2. MERGED DRAWINGS (Rev 1).pdf
PDF 6 MB Posted
- Attached to
- Z2DA--Construction Project Number 538-18-102 Increase Back-Up Electrical Generation and Site Distribution Federal contract opportunity
- Solicitation number
- 36C25022B0053
About this file
This notice provides details for a construction project to increase back-up electrical generation and site distribution capacity at the Chillicothe VA Medical Center in Ohio. The project is set aside for Service-Disabled Veteran-Owned Small Businesses and has an estimated value between $1-5 million.
The contractor will demolish existing items and construct new electrical infrastructure including replacement of automatic transfer switches, panelboards, pad-mount transformers and low-voltage emergency generators. New work also involves installing a medium voltage generator, HVAC systems and site work. Phased construction is required to maintain medical center operations with planned outages.
The solicitation is expected to publish on June 24th with proposals due 30 days later. A site visit will be held and questions must be submitted by email. The base period of performance is 540 days. The North American Industry Classification code is 238210. The contractor must subcontract at least 15% of work to an SDVOSB. Bonds will be required.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site visit attendance roster.pdf | ||
| Solicitation Amendment 0001.pdf | ||
| 36C25022B0053_1.pdf | ||
| 4. RFI TEMPLATE.pdf | ||
| 5. VHA Supplemental Contract Requirements for Ensuring Adequate COVID-19 Safety Protocols for Federal Contractors.pdf | ||
| 3. VHA Directive 1192.01.pdf | ||
| 1. SPECIFICATIONS (Rev 1).pdf | ||
| 36C25022B0053.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
EXTERIOR ELEVATION
INTERIOR ELEVATION
SEE 700 SERIES SHEETS
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
SEE SHEET A001
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
XXXX
X
SIM
XX
TOILET ACCESSORY TAGX SIGNAGE TAGX
U S 35
US 35
US 35
SR 104
EXIT
S R
N . H
IG
H
S T
R E
E T
C R
SCIO
TO R
IVER
S R
N
B
R
ID
G E
S T
R E
E T
Department of Veterans Affairs Medical Campus
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G I S
E T
R
ED RA
C H
TI
E C T
VA Project No.
JPA Project No.
Department of Veterans Affairs Medical Center
ARCHITECTURE PLANNING INTERIOR DESIGN
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
937.461.3290 P
JOHN POE ARCHITECTS
HEAPY ENGINEERING
MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
/2
/2
:4
:0
P
M
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022
COVER SHEET
G001
VRJR
18008.00
538-18-102
Chillicothe, Ohio
INCREASE BACK-UP ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
17273 STATE ROUTE 104 CHILLICOTHE, OHIO 45601 PROJECT #: 538-18-102
STATION
RYAN JETER
G001 COVER SHEET
C100 EXISTING CONDITIONS
C200 DEMOLITION PLAN
C300 SITE PLAN
P001 LEGEND, INDEX & GENERAL NOTES
P101 FIRST FLOOR PLANS
E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
E002 MECHANICAL AND PLUMBING LEGEND AND
ABBREVIATIONS
ES100 SITE PLAN
ES101 SITE PLAN - NEW WORK
ES102 SITE PLAN - GROUNDING
ES103 SITE PLAN - NORTH
1E100 BASEMENT PLAN
3E100 BASEMENT PLAN
7E101 FIRST FLOOR PLAN
9E100 BASEMENT & FIRST FLOOR PLANS
20E101 FIRST FLOOR PLAN
23E101 FIRST FLOOR PLANS
27E100 BASEMENT PLAN
29E100 BASEMENT & FIRST FLOOR PLANS
30E100 BASEMENT PLAN
210E100 BASEMENT PLAN
210E600 SECONDARY SINGLE LINE - BUILDING 210
259E100 BASEMENT & FIRST FLOOR PLANS
261E101 FIRST FLOOR PLAN
261E401 ENLARGED PLANS
261E402 ENLARGED PLANS
261E403 ENLARGED PLANS
261E601 SCHEDULES AND SCHEMATICS
261E701 CONTROLS
297E101 FIRST FLOOR PLAN
E501 DETAILS
E602 PRIMARY SINGLE LINE DIAGRAM - 1
E603 PRIMARY SINGLE LINE DIAGRAM - 2
GENERAL CONSTRUCTION NOTES
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS
SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A
PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS
INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL
SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE
THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF
THE WALL.
