E1-03 - LIGHTING FIXTURE AND PANEL SCHEDULE.pdf
PDF 535 KB Posted
- Solicitation number
- 36C25021B0056
About this file
This solicitation package outlines requirements for a construction project to build out biomedical space at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The project scope includes consolidating all Health Technology Services/Biomedical storage and staff into one location, adding an electronics shop and storage space for Environmental Management Systems equipment, and utilizing vacated spaces for other purposes. The solicitation is a Service Disabled Veteran Owned Small Business set-aside between $500,000 and $1 million requiring bonds and a 240-day period of performance. Interested parties must register at SAM.gov and VetBiz.va.gov by the bid opening date in July 2021 to be eligible. The solicitation and amendments will be posted at SAM.gov, with questions due by the specified cutoff. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 10.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE
TYPE "A"
WORKSTATIONS/BIOMED/STORAGE/CORRIDOR
TYPE "B"
TOILET
OCCUPANCY SENSOR PROGRAM SCHEDULE:
OS
RC
277VAC:24VDC
WHT
BLK RED
RED - SWITCHED HOT
ROOM
CONTROLLER
NEUTRAL
HOT
24V SENSOR-
CEILING
MOUNTED
SENSOR TYPE ON CONTROL OFF CONTROL
DUAL
TECHNOLOGY
MANUAL
OFF TIME DELAY
MANUAL/SENSOR
AUTO OFF AFTER 15
MINUTES
CONNECT AS
REQUIRED -
0-10V DIMMING
MOUNT ABOVE
FINISHED CEILING
CONNECT LOW
VOLTAGE AS REQUIRED
CONNECT LOW
VOLTAGE AS REQUIRED
BRANCH
LIGHTING
CIRCUIT
277V
DLV24V DIMMING
SWITCH
S
DLV
24V DIMMING
SWITCH
S
CONNECT
LOW
VOLTAGE AS
REQUIRED
FOR MULTI-
WAY
SWITCHES
LIGHTING
LOAD
1 #12
1 #12
1 #12
NOT TO SCALE
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
200469 /9
/2
:4
:2
A
M C
R e v it L o c a l F ile s \2
F
F H
C F
R
J e ff re y .R
.D u a le
.r v t
E1-03
757-20-206
JRD LV
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
LIGHTING FIXTURE AND PANEL SCHEDULE
LIGHTING FIXTURE SCHEDULE
TYPE FIXTURE DESCRIPTION MOUNTING MAX HEIGHT LUMEN WATTAGE COLOR TEMP LUMEN MAINTANCE RATING EFFICANCY DRIVER TYPE
A 2' X 2 LED TROFFER WITH DIRECT DISTRIBUTION, SOFT GLOW LENS, MATTE WHITE FINISH, DIE-FORMED STEEL HOUSING WITH WIRING ACCESS PLATE ON TOP OF HOUSING, HIGH-REFLECTANCE PREPAINT MATTE WHITE STEEL REFLECTORS, HIGH-EFFICIENCY ONE-PIECE EXTRUDED ARCYLIC LENS DIFFUSER WITH DROPPED CENTER CHANNEL, LIFT AND SHIFT STEEL DOOR FRAME
LAY-IN GRID 0' - 4" 3000 lm 25 W 4000 K L70@60,000 hrs 120 LPW 0-10V
Dimming(1%)
B NOMINAL 4' LONG CEILING MOUNTED FIXTURE WITH AYSYMMETRICAL KICKER AND DIRECT OPTICS, EXTRUDED DIFFUSE ACRYLIC LENS WITH INTEGRATED OPAQUE WHITE REFLECTOR, FLUSH GYPSUM FLANGE MOUNTING, ELECTROSTATICALLY APPLIED POWDER COAT
WHITE FINISH
LAY-IN GRID 0' - 3 9/16" 1332 lm 18 W 4000 K L70@60,000 hrs 93 LPW 0-10V
Dimming(1%)
EXIT
LED TYPE, AC ONLY, WALL OR CEILING MOUNT AS INDICATED ON DRAWINGS, ALUMINUM CANOPY WITH WHITE FINISH, HIGH IMPACT CLEAR POLYCARBONATE HOUSING, RED LETTERS WITH WHITE FACE. REFER TO LIGHTING PLANS FOR CUSTOM CONFIGURATION OF CHEVRON DIRECTIONAL ARROWS. UL 924 LISTED. CONNECT TO UNSWITCHED EMERGENCY LIFE SAFETY CIRCUIT.
