This document is a solicitation for the construction of a biomedical space project at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The project scope includes building out existing shell space to consolidate all Health Technology Services and Biomedical storage and staff into one location, adding an electronics shop and storage space for Environmental Management Systems equipment, and utilizing vacated spaces for other purposes. The estimated value is between $500,000 and $1 million. The solicitation will be set aside for Service Disabled Veteran Owned Small Businesses and will have a site visit, bid opening date approximately 30 days after posting to SAM.gov on July 9, 2021, and a project duration not to exceed 240 calendar days from receipt of notice to proceed. Questions must be submitted in writing to the contracting officer by the specified deadline.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2018 INTERNATIONAL BUILDING CODE
CHAPTER 3 - USE GROUP:
USE GROUP B - BUSINESS
CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS:
DETAILED REQUIREMENTS IF NEEDED
FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE 601:
CONSTRUCTION TYPE: 1B
STRUCTURAL FRAME: 2 HRS
BEARING WALLS:
EXTERIOR: 2 HRS
INTERIOR: 2 HRS
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 HRS
CHAPTER 7 - FIRE AND SMOKE PROTECTION FEATURES:
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
EXIT PASSAGEWAYS: 0 HRS
BUILDING SEPARATION:
B TO B: 0 HR FIREWALL
CHAPTER 8 - INTERIOR FINISHES:
EXIT ENCLOSURES & PASSAGEWAYS: CLASS B
CORRIDORS: CLASS C
ROOMS & ENCLOSED SPACES: CLASS C
INTERIOR FLOOR FINISH: MINIMUM CLASS II
CHAPTER 9 - FIRE PROTECTION SYSTEMS:
SPRINKLER SYSTEM: FULLY SUPRESSED
FIRE ALARM SYSTEM: YES
FIRE EXTINGUISHERS:
TYPE: 2A-10-B:C
MAXIMUM AREA: 6000 SF
MAXIMUM TRAVEL DISTANCE: 75
CHAPTER 10 - MEANS OF EGRESS:
DOOR WIDTH: 32" MINIMUM CLEAR WIDTH
CORRIDOR WIDTH: .2" PER OCCUPANT, BUT NOT LESS THAN 44"
LENGTH OF EXIT TRAVEL: AMBULATORY: 200'
BUSINESS: 300'
DESIGN OCCUPANT LOAD:
FIRST FLOOR TOTAL:
BUSINESS: 2679 / 100 = 27 PERSONS
STOR/MECH: 1378 / 300 = 5 PERSONS
PROJECT AREA
OCCUPANCY
BUSINESS - OUTPATIENT CLINIC (AMBULATORY)
AMBULATORY HEALTH CARE (CHAPTER 20 / 21)
FIRE SUPPRESSION:
FULLY SPRINKLERED
SMOKE BARRIERS (CHAPTER 20)
1 HOUR
FLOOR: 4,580 S.F.
TRAVEL DISTANCE (CHAPTER 20)
REMOTE POINT TO EXIT
OCCUPANT LOAD FACTORS (CHAPTER 7)
OFFICES:
STORAGE ROOMS:
AMBULATORY CARE:
200 FOOT MAX
100 GROSS
500 GROSS
150 GROSS
FIRE-RESISTANCE RATING REQUIREMENTS (CHAPTER 8)
2018 NFPA 101 LIFE SAFETY CODE - AMBULATORY CARE CENTER
USE GROUP B - AMBULATORY CARE
BUILDING TYPE
TYPE II (222)
CONSTRUCTION TYPE: II
STRUCTURAL FRAME: 2 HRS
BEARING WALLS:
EXTERIOR: 2 HRS
INTERIOR: 2 HRS
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 HRS
APPLICABLE CODE
INTERNATIONAL BUILDING CODE, 2018 EDITION
NFPA 101 LIFE SAFETY CODE, 2018 EDITION
NFPA 70 NATIONAL ELECTRICAL CODE, 2020 EDITION
NFPA 110, 2019 EDITION
AREA OF WORKAREA N.I.C
STRUCTURAL CODE
DESIGN STRESSES
CONCRETE MINIMUM COMPRESSIVE STRENGTH IN 28 DAYS:
SLABS ON GRADE INFILL AND THICKENED SLABS ------------------- F'C = 4,000 PSI
REINFORCING BARS (ASTM A615, GRADE 60) ---------------------------------- FY = 60,000 PSI
WELDED WIRE REINFORCEMENT (ASTM A1064) ------------------------------ FY = 70,000 PSI
MASONRY ------------------------------------------------------------------------------------ F'M = 2,000 PSI
LOAD-BEARING CMU (ASTM C55 OR C90) ------------------------------- F'M = 2,000 PSI
MORTAR (ASTM C270) ---------------------------------------------------------- TYPE S
DESIGN LOADS
FLOOR LIVE LOAD
FIRST FLOOR SLAB ON GRADE INFILL ------------------------------------- 100 PSF (1)
(1) INCLUDES 15 PSF PARTITION ALLOWANCE, UNREDUCED
ROOF LIVE LOAD ---------------------------------------------------------------------------
ROOF SNOW LOAD DATA --------------------------------------------------------------- NOT APPLICABLE
WIND DESIGN DATA ----------------------------------------------------------------------- NOT APPLICABLE
EARTHQUAKE DESIGN DATA ---------------------------------------------------------- PER ASCE 7-10
RISK CATEGORY (ASCE 7, TABLE 1.5-1) ---------------------------------- IV
SEISMIC IMPORTANCE FACTOR (ASCE 7, TABLE 1.5-2) ------------ IE = 1.5
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS
SHORT PERIOD ------------------------------------------------------------ SS = 0.117 G
1-SECOND PERIOD ------------------------------------------------------- S1 = 0.061 G
SITE CLASS (PER GEOTECHNICAL REPORT) --------------------------- D
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS
SHORT PERIOD ------------------------------------------------------------ SDS = 0.125 G
1-SECOND PERIOD ------------------------------------------------------- SD1 = 0.098 G
SEISMIC DESIGN CATEGORY -------------------------------------------------
ALTERATIONS ARE IN ACCORDANCE WITH ASCE 7, APPENDIX 11B.4. PROPOSED
ALTERATIONS DO NOT INCREASE THE SEISMIC FORCE IN ANY EXISTING
STRUCTURAL ELEMENT BY MORE THAN 10 PERCENT, NOR DO THEY DECREASE
THE DESIGN STRENGTH OF ANY EXISTING STRUCTURAL ELEMENT TO RESIST
SEISMIC FORCES BY MORE THAN 10 PERCENT. THEREFORE, FURTHER
ANALYSIS AND DESIGN OF THE EXISTING STRUCTURE FOR SEISMIC
FORCE-RESISTANCE ARE NOT REQUIRED.
SPECIAL LOADS
INTERIOR WALLS AND PARTITIONS (HORIZONTAL) -------------------------- 5 PSF MIN.
CODES AND STANDARDS
1. NEW CONSTRUCTION HAS BEEN DESIGNED TO, AND SHALL BE CONSTRUCTED
IN ACCORDANCE WITH THE FOLLOWING BUILDING CODES AND STANDARDS:
A. 2018 INTERNATIONAL BUILDING CODE (IBC 2018)
B. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES
2. UNLESS EXPLICITLY MODIFIED IN THE CONTRACT DRAWINGS AND
SPECIFICATIONS, THE CONTRACTOR SHALL COMPLY WITH PROVISIONS OF:
A. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
B. ACI 530-16, BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES
C. ACI 530.1-16, SPECIFICATION FOR MASONRY STRUCTURES
D. AISI S100-16, NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS
NOT APPLICABLE
BID ALTERNATE #1
REPLACE EPOXY FLOORING AND INTEGRAL WALL BASE WITH LUXURY VINYL
TILE FLOORING AND RUBBER WALL BASE, AS LOCATED IN THE FINISH
SCHEDULE AND THE SCHEDULE OF FINISHES 090600.
BID ALTERNATE #2
PROVIDE TWO (2) CAT6A CABLES AT EACH DATA DROP LOCATION ON PLANS IN
LIEU OF FOUR (4). EACH FACEPLATE SHALL HAVE TWO (2) BLANK POSITIONS
FOR FUTURE USE. REFER TO VA TELECOMMUNICATIONS OUTLET DETAIL FOR
ADDITIONAL INFORMATION.
BID ALTERNATE #3
REMOVE OXYGEN AND MEDICAL VACUUM PIPING, VALVES AND OUTLETS/INLETS
COMPLETELY. MEDICAL AIR PIPING, VALVES AND OUTLETS SHALL REMAIN,
REFERENCE DWG PG-101.
THIS PROJECT WOULD BUILD OUT APPROXIMATELY 4,580 SF OF SHELL SPACE
IN THE EXISTING AMBULATORY CARE CENTER TO RELOCATE THE HEALTH
TECHNOLOGY MAINTENANCE (HTM) SHOP DISPLACED BY THE COMPUTED
TOMOGRAPHY (CT) PROJECT. THIS PROJECT WILL CONSOLIDATE ALL
HTM/BIOMED STORAGE AND STAFF IN ONE LOCATION TO IMPROVE THE
DEPARTMENTS’ WORKFLOW.
SPACES INCLUDE EMS AND HTM STORAGE FOR EQUIPMENT AND SUPPLIES,
OPEN WORK STATIONS TO ACCOMODATE REPAIR AND TESTING OF HTM
EQUIPMENT, ELECTRONIC WORK AND STORAGE, OFFICE, WAITING AND OTHER
SUPPORT SPACES.
