36C25027Q0065.pdf
PDF 654 KB Posted
- Attached to
- H941--Chemical Hoods & HEPA PM
- Solicitation number
- 36C25027Q0065
About this file
This is a Solicitation/Contract/Order (Standard Form 1449) issued by the Department of Veterans Affairs, Network Contracting Office 10, for chemical hoods and HEPA filter testing and maintenance services at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana.
The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Business (SDVOSB). The contract encompasses a 12-month base period beginning November 15, 2026, and ending November 14, 2027, with four optional 12-month renewal periods and one partial 6-month option period, for a total potential contract value of $19 million. The solicitation number is 36C25027Q0065, with an offer due date of November 10, 2026, at 10:00 EST. The Performance Work Statement requires comprehensive testing, certification, environmental monitoring, and HEPA filtration services for laboratory containment equipment, pharmacy engineering controls, research equipment, and selected engineering HEPA filtration systems across the medical center. Services include annual certifications and semiannual inspections for various biosafety cabinets, laminar airflow workstations, compounding aseptic isolators, chemical fume hoods, and HEPA filter systems, with viability sampling for pharmacy areas and condition-based filter replacements priced separately. A mandatory pre-proposal site visit is scheduled for November 3, 2026, at 10:00 AM, and quotations from vendors not attending will not be accepted. The contract requires monthly invoicing submitted electronically through the VA's designated portal, with recurring services priced as firm-fixed-price line items and optional HEPA replacements and other variable work separately priced. Contractor personnel must comply with VA credentialing requirements including PIV card eligibility, and the contract incorporates standard FAR and VAAR clauses including those addressing security prohibitions, DEI compliance, covered telecommunications equipment restrictions, and basic safeguarding of contractor information systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment II - VAAR 852.219-75.pdf | ||
| Attachment I - SCA WD.pdf | ||
| 36C25027Q0065.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE 1 OF 1. REQUISITION NO.
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NO. 5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
a. NAME b. TELEPHONE NO. (No Collect Calls) 8. OFFER DUE DATE/LOCAL
TIME
9. ISSUED BY CODE 10. THIS ACQUISITION IS UNRESTRICTED OR SET ASIDE: % FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE 16. ADMINISTERED BY CODE
17a. CONTRACTOR/OFFEROR CODE FACILITY CODE 18a. PAYMENT WILL BE MADE BY CODE
TELEPHONE NO. UEI: EFT:
PHONE: FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE ADDENDUM
19. 20. 21. 22. 23. 24.
ITEM NO. SCHEDULE OF SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________ 29. AWARD OF CONTRACT: REF. ___________________________________ OFFER
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DATED ________________________________. YOUR OFFER ON SOLICITATION
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION (REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
583-27-2-669-0011
36C25027Q0065 10-27-2026
Luke A. Turner 513-559-3702 11-10-2026
10:00 EST
36C250
Department of Veterans Affairs
Network Contracting Office 10
260 E University Avenue
Cincinnati OH 45219-2356
X 100
X
541620
$19 Million
N/A
X
Richard L. Roudebush VA Medical Center
1481 W. 10th Street
Indianapolis, IN 46202-2803
36C250
Department of Veterans Affairs
36C250
Financial Services Center
Invoices to be submitted electronically https://www.tungsten-network.com
877-489-6135
See CONTINUATION Page
Chemical Hoods & HEPA PM.
Contact Information: Luke A. Turner, Contracting Officer
513-559-3702, luke.turner@va.gov.
Deliver Services To: Reference Block 15
Please submit your quotation to luke.turner@va.gov, by the closing date/time of this solicitation. No physical quotes will be accepted.
As outlined in the SOW, a site visit is being offered for
11-03-2026, at 10:00 AM Local Time. Quotes from vendors who do not attend the site visit will not be accepted. All attendees must meet at the Building 6 conference room.
See CONTINUATION Page
583-3670162-669-854100-2543 010055590
X X
Luke A. Turner
VA-VHA-RPOC-2024-0076
36C25027Q0065
Table of Contents
SECTION A
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
B.2 PERFORMANCE WORK STATEMENT
B.2 PRICE/COST SCHEDULE
SECTION C - CONTRACT CLAUSES
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION)
C.2 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)
C.3 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000)
C.4 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS
(DEVIATION APR 2026)
C.5 52.240-91 SECURITY PROHIBITIONS AND EXCLUSIONS (NOV 2025)
(DEVIATION)
C.6 52.240-93 BASIC SAFEGAURDING OF COVERED CONTRACTOR INFORMATION
SYSTEMS (DEVIATION) (NOV 2025)
C.7 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—CERTIFICATE
OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (OCT 2026) (DEVIATION) ...44
C.8 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS
D.1 ATTACHMENT I - SCA WD
D.2 ATTACHMENT II - VAAR 852.219-75
SECTION E - SOLICITATION PROVISIONS
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND
COMMERCIAL SERVICES (OCT 2025) (DEVIATION)
E.2 52.209-7 INFORMATION REGARDING RESPONSIBILITY MATTERS (NOV 2025)
(DEVIATION)
E.3 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION)
E.4 52.233-2 SERVICE OF PROTEST (NOV 2025) (DEVIATION)
E.5 52.240-90 SECURITY PROHIBITIONS AND EXCLUSIONS REPRESENTATIONS
AND CERTIFICATIONS (NOV 2025) (DEVIATION)
E.6 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB
1998)
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
1. Contract Administration: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
b. GOVERNMENT: Contracting Officer 36C250 Luke A. Turner/CO
2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:
[] 52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or
[] 52.232-36, Payment by Third Party
3. INVOICES: Invoices shall be submitted in arrears:
a. Quarterly []
b. Semi-Annually []
c. Other [X] Monthly
4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.
https://www.tungsten-network.com/customer-campaigns/veteransaffairs/
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the
Solicitation numbered and dated as follows:
AMENDMENT NO DATE
B.2 PERFORMANCE WORK STATEMENT
Testing, Certification, Environmental Monitoring, and HEPA Filtration Services
1.0 BACKGROUND
The Richard L. Roudebush VA Medical Center (RLRVAMC) requires recurring inspection, testing, certification, environmental monitoring, preventive service, and filter work for laboratory containment equipment, Pharmacy engineering controls and controlled environments, Research equipment, and selected Engineering HEPA filtration systems. The services support patient safety, employee safety, infection prevention, pharmaceutical compounding compliance, and reliable operation of critical ventilation and containment systems.
