S06 Addendum 2 - 553-21-100.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25026B0024
About this file
This document is Addendum #2 to the 100% Bid Documents for VA Project 553-21-100, a renovation project for the A2 South Cancer Clinic at the John D. Dingell VA Medical Center in Detroit, Michigan, dated May 1, 2026. The addendum incorporates multiple revisions to contract documents, specifications, and construction drawings that bidders must acknowledge receipt of on the Bid Form.
The addendum contains significant modifications across multiple discipline areas. Specification Section 10 14 00 (Signage) has been completely reissued to match new facility signage standards. Drawing revisions include: reissued Sheet G-001 adding new sheet I-121; Sheets A-122.1A through A-132 with revised Division 10 schedules, notes legends, and corner guard tags; Sheets A-401 through A-405 with revised corner guards, wall protection heights, and signage; Sheet A-506 with revised infusion bay details; Sheet A-601 with revised door and frame schedule; Sheet I-001 with revised wall protection and corner guards; Sheets I-102.1 series with revised legends and wall protection details; Sheet I-120 and new sheet I-121 with revised signage schedules and details; mechanical Sheets M-401 and M-402 with equipment and piping routing revisions; Sheet M-503 with clarified AHU-2082 details; Sheet M-601 with revised equipment schedules; Sheet EP102.1D with VFD replacements for motor starters; and Sheets ET102.1B through ET102.1D with fire extinguisher cabinet monitor callouts. The A/E firms responsible are Walter Mechanical, MEGA, and C2AE, with project management by Ali Shiraz, Scott Townsend, and Kelly Homic.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25026B0024 0006.docx | DOCX document | |
| 36C25026B0024 0005.docx | DOCX document | |
| S06 36C25026B0024 0004 - 553-21-100.docx | DOCX document | |
| S06 36C25026B0024 0003 - 553-21-100.pdf | ||
| S06 RFI Responses 3 - 553-21-100.pdf | ||
| 36C25026B0024 0003.docx | DOCX document | |
| S06 BSC Product Data - 553-21-100.pdf | ||
| RFI Responses 2 - 553-21-100.pdf | ||
| S06 Addendum 1 - 553-21-100.pdf | ||
| 36C25026B0024 0002.docx | DOCX document | |
| Pre-Bid Site Visit Attendance Log 553-21-100.pdf | ||
| RFI Responses - 553-21-100.pdf | ||
| 36C25026B0024 0001.docx | DOCX document | |
| S02 36C25026B0024 - 553-21-100.pdf | ||
| Specs Vol2 - 553-21-100.pdf | ||
| Specs Vol1 - 553-21-100.pdf | ||
| Wage Determination MI20260101 - 01-02-2026 - 553-21-100.pdf | ||
| Drawings - 553-21-100.pdf | ||
| Contractor EMR Certification Form - 553-21-100.docx | DOCX document | |
| RFI Form - 553-21-100.doc | DOC document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #2
The following changes, revisions, modifications, etc. shall be incorporated into the contract documents, specifications, and plans.
ACKNOWLEDGEMENTS
A2.1 The Bidder shall acknowledge receipt of Addenda #2 by indicating so in the spaces provided on the Bid Form.
SPECIFICATIONS
A2.2 Refer to Section 10 14 00 - Signage (reissued):
Replace section in its entirety. Section revised to match new facility signage standards.
DRAWINGS
A2.3 Refer to Sheet G-001 (reissued):
Revise Sheet list to add new sheet I-121.
A2.4 Refer to Sheets A-122.1A, A-122.1B, A-122.1C, A-122.1D, and A-132 (reissued):
a. Revise Division 10 Schedule.
b. Revise Division 10 – Notes Legend.
c. Revise all tags identifying corner guards to match schedule.
A2.5 Refer to Sheet A-131 (reissued):
Revise detail references.
A2.6 Refer to Sheets A-401, A-402, A-403, A-404, and A-405 (reissued):
a. Revise all corner guards in multiple elevations.
b. Add missing corner guard tags.
c. Revise wall protection heights on multiple elevations.
d. Add signage on elevations as shown.
VA Project No.: 553-21-100 Date: May 1, 2026
Project: Renovate A2 South for Cancer Clinic John D. Dingell VA Medical Center Detroit, Michigan
A/E Firm: Walter Mechanical/MEGA/C2AE
Project Manager: Ali Shiraz/Scott Townsend/Kelly Homic
Owner: John D. Dingell VA Medical Center 4646 John R Street Detroit, MI 48201
Renovate A2 South for Cancer Clinic
A2.7 Refer to Sheet A-403 (reissued):
Revise infusion bay casework.
A2.8 Refer to Sheet A-405 (reissued):
Add side splash to countertops.
A2.9 Refer to Sheet A-506 (reissued):
Revise detail as shown.
A2.10 Refer to Sheet A-601 (reissued):
Revise door and frame schedule.
A2.11 Refer to Sheet I-001 (reissued):
a. Revise wall protection heights and trim.
b. Add corner guards.
A2.12 Refer to Sheet I-102.1, I-102.1A, I-102.1B, I-102.1C, and I-102.1D (reissued):
Revise legend.
A2.13 Refer to Sheet I-102.1C (reissued):
a. Revise length of wall protection.
b. Add keynotes for accent flooring.
c. Revise demarcation line notes.
A2.14 Refer to Sheet I-120 (reissued):
Revise signage
A2.15 Refer to Sheet I-121 (issued):
a. Add new sheet.
b. Revise signage schedule.
c. Revise signage details.
A2.16 Refer to Sheet M-40I (reissued):
a. One EG (Exhaust Grille) selection has been changed from EG-1 to EG-2 on the north wall of Room A2055 between column lines 4N and 5N.
b. Return Grille type has been changed from R-1 to R-2 in Room A2053. Supply and Return CFMs have been updated and their associated ductworks have been updated from 8” to 10” round, near column line 4M.
c. Rooms A2055 and A2056: “ADJ” has been added to the exhaust and return grilles’ tags, respectively.
d. Supply and return CFMs have been updated in Room A2056.
A2.17 Refer to Sheet M-402 (reissued):
Revise AHU-2082, the MPS (medium pressure steam) and MPR pipe routings to/from the steam humidifier and steam heating coil (HC) on “ENLARGED MECHANICAL ROOM A2032 PIPING PLAN” and “SECTION - MECHANICAL
ROOM A2032”.
Renovate A2 South for Cancer Clinic
A2.18 Refer to Sheet M-503 (reissued):
Revise AHU-2082 plan and HC (heating coil) and HM (Humidifier) have been illustrated more clearly; see “AIR
HANDLING UNIT AHU-2082 DETAIL”.
A2.19 Refer to Sheet M-601 (reissued):
a. For AHU-2082, revise the “Air Handling Unit Schedule”.
b. For SF-2082, revise the “Supply Fan Schedule”.
c. PH-2082: add information to the “Steam Heating Coil Schedule”.
d. CC-2082: revise the “Chilled Water Coil Schedule”.
e. For AHU-2082: revise the “Filter Schedule”.
f. SH-2082: revise the “Steam Humidifier Schedule”.
g. Revise the “Air Flow Control Valve Schedule”.
h. Revise the “Exhaust Fan Schedule”, Note 2.
i. Revise the “Air Device Schedule (Exhaust)”.
A2.20 Refer to Sheet EP102.1D (reissued):
Revise motor starters to VFD in seventh floor mechanical room and revised keyed note R15 to reflect VFD instead of starters.
A2.21 Refer to Sheets ET102.1B, ET102.1C, and ET102.1D (reissued):
Provide fire extinguisher cabinet monitor at locations indicated on plan and call out with new keyed note T9.
Revision: 01-21 Renovate A2 South for Cancer Clinic 100% Bid Documents John D. Dingell VA Medical Center
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 1/8
SIGNAGE
SECTION 10 14 00 - SIGNAGE (ADM2)
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies interior signage for room numbers, directional signs, code required signs and temporary signs.
B. Informational and room signage.
1. Acrylic panel signs.
2. Metal framed acrylic panel signs.
C. Dimensional letters.
D. Vinyl characters.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Sustainable Design Requirements.
1.3 QUALITY ASSURANCE
A. Manufacturer’s Qualifications: Provide signage, that is the product of one manufacturer, who has provided signage as specified for a minimum of three (3) years. Submit manufacturer’s qualifications.
B. Installer’s Qualifications: Minimum three (3) years’ experience in the installation of signage of the type as specified in this Section. Submit installer’s qualifications.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND
SAMPLES.
B. Interior Sign Samples: Sign panels and frames, with letters and symbols, for each sign type.
1. Sign Panel, 203 x 254 mm (8 x 10 inches), with letters.
2. Color samples of each color, 152 x 152 mm (6 x 6 inches. Show anticipated range of color and texture.
3. Frame system, one full size sample including divider bar and sample inserts.
4. Sample of typeface, arrow and symbols in a typical full-size layout.
5. Dimensional letter: one full size sample of one character in material and color specified
6. Vinyl letter: one full size sample of one character in material and color specified
C. Manufacturer's Literature:
1. Showing the methods and procedures proposed for the anchorage of the signage system to each surface type.
2. Manufacturer’s printed specifications and maintenance instructions.
3. Compliance with sustainable design VOC requirements as specified.
4. Qualifications as required in 1.3 QUALITY ASSURANCE
Page 4 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 2/8
SIGNAGE
D. Sign Location Plan, showing location, type and total number of signs required.
E. Shop Drawings: Scaled for manufacture and fabrication of sign types. Identify materials, show joints, welds, anchorage, accessory items, mounting and finishes.