PROJECT NUMBER:
SUBMITTAL FOR:
DRAWING INDEX: CODE DATA:LOCATION MAP:
STRUCTURAL CODE DATA:
CONSTRUCT BIOMED SPACE
420 N. JAMES ROAD, COLUMBUS, OH 43219
757-20-206
BID AND CONSTRUCTION
DRAWING INDEX
ELECTRICAL
E1-01 ELECTRICAL LEGEND AND GENERAL NOTES
E1-02 ELECTRICAL DETAILS
E1-03 LIGHT FIXTURE AND PANEL SCHEDULE
E2-01 PARTIAL FIRST FLOOR ELECTRICAL AND TECHNOLOGY KEY PLAN
E3-01 PARTIAL FIRST FLOOR ELECTRICAL DEMOLITION PLAN
E4-01 PARTIAL FIRST FLOOR ELECTRICAL PLANS
TECHNOLOGY
T1-01 TECHNOLOGY LEGEND AND GENERAL NOTES
T1-02 TECHNOLOGY DETAILS
T2-01 PARTIAL FIRST FLOOR TECHNOLOGY PLANS
Grand total: 35
DRAWING INDEX
GENERAL
G1-00 COVER AND DRAWING INDEX
G1-01 ABBREVIATIONS, SYMBOLS AND LEGENDS
G1-02 LIFE SAFETY PLAN
ARCHITECTURE
A1-01 PARTIAL DEMOLITION PLANS
A3-01 PARTIAL FIRST FLOOR PLAN AND RCP
A3-02 PARTIAL ROOM FINISH PLAN AND SCHEDULE
A3-03 PARTIAL FIRST FLOOR FURNITURE AND EQUIPMENT PLAN
A7-01 ENLARGED PLANS AND INTERIOR ELEVATIONS
A7-02 WALL SECTIONS AND PLAN DETAILS
A7-03 PARTITION TYPES
A8-01 DOOR SCHEDULE, DETAILS AND STRUCTURAL DETAILS
A8-02 MILLWORK AND MOUNTING DETAILS
A8-03 PARTIAL INTERIOR SIGNAGE PLAN, SCHEDULE AND DETAILS
FIRE PROTECTION
FX-101 FIRE PROTECTION PLANS, LEGEND AND GENERAL NOTES
PLUMBING
P-001 PLUMBING LEGEND, GENERAL NOTES AND SCHEDULES
P-501 PLUMBING DETAILS
PD-101 PARTIAL FIRST FLOOR UNDERSLAB PLUMBING DEMOLITION PLAN
PG-101 PARTIAL FIRST FLOOR MEDICAL GAS PLAN
PL-101 PARTIAL FIRST FLOOR UNDERSLAB PLUMBING PLAN AND SANITARY
ISOMETRIC
MECHANICAL
M-001 MECHANICAL LEGEND AND GENERAL NOTES
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
MD-101 PARTIAL FIRST FLOOR HVAC DEMOLITION PLAN
MH-101 PARTIAL FIRST FLOOR HVAC PLAN
MH-102 PARTIAL FIRST FLOOR AIR BALANCE PLAN
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/2
/2
:1
:4
P M
C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
G1-00
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
COVER AND DRAWING INDEX
OVERALL KEY PLAN
BID ALTERNATES
STATEMENT OF WORK
Revisions Date
BID AND CONSTRUCTION 03/26/2021
AIR CONDITIONED
ACOUSTICAL CEILING TILE
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ALTERNATE
AUDIO VISUAL
ARCHITECTURAL WOODWORK
AC
A.C.T.
A.C.U.
A.F.F.
ALT
A.V.
A.W.
BD
BLDG
BLK
BLKG
BOT
BR
BRG
BSMT
CONC
CAB
C.B.B.
C.C.T.
C.G.
C.J.
CLR
CLG
C.M.U.
COL
COMM
CONF
CONN
CONST
CONT
CONTR
COORD
CORR
C.R.
C.W.
CYL
DBL
DEMO
DEPT
DET
D.F.
DIA
DIAG
DIM
DISP
DN
DR
D.S.
D.W.
DWG(S)
EXIST
E
EA EACH
EAST
EXISTING
DRAWING(S)
DUMBWAITER
DOWNSPOUT
DOOR
DOWN
DISPENSER
DIMENSION
DIAGONAL
DIAMETER
DRINKING FOUNTAIN
DETAIL
DEPARTMENT
DEMOLITION
DOUBLE
CYLINDER
COLD WATER
CRASH RAIL
CORRIDOR
COORDINATE
CONTRACTOR
CONTINUOUS
CONSTRUCTION
CONNECTION
CONFERENCE
COMMUNICATION
COLUMN
CONCRETE MASONRY UNIT
CEILING
CLEAR
CONTROL JOINT
CORNER GUARD
CUBICAL CURTAIN TRACK
CEMENTITIOUS BACKER BOARD
CABINET
CONCRETE
BASEMENT
BEARING
BRICK
BOTTOM
BLOCKING
BLOCK
BUILDING
BOARD
POUND OR NUMBER #
DIAMETER OR ROUND
CENTERLINE
AT
ANGLE
AND
EXPANSION JOINT
ELECTRICAL
E.I.F.S.
E.J.
ELECT
EL
ELEV
EMER
ENCL
EQ
EQUIP
E.T.R.
EVAC
E.W.C.
EXT
F.B.
F.C.
F.C.U.
F.D.
F.D.V.C.
F.E.
F.E.C.
F.H.C.
FIN
FIXT
FLR
FLEX
FLUOR
F.R.T.
FT
FTG
FURN
FUT
G
GA
GALV
G.C.
G.F.M.U.
GL
GR
GRND
GYP
H.B.
HD
HDWD
H.M.
HOSP
H.P.
HR
H.R.
HORIZ
HT
HTG
HTR
H.V.A.C.
H.W.
HW
HYD
I.D.
ILLUM
INCIN
INCAND
INCL
INFO
INSUL
INT
I.P.S.
ISOL
IV
JT
KITCH
K.O.
K.P.
K.S. KNEE SPACE
KICK PLATE
KNOCK OUT
KITCHEN
JOINT
INTRAVENOUS
ISOLATION
INSIDE PIPE SIZE
INTERIOR
INSULATION
INFORMATION
INCLUDE
INCINERATOR
INCANDESCENT
ILLUMINATION
INSIDE DIAMETER (DIM)
HYDRANT
HARDWARE
HOT WATER
HEATING, VENTILATION, AIR CONDITIONING
HEATER
HEATING
HEIGHT
HORIZONTAL
HANDRAIL
HOUR
HIGH POINT
HOSPITAL
HOLLOW METAL
HEAD
HOSE BIBB
GYPSUM
GROUND
GRADE
GLASS
GROUND FACE MASONRY UNITS
GENERAL CONTRACTOR
GALVANIZED
GAGE
GAS
FUTURE
FURNITURE
FOOTING
FOOT OR FEET
FIRE RESISTANT TREATED
FLUORESCENT
FLEXIBLE
FLOOR
FIXTURE
FINISH
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE DEPARTMENT VALVE CABINET
FLOOR DRAIN
FAN COIL UNIT
FOOT CONTROL
FACE BRICK
EXTERIOR
ELECTRIC WATER COOLER
EVACUATION
EXISTING TO REMAIN
EQUIPMENT
EQUAL
ENCLOSURE
EMERGENCY
ELEVATOR
ELEVATION
L
LAB
LAM
LIB
LIN
LOC
L.P.
LT.WT.
LTG
MACH
MAS
MATL
MAX
MECH
MED
MED.CAB.
MEMB
MEZZ
MFR
MH
MIN
MISC
MKR.BD.
MLDG
M.O.
MOD
M.R.G.B.
MTD
MTL
N
N.C.
NEG
N.I.C.
NO
N.T.S.
O
O.C.
O.D.
OFF
OPNG
OPP
O.F.C.I.
PART.BD.
P.C.
P.C.D.
PERIM
PERP
PLWD
PORT
PR
PREFAB
PREFIN
PROJ
PROP
P.T.
PTD
R
R.A.
REC
RECEP
RECT
REF REFRIGERATOR
RECTANGULAR
RECEPTACLE
RECESSED
RETURN AIR
RADIUS
PAPER TOWEL DISPENSER
PNEUMATIC TUBE
PROPERTY
PROJECT
PREFINISHED
PREFABRICATED
PAIR
PORTABLE
PLYWOOD
PERPENDICULAR
PERIMETER
PAPER CUP DISPENSER
PRECAST CONCRETE
PARTICLEBOARD
OWNER FURNISHED, CONTRACTOR INSTALLED
OPPOSITE
OPENING
OFFICE
OUTSIDE DIAMETER(DIM)
ON CENTER
OXYGEN
NOT TO SCALE
NOMINAL
NUMBER
NOT IN CONTRACT
NEGATIVE
NURSE CALL
NITROGEN/NORTH
METAL
MOUNTED
MOISTURE RESISTANT GYPSUM BOARD
MODIFIED, MODULAR
MASONRY OPENING
MOULDING
MARKERBOARD
MISCELLANEOUS
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MEMBRANE
MEDICINE CABINET
MEDICINE/MEDICAL
MECHANICAL
MAXIMUM
MATERIAL
MASONRY
MACHINE
LIGHTING
LIGHTWEIGHT
LOW POINT
LOCATION/LOCATE
LINEAR
LIBRARY
LAMINATE
LABORATORY
LOCK
REFL REFLECTED
REINF REINFORCED
REM REMOVABLE
REQ'D REQUIRED
REV REVISION
R.F. RADIO FREQUENCY
RM
RND
R.O.
R.S.T. RUBBER STAIR TREADS
ROUGH OPENING
ROUND
S
S.S.
S.A.
SAN
SCHED
S.C.R.
S.D.
SECT
SGL
SH
SHR
SHT
SIM
S.O.G.
SPEC (S)
S&R
S.P.T.
SQ
S.F.
S.I.
S.Y.
S.T.C.
STD
STL
STOR
STRUCT
SURF
SUSP
T
T&B
T&G
TAN
TEL
TEMP
THRESH
THRU
TK.BD.
TLT
T.O.P.
TV
TYP
U.C.
UNFIN
U.O.N.
UTIL
V, VAC
VENT
VERT
VEST
VIT
W
W/
W/O
W.C.
W/C
WD
W.P.
YD YARD
WORKPOINT
WOOD
WHEEL CHAIR
WATER CLOSET
WITHOUT
WITH
WEST/WATER
VITREOUS
VESTIBULE
VERTICAL
VENTILATION
VACUUM
UTILITY
UNLESS OTHERWISE NOTED
UNFINISHED
UNDER COUNTER
TYPICAL
TELEVISION
TOP OF PAVEMENT
TOILET
TACKBOARD
THROUGH
THRESHOLD
TEMPERATURE
TELEPHONE
TANGENT
TONGUE AND GROOVE
TOP AND BOTTOM
THERMOSTAT
SUSPENDED
SURFACE
STRUCTURAL
STORAGE
STEEL
STANDARD
SOUND TRANSMISSION CLASS / COEFFICIENT
SQUARE YARD
SQUARE INCH
SQUARE FOOT
SQUARE
SPECIMEN PASS-THRU
SHELF & ROD
SPECIFICATION(S)
SLAB ON GRADE
SIMILAR
SHEET
SHOWER
SHELVING, SHELF
SINGLE
SECTION
SUPPLY DIFFUSER
SHOWER CURTAIN ROD
SCHEDULE
SANITARY
SUPPLY AIR
STAINLESS STEEL
SOUTH
LT LIGHT
LAV LAVATORY
W.W.F. WELDED WIRE FABRIC
EXTERIOR INSULATION FINISH SYSTEM
HARDWOOD
NOM
ROOM
V.I.F. VERIFY IN FIELD
ALUMINUMAL
F.P. FIRE PROTECTION
F.P.G. FIRE PROTECTED GLAZING
O.F.O.I. OWNER FURNISHED, OWNER INSTALLED
SSM SOLID SURFACE MATERIAL
ø
NOTE: ALL ITEMS/MATERIALS MAY NOT OCCUR IN THIS
PROJECT. LIST PROVIDED FOR REFERENCE ONLY.