2.0 OBJECTIVE AND SCOPE
The Contractor shall furnish all qualified personnel, supervision, labor, test equipment, calibrated instruments, materials, consumables, transportation, reports, labels, videos, disposal services, and incidentals required for scheduled recurring work. Condition-based HEPA replacement filters and associated replacement services shall be furnished only when ordered under an applicable separately priced option contract line item. Pharmacy: certify five primary engineering controls (PECs) to ISO Class
5 specifications or better, certify three ISO Class 7 rooms, perform environmental monitoring, replace prefilters, service diffusers, and test 10 ceiling/pass-through HEPA filters.
Laboratory (P&LMS): service 18 active assets—13 Class II Type A2 BSCs, four chemical fume hoods, and one grossing station.
Research: service all 60 inventory entries—36 chemical fume hoods, 20 BSCs, two LFWS units, one hypoxia chamber, and one mini BSC/special containment device.
Engineering: annually inspect and test 24 HEPA filters in AHU 37A/37B, six HEPA filters in AHU 46, and two terminal HEPA filters in Operating Room 5 served by AHU 38; replace these filters only when failed, damaged, or otherwise unacceptable and authorized; and perform scheduled isolation-exhaust filter service.
The equipment inventories in Appendices A through D are part of the scope. The Contractor shall reconcile the physical inventory after award and shall not service or invoice unlisted equipment without written Government authorization.
2.1 Explicit Scope Boundaries
The AHU 37A/37B filters are the 24-filter bank serving the 9 operating rooms; they are not an additional set of 24 filters in each operating room.
The AHU 46 filters are the six 30-inch by 30-inch by 12-inch-deep HEPA filters serving the Cardiology procedure room.
Operating Room 5 is served by AHU 38. AHU 38 contains no central HEPA filters; the two HEPA filters in scope are terminal filters located in Operating Room 5 and are separate from the AHU 37A/37B filter bank.
Operating room and Cardiology room relationships are provided for system identification and outage coordination. Except for the terminal-filter and room-performance measurements expressly required for
Operating Room 5 in Section 8.5, general room certification, air-change verification, pressure testing, or cleanliness certification is excluded unless expressly stated elsewhere in this PWS.
Isolation-room listings identify systems served. Room-level pressure, ACPH, door/seal, or infection-control certification is excluded from the isolation-exhaust scope.
Repairs and replacement parts not expressly included are outside scope unless ordered under a funded line item or contract modification. Contractor-caused damage and retesting remain the Contractor's responsibility.
3.0 PERIOD AND PLACE OF PERFORMANCE
The anticipated period of performance is one 12-month base period and four 12-month option periods.
Each exercised period includes the service frequencies stated in this PWS.
Place of performance: Richard L. Roudebush VA Medical Center, 1481 West 10th Street, Indianapolis, Indiana 46202, including roofs, mechanical rooms, interstitial spaces, controlled Pharmacy areas, laboratories, Research spaces, and other listed locations.
4.0 APPLICABLE REQUIREMENTS AND ORDER OF PRECEDENCE
The following editions are the technical basis for this PWS. The edition is incorporated by solicitation or contract controls. A later revision does not change contract scope or price unless incorporated by the
Contracting Officer. The Contractor shall promptly notify the COR/COTR and Contracting Officer of conflicts before proceeding.
29 CFR 1910.1450, Occupational Exposure to Hazardous Chemicals in Laboratories, including the facility Chemical Hygiene Plan requirements applicable to hood operation and maintenance.
VHA Directive 1108.12, Management and Monitoring of Pharmaceutical Compounded Sterile
Preparations, dated February 14, 2024.
USP General Chapter <797>, Pharmaceutical Compounding—Sterile Preparations, and USP General
Chapter <800>, Hazardous Drugs—Handling in Healthcare Settings, official versions in effect for the facility.
CETA CAG-002 (2026), CAG-003 (2022), CAG-005 (2025), CAG-006 (2023), CAG-008 (2022), CAG-
009 (2023), CAG-014 (2022), and CAG-015 (2025), as applicable to the specific equipment and service.
ISO 14644-1:2015, ISO 14644-2:2015, and ISO 14644-3:2019.
NSF/ANSI 49-2024, Biosafety Cabinetry: Design, Construction, Performance, and Field Certification.
ANSI/ASHRAE Standard 110-2016 (RA 2025), Methods of Testing Performance of Laboratory Fume
Hoods.
ANSI/ASHRAE Standard 111-2024, Measurement, Testing, Adjusting, and Balancing of Building
HVAC Systems, where airflow system measurement is required.
ANSI/ASHRAE/ASHE Standard 170-2021 and adopted addenda applicable to health care ventilation systems.
IEST-RP-CC034.5 (2022), HEPA and ULPA Filter Leak Tests, and the applicable current edition of
IEST-RP-CC001 for HEPA filter performance and construction.
NFPA 45-2024, Standard on Fire Protection for Laboratories Using Chemicals, where applicable to chemical hood installation and operation.
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, 6th edition, as advisory biosafety practice were incorporated by facility policy.
