T/STEEL @ ROOF
686' - 0"
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
SERVICE ROOM
655' - 0"
BASEMENT
653' - 0"
BUILDING ADDITION
EXISTING BUILDING
A300
A300
A301
A301
PAINT SHOP
661' - 9"
A310
A301
W3 W3
W2 W2 W2
W1 W1 W1 W1
W6 W5
T/STEEL @ ADDITION
675' - 10"
A311
T/STEEL @ ROOF
686' - 0"
FIRST FLOOR
665' - 0"
BUILDING ADDITION
A310
A310
PAINT SHOP
661' - 9"
4 4
8 8
124A 120A
W3 W3
W8 W8
T/STEEL @ ADDITION
675' - 10"
12 12 12
W10
T/STEEL @ ROOF
686' - 0"
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
EXISTING BUILDING
BUILDING ADDITION
A300
A300
A301
A301
PAINT SHOP
661' - 9"
W2 W2 W2
W3W1W1W1W1
EXISTING
GRADE
A301
A301
W0
T/STEEL @ ADDITION
675' - 10"
A311
T/STEEL @ ROOF
686' - 0"
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
A300
A300
GRADE LINE BEYOND
EXISTING BUILDING
W1W1W1W1W1W1W1W1W1W1W1W1 W3W9 W9 W9
A311
A311
A310
1. INFILL BRICK WALL TO MATCH EXISTING ADJACENT.
2. NEW DOWNSPOUT AT LOCATION OF EXISTING. EXTEND TO EXISTING STORM SYSTEM. SEE
CIVIL AND PLUMBING DRAWINGS.
3. NEW DOWNSPOUT TO LOWER ROOF.
4. STEEL PIPE RAILING.
5. EXISTING LOUVER. BLOCK OFF WITH 2" INSULATED PANEL.
6. HANDRAIL.
7. STEEL PIPE RAILING WITH HANDRAIL.
8. CONCRETE LOADING PLATFORM. TIE INTO EXISTING ADJACENT.
9. COMMON BOND BRICK COURSING TO MATCH EXISTING. HEADER EVERY SIXTH COURSE.
10. PREFABRICATED EXTRUDED HANGER ROD CANOPY WITH FLAT SOFFIT. DOWNSPOUT
TO SPLASHBLOCK.
11. NEW ALUMINUM CRAWL SPACE ACCESS COVER
12. PATCH ASPHALT SHINGLE ROOF TO MATCH EXISTING
13. REPAIR EXISTING DAMAGED BRICK.
14. EXISTING FIRE DEPARTMENT CONNECTION - SEE FIRE PROTECTION DRAWINGS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ D o c u m e n ts \F
F E
C h ill ic o th e
R e n o v a te
B p a tr ic k .h ill ie r@ ff e
-s e rv .c o m
.r v t
/1
/2
:0
:0
P
M
A200
BUILDING ELEVATIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
1/8" = 1'-0"A200
3 NORTH ELEVATION
1/8" = 1'-0"A200
2 EAST ELEVATION
1/8" = 1'-0"A200
4 SOUTH ELEVATION
1/8" = 1'-0"A200
1 WEST ELEVATION ( EXISTING )
KEYNOTES - ELEVATIONS 1
Revisions: Date:
ADDENDUM 02 08/07/2021
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
25-CRAWL SPACE
659' - 0"
A B C D E F G
A300
A300
A301
PAINT SHOP
661' - 9"
A301
BUILDING ADDITION
WORKSHOP
PAINT OFFICE
JH
A301
A102 A311
A101 A310
OFFICE AND
BAS
MONITORING
STATION
" 6
A101 A310
T/STEEL @ ADDITION
675' - 10"
T/STEEL @ ROOF
686' - 0"
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
25-CRAWL SPACE
659' - 0"
SERVICE ROOM
655' - 0"
BASEMENT
653' - 0"
8 7 6 5 4 3 2 1
A300
A300
PEST
CONTROL /
SIGNAGE
SHOP
SOILED LINEN
ENVIRONMENTAL
MANAGEMENT
BREAK ROOM
MECHANICAL
PAINT SHOP
661' - 9"
2.96.1 4.5
WORKSHOP
WELDING
T/STEEL @ ADDITION
675' - 10"
A511
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:5
P
M
A300
BUILDING SECTIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
3/16" = 1'-0"A300
1 EAST - WEST BUILDING SECTION
3/16" = 1'-0"A300
2 NORTH - SOUTH BUILDING SECTION
FIRST FLOOR
665' - 0"
6 5 4 3
A300
A300
A310
A310
PAINT SHOP
661' - 9"
PAINT SHOP
SLOPE GRADE AWAY
1/4" PER FOOT MIN.
SLOPE GRADE AWAY
1/4" PER FOOT MIN.
2.96.1 4.5
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER
PAINT
STORAGE
PAINT OFFICE
T/STEEL @ ADDITION
675' - 10"
A301 A310
A301 A311
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
EXISTING
STAIRWELL
EXISTING
BUILDING
STEEL PIPE
RAILINGS
T/STEEL @ ROOF
686' - 0"
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
25-CRAWL SPACE
659' - 0"
BASEMENT
653' - 0"
87654321
A300
A300
A200 A310
A402
A311
A311
A103 A311
EXISTING GRADE
663'-0"
A310
MECHANICAL
ROOM / PIPE
ELECTRICAL
SHOP
TOOL
STORAGE
103A
MEN
ELECTRICAL
CONFERENCE
ROOM
A/C PIPE SHOP
CONFERENCE
ROOM
CLEAN LINEN
STORAGE
T/STEEL @ ADDITION
675' - 10"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:0
P
M
A301
BUILDING SECTIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
1/4" = 1'-0"A301
1 BUILDING SECTION - ADDITION
1/4" = 1'-0"A301
2 CANOPY SECTION
3/16" = 1'-0"A301
3 NORTH - SOUTH BUILDING SECTION B
FIRST FLOOR
665' - 0"
WHITE TPO MEMBRANE ROOF FULLY
ADHERED ON 1/4" PROTECTION BOARD.
MEMBRANE TO WRAP UP TO TOP OF WALL.
4" MIN. TAPERED
POLYISOCYANURATE INSULATION
SLOPED TO ROOF DRAIN AS SHOWN
ON PLAN.
PRE-FORMED, FACTORY FINISHED
ALUMINUM GRAVEL STOP CONTINUOUS
CLEAT. TPO MEMBRANE CAP FLASHING TO
WRAP OVER TOP OF WALL.
CONCRETE FOUNDATION WALL.
SEE STRUCTURAL DWGS.
CONCRETE FLOOR SLAB IN PAINT SHOP.
SEE STRUCTURAL. SLAB TO BE POURED ON
COMPACTED FILL.
PAINT SHOP
661' - 9"
NEW PAVING SLOPING AWAY FROM
BUILDING. SEE CIVIL DRAWINGS.
1/2" EXPANSION MATERIAL AT JOINT
J
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER
ELECTRICALLY-OPERATED
COILING STEEL OVERHEAD
DOOR.
A310 A510
672' - 3"
B/SOFFIT
T/STEEL @ ADDITION
675' - 10"
CLIP STUD TO STRUCTURAL STEEL.
FIRST FLOOR
665' - 0"
BASEMENT
653' - 0"
3" SPRAY FOAM
URETHANE INSULATION.
EXISTING CONCRETE WALL
ALUMINUM FRAME WINDOW
SEE EXTERIOR ELEVATIONS FOR
DETAILS
NEW SOFFIT - SEE R.C.P.
A310 A510
EXISTING FLOOR
A310 A510
NEW DOOR TRANSOM; HOLLOW
METAL W/FINISH TO MATCH
EXISTING DOORS ON THE BUILDING.
NEW EXIT DOOR.
EXISTING BASEMENT FLOOR TO REMAIN.
EXISTING AREAWAY SLAB TO REMAIN.
ELEV. 652'-6"
EXISTING CONCRETE BEYOND
SOLID
SURFACE
WINDOW SILL
PLUMBING CHASE
SIM
2'-0"
FIRST FLOOR
665' - 0"
PAINT SHOP
661' - 9"
WHITE TPO MEMBRANE ROOF FULLY
ADHERED OVER 1/4" PROTECTION
BOARD; WRAP ROOF UP WALL.
ALUMINUM FRAME WINDOW
SEE EXTERIOR ELEVATIONS FOR
DETAILS
GRADE SLOPED AWAY
FROM BUILDING - SEE
CIVIL DRAWINGS.
J
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER
672' - 3"
B/STEEL
T/STEEL @ ADDITION
675' - 10"
VAPOR
BARRIER
A310 A511
H O
L D
A310 A602
SIM.
OPP.
HAND
1'-2"
FIRST FLOOR
665' - 0"
PAINT SHOP
661' - 9"
WHITE TPO MEMBRANE
FULLY ADHERED TO 1/4"
PROTECTION BOARD. WRAP
MEMBRANE UP TO TOP OF
WALL.
