This document provides information for a federal construction contract opportunity to construct biomedical space for the Chalmers P. Wylie Veterans Affairs Ambulatory Care Center in Columbus, Ohio. The project scope involves building out existing shell space to consolidate all Health Technology Services and Biomedical storage and staff into one location, with additions for an electronics shop and storage space for Environmental Management Systems equipment. The project value is between $500,000 and $1 million. This solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and has a 240-day period of performance. Questions regarding this opportunity must be submitted in writing by the specified deadline. The document also contains pre-award questions and answers relating to technical specifications.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7.
ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF
PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE
OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERE
D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED
STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF
CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF
SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) -09 -2021 757-20-206 36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 VA Healthcare System 2780 Airport Dr, Suite 340 Columbus OH 43219 36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 VA Healthcare System 2780 Airport Dr, Suite 340 Columbus OH 43219 To all Offerors/Bidders
36C25021B0056 08-09-2021
X X X
X The purpose of this solicitation amendment is to:
1) Provide the pre-award RFI questions & answers to all interested parties. Please see the continuation pages of this document for details.
All other terms & conditions remain unchanged and in full effect.
CONTINUATION PAGE
CONTINUATION PAGES
CONSTRUCT BIOMED SPACE FOR THE CHALMERS P. WYLIE VETERANS AFFAIRS AMBULATORY CARE CENTER (VAACC)—COLUMBUS, OH
PROJECT NUMBER: 757-20-206
QUESTIONS AND RESPONSES TO INVITATION FOR BID (IFB) NUMBER
36C25021B0056
IFB AMENDMENT NUMBER 00004
1. QUESTION – On Print A1-01 in the general notes #1: it indicates to salvage and return items to owner, is the Wier Mesh in the walls that are being demoed one of those items to be considered?
Response: No, the wire mesh in the temporary gate/walls do not need to be salvaged for return to the VA. The Contractor can dispose or salvage the wire mesh.
2. QUESTION – On print A3-02 Room finish legend-schedule notes Note #2 Indicates to paint interior window frames , Please confirm.
Response: The window frames are NOT to be painted. They are a bronze enameled metal and should not be painted.
3. QUESTION – Is this project taxable.
Response: Please review the entire solicitation.
4. QUESTION - Can the Sherwin Williams ESD System attached be used as substitute. Also, the spec, for this calls for a mortar overlay in the title, but nothing in the body of the spec would indicate installing mortar before the ESD system. Please confirm and/or clarify.
Response: In the Schedule of Finishes, 09 06 00, there are specified “Basis of Design” manufacturers for certain finishes. This includes paint (Sherwin Williams) and ERF (Epoxy Resinous Flooring). Use these products’ salient characteristics for a basis of design. Submit “or equal” product specifications to be approved by the VA.
5. QUESTION – See spec section 014500 Quality Control. Can the GC job superintendent also act as the CQC Manager? Or does there need to be a separate individual on site at all times to fill the CQC Manager role?
Response: The GC job superintendent can also act as the CQC Manager if qualified to do so. The qualified person will meet all requirements contained in the Quality Control Specs 01 45 00.
6. QUESTION – See spec Section 078400 Firestop , 1.5 Quality Assurance. This spec requires firestop installation to be completed by an approved FM Global installer. Please confirm this is a requirement under the contract
Response: A firm needs to be approved by FM Global 4991 or comply with UL’s “Qualified Firestop Contractor Program Requirements” to install firestopping products. This is a standard in the VA specs on the TIL
7. QUESTION – See spec Section 078400 Firestop, 3.5 Inspections Acceptance of Work requires firestop inspection by an approved inspector. Please confirm this is a requirement as part of this project.
Response: A firm needs to be approved by FM Global 4991 or comply with UL’s “Qualified Firestop Contractor Program Requirements” to install firestopping products. This is a standard in the VA specs on the TIL
8. QUESTION – See spec Section 040513 Masonry Mortar, 3.4 Field Tests. The mentioned spec section refers to 014529 Testing spec section for field testing. This spec section was not included in the provided specification. Please verify if mortar field testing is required. If so, please provide testing specification.
Response: Spec 014529 (Testing Laboratory Services) was removed at 65% DD since there was little-to-no scope. For 040513 Masonry Mortar testing, since the CMU walls are not load-bearing they are not required to be tested; however, the VA would still want the contractor to test the mortar and grout. The requirements are in part 1.3 of each spec (Applicable Publications)… for Mortar it is ASTM C780-15 and for Grout is ASTM C1019-14.
9. QUESTION – See Demolition Note D07, Sheet A1-01. It is unclear what demo note D07 is referencing or what the intent is. Please provide clarification on Demo Not D07.
| Response: D07: OWNER TO REMOVE SELECT, EXISTING ELECTRICAL | WIRING AND POWER CONTRACTOR TO COORDINATE AND VERIFY | SCOPE OF OWNER REMOVAL. | |||
| Note D07 is to be removed from documents. See sheet A1-01 addendum (included in | this amendment). Refer to Electrical sheet E3-01 Electrical Demolition (included in | this amendment) Notes: B. ALL EXISTING REMOVED | ELECTRICAL | EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE | OWNER SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR. |
VA to mark all electrical devices to be retained by owner.
CONTRACTOR is responsible to remove select, existing electrical wiring.
10. QUESTION – 10. RFI: There is no exit sign description in the fixture schedule. Will you please provide a description for the new exit signs?
Response: See immediately below.
See attached document: E1-03 - LIGHTING FIXTURE AND PANEL SCHEDULE.
See attached document: A1-01_PARTIAL DEMOLITION PLANS.