VA HVAC Design Manual, VA Pharmacy Service Design Guide, VHA technical guidance, facility policies, infection-control requirements, and manufacturer instructions furnished or identified by the
Government.
Where the PWS prescribes a more frequent service interval than a referenced minimum, the PWS frequency controls. An asset shall not be represented as certified as a standard that does not apply to its equipment type or listing.
5.0 CONTRACTOR QUALIFICATIONS
Pharmacy PEC/SEC certification shall be performed by a CNBT Registered Certification Professional for
Sterile Compounding Facilities (RCP-SCF), or by a firm employing an RCP-SCF who is responsible for the work, as required by VHA Directive 1108.12.
Class II BSC field certification shall be performed by personnel holding current NSF Enhanced BSC
Field Certifier accreditation or another qualification specifically accepted by the applicable standard and the Government.
The lead fume-hood tester shall hold a current CNBT fume-hood credential or demonstrate equivalent documented training and experience with ASHRAE 110 field testing acceptable to the Government.
The lead HEPA/cleanroom tester shall hold a current CNBT cleanroom-testing credential or demonstrate equivalent documented training and experience with in-place aerosol-photometer testing and the cited
IEST/CETA methods.
Personnel conducting viable environmental monitoring shall be trained in aseptic sampling, chain of custody, incubation/media controls, result interpretation, and applicable USP/CETA requirements.
Analysis shall be performed by a qualified microbiology laboratory using documented methods.
The Contractor shall submit technician names, roles, credentials, certificate numbers, expiration dates, relevant experience, and proposed assignments before work begins and whenever personnel change.
All measuring instruments shall be appropriate for the range and accuracy required, maintained in calibration at the manufacturer-prescribed interval, and traceable to recognized standards where applicable.
6.0 PRE-PERFORMANCE SUBMITTALS AND INVENTORY VERIFICATION
6.1 Mandatory Pre-Proposal Site Visit
Offerors shall attend the Government-scheduled site visit. Offerors shall inspect accessible equipment, housings, service clearances, filter banks, test ports, roof/interstitial access, shutdown constraints, and controlled-area entry requirements. Offerors shall verify conditions that materially affect labor, materials, access, safety, scheduling, and pricing.
AHU 37A/37B contains eighteen 24-inch by 24-inch by 11.5-inch deep and six 12-inch by 24-inch by
11.5-inch deep. Offerors shall field-verify dimensions, construction, efficiency, gasket orientation, and replacement requirements.
AHU 46 contains six nominal 30-inch by 30-inch by 12-inch-deep HEPA filters. Offerors shall verify actual dimensions, construction, efficiency, and gasket orientation.
Operating Room 5 contains two terminal HEPA filters served by AHU 38, which have no central HEPA filters. Offerors shall verify each terminal filter's location, dimensions, manufacturer, model, efficiency rating, housing and seal type, access method, test ports, upstream aerosol-injection access, downstream scan access, and replacement requirements.
Pharmacy contains 10 HEPA filters identified collectively as ceiling and pass-through HEPA filters. The
Government does not have the final filter-by-filter allocation; offerors shall verify the number, location, equipment association, access method, and filter identifiers.
Offers will not be accepted from companies that do not attend the site visit. Performance issues in the past made this a necessary restriction to apply to the procurement.
6.2 Post-Award Submittals
Within 10 business days after award: Quality Control Plan, safety plan, credential roster, instrument/calibration list, sample report forms, and proposed annual schedule.
Within 30 calendar days after award: reconciled electronic inventory identifying each asset, room, asset number, manufacturer, model, serial number, equipment classification, service frequency, filter quantity/size/efficiency, and discrepancies.
Before each controlled-area event: work plan, proposed tests, sampling map, shutdown/access needs, aerosol and containment method, and infection-control controls.
No newly discovered asset, repair, or replacement may be performed or invoiced without written authorization under the contract.
7.0 SCHEDULING, ACCESS, AND PROTECTION OF OPERATIONS
Normal performance hours are 0700 through 1800, Monday through Friday, excluding Federal holidays.
Early morning, evening, weekend, and shutdown work may be required to protect patient care and departmental operations. All work shall be scheduled through the COR.
Pharmacy semiannual certifications shall be scheduled so the interval does not exceed six months. Other semiannual events shall be approximately six months apart; annual events shall be completed within the applicable 12-month certification interval.
The Contractor shall not shut down an air handler, exhaust fan, PEC, or critical system without an approved outage and explicit authorization to proceed.
Work in sterile compounding, operating-room, procedural, laboratory, roof, or interstitial areas shall comply with facility infection-control, interim life-safety, fall-protection, lockout/tagout, and access requirements.
Aerosol challenge shall be planned and contained so challenge material is not introduced into occupied clinical spaces or other systems. The Contractor shall coordinate isolation, shutdown, purge, and return-to-service criteria with the COR/COTR and affected department.
Operating Room 5 testing shall be performed during an approved operating-room outage. The Contractor shall coordinate diffuser removal, aerosol challenge, purge or clearance, cleaning, reassembly, and return to service with the COR/COTR and affected operating-room personnel.
Photography and video are limited to required equipment documentation and smoke studies. Images must exclude patients, protected health information, computer screens, labels containing patient data, and unauthorized personnel.
8.0 TECHNICAL PERFORMANCE REQUIREMENTS
8.1 Pharmacy PECs, SECs, Environmental Monitoring, and HEPA Filters
The Contractor shall perform a complete semiannual certification event for all five Pharmacy PECs and all three ISO Class 7 rooms. The five PECs consist of two Class II Type A2 BSCs, two LAFWs, and one
CAI. Semiannual PEC testing shall include the applicable field-certification tests; it is not a limited visual inspection.