F. Signage message schedule: schedule with exact text for each sign to be provided.
G. Installer qualifications as required in 1.3 QUALITY ASSURANCE
1.5 DELIVERY AND STORAGE
A. Deliver materials to the job in manufacturer's original sealed containers with brand name marked thereon. Protect materials from damage.
B. Package to prevent damage or deterioration during shipment, handling, storage, and installation. Maintain protective covering in place and in good repair until removal is necessary.
C. Deliver signs only when the site and mounting services are ready for installation work to proceed.
D. Store products in dry condition inside enclosed facilities.
1.6 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Architectural Manufacturers Association (AAMA):
611-14 .................................... Anodized Architectural Aluminum 2603-13 .................................. Voluntary Specification, Performance Requirements and Test
Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
C. American National Standards Institute (ANSI):
A117.1-09............................... Accessible and Usable Buildings and Facilities
Page 5 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 3/8
SIGNAGE
D. ASTM International (ASTM):
A36/A36M-19 ......................... Carbon Structural Steel A240/A240M-20 ..................... Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications A666-15 ................................. Annealed or Cold-Worked Austenitic Stainless-Steel Sheet, Strip, Plate and Flat Bar A1011/A1011M-18a ................ Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-
Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength
B36/B36M-18 ......................... Brass Plate, Sheet, Strip, and Rolled Bar B152/B152M-19 ..................... Copper Sheet, Strip, Plate, and Rolled Bar B209-14 ................................. Aluminum and Aluminum-Alloy Sheet and Plate B209M-14............................... Aluminum and Aluminum-Alloy Sheet and Plate (Metric) B221-14 ................................. Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes B221M-13............................... Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric) C1036-16 ............................... Flat Glass C1048-18 ............................... Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated
Glass C1349-17 ............................... Architectural Flat Glass Clad Polycarbonate D1003-13 ............................... Test Method for Haze and Luminous Transmittance of
Transparent Plastics D4802-16 ............................... Poly(Methyl Methacrylate) Acrylic Plastic Sheet
E. Code of Federal Regulation (CFR):
40 CFR 59 .............................. Determination of Volatile Matter Content, Water Content, Density Volume Solids, and Weight Solids of Surface Coating
F. Federal Specifications (Fed Spec):
MIL-PRF-8184F ...................... Plastic Sheet, Acrylic, Modified MIL-P-46144C ........................ Plastic Sheet, Polycarbonate
G. National Fire Protection Association (NFPA):
70-14 ...................................... National Electrical Code
PART 2 - PRODUCTS
2.1 SIGNAGE GENERAL
A. Provide signs of type, size and design shown on the construction documents and to comply with VA Signage Design Guide.
B. Provide signs complete with lettering, framing and related components for a complete installation.
C. Provide graphics items as completed units produced by a single manufacturer, including necessary mounting accessories, fittings and fastenings.
Page 6 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 4/8
SIGNAGE
D. Do not scale construction documents for dimensions. Verify dimensions and coordinate with field conditions. Notify Contracting Officer Representative (VA COR) of discrepancies or changes needed to satisfy the requirements of the construction documents.
E. Typography: Comply with VA Signage Design Guide.
1. Type Style: Helvetica LT Std Bold, Helvetica LT Std Regular, and Helvetica LT Std Bold
Condensed. Title Case or Headline Case is standard, or as indicated in VA Design Guide.
2. Arrow: Comply with graphic standards in VA Design Guide.
3. Letter spacing: Comply with graphic standards in VA Design Guide.
4. Letter height: Comply with graphic standards in VA Design Guide.
5. Provide text, arrows, and symbols in size, colors, typefaces and letter spacing shown in
VA Design Guide. Text shall be a true, clean, accurate reproduction of typeface(s). Text shown in construction documents is for layout purposes only; final text for signs is to be approved by VA COR.
2.2 INTERIOR SIGN MATERIALS
A. Aluminum:
1. Sheet and Plate: ASTM B209M (B209).
2. Extrusions and Tubing: ASTM B221M (B221).
B. Cast Acrylic Sheet: MIL-PRF-8184F; Type II, class 1, Water white non-glare optically clear. Matt finish water white clear acrylic shall not be acceptable.
C. Polycarbonate: MIL-P-46144C; Type I, class 1.
D. Vinyl: Premium grade 0.1 mm (0.004 inch) thick machine cut, having a pressure sensitive adhesive and integral colors.
E. Adhesives:
1. Adhesives for Field Application: Mildew-resistant, nonstaining adhesive for use with specific type of panels, sheets, or assemblies; and for substrate application as recommended in writing by signage manufacturer.
2. Adhesives to have VOC content of 50 g/L or less when calculated according to 40 CFR 59, (EPA Method 24).
Page 7 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 5/8
SIGNAGE
2.3 INTERIOR SIGN TYPES
A. Component System Signs:
1. Interchangeable system that allows for changes of graphic components of the installed sign, without changing sign in its entirety.
a. Basis of design: Creative Sign Systems; Continuum Series.
b. Provide sign system comprised of the following primary components:
1) Flex-fit Frame: Anodized extruded aluminum parts, mechanically fastened together, with spring clips to allow front loading of variable thickness components that will keep media flush to sign surface, mechanically fastened to the wall with hidden fasteners.
a) If sign is to be mounted to glazing, the use of VHB double sided tape and silicone adhesive is to be used. A blank acrylic back-up is necessary on the opposite side of the glass to cover mounting adhesive. .
2) Tactile Copy Panels: P95 frosted acrylic material with subsurface digital print and ADA compliant raised tactile text and Grade II Braille. Tactile sign made from a material that provides for letters, numbers and Braille to be integral with sign.
a) Numbers, letters and Braille to be raised 0.8 mm (1/32 inches) from the background surface. The draft of the letters, numbers and Braille to be tapered, vertical and clean.
b) Braille Dots: Conform with ANSI A117.1 for Braille position and layout
3) Regulatory Sign: Removeable 1/16” non-glare acrylic lens, over 1/8” white
ACM back panel with surface printed text and graphics.
4) Changeable Message Insert: Removeable 1/16” non-glare acrylic lens, over
1/8” decorative laminate ACM back panel, and updatable acetate insert with black print.
5) Divider Bar: Removable ¼” aluminum divider bar.
6) Slider Unit: anodized aluminum slider unit with 1/16” non-glare acrylic insert panel with subsurface digital print to be CSS white and CSS fire Red #1003 or finish to match.
c. Provide sign configurations as indicated on construction documents.
B. Acrylic Panel Signs:
1. Single sided, surface mounted signs: 2-ply non-glare acrylic with subsurface digital print, mounted with VHB double sided tape and silicone adhesives.
a. If sign is to be mounted to glazing a blank acrylic back-up is necessary on the opposite side of the glass to cover mounting adhesive.
2. Double sided, bracket mounted signs: 3-ply non-glare acrylic, with subsurface digital print. Bracket to be anodized aluminum continuous mounting bracket to mount sign at 90 degrees from the wall.
C. Vinyl text and graphics:
1. Provide text and graphics as first surface applied stylus cut vinyl.
2. Provide typeface, color, and spacing, with each message or message group on a single quick release backing sheet.
D. Dimensional Letters:
1. Provide dimensional letters that are mill or laser cut ¼” thick brushed aluminum in heights indicated in construction documents.
2. Fabricate letters with square corners, such as where a letter stem and bar intersect.
Page 8 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 6/8
SIGNAGE
3. Stud mounting to be used, unless mounted on glazing, cmu, porcelain or ceramic tile, where tape/glue mounted to be used.
E. Temporary Interior Signs:
1. Fabricated from 50 kg (110 pound) matte finished white paper cut to 101 mm (4 inch) wide by 305 mm (12 inch) long.
a. Mount with removable tape that will not affect the finished surface it is applied to, but strong enough to keep sign attached to surface.
b. Reinforce hole on both sides with suitable material that prevents tie from pulling through hole.
c. Ties: Steel wire 0.3 mm (0.120 inch) thick attached to tag with twist leaving 152 mm (6 inch) long free ends.
2. Mark architectural room number on sign, with broad felt marker in clearly legible numbers or letters that identify room, corridor or space as shown on construction documents.
3. Install temporary signs to rooms that have a room, corridor or space number. Attach to wall adjacent to door frame, or face of door.
a. Doors that do not require signs are: corridor doors in corridor with same number, folding doors or partitions, toilet doors, bathroom doors within and between rooms, closet doors within rooms, communicating doors in partitions between rooms with corridor entrance doors.
4. Replace missing, damaged or illegible signs.
2.4 FABRICATION
A. Design interior signage components to allow for expansion and contraction for a minimum material temperature range of 38 degrees C (100 degrees F), without causing buckling, excessive opening of joints or over stressing of adhesives, welds and fasteners.