UNDISTURBED EARTH OR
UNDISTURBED SUBGRADE
COMPACTED EARTH OR
COMPACTED SUBGRADE
ROCK
POROUS FILL OR SUBBASE
IMPERVIOUS FILL
DRAINAGE FILL
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE
TOPSOIL
CEMENTITIOUS DECKS AND
TOPPINGS
GROUT
BRICK
GLAZED BRICK
STRUCTURAL CLAY TILE UNIT
MASONRY
GLAZED STRUCTURAL CLAY
TILE UNIT MASONRY
CONCRETE UNIT MASONRY
GLAZED CONCRETE UNIT
MASONRY
GLAZED UNIT MASONRY
CUT STONE
FIREBRICK
CAST STONE
STEEL
ALUMINUM
ORNAMENTAL
METAL/STAINLESS STEEL
CONTINUOUS WOOD FRAMING
WOOD BLOCKING
PLYWOOD
PARTICLE BOARD
FINISHED LUMBER FOR
ARCHITECTURAL WORK
BATT INSULATION
RIGID INSULATION
LOOSE FILL INSULATION
EXTERIOR INSULATION AND
FINISH SYSTEM
FIBROUS FIRE SAFING
GLASS
CARPET
LATH AND PLASTER
GYPSUM BOARD
PLASTIC GLAZING
TERRAZZO
ACOUSTICAL CEILING
RESILIENT TILE
CERAMIC TILE
FINISHED CONTOURS
EXISTING CONTOURS
CONTRACT LIMIT LINE
PROPERTY LINE
SPOT ELEVATION INDICATORS
NEW
EXISTING
FENCE
STRUCTURAL GRID COLUMN LINE
INDICATOR (NEW)
STRUCTURAL GRID COLUMN LINE
INDICATOR (EXISTING)
CENTERLINE
REVISION INDICATOR
DRAWING BREAK LINE
MATCH LINE INDICATOR
HIDDEN LINE
1. ITEMS ABOVE OR BEYOND
2. ITEMS NOT IN CONTRACT (N.I.C.)
3. ITEMS BEING DEMOLISHED
ELEVATION DATUM
WINDOW & LOUVER TAG
(SEE WINDOW SCHEDULE)
DOOR TAG
(SEE DOOR SCHEDULE)
EQUIPMENT TAG
(SEE EQUIPMENT SCHEDULE)
WALL TYPE TAG
(SEE PARTITION TYPES)
WORK POINT
ROOM TAG
INTERIOR ELEVATION VIEW INDICATOR
DETAIL INDICATOR
SECTION INDICATOR
DRAWING TITLE
DETAIL NO.
DRAWING NO.
1ELEVATION NO.
DRAWING NO. A7-01
A
NEW
EXISTING
SECTION NO.
DRAWING NO.
X
B
01-001A
ROOM NAME
X
1 / A101
1 / A101
A5-01
A5-01
1A
0' - 0"
0' - 0"
1 View Name
SCALE: 1/8" = 1'-0"A101
LEVEL NAME
0'-0"
LEVEL NAME
0'-0"
ROOM NAME
ROOM NUMBER
BUILDING ELEVATION VIEW INDICATOR
1ELEVATION NO.
DRAWING NO. A4-01
APPROX. AREA REVISED
REVISION NO.
NEW
PARTITION
PATCH TO MATCH
EXISTING PARTITION
EXISTING PARTITION TO
REMAIN
EXISTING DOOR TO
REMAIN
EXISTING DOOR TO BE
REMOVED
NEW DOOR AND
FRAME
POCKET DOOR
CASED OPENING
(PROVIDE SOFFIT
ABOVE
BIFOLD DOOR
SLIDING DOOR
01-001A
ROOM NAME
01-001A
ROOM NAME
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/2
/2
:1
:4
P M
C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
G1-01
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
ABBREVIATIONS, SYMBOLS AND LEGENDS
STANDARD ABBREVIATIONS
MATERIALS LEGEND GRAPHIC SYMBOLS
FLOOR PLAN LEGEND
SMOKE COMPARTMENT
17,515 SF
EXIT OUT
OUT
OUT
EXIT DISTANCE = 136'
EXIT DISTANCE = 148'
EXIT DISTANCE
= 148'
EXIT DISTANCE = 181'
F.E.C.
1B700
EMS
STORAGE
1B704
ELECTRONICS
(WORK
STATIONS +
STORAGE)
1B714
KITCHENETTE
1B713
TOILET
1B712
HTM
STORAGE
1B703
RECEIVING/
WORKSPACE
1B708
SECTION
CHIEF
1B709
BESS LEAD
1B710
BIOMED 01
1B706
BIOMED 02
1B705
BIOMED 03
1B702
RECEPTION /
WAITING
1B701
CORRIDOR
1B715
HOUSE
KEEPING
AREA N.I.C.
AREA N.I.C.
AREA N.I.C.
EXIT DISTANCE = 89'
OCCUPANT LOAD LEGEND
BUSINESS - AMBULATORY
NO OCCUPANCY
STORAGE
R = 75'-0
F.E.C.
NON-RATED SMOKE PARTITION
RATED SMOKE BARRIER
1 HOUR FIRE SEPARATION
2 HOUR FIRE SEPARATION
3 HOUR FIRE SEPARATION
FIRE EXTINGUISHER CABINET
TRAVEL DISTANCE
EXIT SIGN
1B103
EXIST.
REPRODUCTION/MAIL
ROOM
1B012
EXIST.
CORRIDOR
1B100B
EXIST. SCAN
ROOM
1B094
EXIST.
OFFICE
1B100A
EXIST.
CONTROL
1B635A
EXIST. AUDIO
BOOTH
1B634A
EXIST. AUDIO
BOOTH
1B633A
EXIST. AUDIO
BOOTH
1B090
EXIST.
BIOMED
1B092
EXIST.
OFFICE
1B632A
EXIST. AUDIO
BOOTH
1B636
EXIST.
SOILED
UTILITY
1B098
EXIST.
EQUIPMENT
1B101
EXIST.
SUPPLY
STORAGE
1B103A
EXIST.
REVERSE
OSMOSIS
1B121
EXIST.
MEDIA
VAULT
1B101B
EXIST.
ENVIRN.
SERVICES
OFFICE
1B105
EXIST. STAFF
TOILET
1B107
EXIST. FORM
STORAGE
1B093
EXIST.
TOILET
ROOM
1B097
EXIST. M.R.I.
5A002
EXIST. ROOM
1A100C
EXIST.
CLOSET
1B610
EXIST.
SHARED
RECEPTION
1B613
EXIST. PSA
1B630
EXIST.
PASSAGE
1B617
EXIST.
RESIDENTS
1B119
EXIST. CHIEF
OFFICE
1B116
EXIST. OPEN
OFFICE
1B601
EXIST.
VESTIBULE
1B612
EXIST.
HEALTH
TECH
1B614
EXIST.
HEALTH
TECH
1B616
EXIST. FIT
LAB
1B618
EXIST. FIT
LAB
1B620
EXIST. FIT
LAB
1B619
EXIST.
CLEAN
1BS5
EXIST. STAIR
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/8
/2
:2
:5
P
M C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
G1-02
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
LIFE SAFETY PLAN
SCALE: 1/8" = 1'-0"G1-02
1 FIRST FLOOR - LIFE SAFETY PLAN
LIFE SAFETY LEGEND
OCCUPANT LOAD SCHEDULE
AREA
AREA /
OCCUPANT OCCUPANT LOAD OCCUPANCY
FIRST FLOOR
BUSINESS - AMBULATORY
2679 SF 100 SF 26.79 BUSINESS - AMBULATORY
NO OCCUPANCY
169 SF 0 SF 0.00 NO OCCUPANCY
STORAGE
1378 SF 300 SF 4.59 STORAGE
4227 SF 31.39
A
0.8
A.2A.1 A.8
0.7
D03D04
D05
D05D05
D05D05
D09
D09
D06D06
D07D07D07
D10
D09
D11
D12
D10
D15
AREA N.I.C.
AREA N.I.C.
D01D01
A8-01
EX-1B610.B
EX-1B650.A
1. CONTRACTOR SHALL COORDINATE DEMOLITION WITH OWNER; SALVAGE
AND TURN OVER TO OWNER DOORS, HARDWARE, TOILET ACCESSORIES,
CURTAIN TRACKS, LIGHT FIXTURES AND OTHER ITEMS DESIGNATED BY
OWNER. DELIVER TO OWNER ALL ITEMS AS NOTED.
2. DISPOSITION OF MECHANICAL, PLUMBING, GAS, AIR, VAC. PIPING, FIRE
PROTECTION AND ELECTRICAL ITEMS ENCOUNTERED IN AREAS TO BE
DEMOLISHED ARE DESCRIBED IN RESPECTIVE DRAWINGS AND
SPECIFICATIONS. CONTRACTOR SHALL COORDINATE WORK WITH ALL
TRADES.
3. WALLS, DOORS, FIXTURES, ETC. TO BE REMOVED ARE SHOWN DASHED.
SELECTED ITEMS ARE LABELED TO IDENTIFY THE ITEM TO BE REMOVED.
4. LOOSE EQUIPMENT OR FURNITURE NOT IDENTIFIED FOR REMOVAL, RE-USE
OR RELOCATION IS TO BE TURNED OVER TO OWNER.
5. INSTALL SECURE TEMPORARY DUST PARTITIONS TO SEPARATE
DEMOLITION & CONSTRUCTION AREAS FROM OCCUPIED SPACE.
6. REFER TO STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR
ADDITIONAL DEMOLITION ITEMS AND REQUIREMENTS.
7. REMOVE EXISTING FLOOR AND BASE MATERIALS IN AREAS SCHEDULED TO
RECEIVE NEW FLOORING, PREP EXISTING FLOOR TO RECEIVE NEW FINISH.
8. REMOVE EXISTING CEILING MATERIALS AND SUPPORT SYSTEM IN AREAS
SCHEDULED TO RECEIVE NEW CEILING.