Perform nonviable particle counting and classification; measure and document supply and exhaust airflow; calculate and report total air changes per hour (ACPH) for each room; and verify pressure relationships and segregation, temperature, relative humidity, airflow visualization, HEPA filter integrity, and applicable alarms and monitors, as required by USP, CETA, VA, and the approved room design. For the non-HD classified room, the certification report shall separately state: (1) ACPH provided by HVAC supply air and (2) total ACPH, including the airflow contribution from the LAFWs located in that room.
The report shall identify the room volume and measured airflow values used in each calculation. BSCs:
inflow and downflow measurements, supply and exhaust HEPA leak testing, dynamic airflow smoke patterns with video, alarms/interlocks, site installation assessment, and other NSF/ANSI 49 and CETA tests applicable to the model and installation.
LAFWs: HEPA leak testing, airflow velocity and uniformity, nonviable particle count, induction-leak/back-streaming evaluation, dynamic airflow smoke visualization with video, alarms/controls, and diffuser inspection.
CAI: HEPA leak testing, airflow and particle performance, chamber and transfer-chamber pressure, ingress/egress or recovery testing, dynamic airflow smoke visualization with video, alarms/interlocks, and glove/sleeve integrity when required by the manufacturer or governing procedure.
Pass-through HEPA filter(s): test in accordance with CETA CAG-015, the manufacturer method, and the applicable room/containment requirements. Report each pass-through separately.
Perform 48 viable air and surface field samples of PECs, pass-throughs, and ISO Class 7 rooms at each semiannual event. Samples should be collected and incubated in accordance with the dual plate method, each site will have a separate bacterial and fungal sample. Required positive/negative media controls and blanks are additional and shall not be counted among the 48 field samples.
Provide complete laboratory analysis, colony counts, alert/action-level comparison, required organism identification, excursion assessment, and follow-up recommendations. Maintain chain of custody and media/incubation records.
Replace four LAFW prefilters (two per LAFW) semiannually and dispose of removed prefilters. Remove and clean five laminar-flow hood/PEC diffusers semiannually in accordance with manufacturer instructions.
Inspect and perform filter integrity-test for all 10 Pharmacy ceiling/pass-through HEPA filters semiannually. HEPA replacement is condition-based and requires written authorization; see Section 9.0.
Certification activities must be conducted during the hours of 8:00 to 17:00, Monday through Friday during standard business days. Certifications will not be conducted on weekends nor on Federal Holidays without express authorization of Compounded Sterile Preparations Pharmacy Program Manager and
COR.
Contractor shall send at least two personnel to perform certification activities due to the locations of ceiling HEPA filter test ports.
8.2 Laboratory (P&LMS)
The active Laboratory inventory is 13 Class II Type A2 BSCs, four chemical fume hoods, and one grossing station. Missing model, asset, or certification-history fields shall be verified during inventory reconciliation.
BSCs: certify annually using NSF/ANSI 49 field-certification tests applicable to each cabinet. Apply a certification label showing date, status, certifier, and next due date.
Chemical fume hoods: test annually at the designated operating sash position, including condition inspection, face-velocity traverse and uniformity, airflow visualization, sash operation, monitor/alarm verification, fan/exhaust response, and comparison with the facility/manufacturer design criterion.
ASHRAE 110 tracer-gas containment testing is required when the facility Chemical Hygiene Plan, manufacturer, prior certification basis, risk assessment, post-modification condition, failure investigation, or COR/COTR direction requires it. It shall not be substituted for routine measurements or billed without the applicable priced authorization.
Grossing station: annually verify exhaust capture using manufacturer criteria and applicable ventilation methods, including velocity/capture measurements, smoke visualization, controls/alarms, lighting and work-surface condition, and drainage/utility observations relevant to safe operation.
8.3 Research
The Research inventory contains 60 entries: 36 chemical fume hoods, 20 BSCs, two LFWS units, one hypoxia chamber, and one mini BSC/special containment device. All 60 entries are included. The hypoxia chamber is in room D3014.
Standard BSCs: certify annually using the applicable NSF/ANSI 49 field tests and manufacturer criteria.
Chemical fume hoods: test annually using the routine operational tests and tracer-gas conditions stated in
Section 8.2.
LFWS units: certify semiannually for HEPA integrity, airflow velocity/uniformity, particle performance, airflow visualization, alarms/controls, and applicable manufacturer criteria.
Mini BSC/special containment device: determine the actual equipment classification, listing, manufacturer, and intended function. Perform the applicable manufacturer and containment tests annually. Do not label the device NSF-certified unless it is eligible and all applicable criteria are met.
Hypoxia chamber: annually perform manufacturer-required preventive maintenance and functional certification, including oxygen/atmosphere sensor calibration, control and alarm verification, door/seal condition, purge and gas-supply safety functions, exhaust/containment observations, and documented setpoint accuracy. Do not represent this chamber as a BSC or fume hood.
Provide up to two BSC/biological containment decontamination events per contract year only when the
Contracting Officer exercises the applicable separately priced option contract line item. The COR/COTR may validate the need and coordinate scheduling and access.
8.4 AHU 37A/37B and AHU 46 HEPA Filter Banks
Annual service is inspection and applicable integrity/performance testing. Routine annual replacement is prohibited. Each filter and filter-bank position shall receive a unique durable identifier that is carried forward in reports.
Inspect filter media, frames, gaskets, seals, clamps, holding frames, housing surfaces, penetrations, access doors, test ports, and evidence of moisture, corrosion, bypass, damage, loading, or microbial contamination.
Record filter manufacturer, model, serial/lot if available, nominal/actual dimensions, efficiency/performance level, installation date if known, orientation, design airflow, measured differential pressure, and observed condition.
Perform in-place aerosol-photometer leak testing under operating conditions using IEST-RP-CC034.5.
Establish and document upstream challenge concentration and uniformity; scan the downstream filter face, perimeter, gasket, frame, and accessible penetrations; and apply the acceptance criterion for the installed filter's performance level and approved test method.
