This solicitation package outlines requirements for a construction project to build out biomedical space at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The project scope includes consolidating all Health Technology Services/Biomedical storage and staff into one location, adding an electronics shop and storage space for Environmental Management Systems equipment, and utilizing vacated spaces for other purposes. The solicitation is a Service Disabled Veteran Owned Small Business set-aside between $500,000 and $1 million requiring bonds and a 240-day period of performance. Interested parties must register at SAM.gov and VetBiz.va.gov by the bid opening date in July 2021 to be eligible. The solicitation and amendments will be posted at SAM.gov, with questions due by the specified cutoff. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 10.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE

TYPE "A"

WORKSTATIONS/BIOMED/STORAGE/CORRIDOR

TYPE "B"

TOILET

OCCUPANCY SENSOR PROGRAM SCHEDULE:

OS

RC

277VAC:24VDC

WHT

BLK RED

RED - SWITCHED HOT

ROOM

CONTROLLER

NEUTRAL

HOT

24V SENSOR-

CEILING

MOUNTED

SENSOR TYPE ON CONTROL OFF CONTROL

DUAL

TECHNOLOGY

MANUAL

OFF TIME DELAY

MANUAL/SENSOR

AUTO OFF AFTER 15

MINUTES

CONNECT AS

REQUIRED -

0-10V DIMMING

MOUNT ABOVE

FINISHED CEILING

CONNECT LOW

VOLTAGE AS REQUIRED

CONNECT LOW

VOLTAGE AS REQUIRED

BRANCH

LIGHTING

CIRCUIT

277V

DLV24V DIMMING

SWITCH

S

DLV

24V DIMMING

SWITCH

S

CONNECT

LOW

VOLTAGE AS

REQUIRED

FOR MULTI-

WAY

SWITCHES

LIGHTING

LOAD

1 #12

1 #12

1 #12

NOT TO SCALE

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TEA

H

F OO

IO

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

VA Building

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Project Director

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

NORTH

ARCHITECTURAL PROJECT

# 18910

KEY PLAN

200469 /9

/2

:4

:2

A

M C

R e v it L o c a l F ile s \2

F

F H

C F

R

J e ff re y .R

.D u a le

.r v t

E1-03

757-20-206

JRD LV

CONSTRUCT BIOMED SPACE

03/26/2021

420 N. JAMES ROAD, COLUMBUS, OH 43219

LIGHTING FIXTURE AND PANEL SCHEDULE

LIGHTING FIXTURE SCHEDULE

TYPE FIXTURE DESCRIPTION MOUNTING MAX HEIGHT LUMEN WATTAGE COLOR TEMP LUMEN MAINTANCE RATING EFFICANCY DRIVER TYPE

A 2' X 2 LED TROFFER WITH DIRECT DISTRIBUTION, SOFT GLOW LENS, MATTE WHITE FINISH, DIE-FORMED STEEL HOUSING WITH WIRING ACCESS PLATE ON TOP OF HOUSING, HIGH-REFLECTANCE PREPAINT MATTE WHITE STEEL REFLECTORS, HIGH-EFFICIENCY ONE-PIECE EXTRUDED ARCYLIC LENS DIFFUSER WITH DROPPED CENTER CHANNEL, LIFT AND SHIFT STEEL DOOR FRAME

LAY-IN GRID 0' - 4" 3000 lm 25 W 4000 K L70@60,000 hrs 120 LPW 0-10V

Dimming(1%)

B NOMINAL 4' LONG CEILING MOUNTED FIXTURE WITH AYSYMMETRICAL KICKER AND DIRECT OPTICS, EXTRUDED DIFFUSE ACRYLIC LENS WITH INTEGRATED OPAQUE WHITE REFLECTOR, FLUSH GYPSUM FLANGE MOUNTING, ELECTROSTATICALLY APPLIED POWDER COAT

WHITE FINISH

LAY-IN GRID 0' - 3 9/16" 1332 lm 18 W 4000 K L70@60,000 hrs 93 LPW 0-10V

Dimming(1%)

EXIT

LED TYPE, AC ONLY, WALL OR CEILING MOUNT AS INDICATED ON DRAWINGS, ALUMINUM CANOPY WITH WHITE FINISH, HIGH IMPACT CLEAR POLYCARBONATE HOUSING, RED LETTERS WITH WHITE FACE. REFER TO LIGHTING PLANS FOR CUSTOM CONFIGURATION OF CHEVRON DIRECTIONAL ARROWS. UL 924 LISTED. CONNECT TO UNSWITCHED EMERGENCY LIFE SAFETY CIRCUIT.