B. Form work to required shapes and sizes, with true curve lines and angles. Provide necessary rebates, lugs and brackets for assembly of units. Provide concealed fasteners wherever possible.
C. Shop fabricate so far as practicable. Fasten joints flush to conceal reinforcement, or weld joints, where thickness or section permits.
D. Level and assemble contract surfaces of connected members so joints shall be tight and practically unnoticeable, without applying filling compound.
E. Signs: Fabricate with fine, even texture to be flat and sound.
1. Maintain lines and miters sharp, arises unbroken, profiles accurate and ornament true to pattern.
2. Plane surfaces to be smooth, flat and without oil-canning, free of rack and twist.
3. Maximum variation from plane of surface plus or minus 0.3 mm (0.015 inches). Restore texture to filed or cut areas.
F. Finish extruded members to be free from extrusion marks. Fabricate square turns, sharp corners, and true curves.
G. Finish hollow signs with matching material on all faces, tops, bottoms and ends. Miter edge joints to give appearance of solid material.
Page 9 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 7/8
SIGNAGE
H. Do not manufacture signs until final sign message schedule and location review has been completed by the VA COR and forwarded to contractor.
I. Drill holes for bolts and screws. Mill smooth exposed ends and edges with corners slightly rounded.
J. Form joints exposed to weather to exclude water.
K. Movable Parts, Including Hardware: Cleaned and adjusted to operate as designed without binding or deformation of members. Center doors and covers in opening or frame.
1. Align contact surfaces fit tight and even without forcing or warping components.
L. Pre-assemble items in shop to minimize field splicing and assembly. Disassemble units only as necessary for shipping and handling limitations. Clearly mark units for re-assembly and coordinated installation.
M. Prime painted surfaces as required. Apply finish coating of paint for complete coverage with no light or thin applications allowing substrate or primer to show.
1. Finish surface smooth, free of scratches, gouges, drips, bubbles, thickness variations, foreign matter and other imperfections.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Locate signs as shown on the construction documents.
B. Where not otherwise indicated conform to the VA Signage Design Manual for installation requirements.
C. At each sign location there are no utility lines behind each sign location that shall be affected by installation of signs.
1. Correct and repair damage done to utilities during installation of signs at no additional cost to Government.
D. Provide inserts and anchoring devices which shall be set in concrete or other material for installation of signs. Submit setting drawings, templates, instructions and directions for installation of anchorage devices, which shall involve other trades.
E. Mount signs in proper alignment, level and plumb according to the Sign Location Plan and the dimensions given on elevation and Sign Location Plans. When exact position, angle, height or location is not clear, contact VA COR for resolution.
F. When signs are installed on glass, provide blank glass back up to be placed on opposite side of glass exactly behind sign being installed. Provide blank glass back that is the same size as sign being installed.
G. Touch up exposed fasteners and connecting hardware to match color and finish of surrounding surface.
H. At completion of sign installation, clean exposed sign surfaces. Clean and repair adjoining or adjacent surfaces that became soiled or damaged as a result of installation of signs.
Page 10 of 41 Addendum #2
Detroit, Michigan VA Project No. 553-21-100
10 14 00 - 8/8
SIGNAGE
END OF SECTION 10 14 00
Page 11 of 41 Addendum #2
1.
1.
2.
A.
B.
3.
1.
2.
1.
2.
DEDUCTIVE ALTERNATE #1
REMOVE BUILT-IN CASEWORK AND REPLACING WITH FURNITURE
PACKAGE IN ROOMS: A2013, A2014, A2020, A2022, A2058 AND A2060.
DEDUCTIVE ALTERNATE #2
EVERYTHING IN DEDUCTIVE ALTERNATE #1.
PARTIAL HEIGHT WALL:
REMOVE RESIN PANEL, ALL INTERNAL BLOCKING/ SUPPORTS USED
TO SUPPORT RESIN PANEL, ALL COLD FORMED METAL FRAMING
AND SOLID SURFACE SILL. MODIFY WALL TO BE PARTITION TYPE
'2A', FULL HEIGHT, CONNECTING TO THE DECK ABOVE.
REMOVE CEILING, LMC-1, AND (3) DOWNLIGHTS, L7, LOCATED IN
ALCOVE A2079. REPLACE WITH GYPSUM BOARD BULKHEAD, HEIGHT
AT 7'-0" A.F.F. AND ADD (3) DOWNLIGHTS, L5. PAINT BULKHEAD AS
INDICATED IN REFLECTED CEILING PLAN LEGEND.
REMOVE FOLDING GLASS PARTITION SYSTEM IN ITS ENTIRETY FROM
THE SCOPE OF WORK. TO INCLUDE: RESIN PANELS, HARDWARE,
TRACKS, AND ALL STRUCTURAL STEEL.
DEDUCTIVE ALTERNATE #3
EVERYTHING IN DEDUCTIVE ALTERNATE #1 AND #2.
REMOVE LMC-1 AND LINEAR LIGHT FIXTURES, L22, OVER INFUSION
BAYS A2068, A2070, A2072, A2074, A2076, A2078, A2080, A2081, A2082,
AND A2083. REPLACE WITH SMC-1 AND 2X2 LIGHTING FIXTURES, L2.
LIGHT FIXTURE COUNT TO REMAIN THE SAME.
DEDUCTIVE ALTERNATE #4
EVERYTHING IN DEDUCTIVE ALTERNATE #1, #2, AND #3.
REMOVE IN-FLOOR RECESSED SCALE IN ITS ENTIRETY FROM THE
SCOPE OF WORK. TO INCLUDE: CONCRETE WORK, IN FLOOR POWER /
DATA ASSOCIATED WORK, AND RECESSED SCALE EQUIPMENT IN
WEIGHT ALCOVES A2024 AND A2063.
DEDUCTIVE ALTERNATE LEGEND:
SOLE SOURCE LIST
DIVISION ITEM
CHEMTRONVACUUM SYSTEMS22 63 00
SIEMENSDISTRIBUTION SWITCHBOARDS26 24 11
SIEMENSELECTRICAL PANELBOARDS26 24 16
SIEMENSMOTOR CONTROL CENTERS26 24 19
BRAND
08 71 00 LATCH AND LOCK SETS YALE
CHEMTRONMEDICAL GASES22 63 00
SIEMENSDIRECT-DIGITAL CONTROL SYSTEM FOR HVAC23 09 23
SIEMENSDRY-TYPE TRANSFORMERS26 22 00
SIEMENSMOTOR STARTERS26 29 11
SIEMENSLOW-VOLTAGE DISCONNECT SWITCHES26 29 21
EATONAUTOMATIC TRANSFER SWITCHES26 36 23
SIEMENSTRANSIENT-VOLTAGE SURGE SUPPRESSION26 43 13
RAULAND-BORGNURSE CALL AND CODE BLUE SYSTEMS27 52 23
SIMPLEXFIRE DETECTION AND ALARM28 31 00
07 81 00 FS-1 FOR FIRESTOPPING HILTI
ARJO, SKI-2PATIENT LIFT11 73 00
SECURITY 2000CCTV SYSTEM28 23 00
LYNX ALARM SYSTEMALARM SYSTEM (COMPUTER, 2 ALT
KEYS ON PAD)
28 26 00
08 71 00 PUSH BUTTON COMBINATION LOCKSET ALARM LOCK TRILOGY DL3500
ACCESS CONTROL SYSTEM (CARD
READERS)28 13 00 SECURITY 2000
1.
2.
3.
ALL REFERENCES TO OWNER IN THESE DOCUMENTS REFER TO THE VA,
THE CO AND/OR THE COR.
ALL REFERENCES TO GOVERNMENT IN THESE DOCUMENTS REFER TO
THE VA, THE CO AND/OR THE COR.
PRODUCTS LISTED HEREIN BY MANUFACTURER'S TRADE NAME AND
NUMBERS ARE TO BE USED FOR BASIS OF DESIGN ONLY, U.N.O.
PRODUCTS ARE SUBJECT TO COMPLIANCE WITH SALIENT
CHARACTERISTICS AND REQUIREMENTS IN THE SPECIFICATIONS.
PROVIDE PRODUCTS LISTED OR COMPARABLE PRODUCTS BY OTHER
MANUFACTURERS.
GENERAL NOTES:
N
EW
S
LAKE ERIE
GRAND
RAPIDS
TRAVERSE
CITY
LAKE SUPERIOR
UPPER PENINSULA
MACKINAW
CITY LAKE HURONALPENA
PETOSKEY
GAYLORD
GRAYLING
LA
KE
M
IC
HI
GA
N
SAGINAW
FLINT
LANSING
DETROIT
KALAMAZOO ANN
ARBOR
BATTLE
CREEK
LOCATION MAP
NOT TO SCALE
N
EW
S
CAMPUS MAP
NOT TO SCALE
SOUTH
PARKING
DECK
ENERGY
CENTER
NORTH
PARKING
DECK
E. WARREN AVE.
E. HANCOCK ST.
E. CANFIELD ST.
JOHN R ST.
BRUSH ST.
ST. ANTOINE
WOODWARD AVE. E. FOREST ST.