Measure/document airflow, face velocity, differential pressure, and other system performance needed to establish that testing occurred under representative conditions. Identify limitations that prevent a complete scan; a limited test shall not be reported as a full certification.
Permitted adjustment, reseating, or manufacturer-allowed repair shall be documented and require
COR/COTR coordination. Filters that remain unacceptable, are damaged, or exceed manufacturer/standard repair limits shall be recommended for replacement under Section 9.0.
Following test activity, restore the system, verify normal airflow and controls, remove challenge aerosol in accordance with the approved plan, and obtain authorization before returning the system to clinical service.
8.5 Operating Room 5 Terminal HEPA Filters
AHU 38 serves Operating Room 5 and contains no central HEPA filters. Operating Room 5 contains two terminal HEPA filters. The Contractor shall inspect and test each terminal filter annually and after installation, replacement, repair, reseating, terminal-housing work, or another significant disturbance that could affect integrity or performance.
Inspect the filter media, frame, terminal housing, gasket or gel seal, retaining devices, diffuser, ceiling interface, accessible penetrations, and evidence of damage, deterioration, moisture, loading, or bypass.
Assign a durable unique identifier to each terminal filter and record its location, manufacturer, model, serial or lot number when available, nominal and actual dimensions, efficiency rating, installation date if known, housing and seal type, and observed condition.
Perform an in-place aerosol-photometer integrity and leak test under representative operating airflow using IEST-RP-CC034.5. Establish and document a safe upstream challenge concentration and uniformity for each terminal; scan the entire accessible downstream filter face, perimeter, frame, seal, housing joints, and penetrations; and apply the acceptance criterion for the installed filter's performance level, approved method, manufacturer requirements, and facility design.
Measure and report terminal airflow volume or face velocity and uniformity, as applicable to the terminal design, and differential pressure when a manufacturer-provided test port, gauge, or approved measurement method is available.
Under the representative operating mode, document total supply airflow to Operating Room 5, the room dimensions and calculated volume, total air changes per hour, room pressure relationship and airflow direction relative to adjacent spaces, temperature, and relative humidity. Compare results with the facility-approved design criteria and the contract-adopted VA and ASHRAE/ASHE healthcare ventilation requirements.
Identify any surface or component that could not be accessed or scanned. A limited scan or incomplete room-performance test shall not be reported as a complete certification.
After testing, reinstall and clean diffusers and disturbed surfaces as required, remove challenge aerosol under the approved plan, verify normal airflow and controls, document final operating status, and obtain authorization before returning Operating Room 5 to service.
8.6 Isolation Exhaust Filter Systems
Provide and replace 23 isolation-exhaust prefilters quarterly and 23 HEPA filters annually using the bag-in/bag-out or other housing-specific safe-change method. Verify quantities, sizes, filter-bank relationships, and housing access during the site visit and initial inventory reconciliation.
Coordinate exhaust shutdowns and room impact before work; follow facility infection-control and respiratory-protection requirements.
Contain, label, transport, and dispose of removed filters in accordance with the facility waste determination and applicable regulations. Do not assume all filters have the same waste classification.
After HEPA replacement, verify seating and seals, perform an in-place integrity test where the housing permits and the system requirement call for it, document differential pressure and operation, and obtain release to service.
9.0 CONDITION-BASED HEPA REPLACEMENT
This section applies to the 24 filters in AHU 37A/37B, six filters in AHU 46, two terminal HEPA filters in Operating Room 5, and 10 Pharmacy ceiling/pass-through HEPA filters. It does not change scheduled prefilter replacement or the stated annual isolation-exhaust HEPA replacement.
A HEPA filter shall be replaced only when one or more of the following is documented: failure of the applicable integrity/performance acceptance criterion; physical or moisture damage; failed gasket/frame/seal that cannot be corrected within manufacturer limits; unacceptable loading or pressure drop; contamination or condition requiring replacement under facility policy; or another manufacturer/standard requirement.
The Contractor shall immediately identify the filter, measured failure, acceptance criterion, operational consequence, recommended replacement, and proposed replacement filter.
The Contractor shall notify the COR/COTR and provide documentation supporting the recommended replacement. The COR/COTR may validate the technical need and recommend replacement.
Replacement shall not begin until the Contracting Officer provides written authorization by exercising the applicable separately priced option contract line item or issuing another authorized contractual action.
The applicable firm-fixed unit price shall include the correctly rated replacement filter, freight, labor, outage coordination, removal, containment, disposal, cleaning, gasket/seal materials, installation, labeling, and post-replacement integrity/performance testing.
Replacement filters shall match the approved dimensions, efficiency/performance level, airflow capacity, pressure-drop characteristics, frame construction, fire classification, gasket/gel-seal arrangement, and environmental compatibility. Substitutions require Government approval.
After installation, repeat the failed test and all tests needed to establish acceptable final operation. Report the complete sequence: initial result, failure, authorization, replacement, post-test, and final status.
