ADDENDUM NO. 1

UPGRADE AIR HANDLER UNIT-9 AND LOCKER ROOMS

OSCAR G. JOHNSON VA MEDICAL CENTER

IRON MOUNTAIN, MICHIGAN

VA PROJECT NO. 585-17-111

This Addendum is issued to modify, explain or correct the original drawings and specifications and is hereby made part of the Contract Documents.

REQUESTS FOR INFORMATION

1. QUESTION: New Work Plan Sheet A101B, Note 10 states to infill with partition type S3-010. I did not see this particular wall type on

Sheet A610B.

RESPONSE: Refer to following wall type:

2. QUESTION: I couldn’t find where you specified a certain concrete sealer for the corridor and shipping and receiving floor.

RESPONSE: Reference Section 03 30 53 CAST-IN-PLACE CONCRETE, Article 2.1

MATERIALS, Paragraph N (100 percent active colorless aqueous siliconate solution); and Article 3.8 SURFACE TREATMENTS, Paragraph B (Use for exposed concrete floors and concrete floors to receive carpeting.)

BERNERS-SCHOBER ASSOCIATES, INC.

GREEN BAY, WISCONSIN

November 16, 2018