W. FOREST ST.
N
EW
S
VICINITY MAP
NOT TO SCALE
W. FORT ST.
MICHIGAN AVE. 1212
W. GRAND BLVD.
MARTIN LUTHER KING JR. BLVD.
W. WARREN AVE.
WOODWARD AVE.
W. GRAND BLVD.
W. GRAND RIVER AVE.
GR
AT
IO
T A
VE
DETROIT RIVER
MCDOUGALL ST.
E. GRAND BLVD.
E. GRAND BLVD. E. GRAND BLVD.
VAN DYKE.
E. WARREN AVE.
MACK AVE. VERNOR HWY.
E. LAFAYETTE ST.
E. JEFFERSON AVE.
DETROIT
RA
ILR
OA
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
SIGNATURE DATE
Director
Associated Director
Chief of Staff
Associate Director for Patient Care Services
Chief, FMS
Chief, Engineering Section
Chief, Environmental Management Section
Infection Control Officer
SIGNATURE BLOCK
POSITION
DEPARTMENT OF VETERANS AFFAIRS - JOHN D. DINGELL VA MEDICAL CENTER
DETROIT, MICHIGAN
John D. Dingell VA Medical Center
4646 John R. Street
Detroit , MI 48201
3419 Pierson Place Flushing, Michigan, 48433 810-230-6202
(866) 454-3923 | WWW.C2AE.COM
Au tod es k D oc s:/
/V A
MI
D etr oit
/21
_A
.rv t
5/1 /20
8:
:53
A M
G-001
COVER SHEET RENOVATE A2 SOUTH
FOR CANCER CLINIC
DETROIT, MI
553-21-100
10-JAN-2025 KJH MRB
100% BID DOCUMENTS
RENOVATE A2 SOUTH FOR CANCER
CLINIC
553-21-100
10-JAN-2025
100% BID DOCUMENTS
553-21-100
SHEET
NO. SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 LIFE SAFETY AND ICRA LEGENDS
G-102.1 LIFE SAFETY PLAN - SECOND LEVEL - ZONE 1
GENERAL - ICRA
G-200 ICRA PLAN - LOWER LEVEL
G-201.1I ICRA PLAN – FIRST LEVEL INTERSTITIAL – ZONE 1
G-202.1 ICRA PLAN - SECOND LEVEL - ZONE 1
G-202.1I ICRA PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
G-203.1 ICRA PLANS - ZONE 1D
STRUCTURAL
S-001 GENERAL NOTES AND LEGENDS
SD102.1 STRUCT DEMO PLAN - SECOND LEVEL - ZONE 1
SD102.1I STRUCT DEMO PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
S-102.1 FRAMING PLAN - SECOND LEVEL - ZONE 1
S-102.1I FRAMING PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
S-103.1 PARTIAL FRAMING PLANS - MECHANICAL ROOMS - ZONE 1
S-104.1 PARTIAL FRAMING PLANS - MECHANICAL ROOMS - ZONE 1
S-401 ENLARGED PLANS
S-501 SECTIONS AND DETAILS
ARCHITECTURAL
A-001 ARCHITECTURAL LEGENDS, SYMBOLS, AND ABBREVIATIONS
A-002 PARTITION TYPES
AD102.1 DEMOLITION PLAN - SECOND LEVEL - ZONE 1
A-102.1 FLOOR PLAN - SECOND LEVEL - ZONE 1
A-102.1A FLOOR PLAN - SECOND LEVEL - ZONE 1A
A-102.1B FLOOR PLAN - SECOND LEVEL - ZONE 1B
A-102.1C FLOOR PLAN - SECOND LEVEL - ZONE 1C
A-102.1D FLOOR PLAN - SECOND, THIRD, ROOF LEVELS - ZONE 1D
A-112.1 REFLECTED CEILING PLAN - SECOND LEVEL - ZONE 1
A-112.1A REFLECTED CEILING PLAN - SECOND LEVEL - ZONE 1A
A-112.1B REFLECTED CEILING PLAN - SECOND LEVEL - ZONE 1B
A-112.1C REFLECTED CEILING PLAN - SECOND LEVEL - ZONE 1C
A-112.1D REFLECTED CEILING PLAN - SECOND LEVEL - ZONE 1D
A-122.1 EQUIPMENT PLAN - SECOND LEVEL - ZONE 1
A-122.1A EQUIPMENT PLAN - SECOND LEVEL - ZONE 1A
A-122.1B EQUIPMENT PLAN - SECOND LEVEL - ZONE 1B
A-122.1C EQUIPMENT PLAN - SECOND LEVEL - ZONE 1C
A-122.1D EQUIPMENT PLAN - SECOND LEVEL - ZONE 1D
A-131 ENLARGED PLANS
A-132 ENLARGED PLANS - PHARMACY
A-401 INTERIOR ELEVATIONS - ZONE 1A
A-402 INTERIOR ELEVATIONS - ZONE 1B
A-403 INTERIOR ELEVATIONS - ZONE 1C
A-404 INTERIOR ELEVATIONS - ZONE 1C
A-405 INTERIOR ELEVATIONS - ZONE 1C
A-501 DETAILS
A-502 SECTIONS AND DETAILS
A-503 DETAILS AND ELEVATIONS - EXAM CLINIC - CHECK-IN DESK
A-504 DETAILS - NURSE STATION, CHECK-IN AND CHECK-OUT
A-505 DETAILS - MILLWORK
A-506 DETAILS - INFUSION BAYS
A-601 DOOR SCHEDULE AND DETAILS
INTERIORS
I-001 INTERIORS GENERAL NOTES AND LEGENDS
I-102.1 FINISH PLAN - SECOND LEVEL - ZONE 1
I-102.1A FINISH PLAN - SECOND LEVEL - ZONE 1A
I-102.1B FINISH PLAN - SECOND LEVEL - ZONE 1B
I-102.1C FINISH PLAN - SECOND LEVEL - ZONE 1C
I-102.1D FINISH PLAN - SECOND LEVEL - ZONE 1D
I-111 FURNITURE PLAN - SECOND LEVEL - ZONE 1 (FOR REFERENCE ONLY)
I-120 SIGNAGE PLAN - SECOND LEVEL - ZONE 1
I-121 SIGNAGE DETAILS
SHEET
NO. SHEET NAME
I-130 FLOORING SEAM PLAN - SECOND LEVEL - ZONE 1
FIRE PROTECTION
FD102 FP DEMO PLAN - SECOND LEVEL- ZONE 1
FD102.I FP DEMO PLAN - SECOND LEVEL INTERSTITAL - ZONE 1
FP102 FP PLAN - SECOND LEVEL - ZONE 1
PLUMBING
PD101.I DEMO PLAN - FIRST LEVEL INTERSTITIAL - ZONE 1
PD102 DEMO PLAN - SECOND LEVEL - ZONE 1
PD102.I DEMO PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
PP102.I PIPING PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
PW101.I DWV PLAN - FIRST LEVEL INTERSTITIAL - ZONE 1
PW102.I DWV PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
P-102 PLUMBING PLAN - SECOND LEVEL - ZONE 1
P-501 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
MECHANICAL
M-001 MECHANICAL LEGENDS
MD101.I DEMO PLAN - FIRST LEVEL INTERSTITAL - ZONE 1
MD102 DEMO PLAN - SECOND LEVEL - ZONE 1
MD102.1I PIPING DEMO PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
MD102.2I HVAC DEMO PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
MD401 ENLARGED MECHANICAL DEMO PLANS
MH102 HVAC PLAN - SECOND LEVEL - ZONE 1
MH102.I HVAC PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
MP101.I PIPING PLAN - FIRST LEVEL INTERSTITIAL - ZONE 1
MP102 PIPING PLAN - SECOND LEVEL - ZONE 1
MP102.I PIPING PLAN - SECOND LEVEL INTERSTITIAL - ZONE 1
M-401 ENLARGED MECHANICAL PLANS
M-402 ENLARGED MECHANICAL PLANS
M-403 ENLARGED MECHANICAL PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL AHU DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-701 MECHANICAL DIAGRAMS & SCHEMATICS
M-801 MECHANICAL CONTROLS
M-802 MECHANICAL CONTROLS
ELECTRICAL
E-000 ELECTRICAL GENERAL INFORMATION
E-001 LIGHTING SCHEDULES
ELD102.1 LIGHTING DEMOLITION PLAN-SECOND LEVEL-ZONE 1
EPD102.1 POWER DEMOLITION PLAN-SECOND LEVEL-ZONE 1
ETD102.1 TECHNOLOGY DEMOLITION PLAN-SECOND LEVEL-ZONE 1
EL102.1 LIGHTING PLAN-SECOND LEVEL-ZONE 1
EL102.1A LIGHTING PLAN-SECOND LEVEL-ZONE 1A
EL102.1B LIGHTING PLAN-SECOND LEVEL-ZONE 1B
EL102.1C LIGHTING PLAN-SECOND LEVEL-ZONE 1C
EL102.1D LIGHTING PLAN-SECOND LEVEL-ZONE 1D
EP102.1 POWER PLAN-SECOND LEVEL-ZONE 1
EP102.1A POWER PLAN-SECOND LEVEL-ZONE 1A
EP102.1B POWER PLAN-SECOND LEVEL-ZONE 1B
EP102.1C POWER PLAN-SECOND LEVEL-ZONE 1C
EP102.1D POWER PLAN-SECOND LEVEL-ZONE 1D
ET102.1 TECHNOLOGY PLAN-SECOND LEVEL-ZONE 1
ET102.1A TECHNOLOGY PLAN-SECOND LEVEL-ZONE 1A
ET102.1B TECHNOLOGY PLAN-SECOND LEVEL-ZONE 1B
ET102.1C TECHNOLOGY PLAN-SECOND LEVEL-ZONE 1C
ET102.1D TECHNOLOGY PLAN-SECOND LEVEL-ZONE 1D
E-300 ELECTRICAL ELEVATIONS
E-500 ELECTRICAL DETAILS
E-501 ELECTRICAL DETAILS
E-600 PANEL SCHEDULES
E-702 LOW VOLTAGE RISER DIAGRAM
TOTAL SHEETS: 118
RESPONSIBILITY MATRIX
DESCRIPTION SPECIFIED BY AI REMARK
TIS - CONDUIT, BOXES AND RACEWAYS ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
TIS - CABLE, CABLE INSTALLATION, AND TERMINATIONS ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN
TIS - MONITOR BRACKETS/MOUNTS GOVERNMENT C C BLOCKING BY CONTRACTOR
TIS - EQUIPMENT ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN, POWER,
ETC.