WALL/CEILING 0' - 0" 4000 K - - -
LIGHTING FIXTURE APPEARANCE GUIDE 1ROOM CONTROLLER WIRING DIAGRAM 2
Total New Est. Demand Amps: 21 A
Total New Est. Amps: 26 A 21 A 17 A
Total New Est. Load: 3.1 kVA 2.4 kVA 2.1 kVA
F,41 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F,42
F,39 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,40
F,37 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,38
F,35 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,36
F,33 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,34
F,31 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD F,32
F,29 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,30
F,27 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,28
F,25 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD F,26
F,23 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD F,24
F,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD F,22
F,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A SPARE F,20
F,17 EXISTING LOAD 20 A 1 0.0 0.0 F,18
F,15 BIOMED WRKSTAT 20 A 1 0.4 0.0
2 20 A SPARE
F,16
F,13 BIOMED WRKSTAT 20 A 1 0.4 0.0 F,14
F,11 EXISTING LOAD 20 A 1 0.0 0.0
2 20 A SPARE
F,12
F,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A SPARE F,10
F,7 EXISTING LOAD 20 A 1 0.0 1.0 F,8
F,5 EXISTING LOAD 20 A 1 0.0 1.0
2 30 A
ELECTRONICS
WORK STATIONS
F,6
F,3 SPARE 20 A 1 0.0 1.0 F,4
F,1 EXISTING LOAD 20 A 1 0.0 1.0
2 30 A
ELECTRONICS
WORK STATIONS
F,2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Comments: Existing Panel A.I.C Rating: Existing
Mounting: Surface Main: MCB
Location: EXIST. ELEC 1B608 OCP: 100 A
F1C1-120/208 Wye-3Φ-4W CRITICAL
Total New Est. Demand Amps: 63 A
Total New Est. Amps: 67 A 77 A 85 A
Total New Est. Load: 8 kVA 9.1 kVA 10 kVA
B,41 3.6 5.5 B,42
B,39 2.5 5.2 B,40
B,37
F1N2 100 A 3
2.2 5.9
3 100 A F1N3
B,38
B,35 BIOMED EMS STO 20 A 1 0.5 0.4 1 20 A BIOMED WRK STA B,36
B,33 BIOMED EMS STO 20 A 1 0.9 0.5 1 20 A BIOMED WRK STA B,34
B,31 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,32
B,29 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,30
B,27 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,28
B,25 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,26
B,23 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,24
B,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,22
B,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,20
B,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,18
B,15 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,16
B,13 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,14
B,11 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,12
B,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,10
B,7 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,8
B,5 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,6
B,3 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,4
B,1 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Comments: Existing Panel A.I.C Rating: Existing
Mounting: Surface Main: MLO
Location: EXIST. ELEC 1B608 BUS RATING: 225 A
F1N1-120/208 Wye-3Φ-4W NORMAL
Total New Est. Demand Amps: 23 A
Total New Est. Amps: 18 A 21 A 30 A
Total New Est. Load: 2.2 kVA 2.5 kVA 3.6 kVA
C,41 BIOMED OFFICES 20 A 1 0.9 0.5 1 20 A BIOMED OFFICES C,42
C,39 BIOMED OFFICES 20 A 1 0.7 0.5 1 20 A BIOMED OFFICES C,40
C,37 BIOMED OFFICES 20 A 1 1.1 1.1 1 20 A BIOMED OFFICES C,38
C,35 BIOMED OFFICES 20 A 1 1.3 0.9 1 20 A BIOMED EMS ST C,36
C,33 BIOMED FAX 20 A 1 1.2 0.0 1 20 A EXISTING LOAD C,34
C,31 SPARE 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,32
C,29 EXSITING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,30
C,27 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,28