12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO
AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER
RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS
RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS
IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY
FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA
PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE
ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,
TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEXVICINITY MAP
GRAPHIC SYMBOLS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290 Revisions Date
100% Submittal Revised 03/23/22
65% Design Development Resubmittal 01/21/22
100% Submittal 07/22/19
100% Submittal Owner Review 04/05/19
95% Submittal 02/15/19
65% Submittal 12/21/18
35% Submittal 11/08/18
V
I
P
Project NumberProject TitleDrawing Title Phase
N
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
3/
/2
5:
:3
PM
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022 DesignerApprover
18008.00 538-18-102
Chillicothe, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290 Revisions Date
100% Submittal Revised 03/23/22 100% Submittal 07/22/19 100% Submittal Owner Review 04/05/19 95% Submittal 02/15/19 65% Submittal 12/21/18 35% Submittal 11/08/18
C100
EXISTING
CONDITIONS
RYAN JETER
AutoCAD SHX Text
BLDG 218
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
- STORM LINE
AutoCAD SHX Text
- ELECTRIC LINE
AutoCAD SHX Text
- COMMUNICATIONS LINE
AutoCAD SHX Text
- GAS LINE
AutoCAD SHX Text
- SANITARY LINE
AutoCAD SHX Text
- TREE
AutoCAD SHX Text
- SHRUB
AutoCAD SHX Text
- STORM STRUCTURE
AutoCAD SHX Text
- FIRE HYDRANT
AutoCAD SHX Text
- WATER VALVE
AutoCAD SHX Text
- SANITARY MANHOLE
AutoCAD SHX Text
- SIGN
AutoCAD SHX Text
- ELECTRIC BOX
AutoCAD SHX Text
- ELECTRIC MANHOLE
AutoCAD SHX Text
- TELEPHONE MANHOLE
AutoCAD SHX Text
- IRON PIN
AutoCAD SHX Text
- MONUMENTATION
AutoCAD SHX Text
- LIGHT POLE
AutoCAD SHX Text
- FENCE
AutoCAD SHX Text
- BOLLARD
AutoCAD SHX Text
- PULL BOX
AutoCAD SHX Text
- STRAIN POLE
AutoCAD SHX Text
LEGEND:
AutoCAD SHX Text
- POWER/ COMM. POLE
AutoCAD SHX Text
- STORM MANHOLE
AutoCAD SHX Text
- ELECTRIC TRANSFORMER
AutoCAD SHX Text
- FLAG POLE
AutoCAD SHX Text
- LIGHTING
AutoCAD SHX Text
- WATER LINE
AutoCAD SHX Text
EXIST 8" STEEL SAN
AutoCAD SHX Text
EXIST 8" STEEL SAN
AutoCAD SHX Text EXIST SAN MH GRATE 659.51 TOP = 655.91 TOP 8" 90^ BEND DOWN W BEND DOWN W INV = 656.03 8" STEEL S
AutoCAD SHX Text EXIST STM MH GRATE 659.32 INV = 656.41 18" CONC N & S INV = 656.47 18" CONC SW INV = 656.41 6" SE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST 18" CONC STM