SECURITY SYSTEM - CONDUIT AND BOXES ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
SECURITY SYSTEM - CABLE, CABLE INSTALLATION, AND
TERMINATIONS
ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
SECURITY SYSTEM - EQUIPMENT ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN,
LOCATION, POWER, ETC.
NURSE CALL - CONDUIT, BOXES AND RECEWAYS ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
NURSE CALL - CABLE, CABLE INSTALLATION, AND
TERMINATIONS
ARCHITECT C C -
NURSE CALL - EQUIPMENT ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN
FIRE ALARM - CONDUIT, BOXES AND RECEWAYS ARCHITECT C C -
FIRE ALARM - CABLE, CABLE INSTALLATION, AND
TERMINATIONS
ARCHITECT C C -
FIRE ALARM - EQUIPMENT ARCHITECT C C -
PAGING - CONDUIT, BOXES AND RECEWAYS ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
PAGING - CONDUIT, CABLE INSTALLATION,AND
TERMINATIONS
ARCHITECT C C -
PAGING - EQUIPMENT, SPEAKERS ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN
CCTV - CONDUIT, BOXES AND RACEWAYS ARCHITECT C C COORDINATE W/ SH AND GMH STANDARDS AND
STAFF
CCTV - CABLE, CABLE INSTALLATION, AND
TERMINATIONS
ARCHITECT C C -
CCTV - MONITOR BRACKET/ MOUNTS GOVERNMENT V C BLOCKING BY CONTRACTOR
CCTV - EQUIPMENT ARCHITECT C C ARCHITECT COORDINATES W/ DESIGN,
BLOCKING BY CONTRACTOR
COMMISSIONING GOVERNMENT V V
Revisions: Date:
35% SCHEMATIC DESIGN 02-MAR-2022
65% DESIGN DEVELOPMENT 29-AUG-2023
95% CONSTRUCTION DOCUMENTS 15-APR-2024
95% CONSTRUCTION DOCUMENTS - REVISED 27-AUG-2024
100% BID DOCUMENTS 10-JAN-2025
ADDENDUM 01 02-APR-2026
ADDENDUM 02 30-APR-2026
A02
Page 12 of 41 Addendum #2
LL
MM
NN
WORK ROOM
A2013
CONSULATION
ROOM
A2101
OFFICE
A2007
OFFICE
A2005
PATIENT
EDUCATION
(MIND BODY
SOUL)
A2010
HAC
A2103
CART LIFT #01
CL-1
CART LIFT #02
CL-2
INFUSION
CLINIC LOBBY
A2011
OFFICE
A2059
SHARED
OFFICE
A2058
SHARED
OFFICE
A2060
STORAGE
PHARMACEUTI
A2107
HAC
A2016
ELECTRICAL
A2067
CORRIDOR
CA217
CART LIFT #03
CL-3
SHARED
OFFICE
A2108
SHARED
OFFICE
A2109
CORRIDOR
CA216STORAGE
PHARMACEUTI
A2107
HAC
A2016
ELECTRICAL
A2067
CORRIDOR
CA217
CART LIFT #03
CL-3
SHARED
OFFICE
A2108
SHARED
OFFICE
A2109
OFFICE
A2014
CHECK-IN/
CHECK-OUT
A2012
CORRIDOR
CA216
A-4012
A-40115
A-401 12
A-401 10
A-401
WORK ROOM
A2015
A-4015 6
A-401
PRN-1
A-4018
ZONE 1A
ZONE 1B
ZO
NE
1A
ZO
NE
1C
ZONE 1AZONE 1B
ZO
NE
1A
ZO
NE
1CZONE 1ZONE 5
SHR-1
OFFICE - RN
CARE
COORDINATOR
A2023
CORRIDOR
CA216
OFFICE
A2061
A-40118
A-503
A-504
A-504
A-401
LKR2 LKR2LKR2 LKR2
CG3.1
CH-1 CH-1 CH-2
CH-1
CG2.2
CG4.1
CG2.2
CG2.2
CG2.2
CG1.2
CH-2 CH-1
WC-1
CH-1
CH-1
CH-2
CH-2
CH-2 CH-1 CH-1
WC-1
CG1.1
PRN-2
CPU-1
CPU-1
CPU-1
CPU-1
CPU-1
CG1.1E CPU-1 CPU-1
CPU-1
CG1.1
CG1.1E
CG1.1
CPU-1
CPU-1
CPU-1
CPU-1
CG2.2
CG1.1
CG1.1
CG1.1 CG1.1
CH-3
CH-3
CH-3
CH-3 CH-3
CPU-1
CPU-1
TB-1
CH-3
CH-3
CH-3
CPU-1
CPU-1
CH-3
CH-3CH-3
CH-3
CH-3
TB-1
TB-1
TB-1
CH-3
CH-3
CH-3CH-3 CH-3 CH-3
CH-3
CH-3 CH-3
CH-3
CH-3
CH-3CH-3
CH-3
CH-3
CPU-1
CPU-1
CPU-1
CPU-1
A-40216
HR1
HR1 HR1
HR1
HR1
HR1HR1
HR1
HR1
HR1
HR1
TV-1TB-1
CH-1
CH-1
HR1
HR1 HR1
DK-1 DK-1
DK-1
DK-1
TB-1
CH-3
DEDUCTIVE
ALTERNATE #1
DEDUCTIVE
ALTERNATE #1
DEDUCTIVE
ALTERNATE #1
CG4.1
CG1.1E
EXISTING
FIRE HOSE CABINET
CG1.1E
CG2.2
CG2.2
FEC
CG2.2
CG1.1
CG1.1
1. SEE REFLECTED CEILING PLAN FOR CEILING MOUNTED EQUIPMENT
INFORMATION
ABBREVIATIONS
AI - ACQUISTION AND INSTALLATION
C C - CONTRACTOR FURNISHED AND INSTALLED
D - DATA
E - ELECTRICAL
M - MECHANICAL
P - PLUMBING
N - NONE
V C - GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
V V - GOVERNMENT FURNISHED AND INSTALLED
SCHEDULE GENERAL NOTES PARTITION / WALL FIRE RATINGS
2-HR. FIRE
BARRIER
EXISTING 2-HR.
FIRE BARRIER
NOTE: EXISTING RATED WALL SHOWN SCREENED ON PLAN. - V.I.F. WALLS MEET
DESIGNATED REQUIREMENTS & ADD OPENING & PENETRATION PROTECTIVES
AS REQ'D
1-HR. SMOKE
BARRIER
NON-RATED
SMOKE PARTITION
EXISTING 1-HR.
SMOKE BARRIER
EXISTING NON-RATED
SMOKE PARTITION
1-HR. FIRE
BARRIER
EXISTING 1-HR.
FIRE BARRIER
1.
1.
2.
