Amendment A00006 Rev DWGs_Part2.pdf

PDF 3 MB Posted

Attached to
Z1DA--Correct Water Infiltration 610-20-102 Federal contract opportunity
Solicitation number
36C25022B0009
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document package includes construction drawings and a federal contract opportunity solicitation. The drawings show plans for correcting water infiltration issues on the roofs of six buildings at the Northern Indiana VA Medical Center in Marion, Indiana. Work includes removing and replacing asphalt shingles and underlayment with new stone-coated steel shingles, removing and replacing various metal roof sections with new standing seam metal roofing, replacing box gutters and downspouts, and installing snow guards. The solicitation seeks bids for the correct water infiltration project numbered 610-20-102 per the attached drawings and specifications. The work will be awarded through the Department of Veterans Affairs Veterans Health Administration VISN 10 to provide all labor, materials, tools and supervision to complete the project. The response due date is not stated.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Correct Water Infiltration 610-20-102, newest first.
File Type Posted
Amendment 0006 Summary.docx DOCX document
Amendment A00006 Rev DWGs_Part8.pdf PDF
Amendment36C25022B0009 A00006.pdf PDF
Amendment A00006 Rev DWGs_Part5.pdf PDF
Amendment A00006 Rev DWGs_Part3.pdf PDF
Amendment A00006 Rev DWGs_Part7.pdf PDF
Amendment A00006 Rev DWGs_Part1.pdf PDF
Amendment A00006 Rev DWGs_Part4.pdf PDF
Amendment A00006 Rev DWGs_Part6.pdf PDF
Amendment36C25022B0009 A00005.pdf PDF
Amendment 36C25022B0009 A00004.pdf PDF
610-20-102 Correct Water Infiltration pre bid site visit attendance.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part4.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part3.pdf PDF
Amendment 00002 Summary.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part1.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part5.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part6.pdf PDF
2022-0427_Correct Water Infiltration AMEND 00001 DWGs_Part2.pdf PDF
Amendment A00003.docx DOCX document
Amendment A00002 36C25022B0009.pdf PDF
Amendment A00002 - RFI Responses.docx DOCX document
36C25022B0009 Amendment A00001.pdf PDF
610-20-102 Correct Water Infiltration - comb dwgs.pdf PDF
Wage Determination.txt TXT text file
RFI Form.doc DOC document
610-20-102 Correct Water Infiltration - spec.pdf PDF
Contractor Certification Regarding Safety and Environmental.pdf PDF
36C25022B0009 Solicitation.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AE2012

AE201

AE201

AE201 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

13:1213:12

:1

:1

:1

:1

:1

14:1214:12

:1

12:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP. TYP.

TYP.

TYP.2

AE501

Sim6

AE501

Sim

AE501

Sim

AE501

Sim

AE2017

AE201 5

11 122

9 9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:4

:5

A

M

AE101

BUILDING 1 - ROOF PLAN

03/11/2021 PQ BL

MARION, INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 1 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

5 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 PROTECT EXISTING DOWNSPOUT DURING ALL PHASES OF

CONSTRUCTION.

9 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

10 EXISTING COPPER ROOF TO REMAIN. EXISTING COPPER GUTTERS AND

DOWNSPOUTS TO REMAIN.

11 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER.

12 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

No. Revisions: Date:

1 ADDENDUM 001 04/27/22

AE2022

AE202

AE202

AE202 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

12:12 12:12

:1

:1

12:1212:12

12:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP. TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

AE501

Sim4

AE501

Sim

AE501

Sim

AE501

Sim

TYP.

4 4

TYP.

TYP.

TYP.

TYP.

11 11122

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:5

:1

A

M

AE102

BUILDING 2 - ROOF PLAN

03/11/2021 PQ BL

MARION INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 2 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

5 PROTECT EXISTING DOWNSPOUT DURING ALL PHASES OF

CONSTRUCTION.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

9 EXISTING DOWNSPOUT SHALL REMAIN - EXTEND EXISTING DOWNSPOUT

TO EXISTING BOOT - APPROXIMATELY 12 INCHES.

10 EXISTING COPPER ROOF TO REMAIN. EXISTING COPPER GUTTERS AND

DOWNSPOUTS TO REMAIN.

11 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

12 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER

13 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

1 ADDENDUM 001 04/27/2022

AE2032

AE203

AE203

AE203 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

12:1212:12

:1

:1

:1

:1

:1

12:1212:12

:1

12:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.2

AE501

Sim

AE501

Sim

AE501

Sim

AE501

Sim

AE203 AE203 6

TYP.

TYP.

TYP.

TYP.

10 112

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:0

:0

A

M

AE103

BUILDING 3 - ROOF PLAN

03/11/2021 PQ BL

MARION, INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 3 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

5 PROTECT EXISTING DOWNSPOUT DURING ALL PHASES OF

CONSTRUCTION.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

9 EXISTING COPPER ROOF TO REMAIN. EXISTING COPPER GUTTERS AND

DOWNSPOUTS TO REMAIN.