4" BASE LAYER POLYISO
ROOF INSULATION WITH
TAPERED LAYER SLOPED
AT 1/4" PER FT. MIN. AS
SHOWN ON ROOF PLAN.
2" CONTINUOUS RIGID
THERMAL INSULATION
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER
NEW CONCRETE SLAB OVER
COMPACTED FILL - SEE
STRUCTURAL DWGS.
NEW CONCRETE
FOUNDATION WALL - SEE
STRUCTURAL DWGS.
NEW EXTERIOR SLAB/PAVED
SURFACE - SEE CIVIL
DRAWINGS.
VAPOR
BARRIER
2.9
ADJUSTABLE MASONRY
ANCHORS AT 16" O.C. BOTH
WAYS
1/2" EXTERIOR SHEATHING
6" METAL STUDS
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER
A310 A511
T/STEEL @ ADDITION
675' - 10"
BRICK VENEER
A310 A601
LOWER ROOF
678' - 0"
FIRST FLOOR
665' - 0"
A
2" MINIMUM SPRAY FOAM
INSULATION TO UNDERSIDE OF
EXISTING CONCRETE PLANKS
SOLID SURFACE
WINDOW SILL
5/8" GYPSUM WALLBOARD ON 2-1/2"
METAL STUD SET 1" OFF FACE OF
EXISTING WALL; FILL STUD CAVITY
WITH SPRAY FOAM URETHANE
INSULATION AS SPECIFIED.
A310 A511
A310 A602
2'-0"
SCHEDULED
CEILING
NEW SOFFIT - SEE R.C.P.
INFILL WINDOW OPENING WITH FACE
BRICK AND CMU TO MATCH EXISTING
WALL CONSTRUCTION. REMOVE
EXISTING SILL. GROUT SOLID.
PROVIDE BACKER ROD AND SEALANT
AT PERIMETER OF INFILL.
EXISTING LINTEL TO
REMAIN
5/8" GYPSUM
WALLBOARD ON 2-1/2"
METAL STUD
EXISTING EXTERIOR WALL
HORIZONTAL JOINT REINFORCEMENT
AND BRICK TIES AT 16" O.C.
T/STEEL @ ADDITION
675' - 10"
PROVIDE VAPOR
BARRIER AT EXTERIOR
LOCATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ D o c u m e n ts \F
F E
C h ill ic o th e
R e n o v a te
B p a tr ic k .h ill ie r@ ff e
-s e rv .c o m
.r v t
/1
/2
:4
:3
A
M
A310
WALL SECTIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
3/4" = 1'-0"A310
1 TYP. WALL SECTION-NEW WALL
3/4" = 1'-0"A310
4 WALL SECTION AT NORTH LOW-ROOF WALL
3/4" = 1'-0"A310
2 TYP. WALL SECTION-NEW WALL 2
3/4" = 1'-0"A310
3 TYP. WALL SECTION-NEW WALL 3
3/4" = 1'-0"A310
5 WALL SECTION AT LOW BAY WINDOW (STEEL)
3/4" = 1'-0"A310
6 WALL SECTION - INFILL
SIM.
ADDENDUM 02 08/18/2021
FIRST FLOOR
665' - 0"
A
A311 A511
A311 A511
5/8" GYPSUM WALLBOARD
ON 2-1/2" METAL STUD SET 1"
OFF FACE OF EXISTING
WALL; FILL STUD CAVITY
WITH SPRAY FOAM
URETHANE INSULATION AS
SPECIFIED.
EXISTING BEAM
BEYOND
EXISTING STEEL CHANNEL
REMOVED FOR CURTAIN
WALL OPENING. REFER TO
DEMOLITION DRAWINGS.
C
U R
T A
IN
W
A L
L R
.O
SPANDREL GLASS
ALUMINUM FRAME WINDOW
SEE EXTERIOR ELEVATIONS
FOR DETAILS
EXISTING METAL PANEL
EXISTING BEAM
BEYOND
MULLION
MULLION
3" 7 1/2"
FIRST FLOOR
665' - 0"
A
2" MINIMUM SPRAY FOAM
INSULATION TO UNDERSIDE OF
EXISTING CONCRETE PLANKS
5/8" GYPSUM WALLBOARD ON
2-1/2" METAL STUD SET 1" OFF
FACE OF EXISTING WALL; FILL
STUD CAVITY WITH SPRAY
FOAM URETHANE INSULATION
AS SPECIFIED.
A311 A511
A310 A511
SCHEDULED CEILING
NEW SOFFIT - SEE R.C.P.
T/STEEL @ ROOF
686' - 0"
7"
R
O U
G H
O P
E N
IN
G
EXISTING METAL PANEL
EXISTING CONCRETE WALL
EXISTING ROOF
ALUMINUM FRAME WINDOW
SEE EXTERIOR ELEVATIONS FOR
DETAILS
EXISTING JOIST
4"
A311 A511
A311 A511
2" MINIMUM SPRAY
INSULATION AT EXISTING
METAL PANEL
678' - 8"B/CONCRETE PLANK
FIRST FLOOR
665' - 0"
PAINT SHOP
661' - 9"
6.1
T/STEEL @ ADDITION
675' - 10"
WHITE TPO MEMBRANE FULLY
ADHERED TO 1/4" PROTECTION
BOARD. WRAP MEMBRANE UP TO
TOP OF WALL.
4" BASE LAYER POLYISO ROOF
INSULATION WITH TAPERED
LAYER SLOPED AT 1/4" PER FT.
MIN. AS SHOWN ON ROOF PLAN.
2" CONTINUOUS RIGID
THERMAL INSULATION
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER
NEW CONCRETE SLAB OVER
COMPACTED FILL; SEE
STRUCTURAL DWGS.
NEW CONCRETE
FOUNDATION WALL; SEE
STRUCTURAL DWGS.
NEW EXTERIOR SLAB/PAVED
SURFACE.
VAPOR BARRIER
ADJUSTABLE MASONRY
ANCHORS AT 16" O.C. BOTH
WAYS
1/2" EXTERIOR SHEATHING
6" METAL STUDS
THRU-WALL FLASHING
BRICK VENEER
1" AIR SPACE
667' - 1"
TOP OF CMU WALL
CELLULAR WEEPS AT 24" O.C.
8" SOLDIER COURSE
4" ROWLOCK COURSE
BRICK VENTS AT 24" O.C.
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER
1/2" EXPANSION JOINT MATERIAL
H O
L D
6" CMU - SEE STRUCTURAL
DRAWINGS FOR REINFORCING
6" BOND BEAM - SEE STRUCTURAL
DRAWINGS FOR REINFORCING
"L" BEAD RETURN - CUALK AT
DISSIMILAR MATERIALS
1'-5 7/8"
1'-0"
6" THERMAL INSULATION
STRUCTURAL FRAMING - SEE
STRUCTURAL DRAWINGS
SEE STRUCTURAL DRAWINGS
FOR CONNECTION
1/2" EXPANSION JOINT
MATERIAL
5/8" TYPE X GYPSUM BOARD
FIRST FLOOR
665' - 0"
PAINT SHOP
661' - 9"
2.9
T/STEEL @ ADDITION
675' - 10"
WHITE TPO MEMBRANE FULLY
ADHERED TO 1/4" PROTECTION BOARD.
WRAP MEMBRANE UP TO TOP OF WALL.
4" BASE LAYER POLYISO ROOF
INSULATION WITH TAPERED
LAYER SLOPED AT 1/4" PER FT.
MIN. AS SHOWN ON ROOF PLAN.
2" CONTINUOUS RIGID
THERMAL INSULATION
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER
NEW CONCRETE SLAB OVER
COMPACTED FILL - SEE
STRUCTURAL DWGS.
NEW CONCRETE
FOUNDATION WALL; SEE
STRUCTURAL DWGS.
NEW EXTERIOR CONCRETE
SLAB PLATFORM.
VAPOR BARRIER
ADJUSTABLE MASONRY
ANCHORS AT 16" O.C. BOTH
WAYS
1/2" EXTERIOR SHEATHING
6" METAL STUDS
THRU-WALL FLASHING
BRICK VENEER
1" AIR SPACE
667' - 1"
TOP OF CMU WALL
CELLULAR WEEPS AT 24" O.C.
8" SOLDIER COURSE
4" ROWLOCK COURSE
BRICK VENTS AT 24" O.C.
2" RIGID INSULATION EXTENDING
24" HORIZONTAL AND VERTICAL
AT PERIMETER.
1/2" EXPANSION JOINT MATERIAL
6" CMU - SEE STRUCTURAL
DRAWINGS FOR REINFORCING
6" BOND BEAM - SEE STRUCTURAL
DRAWINGS FOR REINFORCING
"L" BEAD RETURN - CUALK AT
DISSIMILAR MATERIALS
1'-5 7/8"
1'-0"
6" THERMAL INSULATION
STRUCTURAL FRAMING - SEE
STRUCTURAL DRAWINGS
METAL STAIR AND RAILING
SHOWN BEYOND
NEW CONCRETE
FOUNDATION WALL - SEE
STRUCTURAL DWGS.