BASIS OF DESIGN:
MANUFACTURER: SR INSTRUMENTS, INC
MODEL: SR463iR-3
FLUSH MOUNTED PLATFORM SCALE
PLATFORM SIZE: 32" X 50"
MAX WEIGHT: 1000LB
WALL MOUNTED DISPLAY WITH LED BACKLIGHT
DISPLAY TO OFFER MEMORY RECALL
DISPLAY UNITS: POUNDS / KILOGRAMS
WALL MOUNTED BUILT-IN PRINTER
POWER: 120VAC 50-60Hz
SCALE TO AUTOMATICALLY TURN ON
BUILT-IN GRAB BAR
WARRANTY: MINIMUM 4 YEARS
FURNITURE & EQUIPMENT - NOTES LEGEND
1. CUBICLE CURTAIN TO BE FAB-1, SEE MATERIALS SCHEDULE
DIVISION 10 - NOTES LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
John D. Dingell VA Medical Center
4646 John R. Street
Detroit , MI 48201
3419 Pierson Place Flushing, Michigan, 48433 810-230-6202
(866) 454-3923 | WWW.C2AE.COM
Au tod es k D oc s:/
/V A
MI
D etr oit
/21
_A
.rv t
5/1 /20
8:
:06
A M
A-122.1A
EQUIPMENT PLAN - SECOND
LEVEL - ZONE 1A
RENOVATE A2 SOUTH
FOR CANCER CLINIC
DETROIT, MI
553-21-100
10-JAN-2025 KJH MRB
100% BID DOCUMENTS
1/4" = 1'-0"
EQUIPMENT PLAN - SECOND LEVEL - ZONE 1A
FURNITURE & EQUIPMENT SCHEDULE
TAG DESCRIPTION UTILITIES AI
BLOCKING
REQ'D NOTES
BCH-1 BENCH, MOBILE - V V NO
BW-1 BLANKET WARMER E V V NO
CC-1 CRASH CART - V V NO
CD-1 EAR CUP DISPENSER - V C NO
CH-1 CHAIR - V V NO
CH-2 CHAIR - V V NO
CH-3 CHAIR - V V NO
CM-1 COFFEE MAKER - TALL E V V NO
CM-2 COFFEE MAKER - SHORT E V V NO
CPU-1 COMPUTER WORKSTATION E, D V V NO
CPU-2 COMPUTER, WALL MOUNTED E, D V V YES
CPW-1 CHEMOTHERAPY PPE WASTE - V V NO
CRT-1 CART, PPE - V V NO
DISP-1 MAGNETIC BULK DISPENSER - V C YES
DK-1 DESK - V V NO
EMP-1 EQUIPMENT MOUNTING PANEL - V C YES
ET-1 EXAM TABLE - V V NO
GL-1 WIRE GLOVE BOX HOLDER N V C YES
H01-72 LAMINAR FLOW E V C NO
H02-48 BIOLOGICAL SAFETY CABINET - CLASS II, TYPE A2 E, M V C NO
HW-1 HAZARDOUS TRASH - 12 GALLON - BLACK - V V NO
HW-2 HAZARDOUS TRASH - 19 GALLON - YELLOW - V V NO
ICE-1 COUNTER ICE MAKER E, P V V NO
IFS-1 IN-FLOOR SCALE E C C NO NOTE: 1
IR-1 INFUSION RECLINER E V V NO
MBC-1 MOBILE L BASE CABINET - V V NO
MED-1 MEDICAL SUPPLY CART - V V NO
MON-2 PATIENT TV, WALL MOUNTED E V V YES
MW-1 MICROWAVE E V V NO
OMC-1 OMNICELL MED MACHINE E, D V V NO
OT-1 OTOSCOPE/OPTHALMOSCOPE, WALL MTD. E V C NO
PL-1 CEILING MOUNTED PATIENT LIFT, SOLE SOURCED E C C YES
PPT-1 PHARMACY PASS THROUGH - CLEAN ROOM E C C NO
PRN-1 PRINTER - FLOOR E, D V V NO
PRN-2 MULTI-FUNCTIONAL DEVICE - COUNTERTOP E V V NO
PRN-3 PRINTER - XEROX VERSALINK B600 E, D V V NO
PRN-4 ZEBRA BAR CODE PRINTER E, D V V NO
REF-1 REFRIGERATOR E V V NO
REF-2 REFRIGERATOR - PHARMACY E V V NO
REF-3 REFRIGERATOR - MEDICATION E V V NO
SHR-1 SHREDDER BOX - V V NO
SLF-1 SHELVING, MOBILE - V V NO
SPH-1 SPHYGMOMANOMETER, WALL MOUNTED - V C NO
SRP-1 SHARPS CONTAINER - V C YES
ST-1 EXAM STOOL - V V NO
STR-1 STRETCHER - V V NO
TB-1 TABLE - V V NO
TB-2 TABLE, MOBILE - V V NO
TC-1 TRASH CAN - V V NO
THM-1 THERMOMETER - V C NO
TV-1 TV AND TV BRACKET E, D V C NO
VSM-1 VITAL SIGNS MONITOR - MOBILE - V V NO
WC-1 WHEELCHAIR - V V NO
WOW-1 WOW E V V NO
DIVISION 10 SCHEDULE
TAG DESCRIPTION
BASIS OF
DESIGN AI
BLOCKING
REQ'D NOTES
CCT1 CUBICLE CURTAIN TRACK & CARRIERS - C C NO NOTES: 1
CG1.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.1E CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.2 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.2E CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG2.2 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG3.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG4.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG5.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CH1 HAT & COAT HOOK BRADLEY, MODEL 9124 C C YES
DCS1 DIAPER CHANGING STATION C C YES
FEC FIRE EXTINGUISHER CABINET, RECESSED - C C NO
FHC FIRE HOSE CABINET, RECESSED - NO
GB1 18" GRAB BAR - C C YES
GB2 42" GRAB BAR - C C YES
GB3 36" GRAB BAR - C C YES
HR1 HAND RAIL AND BUMPER (SEE MATERIALS SCHEDULE) - C C YES
HS1 HAND SANITIZER - V C YES
LKR1 LOCKER (PHENOLIC) - C C YES
LKR2 LOCKER (LAMINATE) - C C YES
MB1 MAGNETIC MARKERBOARD, 2' X 3' - C C YES
MB2 MAGNETIC WHITE BOARD, 4' X 6' - C C YES
MR1 24" x 36" MIRROR - C C YES
PT1 PAPER TOWEL DISPENSER - V C YES
SD1 SOAP DISPENSER - V C YES
SND SANITARY NAPKIN DISPOSAL - V C YES
TTD1 TOILET TISSUE DISPENSER - V C YES
Revisions: Date:
65% DESIGN DEVELOPMENT 29-AUG-2023
95% CONSTRUCTION DOCUMENTS 15-APR-2024
95% CONSTRUCTION DOCUMENTS - REVISED 27-AUG-2024
100% BID DOCUMENTS 10-JAN-2025
ADDENDUM 02 30-APR-2026
A02
A02A02A02
Page 13 of 41 Addendum #2
56789
MM
NN
7.4
Q.4 Q.4
Q.5 Q.5
Q.8 Q.8
Q.9
8.6 6.5
A-131
A-402 12
A-4026
STORAGE
PHARMACEUTI
A2107
HAC
A2016
ELECTRICAL
A2067
CORRIDOR
CA217
CART LIFT #03
CL-3
SHARED
OFFICE
A2108
SHARED
OFFICE
A2109
CORRIDOR
CA216
MENS
LOCKERS
A2113
MENS TOILET
A2113A
STORAGE
PHARMACEUTI
A2107
HAC
A2016
ELECTRICAL
A2067
CORRIDOR
CA217
CART LIFT #03
CL-3
SHARED
OFFICE
A2108
SHARED
OFFICE
A2109
WOMEN'S
LOCKERS
A2110
WOMEN'S
TOILET
A2110A
TOILET
A2017A
BREAK ROOM
A2114
SHARED
OFFICE
A2020
GROUP ROOM
A2018
EXAM CLINIC
WAITING
A2017
OFFICE
A2014
CHECK-IN/
CHECK-OUT
A2012
CORRIDOR
CA216
INFUSION
ROOM 2
A2065
INFUSION
ROOM 3
A2066
OFFICE - RN
CARE
COORDINATOR
A2025
ANTI-COAG
A2026
EXAM
A2028
CORRIDOR
CA208
A-402
A-4029
A-4023 1
A-405
A-40115
A-401 12
A-401 10
A-401
WORK ROOM
A2015
A-4015 6
PRN-1
ZONE 1A
ZONE 1B
ZO
NE
1A
ZO
NE
1C
ZONE 1AZONE 1B
ZO
NE
1C
ZO
NE
1B
ZO
NE
ZO
NE
SHR-1
REF-1
CM-2
MW-1
SHARED
OFFICE
A2022
OFFICE - RN
CARE
COORDINATOR
A2023
CORRIDOR
CA216
CORRIDOR
CA213
WEIGHT
A2024
A-503
A-504
A-401
A-40213
PRN-2
PRN-2
CPU-1
CPU-1
CPU-1
CPU-1
CPU-1
CPU-1
CG3.1
CH-1 CH-1 CH-2
CH-1
CG2.2
CG4.1
CG2.2
CG2.2
CG2.2
CPU-1
CG1.1
CG1.1E
CG1.1
CPU-1
CPU-1
CPU-1
CPU-1
CH-2
WC-1
CH-2 CH-2
CH-2 CH-2
CH-2 WC-1
CH-2
CH-2
CH-1
CH-1CH-1CH-2CH-2
CG3.1
CG3.1
CG3.1
TV-1
CG1.1
CPU-1
CG1.1CG1.1
CG1.1
CG3.1
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
TB-1
CH-3
CH-3CH-3
TB-1
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
TB-1 TB-1 TB-1
CH-3
CH-3
CH-3 CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CPU-1
CPU-1
CPU-1
CPU-1
TB-1
CH-3
IFS-1
CH-3
CH-3
CPU-1
CPU-1
CH-3
CH-3CH-3
CH-3
CH-3
A-40216
HR1
HR1
HR1 HR1
HR1
HR1
HR1HR1
HR1 HR1HR1
HR1HR1
HR1
HR1
DK-1
DK-1
TB-1 TB-1
DK-1
HR1
HR1
HR1
MB2
CH-3
CG4.1
CG4.1
CG3.1
DEDUCTIVE
ALTERNATE #1
DEDUCTIVE ALTERNATE #1
DEDUCTIVE
ALTERNATE #4
CG4.1
LKR1
LKR1
CG1.1
CG1.2 CG1.2E
CG1.1E
EXISTING
FIRE HOSE CABINET
CG1.1E
CG2.2
CG2.2
FEC
CG1.1
1. SEE REFLECTED CEILING PLAN FOR CEILING MOUNTED EQUIPMENT
INFORMATION
ABBREVIATIONS
AI - ACQUISTION AND INSTALLATION
C C - CONTRACTOR FURNISHED AND INSTALLED
D - DATA
E - ELECTRICAL
M - MECHANICAL
P - PLUMBING
N - NONE
V C - GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
V V - GOVERNMENT FURNISHED AND INSTALLED
SCHEDULE GENERAL NOTES PARTITION / WALL FIRE RATINGS
2-HR. FIRE
BARRIER
EXISTING 2-HR.