9. DEMOLITION CONTRACTOR TO VERIFY LOCATION OF ALL UNDERGROUND
UTILITIES. NOTIFY OWNER AND ARCHITECT OF ANY DISCREPANCIES.
10. REMOVE ALL DEBRIS, RUBBISH, AND OTHER MATERIALS RESULTING FROM
DEMOLITION OPERATIONS IN ACCORDANCE WITH LOCAL, STATE, AND
FEDERAL LAWS FROM THE PROJECT SITE. BURNING OF REMOVED
MATERIALS IS NOT PERMITTED ON PROJECT SITE.
11. COORDINATE WITH OWNER FOR SHUTOFF, CAPPING AND CONTINUATION
OF UTILITY SERVICES AS REQUIRED. DO NOT INTERRUPT EXISTING
UTILITIES SERVING OCCUPIED OR FACILITIES USED.
12. MAKE PORTABLE FIRE EXTINGUISHER AVAILABLE DURING DEMOLITION
PROCESS.
13. USE OF EXPLOSIVES IS NOT PERMITTED.
14. COMPLY WITH ALL GOVERNING REGULATIONS PERTAINING TO
ENVIRONMENTAL PROTECTION (FEDERAL, STATE AND LOCAL).
15. CONTRACTOR TO PATCH AND REPAIR ALL EXISTING FIREPROOFING DURING
INSTALLATION OF NEW WORK AS REQUIRED TO MAINTAIN REQUIRED FIRE
RATING. CONTRACTOR TO USE MATERIALS COMPATIBLE WITH EXISTING
FIREPROOFING FOR PATCH WORK.
16. FIRE CALKING NEEDS TO BE COMPLETED WITHIN 24 HOURS OF MAKING THE
PENETRATION.
A
0.8
A.2A.1 A.8
0.7
D02D02
D13D13
D14 AREA N.I.C.
AREA N.I.C.
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/8
/2
:2
:5
A
M C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A1-01
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL DEMOLITION PLANS
SCALE: 1/8" = 1'-0"A1-01
1 FIRST FLOOR - DEMOLITION PLAN
DEMOLITION GENERAL NOTES
DEMOLITION KEYNOTES
TAG NOTE
D01 INSTALL TEMPORARY PARTITION AND DOOR(S) FOR EXISTING
CORRIDOR WORK. MAINTAIN MINIMUM WIDTH OF 6'-0" EGRESS PATH IN
CORRIDOR. REMOVE PARTITIONS AT COMPLETION OF WORK, PATCH
AND MATCH EXISTING AND NEW FINISHES AS REQUIRED.
D02 REMOVE EXISTING INTERIOR CEILING, INCLUDING CEILING
SUSPENSION SYSTEM, GYPSUM BOARD SOFFITS, AND ALL
ASSOCIATED ITEMS, CUBICLE CEILING TRACKS, LIGHT FIXTURES AND
DIFFUSERS, ETC. COORDINATE WITH MECHANICAL, ELECTRICAL AND
PLUMBING DRAWINGS.
D03 REMOVE EXISTING MASONRY WALL, REINFORCEMENT AND ALL
ATTACHMENTS.
D04 REMOVE EXISTING DOOR, FRAME, HARDWARE AND FRAME
PROTECTION.
D05 REMOVE EXISTING TEMPORARY BARRIERS, DOORS, HARDWARE, AND
ALL ASSOCIATED ITEMS.
D06 EXISTING FURNITURE, FREESTANDING EQUIPMENT, AND ENTOURAGE
REMOVED BY OWNER.
D07 OWNER TO REMOVE SELECT, EXISTING ELECTRICAL WIRING AND
POWER. CONTRACTOR TO COORDINATE AND VERIFY SCOPE OF
OWNER REMOVAL.
D09 TRENCH SLAB AS NECESSARY FOR REROUTING EXISTING
UNDERGROUND ACCESS, PIPING, ELECT. CONDUIT, ETC. COORDINATE
W/ MEP DWGS.
D10 CONCRETE CUTTING AS NECESSARY TO PREP FOR NEW FOOTER
UNDER NEW MASONRY WALL. SEE STRUCTURAL DRAWINGS.
D11 DEMO EXISTING MASONRY JAMB AS REQUIRED FOR NEW 16" BOND
BEAM LINTEL OVER OPENING, W/ (2) #6 TOP AND BOTTOM.
D12 PREP EXISTING SLAB EDGES AT PIT FOR NEW INFILL. SEE
STRUCTURAL DRAWINGS FOR DETAILS. VERIFY DIMENSIONS IN FIELD.
D13 DEMO EXISTING WALLS AS REQUIRED THROUGHOUT FOR NEW MEP
PENETRATIONS. PATCH AND MATCH EXISTING AND NEW FINISHES.
COORDINATE WITH MEP DRAWINGS.
D14 REMOVE EXISTING HALLWAY CEILING SYSTEM AS REQUIRED TO PREP
FOR NEW WALL LOCATIONS. COORDINATE WITH ARCHITECTURAL AND
MEP DRAWINGS, REPLACE EXIST. CEILING OR REPLACE WITH NEW
CEILING SYSTEM TO A "LIKE NEW" CONDITION.
D15 DEMO EXISTING SLAB AS NECESSARY TO PREP FOR NEW PLUMBING
PIPING, FLOOR DRAINS, ETC. COORDINATE WITH MEP DRAWINGS.
SCALE: 1/8" = 1'-0"A1-01
2 FIRST FLOOR - DEMOLITION REFLECTED CEILING PLAN
0.8
A.2A.1 A.8
0.7
1B700
EMS
STORAGE
1B704
ELECTRONICS
(WORK
STATIONS +
STORAGE)
1B712
HTM
STORAGE
1B714
KITCHENETTE
1B713
TOILET
1B715
HOUSE
KEEPING
1B706
BIOMED 02
1B705
BIOMED 03
1B703
RECEIVING/
WORKSPACE
A7-01
A7-01
A7-01
O
O
1B701
CORRIDOR
1B707
CORRIDOR
1B711
CORRIDOR
A7-02
A7-02
1B690
EXISTING
CORRIDOR
1B685
EXISTING
MAILROOM
1B703A
CLEANING
A7-01 13
A7-01 108
A7-02
SIM.
C
CC
CC
C
C
GG
C
G
C
C
C
G
G
D
D
DD G
D
M
G
G
C
C
G
C
A7-02
GG
A7-02
AREA N.I.C.
AREA N.I.C.
A7-02
TYP.
15'-4 3/8"
/2
16'-4 7/8"
10'-3 1/8"
8'-0" 8'-0"
5'-0"
15'-11 3/8"
/8
7'-2 3/8"
/4
/4
15'-10 7/8"
10'-3 1/8"
/4
7'-1 7/8"
G
G
M
G
DD
C
G
G1G1
G
GG
B
.A
B
.A
B
.A
1B702.A
B
.A1
B .A
1B704.A
1B708.A
1B709.A
1B710.A
B
.A
1B713.A
B
.A
1B702.B 1
G1
G G
G1
C
1B702
RECEPTION /
WAITING
1B708
SECTION
CHIEF
1B709
BESS LEAD
1B710
BIOMED 01
1B707A
PRINTER
AREA
A7-01
G
A7-02
TYP.
REPLACED WATER
DAMAGED GYPSUM
BOARD, P&M AROUND
WINDOW, TYP. ALL
WINDOWS IN AREA OF
WORK
A8-01
G
EX-1B610.B
EX-1B650.A
A
0.8
A.2A.1 A.8
0.7
1B712
HTM
STORAGE
1B704
ELECTRONICS
(WORK
STATIONS +
STORAGE)
1B700
EMS
STORAGE
1B702
RECEPTION /
WAITING
1B708
SECTION
CHIEF
1B709
BESS LEAD
1B710
BIOMED 011B706
BIOMED 02
1B705
BIOMED 03
1B703
RECEIVING/
WORKSPACE
1B703A
CLEANING
1B701
CORRIDOR
1B685
EXISTING
MAILROOM
1B690
EXISTING
CORRIDOR
1B711
CORRIDOR
AREA N.I.C.
AREA N.I.C.
9' - 0"
8' - 6"
8' - 6"
9' - 0" 9' - 0"
9' - 0" 9' - 0"
9' - 0"
9' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 6"
1B707
CORRIDOR
1B707A
PRINTER
AREA
7' - 2"
7' - 2"
P+M
A7-02
A7-02
8' - 0"
8' - 0"
9' - 0"
7' - 10"
7' - 2"
7' - 10"
7' - 10"
A7-02
A7-02
WS-1
WS-1
WS-1
WS-1
WS-1
WS-1
1B714
KITCHENETTE
1B713
TOILET
1B715
HOUSE
KEEPING
A7-02
TYP.
8' - 0"
1. ALL EXTERIOR DIMENSIONS TO FACE OF CONCRETE WALL, FACE OF BRICK,
OR FACE OF EXISTING WALL UNLESS NOTED OTHERWISE.
2. ALL MASONRY OPENING DIMENSIONS ARE NOMINAL (NOM.) UNLESS
OTHERWISE NOTED .
3. ALL INTERIOR PARTITION DIMENSIONS TO FACE OF CONCRETE BLOCK,
FACE OF GYPSUM WALL BOARD, OR FACE OF EXISTING WALL UNLESS
OTHERWISE NOTED.
4. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO
COMMENCEMENT OF WORK. WHEN DIMENSIONS AND/OR CONDITIONS AS
INDICATED ON THE DRAWINGS CONFLICT WITH ACTUAL, CONTACT
ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING WITH WORK.
5. NO ATTEMPT HAS BEEN MADE TO SHOW SECTIONS CUTS OR DETAIL
DESIGNATORS AT ALL LOCATIONS WHERE SIMILAR CONDITIONS OCCUR.
6. ANY MATERIAL INDICATIONS OR NOTES SHOWN ON ONE SECTION (USUALLY
THE FIRST SECTION OF EACH SHEET), ELEVATION OR DETAIL ALSO APPLY
TO ALL SIMILAR CONDITIONS ON OTHER SECTIONS, ELEVATIONS, OR
DETAILS.
7. SECTIONS AND DETAILS ARE TYPICAL FOR ALL LOCATIONS AT WHICH
SIMILAR CONDITIONS OCCUR UNLESS NOTED AS APPLICABLE TO A
SPECIFIC LOCATION ONLY.
8. ALL METAL STUDS SHALL BE 3 5/8" ACTUAL UNLESS OTHERWISE NOTED.
BRACE AS REQUIRED FOR LATERAL SUPPORT.