2" RIGID INSULATION AT
PERIMETER TO FOOTING
CONTINUOUS
WATERPROOFING
MEMBRANE
CONCRETE FOOTING ALIGNED
WITH EXISTING BUILDING
FOOTING - SEE STRUCTURAL
DRAWINGS.
STUD CLIP TO STRUCTURAL
BEAM.
5/8" TYPE X GYPSUM BOARD.
GLUE TO STUDS AT TOP OF WALL
WHERE ACCESS IS LIMITED BY
STRUCTURAL FRAMING.
SEE STRUCTURAL DRAWINGS
FOR CONNECTION
MORTAR BED TO ALIGN BRICK
COURSING BEYOND.
ALIGN MORTAR BED FLUSH WITH
ADJACENT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ D o c u m e n ts \F
F E
C h ill ic o th e
R e n o v a te
B p a tr ic k .h ill ie r@ ff e
-s e rv .c o m
.r v t
/1
/2
:4
:3
A
M
A311
WALL SECTIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
3/4" = 1'-0"A311
2 WALL SECTION AT HIGH BAY CURTAINWALL
3/4" = 1'-0"A311
3 WALL SECTION AT LOW BAY WINDOW (CMU)
3/4" = 1'-0"A311
1 WALL SECTION AT HIGH BAY WINDOW
3/4" = 1'-0"A311
4 WALL SECTION AT ADDITION
3/4" = 1'-0"A311
5 WALL SECTION AT PLATFORM AND ADDITION
C
D
E
MEN
UNISEX
A401
A401
9'-0 1/4" 1'-8"
/4
/8
"5
/2
A401
11 13
A401
102 101
ALIGN TOP OF HALF WALL
WITH WINDOW SILL
MATTE PRIVACY FILM
MATTE PRIVACY FILM
MATTE PRIVACY FILM
A3
/4
/4
/2
CONCRETE FILL AT
EXISTING FLOOR
OPENING
PLUMBING CHASE
SIM
/2
/2
8'-10 1/8"
3'-0"
5'-10 3/4"
SINK
PAPER
TOWEL
DISPENSER
SOAP
DISPENSER
SINK
PAPER
TOWEL
DISPENSER
SOAP
DISPENSER
URINAL
URINAL
WATER CLOSET
WATER CLOSET
WATER CLOSET
WATER CLOSET
SHOWER
SHOWER
WT-1
TOILET
PARTITIONS,
TP-1
P-1
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
TOILET PARTITIONS,
TP-1
F
U L L
T
IL
E S6
GB18
GB42
GB36
T.P.D.
W1W1W1
WATER CLOSET
URINAL URINALWATER CLOSET
WT-1, 12" X 12"
TOILET PARTITIONS,
TP-1
P-1
SOAP
DISP.
(VV)
P.T.D.
(CC)
P.T.D.
(CC)
CEILING HUNG
TOILET PARTITIONS,
TP-1
SHOWER
BEYOND,
SS-2
24X36
MIRRORS
(CC)
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E
SSS-3 COUNTER,
BACK AND
SIDE SPLASH
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
SOLID SURFACE,
SS-2 SHOWER WALLS
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
CURTAIN ROD
(CC)
SOAP
HOLDER(REC
ESSED)40"
AFF (CC)
SOLID
SURFACE,
SS-2 SHOWER
WALLS
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
REFER TO
SHOWER BASE
DETAIL 1/A901
CONTINUOUS
SCHLUTER SCHIENE
A-100 TRIM, TYP.
SOLID SURFACE,
SS-2 SHOWER WALLS
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
GB18
GB42
T.P.D.
GB18
GB36
GB42
T.P.D. WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
SOAP
DISP.
(VV)
P.T.D.
(CC)
3'-0"
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E
SSS-3 COUNTER,
BACK AND
SIDE SPLASH
24X36
MIRRORS
(CC)
SOLID SURFACE,
SS-2 SHOWER WALLS
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
REFER TO SHOWER
BASE DETAIL 1/A901
CONTINUOUS
SCHLUTER SCHIENE
A-100 TRIM, TYP.
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
SOLID SURFACE, SS-2
SHOWER WALLS
F
U L L
T
IL
E S
SOLID SURFACE, SS-2
SHOWER WALLS
SOLID SURFACE, SS-2
SHOWER WALLS
CONTINUOUS
SCHLUTER SCHIENE
A-100 TRIM.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:2
P
M
A401
ENLARGED RESTROOM PLANS
AND ELEVATIONS
RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
08/14/2019 BJR JRR
3/8" = 1'-0"A401
1 RESTROOM ENLARGED PLANS
3/8" = 1'-0"A401
6 MEN'S TLT WEST ELEVATION
3/8" = 1'-0"A401
7 MEN'S TLT NORTH ELEVATION
3/8" = 1'-0"A401
8 MEN'S TLT EAST ELEVATION
3/8" = 1'-0"A401
9 MEN'S TLT SOUTH ELEVATION
3/8" = 1'-0"A401
2 MEN'S SHOWER WEST ELEVATION
3/8" = 1'-0"A401
3 MEN'S SHOWER NORTH ELEVATION
3/8" = 1'-0"A401
4 MEN'S SHOWER EAST ELEVATION
3/8" = 1'-0"A401
5 MEN'S SHOWER SOUTH ELEVATION
3/8" = 1'-0"A401
12 UNISEX TLT WEST ELEVATION
3/8" = 1'-0"A401
13 UNISEX TLT NORTH ELEVATION
3/8" = 1'-0"A401
10 UNISEX TLT EAST ELEVATION
3/8" = 1'-0"A401
11 UNISEX TLT SOUTH ELEVATION
3/8" = 1'-0"A401
14 UNISEX SHOWER WEST ELEVATION
3/8" = 1'-0"A401
15 UNISEX SHOWER EAST ELEVATION
A402
4 3
TLT
6'-0"
E1
A2
A2
/8
3'-7 1/2" 2'-6"
A403
LOCKER
ROOM
6 DOUBLE TIER
LOCKERS WITH
SLOPED TOP
42GB
18GB
36GB
PAPER TOWEL
DISPENSER
WALL MOUNTED
SINK
SOAP DISPENSER
1'-6"
1'-3"
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
PTD
WT-1 , 12" X 12"
WALL MOUNTED SINK
GB18
GB36
GB42
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
SINK
WALL MOUNTED
WATER CLOSET
PTD
SOAP DISPENSER
WT-1 , 12" X 12"
WT-3 , 4" X 12" MOSAIC
WT-1 , 3" X 12" BULLNOSE
WT-2 DECORATIVE LINER
WT-2 DECORATIVE LINER
P-1
F
U L L
T
IL
E S
GB18
GB42
WALL MOUNTED
WATER CLOSET
SOAP
DISPENSER
GB36
A402
10'-0"
1:20 RAMP
EXISTING
CONCRETE FLOOR
CART WASH
CONCRETE TOPPING SLAB
SLOPED TO FLOOR DRAIN.
SOLID SURFACE WALL PANEL, SS-2
A402
CART WASH
10'-0"
CONCRETE TOPPING SLAB
SLOPED TO FLOOR DRAIN.
PREP EXISTING
CONCRETE PER
MANUFACTURER'S
RECOMENDATION.
SOLID SURFACE WALL
PANELS,SS-2. ALIGN TOP OF
COATING WITH TOP OF HALF
WALL
HALF WALL WITH INTERNAL
HSS4X4X3/8 SUPPORT AT
END OF WALL - ANCHOR TO
FLOOR WITH FOUR (4) 1/2"
DIAMETER X 6" EXPANSION
BOLTS.
REFER TO FLOOR PLAN
FOR NEW CONSTRUCTION
WALL TYPES SOLID SURFACE WALL CAP,
SS-2. EXTEND 1/2" EACH
SIDE.