10.0 SERVICE SUMMARY AND FREQUENCIES
Area Quantity / Asset Service Frequency
Pharmacy 5 PECs (2 BSC, 2
LAFW, 1 CAI)
Complete certification including but not limited to: Dynamic smoke-pattern testing with video; non-viable particle count;
HEPA filter challenge/leak testing;
airflow testing; applicable certification testing; ISO Class 5 classification
Semiannual; interval not to exceed 6 months
Area Quantity / Asset Service Frequency
Pharmacy 3 ISO Class 7 rooms
Room/SEC certification including but not limited to: USP room performance testing; ISO 7 environmental classification/particle testing;
pressure/airflow/ACPH [VHA requires 35
ACPH for ISO Class 7 rooms]
Semiannual
Pharmacy 48 field samples per event
Viable bacterial/fungal air and surface sampling; positive/negative controls additional; laboratory analysis; action-level comparison
Semiannual
Pharmacy 10 HEPA filters
HEPA filter challenge/leak testing for ceiling and pass-through HEPA filters;
replace only if authorized/required
Semiannual
Pharmacy 4 LAFW prefilters Change prefilters; dispose of removed filters (2 prefilters per LAFW) Semiannual
Pharmacy 5 PEC diffusers Remove, clean, and reinstall Semiannual
Laboratory 13 BSCs NSF/ANSI 49 field certification Annual
Laboratory 4 fume hoods Operational certification/testing Annual
Laboratory 1 grossing station Capture/exhaust certification Annual
Research 20 BSCs NSF/ANSI 49 field certification Annual
Research 36 fume hoods Operational certification/testing Annual
Research 2 LFWS units HEPA/airflow certification Semiannual
Research 1 hypoxia chamber Manufacturer PM and functional certification Annual
Research 1 mini BSC/special device
Classification and applicable containment certification Annual
Engineering
24 AHU 37A/37B
HEPA filters Inspect and integrity/performance test
Annual; replacement condition-based
Engineering 6 AHU 46 HEPA filters Inspect and integrity/performance test Annual; replacement condition-based
Engineering 2 OR 5 terminal HEPA filters
Integrity/leak testing; terminal airflow and room-performance verification
Annual and after disturbance;
replacement condition-based
Engineering 23 isolation prefilters Provide, replace, dispose Quarterly
Area Quantity / Asset Service Frequency
Engineering 23 isolation HEPA filters
Provide, replace, dispose; post-test as applicable Annual
On call
Up to 2 decontamination events/year
BSC/biological containment decontamination
Up to two events per contract year;
Contracting Officer authorization required.
11.0 REPORTING AND DELIVERABLES
The Contractor shall provide preliminary pass/fail information before leaving the work area. Critical deficiencies shall be reported immediately to the COR/COTR and affected department, followed by written notice within 24 hours. Final routine reports other than Pharmacy reports shall be submitted electronically within five business days after service. Final Pharmacy reports, including completed incubation and laboratory results, shall be submitted within 10 calendar days after service and within the
VHA reporting limit incorporated into the contract.
One searchable PDF report package and one editable electronic inventory/report data file for each service event.
Asset/system identification, room, department, date/time, operating condition, technician, credentials, and work performed.
Applicable standard/method and edition, manufacturer criterion, instrument identification, calibration date/status, raw measurements, calculations, acceptance criteria, and pass/fail determination. The final report shall include a current calibration certificate for each test instrument used. The certificate shall match the instrument identified in the report, be valid on the testing date, and document traceability to
NIST or another recognized standard, as applicable.
For HEPA tests: filter-bank or terminal-filter map, unique filter ID and location, upstream concentration and uniformity, scan method, leakage or penetration results, accessible surfaces scanned, limitations, repairs or adjustments, and final result.
For fume hoods: sash test position, traverse points, individual and average velocities, variability, smoke result, monitor/alarm result, observed cross-drafts/room conditions, and certification status.
For Pharmacy: whether testing occurred under dynamic or static conditions; room diagrams showing viable and nonviable sampling locations; equipment and room dimensions; supply and exhaust filters;
pressure differentials; total ACPH for each classified room; for the non-hazardous-drug room, supply-air
ACPH and total ACPH including LAFW airflow; number of personnel present during certification;
viable-sample media, lot, expiration, certificates of analysis, and incubation conditions; bacterial and fungal colony-forming-unit counts; genus and species identification when an action level is exceeded and identification is practicable; alert and action-level comparisons; as-found and as-left conditions for adjusted equipment; PEC-specific reports that reference manufacturer-approved values; calibration documentation; and smoke-study videos in a VA-acceptable format using clearly visible, neutrally buoyant smoke.
For Operating Room 5: each terminal filter's identifier and location, challenge concentration and uniformity, complete scan results, terminal airflow, total room supply airflow, room volume, calculated total air changes per hour, pressure relationship and airflow direction, temperature, relative humidity, test operating mode, access limitations, acceptance criteria, and final pass/fail status.
For filter replacement: old/new filter data, reason, authorization reference, disposal/manifest information as applicable, installation details, post-test data, and final return-to-service status.
Certification labels shall not be applied to failed equipment. Restricted/conditional labels shall plainly state the limitation and refer to the report.
Incomplete or inaccurate reports shall be corrected and resubmitted within three business days after
Government notice. The Contractor shall retain service documentation for at least six years after final payment, or longer if the contract or law requires.
12.0 DEFICIENCIES, CORRECTIVE ACTION, AND RETESTING
Class Definition Notification
Critical Immediate or significant patient, personnel, infection-control, containment, or critical-system risk
Immediate verbal notice;
written within 24 hours
Major Failure of an applicable acceptance criterion or inability to complete a required certification
Prompt COR/COTR notice and written deficiency in final report
Minor Condition requiring correction or monitoring without failure of required performance Document in routine report
Document the failed parameter, measured result, acceptance criterion, likely impact, and recommended corrective action.
Minor adjustments customarily required to complete certification are included. Repairs, parts, and condition-based replacements require written Contracting Officer authorization under the applicable priced option contract line item or another authorized contractual action.
Retesting after Contractor error, damage, improper adjustment, incomplete work, or invalid test is at no additional cost.
Retesting after an authorized Government repair or condition-based replacement shall be performed under the applicable contract line item and documented to final status.
13.0 QUALITY CONTROL AND GOVERNMENT SURVEILLANCE
The Contractor is responsible for quality control. The Quality Control Plan shall address personnel qualification, method control, calibration, sampling controls, report review, data integrity, nonconforming work, corrective action, and document retention. The Government may observe work, review records, independently verify measurements, reject incomplete deliverables, and require correction of nonconforming work.