9. WALL THICKNESS INDICATED ON 1/8" AND 1/4" SCALE FLOOR PLANS SHALL
BE CONSTANT FOR THE ENTIRE LENGTH OF WALL, UNLESS OTHERWISE
NOTED.
10. ALL FIRE RATED ASSEMBLIES SHALL EXTEND FROM FLOOR TO STRUCTURE
ABOVE CONTINUOUSLY WITH OPENINGS AROUND STRUCTURE, HVAC,
PLUMBING, ETC. FIRESTOPPED.
11. PROVIDE BEHIND WALL REINFORCING FOR ATTACHMENT OF MILLWORK,
CASEWORK, ACCESSORIES, ETC.
12. NEW OPENINGS FOR MECHANICAL WORK SHALL BE EITHER CORE DRILLED
OR POWER SAWED, NO JACKHAMMERING.
13. P&M DENOTES "PATCH TO MATCH EXISTING CONSTRUCTION AND
FINISHES". ALL PATCHING OF EXISTING MATERIAL SHALL BE DONE WITH THE
MATERIALS AND WORKMANSHIP MATCHING ADJACENT SURFACES.
14. NO ATTEMPT HAS BEEN MADE TO INDICATE ALL AREAS REQUIRING CUTTING
AND PATCHING DUE TO MECHANICAL AND/OR ELECTRICAL WORK.
15. PATCH AND LEVEL FOR NEW FLOORING AT AREAS WHERE EXISTING
FLOORING HAS BEEN REMOVED.
16. PATCH AND MATCH EXISTING WALL, FLOOR, AND CEILING SURFACES FOR
NEW FINISHES AT AREAS WHERE EXISTING WALLS, DOORS, FRAMES,
CASEWORK, COUNTERS, LOCKERS, ETC HAVE BEEN REMOVED OR
SURFACES CUT FOR INSTALLATION OF SERVICES, EQUIPMENT, ETC.
17. PROVIDE BULLNOSE UNITS AT ALL EXPOSED OUTSIDE CORNERS OF
INTERIOR CONCRETE UNIT MASONRY WALLS AND COLUMNS.
18. WHERE ROOM FINISH SCHEDULE INDICATES CERAMIC TILE OR SPECIAL
COATING, GYPSUM BOARD SHALL BE MOISTURE RESISTANT.
1. CENTERLINES OF ROOM SHALL BE STARTING POINT OF CEILING GRID
LAYOUT, UNLESS OTHERWISE NOTED.
2. SPRINKLER HEADS, DOWNLIGHTS, DIFFUSERS, ETC. SHALL BE CENTERED IN
CEILING PANELS IN BOTH DIRECTIONS, UNLESS OTHERWISE INDICATED.
3. DIFFUSERS AND RETURN GRILLES NOT SHOWN IN ROOMS WITHOUT
CEILINGS.
4. ALL CEILING HEIGHTS SHALL BE 8'-6" A.F.F. UNLESS OTHERWISE NOTED.
5. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF EXIT LIGHTS.
6. ALL SOFFITS AND VERTICAL SURFACES CONNECTING CEILINGS AND/OR
SOFFITS AT DIFFERENT ELEVATIONS SHALL BE CONSTRUCTED OF METAL
STUDS/FURRING AND GYPSUM WALLBOARD, UNLESS OTHERWISE
INDICATED.
7. P&M DENOTES PATCH TO MATCH EXISTING CONSTRUCTION AND FINISHES.
ALL PATCHING OF EXISTING MATERIAL SHALL BE DONE WITH MATERIALS
AND WORKMANSHIP MATCHING ADJACENT SURFACES.
8. NO ATTEMPT HAS BEEN MADE TO INDICATE ALL AREAS REQUIRING CUTTING
AND PATCHING DUE TO MECHANICAL AND/OR ELECTRICAL WORK.
7'-10"
SUPPLY AIR DIFFUSER, SEE
MECH. DWGS.
RETURN AIR GRILL, SEE
MECH. DWGS.
RADIANT PANEL, SEE MECH.
DWGS.
CEILING HEIGHT TAG
RECESSED LIGHT FIXTURE
RECESSED LIGHT FIXTURE
LINEAR LIGHT FIXTURE
LINEAR LIGHT FIXTURE
NEW ACOUSTICAL LAY-IN
CEILING
GYPSUM BOARD CEILING OR
SOFFIT
EXISTING ACOUSTICAL LAY-IN
CEILING
RETURN AIR GRILL, SEE
MECH. DWGS.
RETURN AIR GRILL, SEE
MECH. DWGS.
1B103
EXIST.
REPRODUCTION/MAIL
ROOM
1B012
EXIST.
CORRIDOR
1B100B
EXIST. SCAN
ROOM
1B094
EXIST.
OFFICE
1B100A
EXIST.
CONTROL
1B635A
EXIST. AUDIO
BOOTH
1B634A
EXIST. AUDIO
BOOTH
1B636
EXIST.
SOILED
UTILITY
1B610
EXIST.
SHARED
RECEPTION
1B613
EXIST. PSA
1B630
EXIST.
PASSAGE
1B119
EXIST. CHIEF
OFFICE
1B103
EXIST.
REPRODUCTION/MAIL
ROOM
1B012
EXIST.
CORRIDOR
1B100B
EXIST. SCAN
ROOM
1B094
EXIST.
OFFICE
1B100A
EXIST.
CONTROL
1B635A
EXIST. AUDIO
BOOTH
1B634A
EXIST. AUDIO
BOOTH
1B636
EXIST.
SOILED
UTILITY
1B610
EXIST.
SHARED
RECEPTION
1B613
EXIST. PSA
1B630
EXIST.
PASSAGE
1B119
EXIST. CHIEF
OFFICE
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/8
/2
:3
:0
A
M C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A3-01
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL FIRST FLOOR PLAN AND RCP
SCALE: 1/8" = 1'-0"A3-01
1 FIRST FLOOR - PLAN
SCALE: 1/8" = 1'-0"A3-01
2 FIRST FLOOR - REFLECTED CEILING PLAN
FLOOR PLAN GENERAL NOTES REFLECTED CEILING PLAN GENERAL NOTES
REFLECTED CEILING PLAN LEGEND
FLOOR
CPT CARPET TILE
CT PORCELAIN CERAMIC TILE
ERF EPOXY RESINOUS FLOORING
RFT RUBBER FLOOR TILE
WSF VINYL SHEET FLOORING
VT VINYL TILE
ROOM FINISH LEGEND
WALL
CWT CERAMIC WALL TILE
IRWC IMPACT-RESISTANT WALLCOVERING
P PAINT
CG1 CORNER GUARD
CG2 CORNER GUARD
BASE
CT CERAMIC TILE
ERF EPOXY RESINOUS FLOORING INTEGRAL BASE
RB RUBBER BASE
WSF VINYL SHEET FLOORING INTEGRAL BASE
CEILINGS
ACP ACOUSTICAL CEILING PANEL
P PAINT
GENERAL NOTES
1. EXP DENOTES EXPOSED STRUCTURE.
2. SEE REFLECTED CEILING PLAN FOR CEILING
HEIGHTS.
3. SEE DRAWINGS FOR LOCATION AND ELEVATIONS OF
ARCHITECTURAL WOODWORK.
4. GYPSUM BOARD SOFFITS: UNLESS NOTED,
HORIZONTAL SURFACES SHALL BE P-1 & VERTICAL
SURFACE SHALL BE SAME AS ANY CONNECTING WALL
SURFACE. IF NO WALL SURFACE OCCURS AT SAME
PLANE, VERTICAL SURFACE SHALL BE P-1. SEE
REFLECTED CEILING PLAN FOR SOFFIT HEIGHT.
5. PAINT ALL NEW METAL DOORS AND DOOR FRAMES
(INCLUDING VISION PANELS IN DOORS) UNLESS NOTED.
SEE PAINT SPECIFICATIONS FOR FINISH.
6. PAINT ALL NEW METAL COVERPLATES, ETC. UNLESS
NOTED. SEE PAINT SPECIFICATIONS FOR FINISH.
7. P&M DENOTES PATCH AND MATCH TO EXISTING
ADJACENT MATERIALS, FINISHES AND COLORS
SUBSTRATE
C CONCRETE
CBB CEMENTITIOUS BACKER BOARD
CMU CONCRETE MASONRY UNITS
GWB GYPSUM BOARD
ARCHITECTURAL WOODWORK
PL PLASTIC LAMINATE
SSM SOLID SURFACE MATERIAL
SCHEDULE NOTES
1. WINDOW SILL FINISH SHALL BE SSM-1.
2. PAINT INTERIOR WINDOW FRAMES P-4.
3. SEE DRAWINGS FOR LOCATION OF CORNER
GUARDS AND IMPACT RESISTANT WALL COVERING.
4. REFER TO FLOOR PATTERN PLANS FOR FLOOR
PATTERN INFORMATION AND DIRECTION.
5. SEE DRAWINGS FOR WALL ELEVATIONS
A
0.8
A.2A.1 A.8
0.7
1B700
EMS
STORAGE
1B704
ELECTRONICS
(WORK
STATIONS +
STORAGE)
1B708
SECTION
CHIEF
1B709
BESS LEAD
1B712
HTM
STORAGE
1B714
KITCHENETTE
1B713
TOILET
1B702
RECEPTION /
WAITING
1B715
HOUSE
KEEPING
1B710
BIOMED 01
1B706
BIOMED 02
1B705
BIOMED 03
1B703
RECEIVING/
WORKSPACE
1B707A
PRINTER
AREA
1B701
CORRIDOR
1B707
CORRIDOR
1B711
CORRIDOR
1B690
EXISTING
CORRIDOR
1B685
EXISTING
MAILROOM
1B703A
CLEANING
CG1 CG1
CG1
CG1
CG1CG1
CG1
CG1
P-3/A
P-2/A P-2/A
P-2/A
P-2/A
P-2/A
CG1
P-3/A
IRWC-1
CG1
IRWC-1
P-3/A
P-3/A
P-3/A
P-3/A
IRWC-1
AREA N.I.C.
AREA N.I.C.
IRWC-1
IRWC-1
IRWC-1
P+M
ERF-1
ERF-1
ERF-1
ERF-1
ERF-1
CPT-1
CPT-1
CPT-1CPT-1
CPT-1
CPT-1
CPT-1
IRWC-1
VT-1
CT-1
WSF-1
CG1
CG1CG1
P-3/A
P-3/A
P-3/A
CG1
IRWC-1
IRWC-1
IRWC-1
IRWC-1
CPT-1
CT-1:INSTALL AS SHOWN ON DRAWINGS
VT-1
WSF-1
ERF-1
3 5/8" STUDS WITH
5/8" GYP. BD.