FIRE BARRIER
NOTE: EXISTING RATED WALL SHOWN SCREENED ON PLAN. - V.I.F. WALLS MEET
DESIGNATED REQUIREMENTS & ADD OPENING & PENETRATION PROTECTIVES
AS REQ'D
1-HR. SMOKE
BARRIER
NON-RATED
SMOKE PARTITION
EXISTING 1-HR.
SMOKE BARRIER
EXISTING NON-RATED
SMOKE PARTITION
1-HR. FIRE
BARRIER
EXISTING 1-HR.
FIRE BARRIER
1.
1.
2.
BASIS OF DESIGN:
MANUFACTURER: SR INSTRUMENTS, INC
MODEL: SR463iR-3
FLUSH MOUNTED PLATFORM SCALE
PLATFORM SIZE: 32" X 50"
MAX WEIGHT: 1000LB
WALL MOUNTED DISPLAY WITH LED BACKLIGHT
DISPLAY TO OFFER MEMORY RECALL
DISPLAY UNITS: POUNDS / KILOGRAMS
WALL MOUNTED BUILT-IN PRINTER
POWER: 120VAC 50-60Hz
SCALE TO AUTOMATICALLY TURN ON
BUILT-IN GRAB BAR
WARRANTY: MINIMUM 4 YEARS
FURNITURE & EQUIPMENT - NOTES LEGEND
1. CUBICLE CURTAIN TO BE FAB-1, SEE MATERIALS SCHEDULE
DIVISION 10 - NOTES LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
John D. Dingell VA Medical Center
4646 John R. Street
Detroit , MI 48201
3419 Pierson Place Flushing, Michigan, 48433 810-230-6202
(866) 454-3923 | WWW.C2AE.COM
Au tod es k D oc s:/
/V A
MI
D etr oit
/21
_A
.rv t
5/1 /20
8:
:22
A M
A-122.1B
EQUIPMENT PLAN - SECOND
LEVEL - ZONE 1B
RENOVATE A2 SOUTH
FOR CANCER CLINIC
DETROIT, MI
553-21-100
10-JAN-2025 KJH MRB
100% BID DOCUMENTS
1/4" = 1'-0"
EQUIPMENT PLAN - SECOND LEVEL - ZONE 1B
FURNITURE & EQUIPMENT SCHEDULE
TAG DESCRIPTION UTILITIES AI
BLOCKING
REQ'D NOTES
BCH-1 BENCH, MOBILE - V V NO
BW-1 BLANKET WARMER E V V NO
CC-1 CRASH CART - V V NO
CD-1 EAR CUP DISPENSER - V C NO
CH-1 CHAIR - V V NO
CH-2 CHAIR - V V NO
CH-3 CHAIR - V V NO
CM-1 COFFEE MAKER - TALL E V V NO
CM-2 COFFEE MAKER - SHORT E V V NO
CPU-1 COMPUTER WORKSTATION E, D V V NO
CPU-2 COMPUTER, WALL MOUNTED E, D V V YES
CPW-1 CHEMOTHERAPY PPE WASTE - V V NO
CRT-1 CART, PPE - V V NO
DISP-1 MAGNETIC BULK DISPENSER - V C YES
DK-1 DESK - V V NO
EMP-1 EQUIPMENT MOUNTING PANEL - V C YES
ET-1 EXAM TABLE - V V NO
GL-1 WIRE GLOVE BOX HOLDER N V C YES
H01-72 LAMINAR FLOW E V C NO
H02-48 BIOLOGICAL SAFETY CABINET - CLASS II, TYPE A2 E, M V C NO
HW-1 HAZARDOUS TRASH - 12 GALLON - BLACK - V V NO
HW-2 HAZARDOUS TRASH - 19 GALLON - YELLOW - V V NO
ICE-1 COUNTER ICE MAKER E, P V V NO
IFS-1 IN-FLOOR SCALE E C C NO NOTE: 1
IR-1 INFUSION RECLINER E V V NO
MBC-1 MOBILE L BASE CABINET - V V NO
MED-1 MEDICAL SUPPLY CART - V V NO
MON-2 PATIENT TV, WALL MOUNTED E V V YES
MW-1 MICROWAVE E V V NO
OMC-1 OMNICELL MED MACHINE E, D V V NO
OT-1 OTOSCOPE/OPTHALMOSCOPE, WALL MTD. E V C NO
PL-1 CEILING MOUNTED PATIENT LIFT, SOLE SOURCED E C C YES
PPT-1 PHARMACY PASS THROUGH - CLEAN ROOM E C C NO
PRN-1 PRINTER - FLOOR E, D V V NO
PRN-2 MULTI-FUNCTIONAL DEVICE - COUNTERTOP E V V NO
PRN-3 PRINTER - XEROX VERSALINK B600 E, D V V NO
PRN-4 ZEBRA BAR CODE PRINTER E, D V V NO
REF-1 REFRIGERATOR E V V NO
REF-2 REFRIGERATOR - PHARMACY E V V NO
REF-3 REFRIGERATOR - MEDICATION E V V NO
SHR-1 SHREDDER BOX - V V NO
SLF-1 SHELVING, MOBILE - V V NO
SPH-1 SPHYGMOMANOMETER, WALL MOUNTED - V C NO
SRP-1 SHARPS CONTAINER - V C YES
ST-1 EXAM STOOL - V V NO
STR-1 STRETCHER - V V NO
TB-1 TABLE - V V NO
TB-2 TABLE, MOBILE - V V NO
TC-1 TRASH CAN - V V NO
THM-1 THERMOMETER - V C NO
TV-1 TV AND TV BRACKET E, D V C NO
VSM-1 VITAL SIGNS MONITOR - MOBILE - V V NO
WC-1 WHEELCHAIR - V V NO
WOW-1 WOW E V V NO
DIVISION 10 SCHEDULE
TAG DESCRIPTION
BASIS OF
DESIGN AI
BLOCKING
REQ'D NOTES
CCT1 CUBICLE CURTAIN TRACK & CARRIERS - C C NO NOTES: 1
CG1.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.1E CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.2 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG1.2E CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG2.2 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG3.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG4.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CG5.1 CORNER GUARD (SEE MATERIALS SCHEDULE) - C C NO
CH1 HAT & COAT HOOK BRADLEY, MODEL 9124 C C YES
DCS1 DIAPER CHANGING STATION C C YES
FEC FIRE EXTINGUISHER CABINET, RECESSED - C C NO
FHC FIRE HOSE CABINET, RECESSED - NO
GB1 18" GRAB BAR - C C YES
GB2 42" GRAB BAR - C C YES
GB3 36" GRAB BAR - C C YES
HR1 HAND RAIL AND BUMPER (SEE MATERIALS SCHEDULE) - C C YES
HS1 HAND SANITIZER - V C YES
LKR1 LOCKER (PHENOLIC) - C C YES
LKR2 LOCKER (LAMINATE) - C C YES
MB1 MAGNETIC MARKERBOARD, 2' X 3' - C C YES
MB2 MAGNETIC WHITE BOARD, 4' X 6' - C C YES
MR1 24" x 36" MIRROR - C C YES
PT1 PAPER TOWEL DISPENSER - V C YES
SD1 SOAP DISPENSER - V C YES
SND SANITARY NAPKIN DISPOSAL - V C YES
TTD1 TOILET TISSUE DISPENSER - V C YES
Revisions: Date:
65% DESIGN DEVELOPMENT 29-AUG-2023
95% CONSTRUCTION DOCUMENTS 15-APR-2024
95% CONSTRUCTION DOCUMENTS - REVISED 27-AUG-2024
100% BID DOCUMENTS 10-JAN-2025
ADDENDUM 02 30-APR-2026
A02
A02
Page 14 of 41 Addendum #2
23456
LL
MM
NN
A-4054
A-4056
A-403 10
A-40513
A-4042
A-4046
A-40516 15
A-131
A-131
A-132
A-4035
A-403
INFUSION
ROOM 1
A2064
INFUSION
ROOM 2
A2065
