE LINE DIAGRAM - BUILDING 111 SINGLE LINE DIAGRAM BUILDING 111 SINGLE LINE DIAGRAM ED100A-111 - PHASE 1 DEMOLITION PLAN - PHASE 1 DEMOLITION PLAN PHASE 1 DEMOLITION PLAN E100A-111 - PHASE 1 CONSTRUCTION PLAN - PHASE 1 CONSTRUCTION PLAN PHASE 1 CONSTRUCTION PLAN E700A.1-111 - PHASE 1 SINGLE LINE DIAGRAM - PHASE 1 SINGLE LINE DIAGRAM PHASE 1 SINGLE LINE DIAGRAM E700A.2-111 - PHASE 1 SINGLE LINE DIAGRAM- PHASE 1 SINGLE LINE DIAGRAMPHASE 1 SINGLE LINE DIAGRAM

AutoCAD SHX Text

PHASE 2 WORK SEQUENCE

AutoCAD SHX Text

1. CONTRACTOR SHALL DEMOLISH EXISTING INCOMING FEED TO PANEL CONTRACTOR SHALL DEMOLISH EXISTING INCOMING FEED TO PANEL EPH-Q-B04-1 FROM PANEL EPH-Q-B06-1 LOCATED IN MER 2 (B0621). 2. PROVIDE NEW INCOMING FEEDER TO PANEL EPH-Q-B04-1 FROM PROVIDE NEW INCOMING FEEDER TO PANEL EPH-Q-B04-1 FROM MTS- PNEUMATIC TUBE SYSTEM. REFER TO PHASE 2 SINGLE LINE DIAGRAM FOR SIZE. PHASE 2 REFERENCE DRAWINGS: ED501-111 - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION E501-111 - BUILDING 111 SINGLE LINE DIAGRAM - BUILDING 111 SINGLE LINE DIAGRAM BUILDING 111 SINGLE LINE DIAGRAM ED100B-111 - PHASE 2 DEMOLITION PLAN - PHASE 2 DEMOLITION PLAN PHASE 2 DEMOLITION PLAN E100B-111 - PHASE 2 CONSTRUCTION PLAN - PHASE 2 CONSTRUCTION PLAN PHASE 2 CONSTRUCTION PLAN E700B-111 - PHASE 2 SINGLE LINE DIAGRAM- PHASE 2 SINGLE LINE DIAGRAMPHASE 2 SINGLE LINE DIAGRAM

AutoCAD SHX Text

PHASE 3 WORK SEQUENCE

AutoCAD SHX Text

1. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. REFER TO PHASE 3 SINGLE LINE DIAGRAM FOR SIZES OF VARIOUS NEW EQUIPMENT, CABLES, CONDUITS, AND NEW CIRCUIT BREAKERS. A. REPLACE EXISTING MCC EUH-Q-16-1 WITH NEW REPLACE EXISTING MCC EUH-Q-16-1 WITH NEW DISTRIBUTION PANEL B. REPLACE EXISTING TRANSFORMER EQT-11 WITH NEW REPLACE EXISTING TRANSFORMER EQT-11 WITH NEW TRANSFORMER C. REPLACE EXISTING PANELS EUL-Q-16-1 AND REPLACE EXISTING PANELS EUL-Q-16-1 AND EUL-Q-16-2 WITH ONE NEW PANEL. CONSOLIDATE ALL EXISTING CIRCUITS INTO NEW PANEL. 2. REFER TO PHASE 3 SINGLE LINE DIAGRAM FURNISH AND REFER TO PHASE 3 SINGLE LINE DIAGRAM FURNISH AND INSTALL REMOTE STARTER. FILED VERIFY THE LOCATION. 3. PROVIDE PANEL EPH-Q-103-1(N) SPECIFIED IN PHASE 6. PROVIDE PANEL EPH-Q-103-1(N) SPECIFIED IN PHASE 6. THIS PANEL SHALL BE USED AS A TEMP PANEL FOR THIS PHASE AND AFTER COMPLETION OF THIS PHASE, WILL BE INSTALLED IN PHASE 6 AS A PERMANENT PANEL. REFER TO PHASE 6 SINGLE LINE DIAGRAM FOR DETAILS FOR THE SIZES OF BREAKERS NEEDED ON THIS PANEL. PHASE 3 REFERENCE DRAWINGS: ED501-111 - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION E501-111 - BUILDING 111 SINGLE LINE DIAGRAM - BUILDING 111 SINGLE LINE DIAGRAM BUILDING 111 SINGLE LINE DIAGRAM ED101-111 - PHASE 3 DEMOLITION PLAN - PHASE 3 DEMOLITION PLAN PHASE 3 DEMOLITION PLAN E101-111 - PHASE 3 CONSTRUCTION PLAN - PHASE 3 CONSTRUCTION PLAN PHASE 3 CONSTRUCTION PLAN E701-111 - PHASE 3 SINGLE LINE DIAGRAM- PHASE 3 SINGLE LINE DIAGRAMPHASE 3 SINGLE LINE DIAGRAM