AutoCAD SHX Text
EXIST 6" STM
AutoCAD SHX Text
EXIST STM MH GRATE 661.56 INV = 657.67 18" CONC NE
AutoCAD SHX Text
EXIST 140.6' ~ 18" CONC STM @ 0.85%
AutoCAD SHX Text
EXIST STM MH GRATE 660.91 INV = 657.36 18" CONC N
AutoCAD SHX Text
EXIST 102.0' ~ 18" CONC STM @ 0.93%
AutoCAD SHX Text
EXIST 6" PVC ELEC CONDUIT
AutoCAD SHX Text
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
ATS
AutoCAD SHX Text
MV GEN 2
AutoCAD SHX Text
MV GEN 1
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
PETER S. BATTAGLIA E51255
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text R
P
Project NumberProject TitleDrawing Title Phase
N
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
3/
/2
5:
:3
PM
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022 DesignerApprover
18008.00 538-18-102
Chillicothe, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290 Revisions Date
100% Submittal Revised 03/23/22 100% Submittal 07/22/19 100% Submittal Owner Review 04/05/19 95% Submittal 02/15/19 65% Submittal 12/21/18 35% Submittal 11/08/18
DEMOLITION PLAN
C200RYAN JETER
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
- STORM LINE
AutoCAD SHX Text
- ELECTRIC LINE
AutoCAD SHX Text
- COMMUNICATIONS LINE
AutoCAD SHX Text
- GAS LINE
AutoCAD SHX Text
- SANITARY LINE
AutoCAD SHX Text
- TREE
AutoCAD SHX Text
- SHRUB
AutoCAD SHX Text
- STORM STRUCTURE
AutoCAD SHX Text
- FIRE HYDRANT
AutoCAD SHX Text
- WATER VALVE
AutoCAD SHX Text
- SANITARY MANHOLE
AutoCAD SHX Text
- SIGN
AutoCAD SHX Text
- ELECTRIC BOX
AutoCAD SHX Text
- ELECTRIC MANHOLE
AutoCAD SHX Text
- TELEPHONE MANHOLE
AutoCAD SHX Text
- IRON PIN
AutoCAD SHX Text
- MONUMENTATION
AutoCAD SHX Text
- LIGHT POLE
AutoCAD SHX Text
- FENCE
AutoCAD SHX Text
- BOLLARD
AutoCAD SHX Text
- PULL BOX
AutoCAD SHX Text
- STRAIN POLE
AutoCAD SHX Text
LEGEND:
AutoCAD SHX Text
- POWER/ COMM. POLE
AutoCAD SHX Text
- STORM MANHOLE
AutoCAD SHX Text
- ELECTRIC TRANSFORMER
AutoCAD SHX Text
- FLAG POLE
AutoCAD SHX Text
- LIGHTING
AutoCAD SHX Text
- WATER LINE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
BEGIN FENCE REMOVAL
AutoCAD SHX Text
FENCE REMOVAL
AutoCAD SHX Text
END FENCE REMOVAL
AutoCAD SHX Text
SAW CUT
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST FENCE TO BE REMOVED
AutoCAD SHX Text
EXIST FENCE TO REMAIN
AutoCAD SHX Text
DEMOLITION LEGEND:
AutoCAD SHX Text
REMOVE EXISTING CONCRETE
AutoCAD SHX Text
EXISTING CONCRETE
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
PETER S. BATTAGLIA E51255
P
Project NumberProject TitleDrawing Title Phase
N
SITE PLAN
C300
VA Project No.
JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
3/
/2
5:
:3
PM
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022 DesignerApprover
18008.00 538-18-102
Chillicothe, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290 Revisions Date
100% Submittal Revised 03/23/22 100% Submittal 07/22/19 100% Submittal Owner Review 04/05/19 95% Submittal 02/15/19 65% Submittal 12/21/18 35% Submittal 11/08/18
RYAN JETER
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
SOFT SHOT (LIDAR CONTROL)
AutoCAD SHX Text
BLDG 218
AutoCAD SHX Text
DS
AutoCAD SHX Text
DS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
- STORM LINE
AutoCAD SHX Text
- ELECTRIC LINE
AutoCAD SHX Text
- COMMUNICATIONS LINE
AutoCAD SHX Text
- GAS LINE
AutoCAD SHX Text
- SANITARY LINE
AutoCAD SHX Text
- TREE
AutoCAD SHX Text
- SHRUB
AutoCAD SHX Text
- STORM STRUCTURE
AutoCAD SHX Text
- FIRE HYDRANT
AutoCAD SHX Text
- WATER VALVE
AutoCAD SHX Text
- SANITARY MANHOLE
AutoCAD SHX Text
- SIGN
AutoCAD SHX Text
- ELECTRIC BOX
AutoCAD SHX Text
- ELECTRIC MANHOLE
AutoCAD SHX Text
- TELEPHONE MANHOLE
AutoCAD SHX Text
- IRON PIN
AutoCAD SHX Text
- MONUMENTATION
AutoCAD SHX Text
- LIGHT POLE
AutoCAD SHX Text
- FENCE
AutoCAD SHX Text
- BOLLARD
AutoCAD SHX Text
- PULL BOX
AutoCAD SHX Text
- STRAIN POLE
AutoCAD SHX Text
LEGEND:
AutoCAD SHX Text
- POWER/ COMM. POLE
AutoCAD SHX Text
- STORM MANHOLE
AutoCAD SHX Text
- ELECTRIC TRANSFORMER
AutoCAD SHX Text
- FLAG POLE
AutoCAD SHX Text
- LIGHTING
AutoCAD SHX Text
- WATER LINE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING SANITARY SEWER (TO REMAIN)
AutoCAD SHX Text
NEW 8" CONCRETE
AutoCAD SHX Text
PIPE BOLLARD 4' O.C. (TYP.)
AutoCAD SHX Text
PROTECT EXISTING COMMUNICATION DUCTS (TO REMAIN)
AutoCAD SHX Text
PROTECT EXISTING STORM LINE (TO REMAIN)
AutoCAD SHX Text
NEW ASPHALT PAVING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
SECTION A-A
AutoCAD SHX Text
SLAB W/ TURNED DOWN EDGE
AutoCAD SHX Text
(2) #5 BARS x 16" @ 90°
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BOLLARD DETAIL
AutoCAD SHX Text
EXISTING GENERATOR
AutoCAD SHX Text
NEW GENERATOR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST ELEC CONDUIT (TO REMAIN)
AutoCAD SHX Text
AutoCAD SHX Text
CONNECT NEW 8' CHAIN LINK FENCE TO EXIST FENCE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW 2 - 6' SWING GATES (12'-0" OPENING)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REMOVABLE PIPE BOLLARD IN GATE OPENING PROVIDE SLEEVE IN CONCRETE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW 4' MAN GATES COORDINATE OPENING WITH PIPE BOLLARDS
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING GENERATOR
AutoCAD SHX Text
660.78 EX
AutoCAD SHX Text
660.60 EX
AutoCAD SHX Text
659.92 EX
AutoCAD SHX Text
660.89 EX
AutoCAD SHX Text
660.85 EX
AutoCAD SHX Text
660.96 EX
AutoCAD SHX Text
660.99 EX
AutoCAD SHX Text
661.02 EX
AutoCAD SHX Text
660.91 EX
AutoCAD SHX Text 660.90
AutoCAD SHX Text 660.90
AutoCAD SHX Text 660.90
AutoCAD SHX Text 660.90
AutoCAD SHX Text 660.80
AutoCAD SHX Text 660.80
AutoCAD SHX Text 660.80
AutoCAD SHX Text
659.34 EX
AutoCAD SHX Text
659.57 EX
AutoCAD SHX Text 660.65
AutoCAD SHX Text 660.45
AutoCAD SHX Text 660.05
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
CONCRETE GENERATOR SLAB
AutoCAD SHX Text 660.40
AutoCAD SHX Text 660.30
AutoCAD SHX Text 660.80
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CREATE SWALE TO DRAIN AS INDICATED
AutoCAD SHX Text
CREATE SWALE IN CONCRETE PAVEMENT TO DRAIN AS INDICATED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW 8' CHAIN LINK FENCE W/ 3 STRAND BARBED WIRE
AutoCAD SHX Text NOTE: 4" SCHEDULE 40 GALV. PIPE x 7' LONG, CONCRETE FILLED, 4'-0" O.CC. 36" DEEP FOOTING 3000 PSI CONCRETE BASE
AutoCAD SHX Text
HEIGHT VARIES
AutoCAD SHX Text
PROVIDE CONDUIT FOR EXISTING ELECTRIC LINE
AutoCAD SHX Text
SLEEVE FOR FENCE POST
AutoCAD SHX Text #4 @ 18" O.C. E.W.
