This document is a Standard Form 30 Amendment of Solicitation/Modification of Contract issued by the Department of Veterans Affairs Network Contracting Office 10 in Indianapolis, Indiana. The amendment (number 0003) is focused on correcting a previously posted Statement of Work (SOW), specifically modifying paragraph 5B related to a Medical Air Compressor Unit replacement.
The key modification changes the specifications for the Medical Air Compressor Unit in location B330-BC120, updating the power configuration from 460V-1PH-10HP to 230/460V-3PH-15HP. The revised requirements maintain NFPA 99 compliance and include detailed specifications for the medical air unit, such as a minimum 120 PSIG discharge pressure, dual desiccant air dryers, high-efficiency filters, and specific installation requirements like gas-specific demand check fittings, correct piping materials, and a valve sample port for medical air sampling. The amendment does not alter the solicitation's opening date and emphasizes that all other terms and conditions remain unchanged.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SOW UPDATED.doc | DOC document | |
| 36C25026B0004 0002.pdf | ||
| Site Visit Attendance 552-25-50510-29-2025-151305.pdf | ||
| 36C25026B0004 0001.pdf | ||
| Attachment II - RFI Response Pictures.pdf | ||
| Attachment X - Exhibit 4.pdf | ||
| Attachment IV - EMR.docx | DOCX document | |
| Attachment III - VA Notice of Limitations on Subcontracting.docx | DOCX document | |
| Attachment XII - RFI Template.doc | DOC document | |
| Attachment XI - Exhibit 5.pdf | ||
| Attachment VI - Specifications.pdf | ||
| 36C25026B0004_1.docx | DOCX document | |
| Attachment IX - Exhibit 3.pdf | ||
| Attachment VIII - Exhibit 2.pdf | ||
| Attachment V - Drawings.pdf | ||
| Attachment II - VHA Directive 1192-01.pdf | ||
| Attachment VII - Exhibit 1.pdf | ||
| Attachment I - Wage Determination.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 2
0003 11-18-2025
552-26-1-6976-0004
552-25-505
36C250
Department of Veterans Affairs Network Contracting Office 10 8888 Keystone Crossing Suite 325 Indianapolis IN 46240
36C250
Department of Veterans Affairs Network Contracting Office 10 8888 Keystone Crossing Suite 325 Indianapolis IN 46240
To all Offerors/Bidders
36C25026B0004
10-20-2025
X
X X
552-3660162-6976-854200-2670-23NRNR001
X 1
The purpose of this amendment is to make a correction to the previously posted Statement of Work. The error is on page 6 of the solicitation.
See page 2 of this amendment for further details.
All other terms and conditions remain unchanged.
Luke A. Turner Contracting Officer
VA-VHA-RPOC-2024-0076
Previous SOW paragraph 5 B:
B. Replace Medical Air Compressor Unit and corresponding components in B330-BC120 with equivalent skid mounted NFPA 99, 2024 compliant triplex oil-less scroll Medical Air unit. (460V -1PH- 10HP). The Medical Air Unit shall have a minimum pressure rating of 120 PSIG discharge pressure. Dual desiccant air dryers with an integral demand‐based purge saving control. Each dryer individually sized per unit for peak demand and capable of producing a 10° F pressure dew point. High efficiency coalescing pre‐filter rated for 0.01 micron on each dryer with automatic drain and element change indicator. Particulate final line filters rated 0.01 micron on each dryer with element change indicator. (Refer to exhibit 4)
1. All pressure-sending devices and main line pressure gauges downstream of the source valves shall be provided with gas-specific demand check fitting to facilitate service testing or replacement. Pressure switch and gauge are currently on Hansen fitting and shall be replaced.
. (NFPA 99, 2024 Ed., 5.1.8.2.3 )
2. Correct piping materials shall be used to connect all components (copper, brass, or stainless steel). Remove all associated threaded fittings and nipples. (NFPA 99, 2024).
3. A DN8 (NPS 1/4”) valve sample port shall be installed downstream of the main source shutoff valve to allow for sampling of medical air. (NFPA 99,2024 ED., 5.1.3.6.3.9(K)).
New SOW paragraph 5 B:
B. Replace Medical Air Compressor Unit and corresponding components in B330-BC120 with equivalent NFPA 99 compliant triplex oil-less scroll Medical Air unit. (230/460V -3PH- 15HP).
The Medical Air Unit shall have a minimum pressure rating of 120 PSIG discharge pressure.
Dual desiccant air dryers with an integral demand‐based purge saving control. Each dryer individually sized per unit for peak demand and capable of producing a 10° F pressure dew point.
High efficiency coalescing pre‐filter rated for 0.01 micron on each dryer with automatic drain and element change indicator. Particulate final line filters rated 0.01 micron on each dryer with element change indicator. (Refer to exhibit 4)
1. All pressure-sending devices and main line pressure gauges downstream of the source valves shall be provided with gas-specific demand check fitting to facilitate service testing or replacement. Pressure switch and gauge are currently on Hansen fitting and shall be replaced.
(NFPA 99, 2024 Ed., 5.1.8.2.3 )
2. Correct piping materials shall be used to connect all components (copper, brass, or stainless steel). Remove all associated threaded fittings and nipples. (NFPA 99, 2024).
3. A DN8 (NPS 1/4”) valve sample port shall be installed downstream of the main source shutoff valve to allow for sampling of medical air. (NFPA 99,2024 ED., 5.1.3.6.3.9(K)).