STAINLESS STEEL
CORNER GUARD
ATTACH PER
MANUFACTURER'S
ADHESIVE STANDARD
CG1
2"
CG2
PART. TYPE
SEE
3 5/8" STUDS WITH
5/8" GYP. BD.
STAINLESS STEEL
CORNER GUARD
ATTACH PER
MANUFACTURER'S
ADHESIVE STANDARD
1B103
EXIST.
REPRODUCTION/MAIL
ROOM
1B012
EXIST.
CORRIDOR
1B100B
EXIST. SCAN
ROOM
1B094
EXIST.
OFFICE
1B100A
EXIST.
CONTROL
1B635A
EXIST. AUDIO
BOOTH
1B634A
EXIST. AUDIO
BOOTH
1B636
EXIST.
SOILED
UTILITY
1B610
EXIST.
SHARED
RECEPTION
1B613
EXIST. PSA
1B630
EXIST.
PASSAGE
1B119
EXIST. CHIEF
OFFICE
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/2
/2
:1
:2
P M
C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A3-02
757-20-206
JVV AR
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL ROOM FINISH PLAN AND SCHEDULE
ROOM FINISH SCHEDULE
ROOM FLOOR BASE WALLS CEILING ARCH.
WOODWORK
WINDOW
SILL NOTESNUMBER NAME SUBSTR. FINISH SUBSTR. FINISH SUBSTR. NORTH SOUTH EAST WEST SUBSTR. FINISH
FIRST FLOOR
1B685 EXISTING MAILROOM C ETR ETR ETR ETR ETR ETR ETR ETR ETR ETR
1B690 EXISTING CORRIDOR C P+M CMU P+M CMU P+M P+M P+M P+M - P+M SEE FINISH PLAN AND RCP
1B700 EMS STORAGE C ERF-1 CMU/GWB ERF-1 CMU P-1/C/IRWC-1* P-1/A/IRWC-1* P-1/C/IRWC-1* P-1/A/IRWC-1* - ACP-1 *IRWC-1 @3'-8"ABOVE WALL BASE
1B701 CORRIDOR C ERF-1 GWB ERF-1 GWB P-1/A/IRWC-1* P-1/A/IRWC-1* P-1/A/IRWC-1* P-1/A/IRWC-1* - ACP-1 *IRWC-1 @3'-8"ABOVE WALL BASE
1B702 RECEPTION / WAITING C CPT-1 GWB RB-1 GWB P-1/A P-3/A P-1/A P-1/A - ACP-1
1B703 RECEIVING/ WORKSPACE C ERF-1 GWB ERF-1 GWB P-1/A P-1/A P-1/A P-3/A* - ACP-1 SSM-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATIONS
1B703A CLEANING C ERF-1 GWB ERF-1 GWB P-1/A P-3/A* P-3/A* P-1/A - ACP-1 SSM-1/PL-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATION
1B704 ELECTRONICS (WORK STATIONS + STORAGE) C ERF-1 GWB ERF-1 GWB P-1/B P-1/B P-1/B P-1/B - ACP-1
1B705 BIOMED 03 C CPT-1 GWB RB-1 GWB P-1/A P-1/A P-1/A P-2/A - ACP-1
1B706 BIOMED 02 C CPT-1 GWB RB-1 GWB P-1/A P-1/A P-1/A P-2/A - ACP-1
1B707 CORRIDOR C CPT-1 GWB RB-1 GWB P-1/A - P-1/A P-1/A - ACP-1
1B707A PRINTER AREA C CPT-1 GWB RB-1 GWB P-1/A - P-1/A P-1/A - ACP-1
1B708 SECTION CHIEF C CPT-1 GWB RB-1 GWB P-1/A P-1/A P-1/A P-2/A - ACP-1 SSM-1
1B709 BESS LEAD C CPT-1 GWB RB-1 GWB P-2/A P-1/A P-1/A P-1/A - ACP-1 SSM-1
1B710 BIOMED 01 C CPT-1 GWB RB-1 GWB P-1/A P-2/A P-1/A P-1/A - ACP-1
1B711 CORRIDOR C ERF-1 GWB ERF-1 GWB P-3/A* P-3/A* P-1/A P-3/A* - ACP-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATION
1B712 HTM STORAGE C ERF-1 GWB ERF-1 GWB P-1/B P-1/B P-1/B P-1/B - ACP-1
1B713 TOILET C CT-1 CBB -- GWB P-1/B/CWT-1 P-1/B/CWT-1 P-1B/CWT-1 P-1/B/CWT-1 - ACP-1 *SEE INTERIOR ELEVATIONS
1B714 KITCHENETTE C VT-1 GWB RB-1 GWB P-1/A P-1/A P-1A P-1/A - ACP-1 SSM-1/PL-1
1B715 HOUSE KEEPING C WSF-1 GWB WSF-1 GWB P-1/B/IRWC-1* P-1/B/IRWC-1* P-1/B/IRWC-1* P-1/B/IRWC-1* - ACP-2 *IRWC-1 @3'-8"ABOVE WALL BASE
SCALE: 1/8" = 1'-0"A3-02
1 FIRST FLOOR - FINISH PLAN
PATTERN LEGEND
CORNER GUARDS
(DEDUCT ALTERNATE) ROOM FINISH SCHEDULE
ROOM FLOOR BASE WALLS CEILING ARCH.
WOODWORK
WINDOW
SILL NOTESNUMBER NAME SUBSTR. FINISH SUBSTR. FINISH SUBSTR. NORTH SOUTH EAST WEST SUBSTR. FINISH
FIRST FLOOR
1B700 EMS STORAGE C VT-1 CMU/GWB RB-1 CMU P-1/C/IRWC-1* P-1/A/IRWC-1* P-1/C/IRWC-1* P-1/A/IRWC-1* - ACP-1 *IRWC-1 @3'-8"ABOVE WALL BASE
1B701 CORRIDOR C VT-1 GWB RB-1 GWB P-1/A/IRWC-1* P-1/A/IRWC-1* P-1/A/IRWC-1* P-1/A/IRWC-1* - ACP-1 *IRWC-1 @3'-8"ABOVE WALL BASE
1B703 RECEIVING/ WORKSPACE C VT-1 GWB RB-1 GWB P-1/A P-1/A P-1/A P-3/A* - ACP-1 SSM-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATIONS
1B703A CLEANING C VT-1 GWB RB-1 GWB P-1/A P-3/A* P-3/A* P-1/A - ACP-1 SSM-1/PL-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATION
1B704 ELECTRONICS (WORK STATIONS + STORAGE) C VT-1 GWB RB-1 GWB P-1/B P-1/B P-1/B P-1/B - ACP-1
1B711 CORRIDOR C VT-1 GWB RB-1 GWB P-3/A* P-3/A* P-1/A P-3/A* - ACP-1 *SEE FINISH PLAN FOR ACCENT WALL
LOCATION
1B712 HTM STORAGE C VT-1 GWB RB-1 GWB P-1/B P-1/B P-1/B P-1/B - ACP-1
0.8
A.2A.1 A.8
0.7
EXISTING
ELECTRICAL
PANEL/BOX
01 09
1B690
EXISTING
CORRIDOR
1B685
EXISTING
MAILROOM
AREA N.I.C.
AREA N.I.C.
1B700
EMS
STORAGE
1B704
ELECTRONICS
(WORK
STATIONS +
STORAGE)
1B712
HTM
STORAGE
1B714
KITCHENETTE
1B713
TOILET
1B715
HOUSE
KEEPING
1B703
RECEIVING/
WORKSPACE
1B701
CORRIDOR
1B707
CORRIDOR
1B711
CORRIDOR
1B703A
CLEANING
1B702
RECEPTION /
WAITING
1B708
SECTION
CHIEF
1B709
BESS LEAD
1B710
BIOMED 01
1B707A
PRINTER
AREA
1B706
BIOMED 02
1B705
BIOMED 03
M
IN
'-1
/4
15 08 08
08 08
01 09
VETERANS ADMIN. FURNISHED, CONTRACTOR INSTALLED
VETERANS ADMIN. FURNISHED AND INSTALLED
( V C )
( V V )
1. EQUIPMENT SHOWN FOR REFERENCE ONLY, CONTRACTOR SHALL COORDINATE POWER
AND DATA LOCATIONS WITH FINAL VA PROVIDED FURNITURE PRIOR TO INSTALL.
2. CONTRACTOR TO PROVIDE BLOCKING FOR EQUIPMENT WHERE INDICATED, COORDINATE
ALL BLOCKING QUANTITIES & LOCATIONS FOR EQUIPMENT WITH OWNER.
1B103
EXIST.
REPRODUCTION/MAIL
ROOM
1B012
EXIST.
CORRIDOR
1B100B
EXIST. SCAN
ROOM
1B094
EXIST.
OFFICE
1B100A
EXIST.
CONTROL
1B635A
EXIST. AUDIO
BOOTH
1B634A
EXIST. AUDIO
BOOTH
1B636
EXIST.
SOILED
UTILITY
1B610
EXIST.
SHARED
RECEPTION
1B613
EXIST. PSA
1B630
EXIST.
PASSAGE
1B119
EXIST. CHIEF
OFFICE
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/2
/2
:1
:2
P M
C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A3-03
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL FIRST FLOOR FURNITURE AND
EQUIPMENT PLAN
SCALE: 1/8" = 1'-0"A3-03
1 FIRST FLOOR - FFE PLAN
VA STANDARD ABBREVIATIONS
EQUIPMENT GENERAL NOTES
FURNITURE SCHEDULE
FURN. ID DESCRIPTION
FURNISH /
INSTALLED BLOCKING
01 TASK CHAIR ( V V ) NO
02 GUEST CHAIR ( V V ) NO
03 WORKBENCH (36" X 72') ( V V ) NO
04 MONITOR AND MOUNT ( V V ) YES. COORDINATE LOCATIONS WITH VA MOUNTING BRACKET
05 REFRIGERATOR ( V V ) NO
06 CONFERENCE TABLE ( V V ) NO
07 MULTI-FUNCTION PRINTER ( V V ) NO
08 FILE ( V V ) NO
09 TABLE DESK (30" X 48") ( V V ) NO
10 TABLE DESK (30" X 72") ( V V ) NO
11 TABLE DESK (24" X 78") ( V V ) NO
12 TABLE STORAGE (24" X 36") ( V V ) NO
13 TABLE STORAGE (24" X 48") ( V V ) NO
14 TABLE STORAGE (30" X 72") ( V V ) NO
15 TABLE STORAGE (24" X 78") ( V V ) NO
16 TABLE STORAGE (30" X 84") ( V V ) NO
17 TABLE DESK (30" X 96") ( V V ) NO
18 TABLE DESK (30" X 84") ( V V ) NO
CWT-1
GB-2
CL
SD-1
FM-1
TCD-1
TRIM-1
TRIM-2
2'-10"
CWT-1
GB-3
GB-1
TTD-1
SND-1
TRIM-2
TRIM-1
CWT-1
CL
4'-3"
TRIM-2
TRIM-1
TD-1
PTD-2
CWT-1
TRIM-2
TRIM-1
SSM-1 COUNTERTOP AND
BACKSPLASH
BASE CABINETS - PL-1
WALL CABINET - PL-1
FILLER
(2) EQ.