LOCKERS WITH
SLOPED TOP AND
BENCH
PAINT P-1PAINT P-1 PAINT P-1
SCHEDULED BASE
PAINT P-1
W1 W1 W1 W1 W1
PAINT P-1
SCHEDULED BASE
SCHEDULED BASE
EXISTING WALL
NEW WALL AT
EXISTING OPENING
DRYER
(VV)
24" DEEP SHELF WITH
WALL STANDARDS
FRTW BLOCKING
DRYER
(VV)
WASHER
(VV)
24" DEEP SHELF
SCHEDULED BASE
SECONDARY LINT TRAP
MOUNTED IN WALL
UTILITY SINK
AND FAUCET
SCHEDULED BASE
DRYER
(VV)
24" DEEP SHELF WITH
WALL STANDARDS
FRTW BLOCKING
119A
TOOL
STORAGE
CAGE
SCHEDULED BASE
LOCKERS WITH
SLOPED TOP AND
BENCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:3
P
M
A402
ENLARGED PLANS AND
ELEVATIONS
RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
3/8" = 1'-0"A402
1 RESTROOM ENLARGED PLAN
3/8" = 1'-0"A402
3 INTERIOR ELEVATION - TLT 122 - EAST
3/8" = 1'-0"A402
2 INTERIOR ELEVATION - TLT 122 - SOUTH
3/8" = 1'-0"A402
4 INTERIOR ELEVATION - TLT 122 - WEST
1/2" = 1'-0"A402
10 CART WASH SECTION
1/2" = 1'-0"A402
9 CART WASH SECTION
3/8" = 1'-0"A402
6 ELECTRICAL SHOP EAST ELEVATION
3/8" = 1'-0"A402
5 ELECTRICAL SHOP WEST ELEVATION
3/8" = 1'-0"A402
7 LAUNDRY ROOM ELEVATION
3/8" = 1'-0"A402
13 LAUNDRY ROOM W/D ELEVATION
3/8" = 1'-0"A402
8 LAUNDRY ROOM SINK ELEVATION
3/8" = 1'-0"A402
11 ELECTRICAL SHOP NORTH ELEVATION
3/8" = 1'-0"A402
12 ELECTRIC SHOP LOCKER WALL ELEVATION
2'-6" 2'-6" 2'-9"
2'-6" 2'-6" 2'-9"
MICROWAVE
(VV)
REFRIGERATOR
(VV)
P.T.D.
(CC)
SOAP
DISP.
(VV)
PLAM WALL
CABINETS,
PL-1
PLAM BASE CABINETS, PL-1SOLID SURFACE COUNTERS, SS-1
P-3
12'-11 1/4"
/2
PLASTIC
LAMINATE
CUBBIES,
PL-1,
12"x12"x12"
1'-0"
EXISTING STRUCTURE EXPOSED.
PAINT P-2.
PAINT P-5
WP-1
RANGE HOOD (CC)
RANGE
(VV)
MICROWAVE
(VV)
REFRIGERATOR
(VV)
SOAP
DISP.
(VV)
P.T.D.
(CC)
EXISTING BEAM, PAINTED P-2
SCHEDULED BASE
2" 3'-0" 1'-6" 2'-7" 1'-6" 3'-0" 3'-0" 2'-10"
2" 3'-0" 1'-6" 1'-6" 3'-0" 3'-0"
PLAM WALL
CABINETS,
PL-1
PLAM BASE CABINETS, PL-1
SOLID SURFACE
COUNTERS, SS-1
PAINT P-3
PAINT P-1
PAINT P-1
RANGE VENT (CC)
TYP.
3'-0"
LOCKABLE
CABINETS AT
WORKSTATIONS,
PL-1
10" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 10 1/4"
P.LAM COUNTER
PL-2
SCHEDULED BASE
VERTICAL
SUPPORTS, PL-1
STRUCTURE
PAINTED, P-2
PAINT, P-1
PAINT, P-3
FILLER
PANEL
FILLER
PANEL
W2 W2
PLAM CABINETS, PL-1
SOLID SURFACE COUNTERS, SS-1 PLAM COUNTERS,
PL-2
PLAM CABINETS, PL-1
PLAM CABINETS, PL-1
PAINT P-3
W9W9
W9W9
PLAM
CABINETS, PL-1
SOLID SURFACE
COUNTERS, SS-1
PLAM
CABINETS, PL-1
FIRE EXTINGUISHER
CABINET, FE-2
PAINT P-3
C
L E
A R
M
A X
2'-8" 1'-6 1/8"
SCHEDULED BASE
EYE WASHUTILITY SINK
AND FAUCET
PAINT P-5
WP-1
MOP SINK
8" UTILITY SHELF
W/ MOP/BROOM
HOLDERS
SOLID SURFACE
WALL
PROTECTION
SCHEDULED BASE
PAINT P-5
WP-1
3'-0" 3'-0" 3'-0" 3'-0"
PLAM COUNTER,
PL-2
PLAM CABINETS,
PL-1
PLAM CABINETS,
PL-1
1" +/- 1" +/-
FILLER PANEL
PLAM BACKSPLASH,
PL-2
FILLER PANEL
PAINT P-5
WP-1
2'-6" 2'-6"
2'-6" 2'-6"
SCHEDULED BASE
P.LAM. TOP,
PL-2
P.LAM.
CABINETS,
PL-1
P.LAM.
CABINETS,
PL-1
4'-2"
PAINT P-1
EYE WASH
UTILITY SINK
AND FAUCET
C
L E
A R
M
A X
EXISTING BRICK
EXTERIOR WALL
EXISTING
CONCRETE
FOUNDATION
STRUCTURAL COLUMN
8" CMU INFILL
BRICK INFILLED OPENINGS TO
MATCH EXISTING
DOUBLE TIER
LOCKERS WITH
SLOPED TOP
SCHEDULED BASE
PAINT P-1
2'-8"1'-2"
REFRIGERATOR
(VV)
SCHEDULED BASE4" HOUSEKEEPING PAD SPILL CONTAINMENT CURB
PAINT P-1
CMU INFILL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:4
P
M
A403
INTERIOR ELEVATIONS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
3/8" = 1'-0"A403
11 BREAK ROOM 125 - ELEVATION
3/8" = 1'-0"A403
9 CLEAN LINEN 113 - CUBBIES
3/8" = 1'-0"A403
7 CONFERENCE ROOM KITCHEN 111 - ELEVATION
3/8" = 1'-0"A403
3 CONFERENCE ROOM WORKSTATION 111 -ELEVATION
3/8" = 1'-0"A403
10 CONFERENCE ROOM EXTERIOR 110 - WALL ELEVATION
3/8" = 1'-0"A403
13 CONFERENCE ROOM ENTRY 110 - WALL ELEVATION
3/8" = 1'-0"A403
6 WORKSHOP 113 - SINK AND EYE WASH STATION
3/8" = 1'-0"A403
5 HOUSEKEEPING AIDES 105 - CLOSET
3/8" = 1'-0"A403
12 WORKSHOP 113 - CASEWORK ELEVATION
3/8" = 1'-0"A403
4 PAINT SHOP 115 - CASEWORK ELEVATION
3/8" = 1'-0"A403
8 PAINT SHOP - 115 SINK AND EYE WASH STATION
3/8" = 1'-0"A403
2 LOCKER ROOM 121 - ELEVATION
3/8" = 1'-0"A403
1 MIXING ROOM 115 - ELEVATION
NOTE 1:
OMIT BRACE WHEN "D" DIMENSION IS
LESS THAN 2'-0" [610mm] FOR GYP.
WALLBD. OR 16" [400mm] FOR PLASTER
PARTITION.
SECTION B
VERTICAL STUDS @ 2'-0" [610mm] MAX.
W/GYPSUM WALLBD. 1'-4" [406mm] W/GYPSUM
LATH & PLASTER DOUBLE STUDS FOR
SUPPORTING CONC. BACKER BOARD.
PROVIDE CONTINUOUS BRACING WHEN STUDS
EXCEED 10'-0" [3048mm] & ARE FINISHED
BOTH SIDES
JAMB ANCHOR CLIPS 3 PER SIDE -
COORDINATE W/HINGE REINFORCEMENT.
DETAIL D
SEE
NOTE
1/2" [13mm]
CONST.
JOINT
RUNNER BET. STUDS
SEE
DOOR
SCHEDULE
SHIM
AS
REQ'D.
SEC. B
GYPSUM
WALLBD.
PANELS
CONTROL
JOINT
ISOMETRIC OF CONSTR. JT.
ELEVATION AT DOOR FRAME
DETAIL D
PROVIDE
SOUND
DEADENING
WHERE
REQ'D.
SANITARY STOP
METAL DOOR FRAME
METAL
ANCHOR
CLIP
SHIM AS
REQ'D.
DETAIL C
[1 m m
JAMB
ANCHOR
SECTION A
DOUBLE STUDS
DETAIL C
MET.
DOOR
FRAME
1/2" [13mm]
[13mm]
CRIPPLE STUD DO
NOT ANCHOR TO
BEARING STUD
A A
[1 m m
WIDTH
[1 m m
[1 m m
1/2" MIN.
[1 m m
JAMB ANCHORS
(FURNISHED WITH FRAME)
E Q
E Q
V A R
IE
SVARIES
M A X . D
E Q
E Q
M
IN
STUD
MINUS 3/16"
[5mm]
JAMB DEPTH
M
IN
M
IN
. WIDTH
STUD
FR
AM
E
FA
CE
MIN
US
/1
[5m m]
MIN
US
/1
FR
AM
E
FA
CE
[5m m]
"M
IN.
mm
5/ 8"
MA
X.