WALL/CEILING 0' - 0" 4000 K - - -

LIGHTING FIXTURE APPEARANCE GUIDE 1ROOM CONTROLLER WIRING DIAGRAM 2

Total New Est. Demand Amps: 21 A

Total New Est. Amps: 26 A 21 A 17 A

Total New Est. Load: 3.1 kVA 2.4 kVA 2.1 kVA

F,41 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F,42

F,39 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,40

F,37 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,38

F,35 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,36

F,33 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,34

F,31 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD F,32

F,29 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,30

F,27 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A SPARE F,28

F,25 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD F,26

F,23 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD F,24

F,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD F,22

F,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A SPARE F,20

F,17 EXISTING LOAD 20 A 1 0.0 0.0 F,18

F,15 BIOMED WRKSTAT 20 A 1 0.4 0.0

2 20 A SPARE

F,16

F,13 BIOMED WRKSTAT 20 A 1 0.4 0.0 F,14

F,11 EXISTING LOAD 20 A 1 0.0 0.0

2 20 A SPARE

F,12

F,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A SPARE F,10

F,7 EXISTING LOAD 20 A 1 0.0 1.0 F,8

F,5 EXISTING LOAD 20 A 1 0.0 1.0

2 30 A

ELECTRONICS

WORK STATIONS

F,6

F,3 SPARE 20 A 1 0.0 1.0 F,4

F,1 EXISTING LOAD 20 A 1 0.0 1.0

2 30 A

ELECTRONICS

WORK STATIONS

F,2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Comments: Existing Panel A.I.C Rating: Existing

Mounting: Surface Main: MCB

Location: EXIST. ELEC 1B608 OCP: 100 A

F1C1-120/208 Wye-3Φ-4W CRITICAL

Total New Est. Demand Amps: 63 A

Total New Est. Amps: 67 A 77 A 85 A

Total New Est. Load: 8 kVA 9.1 kVA 10 kVA

B,41 3.6 5.5 B,42

B,39 2.5 5.2 B,40

B,37

F1N2 100 A 3

2.2 5.9

3 100 A F1N3

B,38

B,35 BIOMED EMS STO 20 A 1 0.5 0.4 1 20 A BIOMED WRK STA B,36

B,33 BIOMED EMS STO 20 A 1 0.9 0.5 1 20 A BIOMED WRK STA B,34

B,31 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,32

B,29 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,30

B,27 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,28

B,25 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,26

B,23 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,24

B,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,22

B,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,20

B,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,18

B,15 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,16

B,13 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,14

B,11 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,12

B,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,10

B,7 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,8

B,5 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,6

B,3 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,4

B,1 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD B,2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Comments: Existing Panel A.I.C Rating: Existing

Mounting: Surface Main: MLO

Location: EXIST. ELEC 1B608 BUS RATING: 225 A

F1N1-120/208 Wye-3Φ-4W NORMAL

Total New Est. Demand Amps: 23 A

Total New Est. Amps: 18 A 21 A 30 A

Total New Est. Load: 2.2 kVA 2.5 kVA 3.6 kVA

C,41 BIOMED OFFICES 20 A 1 0.9 0.5 1 20 A BIOMED OFFICES C,42

C,39 BIOMED OFFICES 20 A 1 0.7 0.5 1 20 A BIOMED OFFICES C,40

C,37 BIOMED OFFICES 20 A 1 1.1 1.1 1 20 A BIOMED OFFICES C,38

C,35 BIOMED OFFICES 20 A 1 1.3 0.9 1 20 A BIOMED EMS ST C,36

C,33 BIOMED FAX 20 A 1 1.2 0.0 1 20 A EXISTING LOAD C,34

C,31 SPARE 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,32

C,29 EXSITING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,30

C,27 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,28

C,25 EXSTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,26

C,23 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,24

C,21 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,22

C,19 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,20

C,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,18

C,15 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXSTING LOAD C,16

C,13 EXISITING LOAD 20 A 1 0.0 0.0 1 20 A EXISITNG LOAD C,14

C,11 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISITNG LOAD C,12

C,9 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,10

C,7 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,8

C,5 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTNG LOAD C,6

C,3 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,4

C,1 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISTING LOAD C,2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Comments: Existing Panel A.I.C Rating: Existing