Government observation, review, or acceptance does not relieve the Contractor of responsibility for compliance. The COR/COTR may coordinate and inspect performance but may not change contract terms, price, quantity ceilings, or funding.
14.0 SECURITY, PIV, AND FACILITY ACCESS
Because performance requires routine and continuing access to VA facilities, Contractor and subcontractor personnel assigned to unescorted work shall be eligible for, promptly apply for, obtain, and maintain the credential determined by VA, including a PIV card when required. The Contractor shall comply with FAR 52.204-9, VAAR 852.204-70, VA Directive 0735, and current VA credentialing procedures incorporated into the contract.
Initiate sponsorship, identity proofing, fingerprinting, background investigation, training, enrollment, and issuance actions promptly after award.
Do not assign personnel who cannot obtain or maintain required eligibility to work requiring that access.
Display/carry credentials as directed, comply with check-in and escort rules, protect keys/badges, and return Government credentials when access ends.
PIV eligibility does not independently authorize entry into Pharmacy, Research, laboratories, roofs, interstitial spaces, mechanical rooms, or clinical areas; area-specific authorization remains required.
No access to VA information systems, patient records, or VA sensitive information is anticipated.
Immediately report inadvertent exposure to the COR/COTR and follow VA privacy/security direction.
The C&A requirements do not apply and a Security Accreditation Package is not required
15.0 GOVERNMENT-FURNISHED ACCESS AND INFORMATION
The Government will designate a COR; provide reasonable coordinated access to listed Government equipment and spaces; furnish available inventories, prior reports, and facility procedures; and coordinate required outages, escorts, and departmental contacts. Access remains subject to patient care, security, safety, infection control, and operational restrictions.
The Government does not furnish Contractor labor, tools, test instruments, calibration, transportation, PPE, routine consumables, replacement filters, sampling materials, laboratory analysis, or other resources required by this PWS.
16.0 PRICING AND AUTHORIZATION CONTROLS
Recurring scheduled services shall be priced under one or more firm-fixed-price contract line items for each contract period. Condition-based HEPA replacement and other variable work shall be separately priced as firm-fixed-price option contract line items. The Government is not obligated to purchase any optional quantity unless the Contracting Officer exercises the applicable option in writing. At a minimum, pricing shall distinguish:
Pricing element Required basis
Recurring services
One or more firm-fixed-price line items per contract period for all scheduled certifications, tests, monitoring, prefilter service, diffuser cleaning, routine isolation-filter service, and reporting.
AHU 37A/37B 24 × 24 ×
11.5-inch HEPA replacement
Fully burdened firm-fixed unit price per filter. Authorized quantity shall not exceed 18 per contract period without Contracting Officer action.
AHU 37A/37B 12 × 24 ×
11.5-inch HEPA replacement
Fully burdened firm-fixed unit price per filter. Authorized quantity shall not exceed six per contract period without Contracting Officer action.
AHU 46 30 × 30 × 12-inch
HEPA replacement
Fully burdened firm-fixed unit price per filter. Authorized quantity shall not exceed six per contract period without Contracting Officer action.
Operating Room 5 terminal HEPA replacement
Fully burdened firm-fixed unit price for each verified terminal-filter type or location. Authorized quantity shall not exceed two per contract period without Contracting Officer action.
Pharmacy HEPA replacement
Fully burdened firm-fixed unit price for each materially different filter type or location verified during the mandatory site visit. Authorized quantity shall not exceed 10 per contract period without Contracting Officer action.
Additional replacement mobilization
Firm-fixed price per return visit when an authorized replacement cannot be completed during scheduled testing. This line item shall not be charged when replacement occurs during a scheduled service event or mobilization is included elsewhere.
BSC decontamination Firm-fixed unit price per authorized event, not to exceed two events per contract period.
ASHRAE 110 tracer-gas testing Firm-fixed unit price per hood when separately required and authorized.
Each HEPA replacement unit price shall include the correctly rated replacement filter, freight, labor, outage coordination, removal, containment, disposal, cleaning, gasket and seal materials, installation, labeling, and required post-replacement integrity and performance testing.
When separately priced work may be required, the Contractor shall provide the COR/COTR with the applicable equipment identification, measured condition or failure, acceptance criterion, recommended action, proposed materials, and applicable contract line item. The COR/COTR may validate the technical need and coordinate scheduling and access.
The Contractor shall not proceed based on an oral request or COR/COTR direction alone. Only the
Contracting Officer may exercise an option contract line item, authorize a payable quantity, change a quantity ceiling, or obligate additional funding. Work performed without the required Contracting Officer authorization shall not be invoiced or paid.
17.0 INVOICING
Invoices shall be submitted in arrears through the VA-designated electronic invoicing process and shall identify the contract line item, service date, department/system, quantity, authorization reference for variable work, accepted report, and amount. Unauthorized, incomplete, failed, or unaccepted work shall not be invoiced as complete. The Contracting Officer will incorporate applicable FAR/VAAR invoicing clauses into the solicitation and award. For variable or optional work, the invoiced quantity shall not exceed the quantity authorized in writing by the Contracting Officer and accepted by the Government.