[16 mm
CONTRACTOR SHALL
COORDINATE LOCATIONS OF
HORIZONTAL FASTENERS.
FASTEN AT BOTH
ENDS WITH MIN. 4
TAPPING SCREWS.
CUT
HORIZONTAL
FASTENER FROM
STUD
VERTICAL WALL
STUDS AT 16"
[406mm] OR 24" [610mm] O.C.
ISOMETRIC
WALL FINISH
PLAN
1.
GENERAL NOTES:
TYPE A2
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. WITH 3" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS TO 6" ABOVE
CEILING. BRACE TOP OF
WALL AS REQUIRED, BUT
NOT LESS THAN 8'-0" O.C.
TYPE A3
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
ROOM SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. WITH 3" SOUND
ATTENUATION BLANKET
IN STUD SPACE. EXTEND
STUDS, BOARD AND
SOUND BLANKETS FULL
HEIGHT TO DECK ABOVE.
ATTACH TO STRUCTURE
ABOVE W/ VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE A4
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
ROOM SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. WITH 3" SOUND
ATTENUATION BLANKET
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS TO 6" ABOVE
CEILING. BRACE TOP OF
WALL AS REQUIRED, BUT
NOT LESS THAN 8'-0" O.C.
TYPE B1
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 6" 20 GA.
METAL STUDS @ 16" O.C.
WITH 6" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS FULL HEIGHT
TO DECK ABOVE. ATTACH
TO STRUCTURE ABOVE
W/ VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE B2
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 6" 20 GA.
METAL STUDS @ 16" O.C.
WITH 6" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS FULL HEIGHT
TO DECK ABOVE. ATTACH
TO STRUCTURE ABOVE
W/ VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE F2
1 HOUR RATED WALL
UL# U419
PROVIDE TYPE "X" GYPSUM
WALLBOARD FOR 1 HR UL RATING
ON EACH SIDE OF 6" 20 GA. METAL
STUDS @ 16" O.C. WITH 6" SOUND
ATTENUATION BLANKETS IN STUD
SPACE. EXTEND STUDS, BOARD,
AND BLANKETS FULL HEIGHT TO
DECK ABOVE. ATTACH TO
STRUCTURE ABOVE W/ VERTICAL
SLIP CONNECTIONS. SEE
PARTITION NOTES THIS DWG.
TYPE F1
1 HOUR RATED WALL
UL# U419
PROVIDE TYPE "X" GYPSUM
WALLBOARD FOR 1 HR UL
RATING ON EACH SIDE OF 3 5/8"
20 GA. METAL STUDS @ 16" O.C.
WITH 3" SOUND ATTENUATION
BLANKETS IN STUD SPACE.
EXTEND STUDS, BOARD, AND
BLANKETS FULL HEIGHT TO
DECK ABOVE. ATTACH TO
STRUCTURE ABOVE W/
VERTICAL SLIP CONNECTIONS.
SEE PARTITION NOTES THIS
DWG.
TYPE C1
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
ROOM SIDE OF 2 1/2" 20 GA.
METAL STUDS @ 16" O.C.
WITH 2" SOUND
ATTENUATION BLANKET IN
STUD SPACE. EXTEND
STUDS, BOARD AND
SOUND BLANKETS FULL
HEIGHT TO DECK ABOVE.
ATTACH TO STRUCTURE
ABOVE W/ VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE A1 (U.N.O.)
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. WITH 3" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS FULL HEIGHT
TO DECK ABOVE. ATTACH
TO STRUCTURE ABOVE
W/ VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE A6
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
ROOM SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. EXTEND STUDS AND
BOARD TO 6" ABOVE
CEILING. BRACE TOP OF
WALL AS REQUIRED, BUT
NOT LESS THAN 8'-0" O.C.
TYPE A5
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
ROOM SIDE OF 3-5/8" 20
GA. METAL STUDS @ 16"
O.C. EXTEND STUDS AND
BOARD FULL HEIGHT TO
DECK ABOVE. ATTACH TO
STRUCTURE ABOVE W/
VERTICAL SLIP
CONNECTIONS. SEE
PARTITION NOTES THIS
DWG.
TYPE B3
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 6" 20 GA.
METAL STUDS @ 16" O.C.
WITH 6" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS TO 6" ABOVE
CEILING. BRACE TOP OF
WALL AS REQUIRED, BUT
NOT LESS THAN 8'-0" O.C.
TYPE B4
ONE LAYER OF 5/8"
GYPSUM WALLBOARD ON
EACH SIDE OF 6" 20 GA.
METAL STUDS @ 16" O.C.
WITH 6" SOUND
ATTENUATION BLANKETS
IN STUD SPACE. EXTEND
STUDS, BOARD, AND
BLANKETS TO 6" ABOVE
CEILING. BRACE TOP OF
WALL AS REQUIRED, BUT
NOT LESS THAN 8'-0" O.C.
5/8" 3 5/8" 5/8"
4 7/8"
3 5/8" 5/8"
4 1/4"
3 5/8" 5/8"
4 1/4"
3 5/8" 5/8"
4 1/4"
5/8" 3 5/8" 5/8"
4 7/8"
3 5/8" 5/8"
4 1/4"
5/8" 6" 5/8"
7 1/4"
5/8" 3 5/8" 5/8"
4 7/8"
6" 5/8"
6 5/8"
5/8" 6" 5/8"
7 1/4"
6" 5/8"
6 5/8"
2 1/2" 5/8"
3 1/8"
5/8" 6" 5/8"
7 1/4"
TYPE G1
INTERIOR H.C.B. WALL
(NON LOAD BEARING)
8" NOM. CONCRETE
BLOCKS.
7 5/8"
TYPE F3
2 HOUR RATED WALL
UL# U419
PROVIDE 2 LAYERS OF TYPE "X"
GYPSUM WALLBOARD FOR 2 HR
UL RATING ON EACH SIDE OF 3 5/8"
20 GA. METAL STUDS @ 16" O.C.
WITH 3" SOUND ATTENUATION
BLANKETS IN STUD SPACE.
EXTEND STUDS, BOARD, AND
BLANKETS FULL HEIGHT TO DECK
ABOVE. ATTACH TO STRUCTURE
ABOVE W/ VERTICAL SLIP
CONNECTIONS. SEE PARTITION
NOTES THIS DWG.
TYPE F5
1 HOUR SHAFT WALL
UL# U415 SYSTEM A
1 LAYER OF 5/8" TYPE "X" GYPSUM
WALLBOARD ON ONE SIDE OF 4" 2O GA.
METAL CH STUD AT 16" O.C. MAX., AND
ONE LAYER OF 1" TYPE "X" GYPSUM
LINER PANEL INSERTED WITHIN "H"
PORTION OF "CH" STUD, AND 3" SOUND
ATTENUATION BLANKETS IN STUD
SPACE. EXTEND STUDS, BOARD, AND
SOUND BLANKETS FULL HEIGHT TO
DECK ABOVE.ATTACH TO STRUCTURE
ABOVE W/ VERTICAL SLIP
CONNECTIONS. SEE PARTITION NOTES
THIS DWG.
5/8"
5/8" 3 5/8"
5/8" 5/8"
6 1/8"
1" 3" 5/8"
4 5/8"
1. TYPICAL PARTITION TYPE IS WALL TYPE "A1" UNLESS NOTED OTHERWISE ON PLAN.
2. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION SCHEDULE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE RESISTANCE DIRECTORY.
3. ALL WALLBOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
4. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
5. METAL STUD GAUGES SCHEDULED ARE THE MINIMUM REQUIRED, AND MAY BE INCREASED BY SPECIFICATIONS TO ACCOMMODATE LOADS, FINISHES, OR UNBRACED CEILING HEIGHT LIMITS. DO NOT CONSIDER CEILING SYSTEM(S) AS A PARTITION BRACING ELEMENT.
6. SOUND ATTENUATION BATT (SAB) IS TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM UNLESS NOTED OTHERWISE.
7. WOOD AND PLYWOOD BLOCKING TO BE FIRE RETARDANT TREATED (FRT).
8. EDGES OF GYPSUM WALL BOARD (GWB) LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L" BEAD
TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
9. PARTITION SCHEDULE IS BASED ON THE USE OF GYPSUM WALL BOARD (GWB), BUT FACING BOARD MAY VARY, DEPENDENT ON FINAL FINISH
SCHEDULED FOR THAT PARTITION: USE CEMENTITIOUS BACKER BOARD (CBB) WHERE CERAMIC TILE SCHEDULED IN "WET" AREAS; USE MOISTURE RESISTANT BOARD (MR) WHERE CERAMIC TILE SCHEDULED IN "DRY" AREAS; USE GYPSUM LATH (BLUE BOARD) WHERE VENEER PLASTER IS SCHEDULED. SEE FINISH SCHEDULE AND SPECIFICATIONS FOR PARTICULARS. AT ALL PLUMBING FIXTURES INSTALL 4X8 (MR)
MOISTURE RESISTANT BOARD CENTERED ON FIXTURE,
10. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
11. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR DETAILED OTHERWISE.