C,25 EXSTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,26
C,23 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,24
C,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,22
C,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,20
C,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,18
C,15 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXSTING LOAD C,16
C,13 EXISITING LOAD 20 A 1 0.0 0.0 1 20 A EXISITNG LOAD C,14
C,11 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISITNG LOAD C,12
C,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,10
C,7 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,8
C,5 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTNG LOAD C,6
C,3 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,4
C,1 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Comments: Existing Panel A.I.C Rating: Existing
Mounting: Surface Main: MCB
Location: EXIST. ELEC 1B608 OCP: 225 A
F1N2-120/208 Wye-3Φ-4W NORMAL
Total New Est. Demand Amps: 46 A
Total New Est. Amps: 51 A 43 A 46 A
Total New Est.Load: 6.1 kVA 5.2 kVA 5.5 kVA
D,41 BIOMED WRKSTAT 20 A 1 0.4 0.5 1 20 A BIOMED EMS STO D,42
D,39 BIOMED PWR FUR 20 A 1 0.2 0.5 1 20 A BIOMED EMS STO D,40
D,37 BIOMED WRKSTAT 20 A 1 0.4 0.5 1 20 A BIOMED KITCHEN D,38
D,35 BIOMED PWR FUR 20 A 1 1.0 0.5 1 20 A BIOMED KITCHEN D,36
D,33 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,34
D,31 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,32
D,29 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,30
D,27 BIOMED PWR FUR 20 A 1 1.0 1.2 1 20 A BIOMED KITCHEN D,28
D,25 BIOMED WRKSTAT 20 A 1 0.4 1.4 1 20 A BIOMED CONVE D,26
D,23 BIOMED PWR FUR 20 A 1 1.0 0.4 1 20 A BIOMED WRKSTAT D,24
D,21 BIOMED WRKSTAT 20 A 1 0.4 0.2 1 20 A BIOMED PWR FUR D,22
D,19 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,20
D,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISITING LOAD D,18
D,15 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISITNG LOAD D,16
D,13 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,14
D,11 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,12
D,9 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,10
D,7 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,8
D,5 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,6
D,3 0.0 0.0 D,4
D,1
EXISTING LOAD 20 A 2
0.0 0.0
2 20 A EXISTING LOAD
D,2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Comments: Existing Panel A.I.C Rating: Existing
Mounting: Surface Main: MCB
Location: EXIST. ELEC 1B608 OCP: 100 A
F1N3-120/208 Wye-3Φ-4W NORMAL
GENERAL LIGHTING INSTALLATION NOTES
A CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING
TYPES.
B CONTRACTOR SHALL VERIFY ALL DRIVER QUANTITIES WITH SWITCHING SHOWN ON PLANS PRIOR TO ORDERING
FIXTURES. ADJUST DRIVER QUANTITIES AS REQUIRED TO MATCH SWITCHING.
C VERIFY LIGHTING CIRCUIT VOLTAGE (277V-1Ø OR 120V-1Ø) PRIOR TO ORDERING LIGHTING FIXTURES OR STARTING ROUGH-IN OF BRANCH CIRCUITS. IMMEDIATELY CONTACT ENGINEER WITH ANY DISCREPANCIES.
CONTRACTOR IS RESPONSIBLE FOR ORDERING THE PROPER VOLTAGE FOR LIGHTING FIXTURES, REGARDLESS
OF VOLTAGE SHOWN ON LIGHTING FIXTURE SCHEDULE.
D CONTRACTOR SHALL VERIFY ALL FIXTURES TO BE CONTROLLED BY DIMMER SWITCHES AS SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. PROVIDE ARCHITECTURAL DIMMING DRIVER (LED) WITH DIMMING RANGE FROM 100% DOWN TO 1% ON ALL DIMMED FIXTURES AND COMPATIBLE DIMMER CONTROLS WHERE DIMMING IS
INDICATED ON PLANS.
E REFER TO ELECTRICAL SPECIFICATIONS FOR LED COLOR TEMPERATURE AND DRIVER TYPE.
Revisions Date
BID AND CONSTRUCTION 03/26/2021
ADDENDUM #1 09/09/2021
3W
| 20046 FFH CF R20_Jeffrey.R.Duale |
| E1-03 - LIGHTING FIXTURE AND PANEL SCHEDULE |
File details come from the government source that posted it. Updated .