AutoCAD SHX Text

PHASE 4 WORK SEQUENCE

AutoCAD SHX Text

1. CONTRACTOR SHALL FURNISH AND INSTALL NEW CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. REFER TO PHASE 4 SINGLE LINE DIAGRAM FOR SIZES OF VARIOUS NEW EQUIPMENT, CABLES, CONDUITS, AND NEW CIRCUIT BREAKERS. A. REPLACE EXISTING MCC EPH-Q-24-3 WITH NEW REPLACE EXISTING MCC EPH-Q-24-3 WITH NEW DISTRIBUTION PANEL B. REPLACE EXISTING TRANSFORMER EQT-13 WITH NEW REPLACE EXISTING TRANSFORMER EQT-13 WITH NEW TRANSFORMER C. REPLACE EXISTING TRANSFORMER ELST-12 WITH NEW REPLACE EXISTING TRANSFORMER ELST-12 WITH NEW TRANSFORMER D. REPLACE EXISTING TRANSFORMER ECRT-21 WITH NEW REPLACE EXISTING TRANSFORMER ECRT-21 WITH NEW TRANSFORMER E. REPLACE EXISTING PANEL EUL-CR-24-6 AND REPLACE EXISTING PANEL EUL-CR-24-6 AND EUL-CR-24-7 WITH ONE NEW PANEL F. PROVIDE NEW MANUAL TRANSFER SWITCH MTS-COMP. PROVIDE NEW MANUAL TRANSFER SWITCH MTS-COMP. CONTROL AND INSTALL IN MER 6 (6420) LOCATED ON SIXTH FLOOR 2. FOR TEMPORARY POWER NEEDS DURING REPLACEMENT, FOR TEMPORARY POWER NEEDS DURING REPLACEMENT, CONTRACTOR SHALL PROVIDE TEMPORARY PANEL TEMP-4/5/6/7/113. REFER TO PHASE 4, 5, 6, 7, AND GRAPHIC BLDG. 113 SINGLE LINE DIAGRAMS AND PROVIDE REQUIRED CIRCUIT BREAKER. AFTER COMPLETION OF THIS PHASE WORK, SAME PANEL SHALL BE USED AS A TEMP PANEL FOR PHASE NEXT PHASE. PHASE 4 REFERENCE DRAWINGS: ED501-111 - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION E501-111 - BUILDING 111 SINGLE LINE DIAGRAM - BUILDING 111 SINGLE LINE DIAGRAM BUILDING 111 SINGLE LINE DIAGRAM ED102-111 - PHASE 4 DEMOLITION PLAN - PHASE 4 DEMOLITION PLAN PHASE 4 DEMOLITION PLAN E102-111 - PHASE 4 CONSTRUCTION PLAN - PHASE 4 CONSTRUCTION PLAN PHASE 4 CONSTRUCTION PLAN E702-111 - PHASE 4 SINGLE LINE DIAGRAM- PHASE 4 SINGLE LINE DIAGRAMPHASE 4 SINGLE LINE DIAGRAM

AutoCAD SHX Text

PHASE 6 WORK SEQUENCE

AutoCAD SHX Text NOTE: IN ORDER TO MINIMIZE DOWNTIME TO LOADS SERVED BY IN ORDER TO MINIMIZE DOWNTIME TO LOADS SERVED BY THE MCC IN THIS PHASE DURING REPLACEMENT, WORK IN THIS PHASE SHALL BE PERFORMED DURING SUMMER MONTHS PER VA REQUEST. 1. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. REFER TO PHASE 6 SINGLE LINE DIAGRAM FOR SIZES OF VARIOUS NEW EQUIPMENT, CABLES, CONDUITS, AND NEW CIRCUIT BREAKERS. A. REPLACE EXISTING MCC EPH-Q-103-1 WITH NEW REPLACE EXISTING MCC EPH-Q-103-1 WITH NEW DISTRIBUTION PANEL B. REPLACE EXISTING DISTRIBUTION PANEL PH-103-1 WITH REPLACE EXISTING DISTRIBUTION PANEL PH-103-1 WITH NEW DISTRIBUTION PANEL. C. REPLACE EXISTING TRANSFORMER EQT-18 WITH NEW REPLACE EXISTING TRANSFORMER EQT-18 WITH NEW TRANSFORMER 2. FOR TEMPORARY POWER NEEDS DURING REPLACEMENT, FOR TEMPORARY POWER NEEDS DURING REPLACEMENT, CONTRACTOR SHALL PROVIDE TEMPORARY PANEL TEMP-4/5/6/7/113. REFER TO PHASE 4, 5, 6, 7, AND GRAPHIC BLDG. 113 SINGLE LINE DIAGRAMS AND PROVIDE REQUIRED CIRCUIT BREAKER. AFTER COMPLETION OF THIS PHASE WORK, SAME PANEL SHALL BE USED AS A TEMP PANEL FOR PHASE NEXT PHASE. PHASE 6 REFERENCE DRAWINGS: ED501-111 - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION - BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION BUILDING 111 SINGLE LINE DIAGRAM-DEMOLITION E501-111 - BUILDING 111 SINGLE LINE DIAGRAM - BUILDING 111 SINGLE LINE DIAGRAM BUILDING 111 SINGLE LINE DIAGRAM ED110-111 - PHASE 6 DEMOLITION PLAN - PHASE 6 DEMOLITION PLAN PHASE 6 DEMOLITION PLAN E110-111 - PHASE 6 CONSTRUCTION PLAN - PHASE 6 CONSTRUCTION PLAN PHASE 6 CONSTRUCTION PLAN E710-111 - PHASE 6 SINGLE LINE DIAGRAM- PHASE 6 SINGLE LINE DIAGRAMPHASE 6 SINGLE LINE DIAGRAM

AutoCAD SHX Text

PHASE 5 WORK SEQUENCE

AutoCAD SHX Text

1. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT. CONTRACTOR SHALL FURNISH AND INSTALL NEW EQUIPMENT.