2'-11"
(3) EQ.
4'-3"
(2) EQ.
2'-11"FILLER
A8-02
A8-02
A8-02
A8-02
HOLD
3'-0"
PAINTED SOFFIT
PTD-2
A7-01
1B713
TOILET
8'-10"
GB-1
GB-3
GB-2
IRWC-1
SCHEDULED WALL
BASE, TYP.
D1A-BP
D1A/F1-BP
IRWC-1
SCHEDULED WALL
BASE, TYP.
D1A/F1-BP
A7-02
IRWC-1
SCHEDULED WALL
BASE, TYP.
IRWC-1
SCHEDULED WALL
BASE, TYP.
A7-02
TYP.
IRWC-1
SCHEDULED WALL
BASE, TYP.
IRWC-1
SCHEDULED WALL
BASE, TYP.
SCHEDULED WALL BASE, TYP.
IRWC-1
D1A/F1-BP
IRWC-1
SCHEDULED WALL
BASE, TYP.
BASE CABINETS - PL-1
SSM-1 COUNTERTOP AND
BACKSPLASH
FILLER
HOLD
3'-0"4'-1"
A8-02
A8-02
MBH-1
SCHEDULED WALL
BASE, TYP.
IRWC-1
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/8
/2
:3
:0
P
M C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A7-01
757-20-206
JVV AR
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
ENLARGED PLANS AND INTERIOR
ELEVATIONS
SCALE: 1/4" = 1'-0"A7-01
2 1B713 TOILET - SOUTH
SCALE: 1/4" = 1'-0"A7-01
5 1B713 TOILET - WEST
SCALE: 1/4" = 1'-0"A7-01
3 1B713 TOILET - NORTH
SCALE: 1/4" = 1'-0"A7-01
4 1B713 TOILET - EAST
SCALE: 1/4" = 1'-0"A7-01
6 1B714 KITCHENETTE - NORTH
SCALE: 1/4" = 1'-0"A7-01
1 1B713 - TOILET FLOOR PLAN
SCALE: 1/4" = 1'-0"A7-01
8 1B701 CORRIDOR - WEST
SCALE: 1/4" = 1'-0"A7-01
10 1B701 CORRIDOR - EAST
SCALE: 1/4" = 1'-0"A7-01
13 1B700 EMS STORAGE - EAST
SCALE: 1/4" = 1'-0"A7-01
12 1B700 EMS STORAGE - SOUTH
SCALE: 1/4" = 1'-0"A7-01
14 1B700 EMS STORAGE - WEST
SCALE: 1/4" = 1'-0"A7-01
15 1B700 EMS STORAGE - NORTH
SCALE: 1/4" = 1'-0"A7-01
9 1B701 CORRIDOR - NORTH
SCALE: 1/4" = 1'-0"A7-01
11 1B701 CORRIDOR - SOUTH
SCALE: 1/4" = 1'-0"A7-01
7 1B703A CLEANING - SOUTH
SCALE: 1/4" = 1'-0"A7-01
16 1B715 HOUSE KEEPING
LEVEL 1
0' - 0"
A7-02
A8-01
A8-01
8" CMU
6" CMU COURSE
WIREMOLD, REFER
TO ELECTRICAL
DWGS.
SHIM AS REQUIRED TO
BRING WIREMOLD FLUSH
TO FACE OF WALL
METAL TRIM, ALL
SIDES OF OPENING
/8
SCHEDULED PARTITION
IMPACT RESISTANT
WALL COVERING
SEALANT ALL SIDES REBAR, SEE STRUCTURAL DETAILS
LEVEL 1
0' - 0"
A7-02
A7-02
EXIST. INSULATED METAL
PANEL
EXIST. INSULATED
GLAZING UNIT
EXIST. INTEGRATED
WINDOW ASSEMBLY
EXIST. WALL
CONSTRUCTION
SOLID SURFACE
WINDOW SILL
EXIST. 5/8" GYP
BOARD
3/4" PLYWOOD
SUBSTRATE
/2
1"
A.2
4'-4"
/8
/8
/8
EXISTING COLUMN AND
FIREPROOFING
CG1
CG1
RECESSED F.E.C. SEE
SPECIFICATIONS3
A7-02
/8
CG1
SCHEDULED PARTITION, TYP.
A.8
2'-2"
CG1
CG1
EXISTING COLUMN AND
FIREPROOFING
SCHEDULED PARTITION,
TYP.
EXISTING PIPE AND
COVERING
EXISTING EXTERIOR
CONSTRUCTION
0.8
A.2
3'-0"
3' -0
EXISTING COLUMN AND
FIREPROOFING
SCHEDULED PARTITIONS,
TYP.
EXISTING EXTERIOR
CONSTRUCTION
NOTE: SEE RCP FOR CEILING HEIGHTS
M
IN
M
IN
PART.
SEE
ACOUSTICAL CEILING
PANEL
ACOUSTICAL
CEILING PANEL
ALIGN WITH
EDGE OF
WALL
BEYOND
GYP. BULKHEAD TO
BE 2" BELOW LOWEST
ADJACENT CEILING
NOTE: SEE RCP FOR CEILING HEIGHTS
SEE RCP
5/8" GYP. BD. ON
SUSPENDED
METAL STUDS
CEILING AS SCHEDULED
5/8" GYP. BD. ON
SUSPENDED
METAL STUDS
HORIZONTAL BRACING, TYP.
PARTITION AS
SCHEDULED, MAINTAIN
SMOKE/FIRE RATING
WHERE REQUIRED
NOTE: SEE RCP FOR CEILING HEIGHTS
M
IN
PART.
SEE
ACOUSTICAL CEILING
PANEL
ACOUSTICAL
CEILING PANEL
ALIGN WITH
EDGE OF
WALL
BEYOND
PLAN
CONTINUOUS
SEALANT ALL SIDE,
TYP.
SECTION
FULL RECESSED
CABINET
CONTINUOUS SEALANT
ALL SIDES
CONTINUOUS SEALANT
ALL SIDES
METAL STUD FRAMING
METAL STUD FRAMING
FIRE EXTINGUISHER
CABINET (F.E.C.)
P L A
N S
E E
EXIST. INSULATED
METAL PANEL
EXIST. INSULATED
GLAZING UNIT
EXIST. INTEGRATED
WINDOW ASSEMBLY
EXIST. WALL CONSTRUCTION
TYP. FOR ALL WS-1
ROLLER SHADE
AND BRACKETS.
MOUNT PER
MANUFACTURER'S
STANDARDS.
SUSPENDED
ACOUSTICAL TILE
CEILING
V.I.F.
7 1/4"
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/2
/2
:1
:3
P M
C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A7-02
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
WALL SECTIONS AND PLAN DETAILS
SCALE: 3/8" = 1'-0"A7-02
1 EMS WALL SECTION - EAST
SCALE: 1 1/2" = 1'-0"A7-02
4 TYP. WIREMOLD SECTION - EMS
SCALE: 3/8" = 1'-0"A7-02
2 EXTERIOR WINDOW SECTION
SCALE: 1 1/2" = 1'-0"A7-02
5 WINDOW SILL SECTION
SCALE: 1 1/2" = 1'-0"A7-02
10 PLAN DETAIL - TYP. COLUMN DETAIL
SCALE: 1 1/2" = 1'-0"A7-02
11 PLAN DETAIL - EXTERIOR COLUMN
SCALE: 1 1/2" = 1'-0"A7-02
12 PLAN DETAIL - CLEANING ROOM COLUMN
SCALE: 1 1/2" = 1'-0"A7-02
6 GYPSUM BULKHEAD
SCALE: 1 1/2" = 1'-0"A7-02
8 GYPSUM CEILING
SCALE: 1 1/2" = 1'-0"A7-02
7 GYPSUM - LOW PROFILE
SCALE: 1" = 1'-0"A7-02
3 FEC CABINET - FULLY RECESSED
SCALE: 1 1/2" = 1'-0"A7-02
9 WINDOW SOFFIT SECTION
PARTITION TYPE 'C'
NON-RATED
(1) LAYER OF 5/8" GYP. BD. ON EACH
SIDE OF 3 5/8" METAL STUD @ 16"O.C.
PARTITION AT FLOOR
INFILL VOID AREAS
W/ SOUND
BLANKET
CONTINUOUS
ACOUSTICAL
SEALANT
CONTINUOUS
RUNNER TRACK
CEILING
STRAP BRIDGING
STRUCTURE ABOVE
EXTEND GYP.
BD. 6" ABOVE
CEILING
DEFLECTION JOINT
CONT. RUNNER TRACK
8" LIGHTWEIGHT CMU
FULL HEIGHT W/ MTL.
HORIZ. WALL REINF.
EVERY OTHER COURSE
STRUCTURE ABOVE
STRUCTURE ABOVE
10 GA. METAL PLATE
8"L AT 4'-0" O.C.
WIDTH MAY VARY
DEPENDING ON
FLUTE LOCATIONS
STRUCTURE ABOVE
COMPRESSIBLE MATERIAL
COMPRESSIBLE MATERIAL
BEYOND AT EACH FLUTE
EXISTING CONSTR.
OR NEW MASONRY
CONSTR. MAY OCCUR
(SEE PLANS FOR
SPECIFIC
CONDITIONS)
SOUND ATTENUATION
BLANKET
5X3X3/8" X 8" LLV (TYP.
EACH SIDE OF WALL)
5X3X3/8" X 8" LLV AT 4'-0"
MAX. WITH (2) - 1/2" DIA.
EXP. ANCHORS WITH MIN.