APPENDIX A — PHARMACY INVENTORY
Equipment / System Location. EE/MX Make/Model SN
ISO Class 5 PEC
Class II, Type A2
Biological Safety
Cabinet (BSC)
A-7086
Right side of room
X18262
Baker BSC
SG404
127090
ISO Class 5 PEC
Class II, Type A2
Biological Safety
Cabinet (BSC)
A-7086
Left side of room
MX1826
Baker BSC
SG404
127091
ISO Class 5 PEC
Horizontal Laminar
Airflow Workstation
(LAFW)
A-7086
Right Side of room
MX2493
NuAire-340-
199005060820
ISO Class 5 PEC
Horizontal Laminar
Airflow Workstation
(LAFW)
A-7086
Left side of room
MX2493
NuAire-340-
198953060420
ISO Class 5 PEC
Restricted Access
Barrier System –
Compounding
Aseptic Isolator
(CAI)
D-2035
MX2717
NuAire
NU-PR797-
209374111521
ISO Class 7
Positive Pressure
Cleanroom
A-7086
Equipment / System Location. EE/MX Make/Model SN
ISO Class 7
Negative Pressure
Cleanroom
A-7086
ISO Class 7
Anteroom A-7086
APPENDIX B — LABORATORY (P&LMS) INVENTORY
Location EE/MX Type Model Serial Number
Cytology A2064 MX3546715 Class II Type A2 NU-540-400 224778021324
Micro A2044 EE51772 Fume Hood 54L590P 54L590P
Micro A2044 MX3610896 Class II Type A2 NU-540-400 224971022624
Micro A2044 MX3610898 Class II Type A2 NU-540-300 225067022924
Histology A2067 MX1895323 Fume Hood EH6V 126690
Frozen Room
A2066 MX1630107 Class II Type A2 NU-540-300 182346100917
Frozen Room
A2066 MX1705534 Fume Hood FH5C 123429
Molecular A2042 MX3400517 Class II Type A2 NU-540-400 216884110822
Molecular A2042 MX3400516 Class II Type A2 NU-540-400 216882110822
Molecular A2042 MX3400474 Class II Type A2 NU-540-400 216887110822
Molecular A2043 MX3400462 Class II Type A2 NU-540-400 216883110822
Molecular A2043 MX3400519 Class II Type A2 NU-540-400 216886110822
Micro A2044 MX3688203 Class II Type A2 NU-540-300 228747111124
Histology A2067 MX1826106 Grossing Station Not provided MB670H15001
Micro A2049 EE4241 Class II Type A2 NU-425-600 22454WN
Processing A2132 EE46944 Class II Type A2 3620400 070874972
Mohs C-1094 MX1982304 Class II Type A2 Not provided N/A
Location EE/MX Type Model Serial Number
Cytology A2064 No EE
Assigned Fume Hood Not provided 231056295
APPENDIX C — RESEARCH INVENTORY
Line Room Inventory Description EE/MX / Identifier
1 D3014 1 Hypoxia Chamber EE82869/EE63841
2 C3077 1 Fume Hood EE24581
3 C3078 1 Fume Hood EE24583
4 C3078 1 BSC IU 000125
5 C3092 1 Fume Hood EE9351
6 C3111 1 Fume Hood EE9361
7 C3113 1 Fume Hood EE9362
8 C3113 1 Fume Hood EE67976
9 C3113 1 LFWS EE63937
10 C3113 1 LFWS EE67766
11 C3116 1 BSC EE79416
12 C3117 1 BSC EE65512
13 C6064 1 Fume Hood EE52550
14 C6071 1 BSC MX3644482
15 C6072 1 BSC EE69558
16 C6077 1 Fume Hood EE51336
17 C6078 1 Fume Hood EE51322
18 C6080 1 Fume Hood Not provided
19 C6082 1 Fume Hood Not provided
20 C6091 1 Fume Hood EE52364
21 C6114 1 Fume Hood EE59407
22 C6115 Mini BSC EE86988
23 C6115 1 Fume Hood EE52475
24 C6133 1 BSC EE34270
25 C6134 1 BSC EE4240
26 C6134 1 BSC EE34271
27 C6139 1 Fume Hood EE59204
28 C7093 1 Fume Hood EE28216
29 C7095 1 Fume Hood EE28215
30 C7098 1 BSC EE51409
31 C7106 1 BSC MX2054121
32 C7110 1 BSC MX2062903
33 D2004 1 BSC EE4544
34 D2005 1 BSC MX1944880
35 D2006 1 Fume Hood EE52041
36 D2007 1 Fume Hood EE51719
37 D2007 1 BSC MX1633251
38 D2010 1 BSC EE67995
39 D2012 1 Fume Hood No MX/EE# Vectaire
40 D3002 1 BSC EE26708
41 D3004 1 Fume Hood No MX/EE# Vectaire #26
42 D3005 1 Fume Hood No MX/EE# Vectaire #21
43 D3006 1 Fume Hood MX1633270
44 D3007 1 Fume Hood No MX/EE# Vectaire #23
45 D3008 1 Fume Hood No MX/EE# Vectaire #24
46 D3014 1 BSC MX1633240
47 D3015 1 BSC MX2031906
48 D3016 1 BSC EE51541
49 D3016 1 Fume Hood No MX/EE# Vectaire #25
50 C3102 1 Fume Hood EE67978
51 C3113 1 Fume Hood EE63937
52 C338A 1 Fume Hood EE73176
53 C340A 1 Fume Hood EE72534
54 C6082 1 Fume Hood EE51329
55 C6136 1 Fume Hood EE746
56 C6136 1 BSC MX2026750
57 D2001 1 Fume Hood EE21352
58 E220 1 Fume Hood EE37551
59 C2192 1 Fume Hood EE9353
60 AB007 1 Fume Hood MX3624750
APPENDIX D — ENGINEERING SYSTEM INVENTORY
System Access Served Area / Rooms Filter / Housing Frequency
AHU
37A/37B 5th Floor MER 9 Surgery operating rooms
24 HEPA filters total; (18) 24 x 24 x 11.5 in, (6) 12 x
24 x 11.5 in
Annual test;
condition-based replacement
AHU 46 6th Floor MER Cardiology procedure room
6 HEPA filters;
nominal 30 x 30 x
12 in
Annual test;
condition-based replacement
OR 5
terminal
HEPA
filters
OR 5 ceiling terminals; upstream challenge access to verify
Operating Room 5; served by
AHU 38
2 terminal HEPA filters; no central
HEPA…
This is the start of the file's text. The full file is on GovTribe.