10 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

11 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER

12 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

AE2042

AE204

AE204

AE204 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

12:12 12:12

:1

:1

12:1212:1212:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP. TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

AE501

Sim

AE501

Sim

AE501

Sim

AE501

Sim

TYP.

TYP.

TYP.

1010 11 12

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:5

:4

A

M

AE104

BUILDING 4 - ROOF PLAN

03/11/2021 PQ BL

MARION, INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 4 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

5 PROTECT EXISTING DOWNSPOUT DURING ALL PHASES OF

CONSTRUCTION.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

9 EXISTING COPPER ROOF TO REMAIN. EXISTING COPPER GUTTERS AND

DOWNSPOUTS TO REMAIN.

10 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

11 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER

12 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

AE2052

AE205

AE205

AE205 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

12:1212:12

:1

:1

:1

:1

:1 211:1211:12

:1

12:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP. TYP.

3 3

TYP.

TYP.

2 222

4 5

AE501

Sim

AE501

Sim

AE501

Sim

AE501

Sim

TYP.

TYP.

TYP.

TYP.

9 10 112

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:5

:5

A

M

AE105

BUILDING 5 - ROOF PLAN

03/11/2021 PQ BL

MARION, INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 5 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

5 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

9 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

10 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER

11 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

AE2062

AE206

AE206

AE206 3

:1

:1

12:1212:12

:1

12:12

:1

:1

:1

12:12 12:12

:1 2 1

:1

12:1212:12

12:12

12:12 12:12

12:12

:1

:1

12:12

:1

12:1212:12

:1

TYP. TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

2 2

AE501

Sim

AE501

Sim

AE501

Sim

AE501

Sim

5 5

8 9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DRAWING OF 24

C U s e rs

\n a te m

\O n e

D ri v e \D o c u m e n ts

\F F

E

M a ri o n

W a te r

In fi lt ra ti o n

B n a te

.m o u ld s .r v t

/1

/2

:5

:1

A

M

AE106

BUILDING 6 - ROOF PLAN

03/11/2021 PQ BL

MARION, INDIANA

#610-20-102CONSTRUCTION

DOCUMENTS

CORRECT WATER

INFILTRATION

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 6 - ROOF PLAN

1 REMOVE EXISTING ASPHALT SHINGLES AND UNDERLAYMENT - REPLACE

WITH NEW STONE COATED STEEL SHINGLES OVER #30 FELT

UNDERLAYMENT OVER EXISTING SHEATHING. REPLACE SHEATHING AND

INSULATION WHERE DAMAGED - ASSUME 10% SHEATHING AND

INSULATION REPLACEMENT AT RAFTERS - SEE SECTIONS AND DETAILS ON

AE501 AND AE502.

2 VALLEY FLASHING BY SHINGLE MANUFACTURER.

3 RIDGE CAP BY SHINGLE MANUFACTURER TO MATCH ADJACENT SHINGLES

- TYPICAL.

4 REMOVE EXISTING ROOF HATCH - PATCH OPENING WITH WOOD FRAMING

AND SHEATHING - PREPARE TO RECEIVE NEW SHINGLES.

5 PROTECT EXISTING DOWNSPOUT DURING ALL PHASES OF

CONSTRUCTION.

6 PROVIDE NEW STEP FLASHING AT INTERSECTION WITH WALL.

7 REMOVE AND REPLACE EXISTING METAL ROOF WITH NEW STANDING

SEAM METAL ROOF - COLOR: COPPER.

8 NEW 3"X4" COPPER COLOR DOWNSPOUT TO EXISTING BOOT.

9 NEW GUTTER FORMED FROM SAME MATERIAL AS ROOF PANELS - COLOR:

COPPER

10 EXISTING COPPER ROOF TO REMAIN. EXISTING COPPER GUTTERS AND

DOWNSPOUTS TO REMAIN.

11 REPLACE EXISTING BOX GUTTER - INSTALL NEW METAL GUTTER BOX,

PEEL & SEAL LINER, AND METAL CORNICE PROFILE AND ASSOCIATED

BLOCKING, TYPICAL UNLESS NOTED OTHERWISE - SEE DETAILS ON AE501

AND AE502.

12 INSTALL CLAMP-TO-SEAM SNOW GUARDS AT 24" AND 36" FROM FASCIA

BOARD - 16" O.C. - COLOR: COPPER TO MATCH ROOFING MATERIAL.

A. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S

CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS

INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE

COMPATIBLE WITH EXISTING ROOF SYSTEM.

B. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION

SYSTEM AS NEEDED. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF

AREA. CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT

CONCLUSION OF PROJECT.

C. NOTE REMOVED.

D. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN THE

PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM

REQUIREMENTS.

E. ALL DOORS AND WINDOWS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D R A W I N G N O T E SG E N E R A L N O T E S

07.03_AE101 - BUILDING 1 - ROOF PLAN
AE101 - BUILDING 1 - ROOF PLAN
07.04_AE102 - BUILDING 2 - ROOF PLAN
AE102 - BUILDING 2 - ROOF PLAN

File details come from the government source that posted it. Updated .