12. ALL PARTITIONS, INCL. STUDS, BOARD, SOUND ATTENUATION BLANKETS, ETC. TO EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF
CONCRETE SLAB ABOVE UNLESS OTHERWISE NOTED.
13. CONTRACTOR IS TO CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING
VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH SURROUNDING MATERIALS AND SHALL BE
IN ACCORDANCE WITH NFPA CODE.
14. REFER TO NEW ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS.
15. CONTRACTOR SHALL SEAL PARTITION WALLS AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS
INCLUDING BUT NOT LIMITED TO THE SLAB, ABOVE AND BELOW CEILINGS.
16. ALL NEW MASONRY WORK INCLUDING NEW PARTITIONS, INFILL AND PATCHING; MATCH EXISTING COURSING AND TOOTH IN WITH EXISTING ADJ.
CONSTRUCTION.
17. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR ANY REASON.
18. IN AREAS OF TOILET ROOMS AND OTHER PLUMBING FIXTURES SUCH AS MOP BASINS, SINKS, SHOWERS, TOILETS, ETC. A TYPE 'X' MOISTURE
RESISTANT GYPSUM WALLBOARD SHALL BE USED FOR THE WALL CONSTRUCTION. WHERE CERAMIC TILE IS SCHEDULED; CEMENTITIOUS BOARD
SHALL BE USED FOR THE WALL CONSTRUCTION.
19. UNLESS NOTED, THE CONNECTION AT THE TOP OF THE PARTITION TO THE STRUCTURE ABOVE MUST ALLOW FOR 1" MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. AT FIRE RATED METAL STUD PARTITIONS, THE TOP CONNECTION MUST BE A FIRE STOP CONNECTION THAT ALLOWS 1" MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. HOLD GYPSUM WALL BOARD AND STEEL STUDS 1" FROM THE BOTTOM OF THE STRUCTURE ABOVE. DO NOT SCREW-ATTACH STEEL VERTICAL STUDS OR GYPSUM WALL BOARD TO THE TOP TRACK. INSTALL BRIDGING 12"
MINIMUM FROM THE TOP OF THE STUDS.
20. ALL EXTERIOR STUDS TO BE 600S137-68 UNO. REFER TO REPORT FOR LOADS IN RESPONSE TO BLAST.
PARTITION NOTES:
TYPE B5
ONE LAYER OF 3/4" FRT
PLYWOOD OVER ONE LAYER
OF 5/8" GYPSUM
WALLBOARD ON ROOM SIDE
OF 6" 20 GA. METAL STUDS
@ 16" O.C. WITH 6" SOUND
ATTENUATION BLANKETS IN
STUD SPACE. ONLY LAYER
OF 5/8" GYPSUM
WALLBOARD ON OPPOSITE
SIDE. EXTEND STUDS,
BOARD, AND BLANKETS TO
6" ABOVE CEILING. BRACE
TOP OF WALL AS REQUIRED,
BUT NOT LESS THAN 8'-0"
O.C.
3/4" 5/8" 6" 5/8"
8"
5/8" GYPSUM WALL
BOARD ON 1 5/8" METAL
STUDS AND 7/8" METAL
FURRING CHANNELS.
1 5/8" METAL STUDS
SECURED TO STEEL
COLUMN.
STEEL COLUMN. SEE S-
SERIES DWGS FOR
SIZE AND
ORIENTATION.
7/8" METAL FURRING
CHANNELS SECURED
TO STEEL COLUMN.
/8
V
A R
IE
S
/8
1 1/2" VARIES 1 1/2"
CURTAINWALL SYSTEM
SOUND BARRIER
MULLION TRIM CAP
MULLION
INTERIOR STUD GAGE AND SPACING CHART*
STUD
WIDTH
DESIGN
THICKNESS
(GAGE)
STUD
SPACING
(INCHES)
PARTITION HEIGHT
DEFLECTION VALUE 5 psf
BRACING
SPACING WHERE
OCCURSL/120 L/240 L/360
1 5/8"
0.0179 " (25)
0.0312" (20)
0.0179 " (25)
0.0312" (20)
0.0179 " (25)
0.0312" (20)
0.0179 " (25)
0.0312" (20)
0.0179 " (25)
0.0312" (20)
2 1/2"
3 5/8"
4"
6"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
10'-7"
9'-9"
12'-1"
11'-0"
13'-3"
11'-10"
16'-5"
14'-10"
15'-4"
13'-9"
20'-8"
18'-6"
17'-2"
15'-1"
23'-1"
20'-9"
19'-9"
16'-9"
30'-10"
27'-2"
8'-4"
7'-11"
9'-8"
8'-9"
11'-3"
10'-7"
12'-10"
11'-7"
14'-4"
13'-5"
16'-5"
14'-9"
15'-4"
14'-2"
18'-4"
16'-5"
19'-9"
16'-9"
24'-6"
21'-7"
8'-5"
7'-8"
9'-10"
9'-3"
11'-2"
10'-0"
12'-4"
11'-7"
14'-3"
12'-9"
13'-4"
12'-4"
15'-11"
14'-3"
17'-11"
16'-9"
21'-4"
18'-10"
4'-0" OC
4'-0" OC
4'-0" OC
4'-0" OC
6'-0" OC
6'-0" OC
6'-0" OC
6'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
8'-0" OC
10'-0" OC
10'-0" OC
10'-0" OC
10'-0" OC
1. PROVIDE MINIMUM 0.0312" STUDS AT WALLS TO RECEIVE FINISH (TILE, STONE, WOOD, ETC.)
2. PROVIDE MINIMUM 0.0312" STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN
PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES,
CASEWORK, PLUMBING FIXTURES, ETC.
3. USE 5/8" FR GWB AT ALL FIRE-RATED PARTITIONS, ANCHOR W/ SCREWS AT 8" OC ON EDGES
AT 12" OC IN FIELD PER UL DESIGN NUMBERS LISTED.
4. SEE ALL SPECIFICATIONS FOR GWB REQUIREMENTS AT TOILETS AND ALL WET AREAS.
5. FOR LOCATIONS OF EXISTING AND NEW FIRE-RATED PARTITIONS, SEE LIFE SAFETY PLANS.
6. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL WALL STUD INSTALLATIONS EXCEEDING
STUD MANUFACTURER REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
INTERIOR STUD CHART NOTES:
* REFERENCE STEEL STUD MANUFACTURER ASSOCIATION'S STANDARDS FOR SECTION PROPERTIES
AND DESIGN OF STUD SIZE LISTED HERE
USE L/240 DEFLECTION CHART FOR ALL AREA UNLESS OTHERWISE NOTED.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:5
P
M
A501
PARTITION TYPES AND DETAILS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
PARTITION SCHEDULE
PARTITION FRAMING FOR DOORSANCHORAGE - GRAB BARS AND CABINETS
3" = 1'-0"A501
1 TYP. COLUMN FURRING
1 1/2" = 1'-0"A501
2 CURTAINWALL TO PARTITION DETAILSTUD PARTITION TABLE
EXISTING CONCRETE WALL AND
ROUGH OPENING TO REMAIN.
14 GA. HOLLOW METAL ENTRANCE; FINISH TO
MATCH EXISTING WINDOWS ON BUILDING.
SEAL FULL PERIMETER OF OPENING BOTH
SIDES.
HOLLOW METAL ENTRANCE; FINISH TO
MATCH EXISTING WINDOWS ON BUILDING.
SEE ELEVATION FOR GLAZING
AT LOUVERS PROVIDE 14 GA. LOUVER
IN LIEU OF GLAZING.
NEW HOLLOW METAL EXTERIOR
DOOR; SEE DOOR SCHEDULE.
A510 A601
SIM
3"
SOLID SURFACE SILL; SEAL AT JOINT TO WINDOW.
NEW 2-1/2" x 7-1/2" BLAST-RESISTANT ALUMINUM
WINDOW SYSTEM; FINISH TO MATCH EXISTING
WINDOWS ON BUILDING.
SEAL FULL PERIMETER OF WINDOW BOTH SIDES;
DO NOT BLOCK WEEP HOLE AT WINDOW SILL.
SILL PAN FLASHING
5/8" GYPSUM WALLBOARD ON 2-1/2" METAL
STUD SET 1/2" OFF FACE OF EXISTING
WALL; FILL STUD CAVITY WITH SPRAY
FOAM URETHANE INSULATION AS
SPECIFIED.
2 1/2" 1/2"
EXISTING CONCRETE WALL TO REMAIN
1/2"
J
PREFABRICATED EXTRUDED
HANGER ROD CANOPY WITH
FLAT SOFFIT - REFER TO
MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
OVERHEAD COILING
DOOR MOTOR
B/SOFFIT AND B/STEEL
2" RIGID INSULATION.
