Aleda Lutz VAMC Bldg. 1 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Supervisory Signal |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 8.3.3.5 |
| Tamper Switch |
| 41 |
| 41 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 35 |
| 35 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 31 |
| 31 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 31 |
| 31 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 3 |
| 3 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Hose Connection |
| 32 |
| 32 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.5.6.2.1 |
| Standpipe |
| 6 |
| 0 |
| 0 |
| 6 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 6.2.1; 6.3.1.1; 6.3.2.1 |
| Pump Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Air Compressor |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 5.4.2.4; |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Piping |
| 5 |
| 5 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 5.2.2 through 5.2.2.2; 14.2.1 |
| Sprinkler Box Spares |
| 13 |
| 13 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 3 |
| 3 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Alarm Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1; 13.4.1.3.1 |
| Check Valve |
| 3 |
| 3 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 42 |
| 42 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
| Dry Pipe Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 13.4.4.2.2; 13.4.4.2.9 |
| Inspector's Test |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 5.3.3.3 |
| Post Indicator Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.3.3.2/13.3.3.3 |
Aleda Lutz VAMC Bldg. 22 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Pressure Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (13.c); NFPA 25 13.4.4.2.6 |
| Tamper Switch |
| 22 |
| 22 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 15 |
| 15 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 13 |
| 13 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 20 |
| 20 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| ITV/Drain |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Hose Connection |
| 12 |
| 12 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.5.6.2.1 |
| Pump Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Air Compressor |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 5.4.2.4; |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Dry Sprinkler |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.2.1.1 through 5.2.1.4 |
| Piping |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 5.2.2 through 5.2.2.2; 14.2.1 |
| Signage |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 4.1.8.1/5.2.6 |
| Sprinkler Box Spares |
| 7 |
| 7 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Check Valve |
| 11 |
| 11 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 23 |
| 23 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
| Dry Pipe Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 13.4.4.2.2; 13.4.4.2.9 |
Aleda Lutz VAMC Bldg. EC – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Pressure Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (13.c); NFPA 25 13.4.4.2.6 |
| Tamper Switch |
| 4 |
| 4 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 3 |
| 3 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 3 |
| 3 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 3 |
| 3 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Hose Connection |
| 4 |
| 4 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.5.6.2.1 |
| Standpipe |
| 1 |
| 0 |
| 0 |
| 1 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 6.2.1; 6.3.1.1; 6.3.2.1 |
| Pump Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Air Compressor |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 5.4.2.4; |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Signage |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 4.1.8.1/5.2.6 |
| Sprinkler Box Spares |
| 3 |
| 3 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Check Valve |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 4 |
| 4 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
| Dry Pipe Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 3-Year |
| NFPA 25 (2011 Edition) |
| 13.4.4.2.2; 13.4.4.2.9 |
Aleda Lutz VAMC Bldg. 21 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Tamper Switch |
| 2 |
| 2 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Piping |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 5.2.2 through 5.2.2.2; 14.2.1 |
| Sprinkler Box Spares |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Alarm Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1; 13.4.1.3.1 |
| Check Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 2 |
| 2 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
| Inspector's Test |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 5.3.3.3 |
Aleda Lutz VAMC Bldg. 6 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Tamper Switch |
| 5 |
| 5 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Sprinkler Box Spares |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Check Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 4 |
| 4 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
| Post Indicator Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.3.3.2/13.3.3.3 |
Aleda Lutz VAMC Bldg. 9 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Tamper Switch |
| 2 |
| 2 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Gauge |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Sprinkler Box Spares |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Control Valve |
| 4 |
| 2 |
| 2 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
Aleda Lutz VAMC Bldg. 35/Pavilion – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Tamper Switch |
| 2 |
| 2 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Dep't Connection |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.7.1 |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Signage |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 4.1.8.1/5.2.6 |
| Sprinkler Box Spares |
| 2 |
| 2 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Check Valve |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.4.1.1 |
| Control Valve |
| 2 |
| 2 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
Aleda Lutz VAMC Bldg. 32 – Summary & Certification
| Alarm Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Tamper Switch |
| 2 |
| 2 |
| 0 |
| 0 |
| Semi-annually |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14i.1) |
| Waterflow Switch |
| 1 |
| 1 |
| 0 |
| 0 |
| Quarterly |
| NFPA 72 (2010 Edition) |
| Table 14.4.2.2 (14j) |
| Device Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Drain |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 13.2.5; 13.2.5.1; 13.25.2; 13.4.4.3.2 |
| Gauge |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 13.2.7.1; 5.3.2.1 |
| Sprinkler Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Piping |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually and 5-Year |
| NFPA 25 (2011 Edition) |
| 5.2.2 through 5.2.2.2; 14.2.1 |
| Sprinkler Box Spares |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Sprinkler Box |
| 1 |
| 1 |
| 0 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 5.4.1.4 |
| Valve Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Control Valve |
| 2 |
| 2 |
| 0 |
| 0 |
| Quarterly |
| NFPA 25 (2011 Edition) |
| 13.3.2.1.1; 13.3.3.1 |
Aleda Lutz VAMC All Hydrants – Summary & Certification
| Hose Equipment |
| Device Totals |
| Passed |
| Failed |
| Untested |
| Test Frequency |
| Code Publication |
| Activity: Test Method Ref. |
| Fire Hydrant |
| 10 |
| 9 |
| 1 |
| 0 |
| Annually |
| NFPA 25 (2011 Edition) |
| 7.3.2 through 7.3.2.2 |