INFUSION
ROOM 3
A2066 SOILED UTILITY
A2052
CLEAN UTILITY
A2050
CLEAN LINEN
A2048 MED ROOM
A2046
NURSE
STATION
A2075
OFFICE - RN
CARE
COORDINATOR
A2025
ALCOVE
A2044
EXAM
A2033
EXAM
A2035
EXAM
A2037
EXAM
A2039
ANTI-COAG
A2026
EXAM
A2028
EXAM
A2030
EXAM
A2034
EXAM
A2036
EXAM
A2038
EXAM
A2040
WORK ROOM
A2042
PATIENT
TOILET
A2069
PATIENT
TOILET
A2071
INFUSION BAY
A2070
INFUSION BAY
A2074
INFUSION BAY
A2076
INFUSION BAY
A2078
INFUSION BAY
A2080 INFUSION BAY
A2082
INFUSION BAY
A2084
INFUSION BAY
A2086
STRETCHER /
WHEELCHAIR
STORAGE
A2087
ALCOVE
A2085
INFUSION BAY
A2083
INFUSION BAY
A2081
NUTRITION
A2049
BREAK ROOM
A2047
LOCKER ROOM
A2047A
STAFF TOILET
A2045
CORRIDOR
CA213
CORRIDOR
CA208
CORRIDOR
CA212
CORRIDOR
CA211
CORRIDOR
CA209
CORRIDOR
CA207
ALCOVE
A2079
EXAM
A2041
EQUIPMENT
STORAGE
A2043
STERILE
HAZARDOUS
DRUG BUFFER
ROOM
A2057
ANTE ROOM
A2055
HAZARDOUS
DRUG
STORAGE
A2054
A-131
A-131
A-131
A-131
A-40416
A-40415A-40414
A-405
A-405
A-405 9
A-4036
ZO
NE
1A
ZO
NE
1C
ZO
NE
1A
ZO
NE
1C
ZO
NE
1C
ZO
NE
1D
ZO
NE
1C
ZO
NE
1D
ZO
NE
1C
ZO
NE
1B
EXAM
A2029
INFUSION BAY
A2068
INFUSION BAY
A2072
WEIGHT
A2063
CORRIDOR
CA213
A-131
A-404
CPU-1
CPU-1
CPU-1
CPU-1
PRN-2
CG1.1
CG1.1CG1.1
CG1.1
CG1.1
CG1.1E
TC-1
MW-1
CM-2
SD1
PT1
CG1.1
WC-1WC-1
STR-1
MED-1VSM-1
CG1.1
CG1.1
CG1.1
CG1.1 CG1.1 CG1.1
IFS-1
MED-1
CPW-1
CC-1
CG1.1
CG3.1 CG3.1
CH-3
CH-3
CH-3
WOW-1
WOW-1
WOW-1
WOW-1OMC-1
TC-1
TC-1
REF-3
CH-3
CH-3
TB-1
CH-3
CH-3
SRP-1
PT1
SD1
CG1.1E CG1.1E
WOW-1 WOW-1 WOW-1 WOW-1 WOW-1
PRN-3
PRN-4
CH-3
CH-3
CH-3CH-3CH-3
CPU-1 CPU-1 CPU-1
CPU-1
CPU-1
REF-1
TC-1
ICE-1
MW-1
PT1
SD1
CM-1
REF-1
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
CH-3
SLF-1
SLF-1
SLF-1
SLF-1
SLF-1
SLF-1
SLF-1
SLF-1
PT1
CH-3
CH-3
CH-3
CH-3
CPU-1
HR1 HR1HR1
HR1 HR1
HR1
HR1
HR1
HR1 HR1
HR1
HR1
HR1
HR1
HR1 HR1
HR1
HR1
HR1
HR1
HR1HR1HR1
HR1
HR1
HR1
HR1
HR1
HR1
TB-1 TB-1
DK-1
HR1
HR1
HR1
HR1
HR1
CPU-1
CG4.1
CG4.1
SD1
CG1.1
CG1.1
CG1.1
CG1.1E LKR1
CG1.1
CG3.1CG3.1
DEDUCTIVE
ALTERNATE #1
DEDUCTIVE
ALTERNATE #1
DEDUCTIVE
ALTERNATE #2
DEDUCTIVE
ALTERNATE #2
DEDUCTIVE
ALTERNATE #2
DEDUCTIVE
ALTERNATE #2
DEDUCTIVE
ALTERNATE #2
DEDUCTIVE
ALTERNATE #4
CG1.1
CG1.1
A-502
A-502
FHC
FHC
FEC
CG1.1
CG1.1
CG1.1 CG1.1
CG1.1
CG1.1CG1.1
CG1.1
CG1.1
CG1.1 CG1.1
CG1.1
CG1.1
CG1.1 CG1.1
CG1.1
CG1.1
CG1.1
CG1.1
CG1.1 CG1.1 CG1.1
CG1.1
CG1.1
A02
1. SEE REFLECTED CEILING PLAN FOR CEILING MOUNTED EQUIPMENT
INFORMATION
ABBREVIATIONS
AI - ACQUISTION AND INSTALLATION
C C - CONTRACTOR FURNISHED AND INSTALLED
D - DATA
E - ELECTRICAL
M - MECHANICAL
P - PLUMBING
N - NONE
V C - GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
V V - GOVERNMENT FURNISHED AND INSTALLED
SCHEDULE GENERAL NOTES PARTITION / WALL FIRE RATINGS
2-HR. FIRE
BARRIER
EXISTING 2-HR.
FIRE BARRIER
NOTE: EXISTING RATED WALL SHOWN SCREENED ON PLAN. - V.I.F. WALLS MEET
DESIGNATED REQUIREMENTS & ADD OPENING & PENETRATION PROTECTIVES
AS REQ'D
1-HR. SMOKE
BARRIER
NON-RATED
SMOKE PARTITION
EXISTING 1-HR.
SMOKE BARRIER
EXISTING NON-RATED
SMOKE PARTITION
1-HR. FIRE
BARRIER
EXISTING 1-HR.
FIRE BARRIER
1.
1.
2.
BASIS OF DESIGN:
MANUFACTURER: SR INSTRUMENTS, INC
MODEL: SR463iR-3
FLUSH MOUNTED PLATFORM SCALE
PLATFORM SIZE: 32" X 50"
MAX WEIGHT: 1000LB
WALL MOUNTED DISPLAY WITH LED BACKLIGHT
DISPLAY TO OFFER MEMORY RECALL
DISPLAY UNITS: POUNDS / KILOGRAMS
WALL MOUNTED BUILT-IN PRINTER
POWER: 120VAC 50-60Hz
SCALE TO AUTOMATICALLY TURN ON
BUILT-IN GRAB BAR
WARRANTY: MINIMUM 4 YEARS
FURNITURE & EQUIPMENT - NOTES LEGEND
1. CUBICLE CURTAIN TO BE FAB-1, SEE MATERIALS SCHEDULE
DIVISION 10 - NOTES LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
John D. Dingell VA Medical Center
4646 John R. Street
Detroit , MI 48201
3419 Pierson Place Flushing, Michigan, 48433 810-230-6202
(866) 454-3923 | WWW.C2AE.COM
Au tod es k D oc s:/
/V A
MI
D etr oit
/21
_A
.rv t
5/1 /20
8:
:39
A M
A-122.1C
EQUIPMENT PLAN - SECOND
LEVEL - ZONE 1C
RENOVATE A2 SOUTH
FOR CANCER CLINIC
DETROIT, MI
553-21-100
10-JAN-2025 KJH MRB
100% BID DOCUMENTS
1/4" = 1'-0"
EQUIPMENT PLAN - SECOND LEVEL - ZONE 1C
FURNITURE & EQUIPMENT SCHEDULE
TAG DESCRIPTION UTILITIES AI
BLOCKING
REQ'D NOTES
BCH-1 BENCH, MOBILE - V V NO
BW-1 BLANKET WARMER E V V NO
CC-1 CRASH CART - V V NO
CD-1 EAR CUP DISPENSER - V C NO
CH-1 CHAIR - V V NO
CH-2 CHAIR - V V NO
CH-3 CHAIR - V V NO
CM-1 COFFEE MAKER - TALL E V V NO
CM-2 COFFEE MAKER - SHORT E V V NO
CPU-1 COMPUTER WORKSTATION E, D V V NO
CPU-2 COMPUTER, WALL MOUNTED E, D V V YES
CPW-1 CHEMOTHERAPY PPE WASTE - V V NO
CRT-1 CART, PPE - V V NO
DISP-1 MAGNETIC BULK DISPENSER - V C YES
DK-1 DESK - V V NO
EMP-1 EQUIPMENT MOUNTING PANEL - V C YES
ET-1 EXAM TABLE - V V NO
GL-1 WIRE GLOVE BOX HOLDER N V C YES
H01-72 LAMINAR FLOW E V C NO
H02-48 BIOLOGICAL SAFETY CABINET - CLASS II, TYPE A2 E, M V C NO
HW-1 HAZARDOUS TRASH - 12 GALLON - BLACK - V V NO
HW-2 HAZARDOUS TRASH - 19 GALLON…
This is the start of the file's text. The full file is on GovTribe.