ADJUSTABLE MASONRY TIES AT
16" O.C. HORIZONTALLY AND
MIN. 12" O.C. VERTICALLY AT
HANGER ROD CANOPY.
1" AIR SPACE.
BRICK VENEER.
THRU-WALL FLASHING.
SOLDIER COURSE HEADER.
(FLUSH WITH ADJACENT BRICK
AT CANOPY).
STEEL ANGLE - SEE
STRUCTURAL DRAWINGS.
5/8" FRT PLYWOOD
BACKER FOR O.H. DOOR.
STEEL FRAMING - SEE
STRUCT. DRAWINGS.
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER.
1/2" EXTERIOR SHEATHING.
OVERHEAD DOOR.
METAL STUD FRAMING.
672' - 3"
/8
STEEL FRAMING - SEE
STRUCTURAL DRAWINGS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ D o c u m e n ts \F
F E
C h ill ic o th e
R e n o v a te
B p a tr ic k .h ill ie r@ ff e
-s e rv .c o m
.r v t
/1
/2
:5
:5
A
M
A510
EXTERIOR SECTION DETAILS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
1 1/2" = 1'-0"A510
4 DOOR 003 TRANSOM AND HEAD DETAIL
1 1/2" = 1'-0"A510
3 SECTION DETAIL-NEW WINDOW SILL AT NORTH LOW-ROOF
1 1/2" = 1'-0"A510
5 SECTION DETAIL AT OVERHEAD COILING DOOR
EXISTING METAL PANEL
EXISTING WALL BEYOND
4-1/2" ALUMINUM WINDOW
SYSTEM; FINISH TO MATCH
EXISTING WINDOWS ON
BUILDING.
NEW STRUCTURAL SUPPORT
TO EXISTING STRUCTURE AT
TOP OF WINDOW
2" MINIMUM SPRAY
INSULATION AT EXISTING
METAL PANEL
EXISTING W16X50
10"
EXISTING CONCRETE PLANK
EXISTING STEEL TUBE BEYOND
4-1/2" BLAST-RESISTANT ALUM.
WINDOW SYSTEM; FINISH TO MATCH
EXISTING WINDOWS ON BUILDING.
EXISTING CONCRETE WALL
CONCRETE ANCHOR
SILL PAN FLASHING
6" 8"
ROOF MEMBRANE
BACKER ROD AND SEALANT
EXISTING TERMINATION BAR; RE-SEAL
10" 4"
A
3"
EXISTING METAL PANEL
NEW 4 1/2" ALUMINUM FRAME - SEE
EXTERIOR ELEVATION FOR GLAZING.
FINISH TO MATCH EXISTING
WINDOWS ON BUILDING. SEAL FULL
PERIMETER BOTH SIDES.
EXISTING ANGLE CUT FOR
CURTAIN WALL
CLEARANCE
4" 8"
BRICK BEYOND
NEW STRUCTURAL SUPPORT
REQUIRED AT TOP CONNECTION.
A
SOLID SURFACE SILL; SEAL AT JOINT TO WINDOW.
4 1/2" ALUMINUM WINDOW SYSTEM; FINISH TO
MATCH EXISTING WINDOWS ON BUILDING.
SEAL FULL PERIMETER OF WINDOW
BOTH SIDES; DO NOT BLOCK WEEP
HOLE AT WINDOW SILL.
SILL PAN FLASHING
5/8" GYPSUM WALLBOARD ON 2-1/2" METAL
STUD SET 1" OFF FACE OF EXISTING WALL;
FILL STUD CAVITY WITH SPRAY FOAM
URETHANE INSULATION AS SPECIFIED.
EXISTING CONCRETE WALL TO REMAIN.
1/2"
3"
A
EXISTING METAL PANEL
4-1/2" ALUMINUM WINDOW SYSTEM;
FINISH TO MATCH EXISTING
WINDOWS ON BUILDING. SEAL FULL
PERIMETER BOTH SIDES.
EXISTING JOIST
SEALANT AND BACKER ROD
3"
A
SOLID SURFACE
WINDOW SILL
SILL PAN FLASHING
4-1/2" ALUMINUM WINDOW SYSTEM;
FINISH TO MATCH EXISTING
WINDOWS ON BUILDING.
SEAL FULL PERIMETER OF WINDOW
BOTH SIDES; DO NOT BLOCK WEEP
HOLE AT WINDOW SILL.
5/8" GYPSUM WALLBOARD ON
2-1/2" METAL STUD SET 1" OFF
FACE OF EXISTING WALL; FILL
STUD CAVITY WITH SPRAY
FOAM URETHANE INSULATION
AS SPECIFIED.
EXISTING CONCRETE WALL
3"
EXISTING CONCRETE CURB BELOW
EXISTING METAL
PANEL
EXISTING 3X5 STEEL TUBE
4 1/2" ALUMINUM WINDOW
SYSTEM; FINISH TO MATCH
EXISTING WINDOWS ON
BUILDING.
NEW ALUMINUM
FLASHING TO MATCH
METAL PANEL
SEALANT JOINT
5" 5"
ROOF STRUCTURE
ROOF DRAIN
ROOF DRAIN
RIGID INSULATION
TPO MEMBRANE
WATER CUT-OFF MASTIC
CLAMPING RING
H
T/STEEL @ ADDITION
675' - 10"
TAPERED RIGID INSULATION.
SLOPED TO DRAIN.
L2-1/2 X 2-1/2 X 1/4
TOP CHORD EXTENSION.
J
T/STEEL @ ADDITION
675' - 10"
FACTORY-FINISHED GRAVEL STOP ON
CONTINUOUS CLEAT. FINISH TO MATCH GRAVEL
STOP ON EXISTING LOW-SLOPE ROOF.
TPO MEMBRANE CAP FLASHING TO WRAP
OVER TOP OF WALL.
CONTINUOUS TREATED 2X NAILER
CONTINUOUS LIQUID-APPLIED AIR &
MOISTURE BARRIER
CONTINUOUS 2" RIGID THERMAL INSULATION
4-1/2" ALUMINUM WINDOW SYSTEM; FINISH
TO MATCH EXISTING WINDOW FINISH ON
BUILDING. SEAL WINDOW FULL
PERIMETER BOTH SIDES.
STRUCTURAL STEEL - SEE STRUCTURAL
DWGS.
METAL DECK; SEE STRUCTURAL DWGS.
VAPOR BARRIER
BACKER ROD AND SEALANT
6" METAL STUDS
CLIP STUD TO STRUCTURAL STEEL.
BRICK VENEER.
1/2" EXTERIOR GRADE SHEATHING
6" BATT INSULATION
672' - 3"
BRICK ROWLOCK COURSE.
BRICK SOLDIER COURSE.
B/STEEL
1/2"
1/2"
1/2"
THRU-WALL FLASHING.
STEEL ANGLE - SEE STRUCTURAL
DRAWINGS
STRUCTURAL STEEL - SEE STRUCTURAL
DWGS.
1'-2 1/8"
BRICK SOLDIER COURSE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ D o c u m e n ts \F
F E
C h ill ic o th e
R e n o v a te
B p a tr ic k .h ill ie r@ ff e
-s e rv .c o m
.r v t
/1
/2
:4
:4
P
M
A511
EXTERIOR SECTION DETAILS RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
1 1/2" = 1'-0"A511
3 HIGH BAY WINDOW HEAD DETAIL AT EXISTING WALL
1 1/2" = 1'-0"A511
4 HIGH BAY WINDOW SILL DETAIL AT EXISTING WALL
1 1/2" = 1'-0"A511
6 CURTAIN WALL HEAD DETAIL AT EXISTING WALL
1 1/2" = 1'-0"A511
7 CURTAIN WALL SILL DETAIL AT EXISTING WALL
1 1/2" = 1'-0"A511
9 STOREFRONT HEAD DETAIL AT EXISTING WALL - CMU
1 1/2" = 1'-0"A511
10 STOREFRONT SILL DETAIL AT EXISTING WALL
1 1/2" = 1'-0"A511
5 EXISTING CLERESTORY WINDOW JAMB
1 1/2" = 1'-0"A511
11 ROOF DETAIL-ROOF DRAIN
1 1/2" = 1'-0"A511
1 ROOF TIE-IN TO EXISTING BUILDING
1 1/2" = 1'-0"A511
2 NEW PARAPET AND WINDOW DETAIL
S E
E E
L E
V A
T
IO
N S
T Y
P
IC
A L
P.LAM FINISH UNDERSIDE
OF TOE KICK
" 3"
BASE AS SCHEDULED
NON-COMBUSTIBLE
WOOD BLOCKING
FINISHED FLOOR
PROVIDE NON-COM. WOOD
BLOCKING AS REQUIRED IN STUD
TO SUPPORT BASE CABINET. TYP.