AutoCAD SHX Text
EXIST GRADE
AutoCAD SHX Text
CONCRETE PAVEMENT INFILL
AutoCAD SHX Text 1.00'
AutoCAD SHX Text 2.00'
AutoCAD SHX Text
2" CLR
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
PETER S. BATTAGLIA E51255
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD
CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER
TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN
UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO
CENTERLINE OF PIPE, UNLESS NOTED OTHERWISE
FIRE SUPPRESSION SYMBOLS
DOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CARBON DIOXIDE OUTLET - HOSPITAL TYPE
MEDICAL AIR OUTLET - HOSPITAL TYPE
MEDICAL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - HOSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OUTLET - HOSPITAL TYPE
WAGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - WALL
VACUUM CLEANING STATION - FLOOR
PLUMBING AND FIRE SUPPRESSION
PIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC
WATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
LV
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS
FOR REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND
HOSE CONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG
IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
VB
TP
CO
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
SOLENOID VALVE
S
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERWISE.
FIRE DEPARTMENT VALVE
WATER METERM
ACID VENT PIPEAV
ACID WASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID WASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT WATER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - DOWN SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DWG - DRAWING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EEW - EMERGENCY EYE WASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOWER
EQS - EQUIPMENT SUPPLIER
EWC - ELECTRICAL WATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE WASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER OR HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY WATER
HPWR - HIGH PURITY WATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD WATER
LEC - LABORATORY EQUIPMENT CONTRACTOR
LHW - LABORATORY HOT WATER
LHWR - LABORATORY HOT WATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY VENT
LW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL CONTRACTOR (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGEN
N/C - NORMALLY CLOSED
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NO - MEDICAL NITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE WATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
02 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW DRAIN
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE WATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (WET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOWER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER
DISCHARGE
TW - TEMPERED WATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/O - WITHOUT
W - WASTE
WAGD - WASTE ANESTHESIA GAS DISPOSAL
WC - WATER CLOSET
WCO - WALL CLEANOUT
WH - WALL HYDRANT OR WATER HEATER
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
GENERAL NOTES
A ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF EXPOSED STRUCTURE
AREAS), UNLESS OTHERWISE NOTED.
B REFER TO SCHEDULE, DETAILS, AND DIAGRAMS FOR PIPING, PIPE
SIZES AND PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION WITH ALL
TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY WORK.
D LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED
FROM A REVIEW OF EXISTING DRAWINGS AND/ OR SITE INSPECTION,
WHERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS,
ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW, ETC., SHALL BE
REQUIRED PRIOR TO BEGINNING NEW WORK.
E NEW CONNECTIONS TO EXISTING PIPING SHALL BE WITH THE SAME
SIZE AS THE EXISTING PIPING, UNLESS OTHERWISE NOTED.
F ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE
COR, SHALL BE TURNED OVER AND PLACED WHERE DIRECTED.
ALL MATERIAL AND EQUIPMENT, WHICH THE COR DOES NOT WISH
TO RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTOR.
REFER TO SPECIFICATION SECTION 01 74 19, CONSTRUCTION WASTE
MANAGEMENT.
G CONTRACTOR SHALL UTILIZE X-RAY METHOD TO VERIFY EXISTENCE
OF OBSTRUCTIONS, INCLUDING EXISTING ELECTRICAL, PLUMBING,
HVAC, FIRE SUPPRESSION, AND/OR STEEL REINFORCEMENT WHEN
CUTTING OR CORE-DRILLING FLOOR SLAB. EITHER RE-ROUTE
EXISTING SYSTEM(S), BRACE FLOOR, OR ALTER LOCATION OF NEW
WORK TO MAINTAIN EXISTING SYSTEM(S).