3 1/2" EMBED. (DO NOT CUT
REINF.) (TYP. EACH SIDE
OF WALL)
FIRESTOP JOINT BETWEEN
TOP OF FIRE-RATED
PARTITION AND STRUCTURE
ABOVE W/ U.L. OR W.H.I.
APPROVED JOINT FIRESTOP
SYSTEM MATCHING WALL
RATING.
HEAD OF PARTITION
METAL DECK PERPENDICULAR TO FLUTES
HEAD OF PARTITION
METAL DECK PARALLEL TO FLUTES
HEAD OF PARTITION
CONCRETE SLAB
4 7/8"
SOUND
ATTENUATION
BLANKET
CONTINUOUS
ACOUSTICAL SEALANT
EACH SIDE
STRUCTURE ABOVE
SOUND
ATTENUATION
BLANKET
CONTINUOUS RUNNER
TRACK
CONTINUOUS
RUNNER TRACK
DEFLECTION JOINT
STRUCTURE ABOVE
CONTINUOUS
RUNNER TRACK
DEFLECTION JOINT
SOUND
ATTENUATION
BLANKET
DEFLECTION JOINT
14 GA. STEEL
PLATE AS
REQUIRED
CONTINUOUS
ACOUSTICAL SEALANT
EACH SIDE
STRUCTURE ABOVE
CONTINUOUS
RUNNER TRACK
SOUND
ATTENUATION
BLANKET
4 1/4"
EXISTING CONSTR.
OR NEW MASONRY
CONSTR. MAY OCCUR
(SEE PLANS FOR
SPECIFIC
CONDITIONS)
8" LIGHTWEIGHT CMU
FULL HEIGHT W/ MTL.
HORIZ. WALL REINF.
EVERY OTHER COURSE
8" LIGHTWEIGHT CMU
FULL HEIGHT W/ MTL.
HORIZ. WALL REINF.
EVERY OTHER COURSE
FIRESTOP JOINT BETWEEN
TOP OF FIRE-RATED
PARTITION AND
STRUCTURE ABOVE W/ U.L.
OR W.H.I. APPROVED JOINT
FIRESTOP SYSTEM
MATCHING WALL RATING.
5X3X3/8" X 8" LLV (TYP.
EACH SIDE OF WALL)
FIRESTOP JOINT BETWEEN
TOP OF FIRE-RATED
PARTITION AND
STRUCTURE ABOVE W/ U.L.
OR W.H.I. APPROVED JOINT
FIRESTOP SYSTEM
MATCHING WALL RATING.
8" LIGHTWEIGHT CMU
FULL HEIGHT W/ MTL.
HORIZ. WALL REINF.
EVERY OTHER COURSE
PARTITION TYPE 'G'
NON-RATED
(1) LAYER OF 5/8" GYP. BD. ON ONE SIDE
OF 3 5/8" METAL STUD FURRING @ 16"
O.C.
ONE & TWO HOUR RATED (U.L. #U905)
THREE HOUR RATED (U.L. #U904)
PARTITION TYPE 'M'
PARTITION AT FLOOR PARTITION AT FLOOR
HEAD OF PARTITION
METAL DECK PARALLEL TO FLUTESPARTITION AT CEILING
HEAD OF PARTITION HEAD OF PARTITION
METAL DECK PERPENDICULAR TO FLUTES
HEAD OF PARTITION
CONCRETE SLAB
SAME AS TYPE 'G' WITH 2 1/2" METAL STUDS
PARTITION TYPE 'G1'
SAME AS TYPE 'C' WITH 6" METAL STUDS
PARTITION TYPE 'C1'
8" LIGHTWEIGHT CMU
W/ MTL. HORIZ. WALL
REINF. EVERY OTHER
COURSE. SEE SHEET
A8-01
PARTITION TYPE 'O'
PARTITION AT FLOOR
CONTINUOUS RUNNER
TRACK; SEAL W/ MASTIC
CORRIDOR SIDE
7 1/4"
SOUND
ATTENUATION
BLANKET
CONTINUOUS
ACOUSTICAL SEALANT
EACH SIDE
STRUCTURE ABOVE
DEFLECTION JOINT
CEILING SYSTEM
CONT. RUNNER TRACK
STRUCTURE ABOVE
HEAD OF PARTITION
METAL DECK PERPENDICULAR TO FLUTES
HEAD OF PARTITION
METAL DECK PARALLEL TO FLUTES
CONTINUOUS
RUNNER TRACK
SOUND
ATTENUATION
BLANKET
SOUND
ATTENUATION
BLANKET
SOUND
ATTENUATION
BLANKET
7 5/8"
PARTITION AT CEILING
8" LIGHTWEIGHT CMU UP TO 9' 4" A.F.F. WITH
NON RATED SMOKE PARTITION ABOVE.
(1) LAYER OF 5/8" GYP. BD. ON EACH SIDE OF
6" METAL STUDS @ 16" O.C.
PROVIDE STUD
KICKERS TO
MATCH WALL
STUDS @ 48" O.C.
FASTEN TO
FLOOR ABOVE
PROVIDE STUD
KICKERS TO
MATCH WALL
STUDS @ 48" O.C.
FASTEN TO
FLOOR ABOVE
SMOKESTOP ALL VOID
AREAS TIGHT TO
UNDERSIDE OF
STRUCTURE W/ SAFING
SMOKESTOP ALL VOID
AREAS TIGHT TO
UNDERSIDE OF
STRUCTURE W/ SAFING
DEFLECTION JOINT
NON-RATED SMOKE PARTITION
(1) LAYER OF 5/8" GYP. BD. ON EACH SIDE
OF 3 5/8" METAL STUDS @ 16" O.C.
PARTITION TYPE 'D'
PARTITION AT FLOOR
PARTITION AT CEILING
CEILING SYSTEM
14 GA. STL PLATE AS REQ
CORRIDOR SIDE
SMOKESTOP ALL VOID
AREAS TIGHT TO
UNDERSIDE OF
STRUCTURE W/ SAFING
HEAD OF PARTITION
METAL DECK PERPENDICULAR
TO FLUTES
HEAD OF PARTITION
METAL DECK PARALLEL TO
FLUTES
4 7/8"
EXTEND GYP. BD. 6"
ABOVE CEILING,
THIS SIDE
SAME AS TYPE 'D' WITH 6" METAL STUDS
PARTITION TYPE 'D1'
CONTINUOUS
ACOUSTICAL SEALANT
EACH SIDE
CONTINUOUS RUNNER
TRACK
SOUND ATTENUATION
BLANKET
SOUND ATTENUATION
BLANKET
SOUND ATTENUATION
BLANKET
CONTINUOUS
RUNNER TRACK
STRUCTURE ABOVE
CONTINUOUS
ACOUSTICAL SEALANT
EACH SIDE
DEFLECTION JOINT
SOUND ATTENUATION
BLANKET
CONTINUOUS
RUNNER TRACK
STRUCTURE ABOVE
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORDCONSULTANT
NORTH
ARCHITECTURAL PROJECT
# 18910
KEY PLAN
FARID MEHR, PE
7850 Freeway Circle Cleveland, OH 44130
440.243.2000 cblhdesign.com
/8
/2
:2
:0
A
M C
R e v it L o c a l\
R
V
A C o lu m b u s C o n s tr u c te d B io m e d
C e n tr a l_ B
H e n n ie s .r v t
A7-03
757-20-206
JVV LS
CONSTRUCT BIOMED SPACE
03/26/2021
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTITION TYPES
DOOR ELEV. A DOOR ELEV. B DOOR ELEV. C
EQ. EQ.
FLUSH FLUSH FLUSH
1' - 0"
ASTRAGAL
FRAME TYPE 1
(GYP. BD.)
/2
/2
3/8"
/1
/1
F R
A M
E W
ID
T
H
S E
E S
C H
E D
F
O R
FRAME TYPE 2
(HEAD)
/1
F R
A M
E W
ID
T
H
S E
E S
C H
E D
F
O R
2" @ JAMB
4" 5/8"
/2
/2
/1
/2
5/8"2"
F R
A M
E W
ID
T
H
S E
E S
C H
E D
F
O R
/2
/1
/1
FRAME TYPE 2
(JAMB)
5/8"2"
TYPES
SEE PARTITION
METAL STUDS AT
12" O.C. ABOVE
HEAD ONLY
SEE SCHEDULE
FOR FRAME
WIDTH AND TYPE
SEE PLAN FOR
DOOR LOCATION
HEAD DETAIL 1 HEAD DETAIL 2
SEE FLOOR PLANS
WALL THICK.
SEALANT ALL SIDES, TYP.
LINTEL ANGLES AS
REQUIRED, SEE
LINTEL SCHEDULE
CONCRETE BLOCK
SEE SCHEDULE
FOR FRAME
WIDTH AND TYPE
/4
T Y
P E
S
S E
E P
A R
T
IT
IO
N
SEALANT ALL SIDES, TYP.
DOUBLE STUD AT JAMB,
TYP.
SEE SCHEDULE
FOR FRAME WIDTH
AND TYPE
STUD
ANCHORS
JAMB DETAIL 1 JAMB DETAIL 2
SEALANT ALL
SIDES, TYP.
CONCRETE BLOCK
MASONRY ANCHORS
SEE SCHEDULE
FOR FRAME
WIDTH AND TYPE
S E
E F
L O
O R
P L
A N
S
W A
L L
T H
IC
K
1/4"
U.O.N.
4"
WHEN HINGE JAMB IS CLOSEST TO WALL
FRAME ELEV. A
SEE SCHED.
2" 2"
S E
E S
C H
E D
S E
E S
C H
E D
2"
SEE SCHED.
2"
FRAME ELEV. B
MAINTAIN EXISTING VAPOR
BARRIER, DO NOT DAMAGE. FOLD
BACK FOR EXCAVATION
EXISTING SLAB ON
GRADE, FIELD VERIFY
CONDITIONS
1'-6"
(4) #5 CONTINUOUS REBAR
#5 REBAR AT 48" O.C. VERTICAL
REINFORCING CENTERED IN CMU
INSTALL #5x1’-4” DOWELS
@ 2’ ON CENTER USING
HILTI HY200 INJECTION
ADHESIVE SYSTEM.
MINIMUM EMBEDMENT 4”
INTO EXISTING SLAB
FLOOR TRENCH REPLACE AND COMPACT
GRANULAR SLAB BASE
NEW VAPOR BARRIER, LAP OVER
EXISTING VAPOR BARRIER AND SEAL
JOINTS WITH TAPE
MAINTAIN EXISTING VAPOR
BARRIER, DO NOT DAMAGE. FOLD
BACK FOR EXCAVATION
#4 AT 16"…