Mounting: Surface Main: MCB

Location: EXIST. ELEC 1B608 OCP: 225 A

F1N2-120/208 Wye-3Φ-4W NORMAL

Total New Est. Demand Amps: 46 A

Total New Est. Amps: 51 A 43 A 46 A

Total New Est.Load: 6.1 kVA 5.2 kVA 5.5 kVA

D,41 BIOMED WRKSTAT 20 A 1 0.4 0.5 1 20 A BIOMED EMS STO D,42

D,39 BIOMED PWR FUR 20 A 1 0.2 0.5 1 20 A BIOMED EMS STO D,40

D,37 BIOMED WRKSTAT 20 A 1 0.4 0.5 1 20 A BIOMED KITCHEN D,38

D,35 BIOMED PWR FUR 20 A 1 1.0 0.5 1 20 A BIOMED KITCHEN D,36

D,33 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,34

D,31 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,32

D,29 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,30

D,27 BIOMED PWR FUR 20 A 1 1.0 1.2 1 20 A BIOMED KITCHEN D,28

D,25 BIOMED WRKSTAT 20 A 1 0.4 1.4 1 20 A BIOMED CONVE D,26

D,23 BIOMED PWR FUR 20 A 1 1.0 0.4 1 20 A BIOMED WRKSTAT D,24

D,21 BIOMED WRKSTAT 20 A 1 0.4 0.2 1 20 A BIOMED PWR FUR D,22

D,19 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,20

D,17 EXISTING LOAD 20 A 1 0.0 0.0 1 20 A EXISITING LOAD D,18

D,15 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISITNG LOAD D,16

D,13 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,14

D,11 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,12

D,9 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,10

D,7 BIOMED WRKSTAT 20 A 1 0.4 0.0 1 20 A EXISTING LOAD D,8

D,5 BIOMED PWR FUR 20 A 1 1.0 0.0 1 20 A EXISTING LOAD D,6

D,3 0.0 0.0 D,4

D,1

EXISTING LOAD 20 A 2

0.0 0.0

2 20 A EXISTING LOAD

D,2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Comments: Existing Panel A.I.C Rating: Existing

Mounting: Surface Main: MCB

Location: EXIST. ELEC 1B608 OCP: 100 A

F1N3-120/208 Wye-3Φ-4W NORMAL

GENERAL LIGHTING INSTALLATION NOTES

A CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING

TYPES.

B CONTRACTOR SHALL VERIFY ALL DRIVER QUANTITIES WITH SWITCHING SHOWN ON PLANS PRIOR TO ORDERING

FIXTURES. ADJUST DRIVER QUANTITIES AS REQUIRED TO MATCH SWITCHING.

C VERIFY LIGHTING CIRCUIT VOLTAGE (277V-1Ø OR 120V-1Ø) PRIOR TO ORDERING LIGHTING FIXTURES OR STARTING ROUGH-IN OF BRANCH CIRCUITS. IMMEDIATELY CONTACT ENGINEER WITH ANY DISCREPANCIES.

CONTRACTOR IS RESPONSIBLE FOR ORDERING THE PROPER VOLTAGE FOR LIGHTING FIXTURES, REGARDLESS

OF VOLTAGE SHOWN ON LIGHTING FIXTURE SCHEDULE.

D CONTRACTOR SHALL VERIFY ALL FIXTURES TO BE CONTROLLED BY DIMMER SWITCHES AS SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. PROVIDE ARCHITECTURAL DIMMING DRIVER (LED) WITH DIMMING RANGE FROM 100% DOWN TO 1% ON ALL DIMMED FIXTURES AND COMPATIBLE DIMMER CONTROLS WHERE DIMMING IS

INDICATED ON PLANS.

E REFER TO ELECTRICAL SPECIFICATIONS FOR LED COLOR TEMPERATURE AND DRIVER TYPE.

Revisions Date

BID AND CONSTRUCTION 03/26/2021

ADDENDUM #1 09/09/2021

3W

20046 FFH CF R20_Jeffrey.R.Duale
E1-03 - LIGHTING FIXTURE AND PANEL SCHEDULE