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
HEAPY PROJECT No. : 2018-05176 OHIO COA No.: 05128 RYAN JETER
/2
/2
:1
:0
A
M
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022
LEGEND, INDEX & GENERAL
NOTES
P001
ABNDPB
538-18-102
Chillicothe, Ohio
STATION
18008.00
INDEX OF DRAWINGS - PLUMBING
Sheet Number Sheet Name
P001 LEGEND, INDEX & GENERAL NOTES
P101 FIRST FLOOR PLANS
Revisions Date
100% Submittal Revised 03/23/22
100% Submittal 07/22/19
100% Submittal Owner Review 04/05/19
95% Submittal 02/15/19
M
UH
UH
F O
S
F O
R
GENERATOR
A
P101
EXISTING ABOVE
GROUND FUEL
OIL TANK
1" 0.5"
DAYTANK
GENERATOR
EXISTING ABOVE
GROUND FUEL
OIL TANK
FOR
FOS
A
P101
FOR
FOS
T
1.5"
0.5" 1"
0.5"
1"
GENERATOR
FOS
FOR
0.5"
1"
A
P101
EXISTING ABOVE
GROUND FUEL
OIL TANK
FOR
FOS
FLOOR LEVEL
NEW EMERGENCY
GENERATORINLINE FUEL OIL FILTER WITH
SCREW ON STYLE STEEL
FILTER BOWL EQUAL TO
EXISTING CURRENTLY IN USE
P
P
FOS
FROM EXISTING
FUEL OIL TANK
FOR
FOS
FOR
EXISTING
FUEL OIL TANK
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
HEAPY PROJECT No. : 2018-05176 OHIO COA No.: 05128 RYAN JETER
/2
/2
:1
:0
A
M
INCREASE BACK-UP
ELECTRICAL GENERATION &
SITE DISTRIBUTION CAPACITY
03/23/2022
FIRST FLOOR PLANS
P101
ABNDPB
538-18-102
Chillicothe, Ohio
STATION
18008.00
SCALE: 1/4" = 1'-0"
BLDG 7 - PARTIAL FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
BLDG 259 - PARTIAL FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
BLDG 297 - PARTIAL FIRST FLOOR PLAN
NOTES
1 DISCONNECT AND REMOVE EXISTING FUEL OIL PIPING AND ACCESSORIES FROM
EXISTING GENERATOR AND CONNECT NEW PIPING TO NEW GENERATOR.
2 MAKE CONNECTION TO EXISTING FUEL OIL TANK.
3 MAKE CONNECTION TO EXISTING FUEL OIL TANK. TANK IS CURRENTLY NOT IN USE,
CLEAN AND PREP TANK FOR SERVICE. UTILIZE EXISTING TANK FITTINGS. EXTEND
VENT TO EXTERIOR AND TERMINATE WITH VENT FITTING.
4 REMOVE EXISTING DAY TANK. REMOVE ALL FUEL OIL PIPING AND ACCESSORIES.
SCALE: NONE
GENERATOR FUEL OIL CONNECTION
A
Revisions Date
100% Submittal Revised 03/23/22
100% Submittal 07/22/19
100% Submittal Owner Review 04/05/19
95% Submittal 02/15/19
1. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
2. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
3. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN
DAMAGED AND/OR REMOVED IN THE PERFORMANCE OF WORK IN THIS PROJECT.
4. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING
BUILDING FOR WORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO
PERFORM THE ROOFING WORK. WHERE ROOFING WORK IS REQUIRED, THE
EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND
RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT CONDITION. THE ROOFING
SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO
MAINTAIN THE EXISTING WARRANTY ON THE ROOF.
5. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE
DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND
SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS
COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL
TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF
THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE
FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE
FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR,
CONTACT THE COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION
BEFORE PROCEEDING.
6. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE
CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE
CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND
PROPERTY DURING PERFORMANCE OF THE WORK. THIS WILL APPLY
CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE
SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.
7. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO
MAINTAIN OPERATION OF THE EXISTING FACILITY.
8. EACH CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHERS.
HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS AND DETAIL
DEVELOPMENT OF THE WORK OF OTHERS AND SHALL BE RESPONSIBLE FOR
COORDINATING AND EXPEDITING HIS WORK WITH OTHERS SO THAT THE
PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.
9. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL
GOVERNING CODES AND STANDARDS.
10. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING
INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE
CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD
VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE
CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL
BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR
RESOLUTION BEFORE PROCEEDING WITH THE WORK.
11. EACH CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS WORK INTO OR ON
THE WORK OF OTHERS DOES SO WITH THE UNDERSTANDING THAT THE
INSTALLATION OF HIS WORK CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY
OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOT ACCEPTABLE, HE SHALL
NOTIFY THE COR AND SUCH WORK SHALL BE CORRECTED. ANY NEW WORK
INSTALLED IN UNSUITABLE EXISTING WORK SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR OR TRADE INSTALLING THE NEW WORK. NO CLAIMS FOR
ADDITIONAL COMPENSATION FOR CORRECTING WORK INSTALLED IN UNSUITABLE
EXISTING CONDITIONS WILL BE CONSIDERED.
12. IF, IN THE PERFORMANCE OF THIS WORK, MATERIALS ARE OBSERVED WHICH ARE
SUSPECTED TO CONTAIN ASBESTOS, THE CONTRACTOR SHALL IMMEDIATELY
INFORM THE COR. WORK THAT WOULD EXPOSE WORKERS TO THE INHALATION OF
ASBESTOS PARTICLES SHALL BE TERMINATED. WORK MAY BE RESUMED ONLY
AFTER A DETERMINATION HAS BEEN MADE AND UNSAFE MATERIALS HAVE BEEN
REMOVED OR ENCAPSULATED AND THE AREA DECLARED SAFE.
13. CONTRACTORS SHALL TAKE SPECIAL CARE WHILE WORKING ADJACENT TO
ASBESTOS MATERIALS AND MUST BE PROPERLY PROTECTED WITH CLOTHING,
BREATHING APPARATUS, ETC. VERIFY REQUIREMENTS OF VAMC'S INFECTION
CONTROL RISK ASSESSMENT TEAM (ICRA).
14. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR
INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
15. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE
DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AUTOMATIC CONTROL
DAMPERS, AND HUMIDIFIER DISPERSION TUBES. REFER TO DETAIL ON SHEET M0.3.
COORDINATE SIZES AND LOCATIONS WITH ACCESSORIES PROVIDED BY OTHER
TRADES.
16. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.
17. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN
THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO
MATCH EXISTING.
18. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR
HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS.
COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT
IMMEDIATELY ANY DIFFICULTIES WHICH CAN BE ANTICIPATED.
19. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT
SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING WORK.
20. ALL ABANDONED EXTRANEOUS PIPING, DUCTWORK, SUPPORTS, CONTROLS, ETC.
SHALL BE REMOVED.
21. WHERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES SHALL BE REMOVED
BACK TO MAIN AND CAPPED; AND CONTROL WIRING AND CONDUIT SHALL BE
REMOVED BACK TO SOURCE.
22. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED
SHALL BE REMOVED. THE MAJORITY OF WORK TO BE REMOVED IS SHOWN.
REMOVE ALL INCIDENTAL AND/OR ABANDONED DUCTWORK, PIPING, ETC. THAT
MAY NOT BE SHOWN BUT IS ASSOCIATED WITH THE REMOVAL WORK.
23. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING,
SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY
ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON
PERMANENT PLATFORMS, WITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES
OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES,
FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.
24. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL REQUIREMENTS AND
THESE DRAWINGS FOR DESCRIPTIONS OF THE BID ITEMS INCLUDING DEDUCT
ALTERNATES, ADDITIONAL INFORMATION NOTED THROUGHOUT THE DRAWINGS.
25. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE SHALL REMAIN
OPERATIONAL DURING CONSTRUCTION. ANY OUTAGES SHALL BE PERFORMED ON
WEEKENDS OR WEEK NIGHTS. DOWNTIME SHALL BE KEPT TO A MINIMUM, AND
SHALL BE COORDINATED AND SCHEDULED 4 WEEKS (30 CALENDAR DAYS) IN
ADVANCE WITH THE COR.
26. REFER TO NEW WORK FLOOR PLANS FOR WORK THAT MAY BE REQUIRED PRIOR
TO ANY REMOVAL WORK.
27. REFER TO SHEET 297E101 FOR DIV 23 SCHEDULES AND DETAILS.
28. READ ALL NOTES THOROUGHLY PRIOR TO STARTING CONSTRUCTION.
GENERAL NOTES:
FIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR ALL OTHER LOCATIONS.
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS
WHERE REQUIRED.
ELECTRICAL CONNECTION.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE
TO HAVE "CONTROLLED" MARKINGS.
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG
ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH
UNLESS NOTED OTHERWISE).
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE)
WITH EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH
UNLESS NOTED OTHERWISE), WITH EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, ON EMERGENCY POWER (18" MH UNLESS NOTED OTHERWISE).
20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN FLOOR BOX WITH COVERPLATE AND
HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.
20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).
JUNCTION BOX.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERWISE).
CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).
SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).
KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.
SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH
AND RECEPTACLE.
FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH
UNLESS NOTED OTHERWISE).
HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
CORD REEL.
POWER POLE.
FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM CHIME & SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM HORN & SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR ALL OTHER LOCATIONS.
GF
WP
WP/GF
EM
T
IG
20A
30A
50A
20A
50A
30A
J
P
K
DM
R
H
UH
FC
AC
CU
UV
PP
T
F
F
F
F
F
S F
CEILING MOUNTED FIRE ALARM SPEAKER.
FIRE ALARM CONTROL PANEL.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).
C
M
CR
P/B
FACP
DUCT HEATER.H
DH
H
EB
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
L
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X R
WALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE
CONFIGURATION.
X V
WALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE
CONFIGURATION.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.
J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.
D WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X I
WALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUITS TO ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT
"X" INDICATES ALTERNATE CONFIGURATION.
AP
WALL MOUNTED WIRELESS ACCESS POINT (96” MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. WAP AND CABLE PER DIV 27.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BIW - BACKWARD INCLINED WHEEL
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CF - CENTRIFUGAL FAN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
COR - CONTRACTING OFFICERS REPRESENTATIVE.
CTR - CENTER
CU -CONDENSING UNIT
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EF - EXHAUST FAN
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
E/R - EXISTING TO BE RELOCATED
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FC - FAN COIL
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY CONTRACTOR
SCH - SCHEDULE
SF - SUPPLY FAN
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
E2
B
E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)
DENOTES CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
X - 1,2
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES
SWITCHING ARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.
A a
WIREMOLD RACEWAY, AS NOTED ON PLANS.
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED
OTHERWISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
FLOOR BOX, # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. IF NO #, PROVIDE FLUSH FLOOR BOX WITH ROUND COVERPLATE AND ONE 20A-125V DUPLEX RECEPTACLE. PROVIDE CARPET FLANGE WHERE REQD.
X
POKE-THRU PER DIV 26. # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE. SUBSCRIPT "X" INDICATES
TECHNOLOGY DEVICE(S), REFER TO TECHNOLOGY DETAILS.
X
CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 75 CANDELA FOR
ALL OTHER LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
WATER FLOW SWITCH.
VALVE SUPERVISORY SWITCH.
CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W"
INDICATES WALL MOUNTED.
SMOKE DAMPER.
FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).
KF
S
H
C
D
FS
V
R W
S D
FT
PRESSURE SWITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.
PS
AM
C/I
PIV
K S
H
S S/R
S/R
S F
FIRE ALARM BELL (80" AFF UNLESS NOTED OTHERWISE). SUBSCRIPT "W" INDICATES EXTERIOR WEATHERPROOF UNIT.F W
BEAM…