PLASTIC LAMINATE BASE CABINET,
DRAWER(S) AND ADJUSTABLE
SHELF; SHELF STANDARDS,
RECESSED FOR FLUSH INTERIORS
PROVIDE P.LAM DRAWER
DIVIDERS. CONSTRUCTION TO
HAVE CONCEALED FASTENERS
SOLID SURFACE COUNTERTOP
WITH BACK AND SIDE SPLASH
2'-1"
/2
P.LAM FINISH UNDERSIDE
OF TOE KICK
BASE AS SCHEDULED
NON-COMBUSTIBLE
WOOD BLOCKING
FINISHED FLOOR
PROVIDE NON-COM. WOOD
BLOCKING AS REQUIRED IN STUD
TO SUPPORT BASE CABINET. TYP.
PLASTIC LAMINATE BASE CABINET,
DRAWERS; REFER TO SPEC FOR
APPROVED CONSTRUCTION
METHOD.
SOLID SURFACE COUNTERTOP
WITH BACK AND SIDE SPLASH
2'-1"
/2
1' - 3"
PROVIDE NON-COM. WOOD
BLOCKING AS REQUIRED IN STUD
TO SUPPORT WALL CABINET. TYP.
PLASTIC LAMINATE WALL CABINET
BODY WITH ADJUSTABLE
SHELVES; SHELF STANDARDS,
RECESSED FOR FLUSH INTERIORS
AT 5/8" INCREMENTS.
CONSTRUCTION TO HAVE
CONCEALED FASTENERS
ALL SCHEDULED PARTITIONS
ASSEMBLIES ARE TO EXTEND
FROM TOP OF FLOOR SLAB TO
UNDERSIDE OF DECK ABOVE.
UNLESS NOTED OTHERWISE;
BRACE AS REQUIRED TO SECURE
TO STRUCTURE ABOVE
UNDERSIDE OF STRUCTURE
ABOVE;V.I.F.
2 X 2 CONTINUOUS ANODIZED
ALUMINUM ANGLE
S E
E E
L E
V A
T
IO
N S
V A
R
IE
S
V A
R
IE
S
S E
E E
L E
V A
T I O
N S
O R
T Y
P
IC
A L
CEILING SYSTEM PER
REFLECTED CEILING
PLAN
/2
PLASTIC LAMINATE
SLOPED TOP
.0
BASE AS SCHEDULED
FINISHED FLOOR
PLASTIC LAMINATE
COUNTERTOP WITH 4" BACK
AND SIDE SPLASH
S E
E E
L E
V A
T
IO
N S
H E
IG
H
T V
A R
IE
S
O
R
CONCEALED WORK STATION
BRACKET. PROVIDE
CONTINUOUS FRTW BLOCKING
AROUND PERIMETER.
2'-1"
9B.1
9B.2
9D.1 9D.2
CABINET DOOR
SCRIBE #2
CABINET DOOR
SCRIBE #2
CABINET DOOR
LIGHT VALANCE
WALL
CABINET DOOR
SCRIBE #2
WALL
CABINET DOOR
SCRIBE #2
CABINET PULL-
AFIX CABINET
PULL ABOVE
CABINET BOTTOM
A5.10
9B.1
A5.10
9B.2
SCRIBE #1
CABINET BODY
ALIGN
ALIGN
*NOTE: WHERE BASE AND WALL CABINETS APPEAR
WITHOUT DOORS, SCRIBE AND FILLER DETAIL
WILL BE REVIEWED IN SHOP DRAWING PHASE.
ALL SPECIAL CONDITIONS WILL BE ASSESSED
IN SHOP DRAWING SUBMITTALS.
CABINET BODY
ALIG
N
ALIGN
SCRIBE #1
CABINET DOOR
CABINET BODY
ALIGN
ALIGN
CABINET BODY
FASTENER TO BE
CONCEALED
*NOTE: VALANCE TO BE CONTINUOUS ACROSS
FRONT AND SIDES OF WALL CABINETS WHICH
ARE EXPOSED, WITH MINIMAL SEAMS.
WHERE SEAMS ARE NECESSARY,
PLACE SEAM ALIGNING WITH CABINET BODY JOINT.
SCRIBE #1
CABINET BODY
ALIGN
ALIGN
CABINET BODY
ALIGN
ALIGN
SCRIBE #1
CABINET DOOR
CABINET BODY
ALIGN
ALIGN
FILLER PANEL TO BE FLUSH
WITH CABINET BODY FACE
SCRIBE TO BE FLUSH WITH
FACE OF CABINET DOOR
*NOTE: WHERE WALL CABINETS
DO NOT ABUT A SOFFIT,
FILLER IS TO RUN
CONTINUOUSLYACROSS THE TOP OF THE
CABINET TO BACK WALL.
SOFFIT
TYPICAL WALL
CABINET
ALIGN
FILLER PANEL TO BE FLUSH
WITH CABINET BODY FACE
SCRIBE TO BE FLUSH WITH
FACE OF CABINET DOOR
SILENCER
COUNTER SINK
HARDWARE
BASE AS SCHEDULED
TYPICAL BASE
CABINET
*NOTE: THESE DRAWINGS ARE MEANT
TO EXPRESS INTENT OF
CASEWORK APPEARANCE ONLY
PLASTIC LAMINATE
SHELVES, PL-1
PLASTIC LAMINATE
TOP WITH BACK
SPLASH, PL-2
TOE KICK
A520
P.LAM FINISH UNDERSIDE
OF TOE KICK
BASE AS SCHEDULED
NON-COMBUSTIBLE
WOOD BLOCKING
FINISHED FLOOR
PROVIDE NON-COM. WOOD
BLOCKING AS REQUIRED IN STUD
TO SUPPORT BASE CABINET. TYP.
PLASTIC LAMINATE BASE CABINET,
SHELVES; REFER TO SPEC FOR
APPROVED CONSTRUCTION
METHOD.
P.LAM COUNTERTOP WITH
BACK SPLASH
3'-1"
/2
PLAM COUNTER,
PL-2 WITH BACKSPLASH
PLAM CABINETS,
PL-1
FILLER PANEL
FILLER PANEL
FILLER PANEL
3'-0"3'-0"3'-0"3'-0"
12'-2 3/4" +/- 12'-2 3/4" +/-
3'-0"3'-0"3'-0"3'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTATION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
T 513.241.4474
720 E Pete Rose Way, Cincinnati, OH 45202
F 513.241.0081
ISSUED FOR BID
Ryan Jeter
C U s e rs
\p a tr i\ O n e
D ri v e
\D o c u m e n ts
\R
V
A C h ill ic o th e
B ld g
R e n o v a ti o n p a tr ic k .h ill ie r@ ff e -s e rv
.c o m
.r v t
/1
/2
:3
:0
P
M
A520
CASEWORK SECTIONS AND
DETAILS
RENOVATE B25 TO IMPROVE
EFFICIENCY
Chillicothe VA Medical Center
538-16-101
07/20/2020 BJR JRR
1" = 1'-0"A520
BC01 BC01 - CW-TYP. BASE CABINET
1" = 1'-0"A520
BC02 BC02 - CW-BASE DRAWERS
1" = 1'-0"A520
UC01 UC01 - CW-TYP. WALL CABINET
1" = 1'-0"A520
MC03 MC03 - CW-COUNTERTOP WITH CONCEALED BRACKET
3" = 1'-0"A520
3 CW-TYPICAL CW DETAILS
1" = 1'-0"A520
2 CW - SHEET STORAGE SHELVES ELEVATION
1" = 1'-0"A520
1 CW- SHEET STORAGE SHELVES
3/8" = 1'-0"A520
4 WORKSHOP CASEWORK (ALTERNATE 3)
6.1
J
/8
3'-3 5/8"
4"
1'-10 1/8"
/8
STANDARD BRICK - 3/8" JOINT
2" RIGID INSULATION.
8" CMU.
8" CMU.
6" CMU.
3" AIRSPACE1" AIRSPACE
CONTINUOUS LIQUID-
APPLIED AIR & MOISTURE
BARRIER
ADJUSTABLE BRICK TIE 16"
O.C. VERTICAL AND 24" O.C.
HORIZONTAL
4"
STEEL FRAMING. SEE
STRUCTURAL DRAWING
DOVETAIL ANCHOR TO COLUMN
AT 16" O.C. VERTICAL
6.1
H
EXISTING EXTERIOR
WALL.
INFILL OPENING TO
MATCH EXISTING.
1" EXPANSION JOINT WITH
PRE-COMPRESSED JOINT
SYSTEM.
BRICK VENEER.
2" CONTINUOUS
RIGID INSULATION.
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER.
1" AIR SPACE.
1/2" EXTERIOR SHEATHING.
6" METAL STUDS AT 16" O.C.
STEEL FRAMING - SEE
STRUCTURAL
DRAWINGS.
5/8" GYPSUM BOARD.
VAPOR BARRIER.
A310
6.1
J
/8
/8
ADJUSTABLE BRICK TIE 16"
O.C. VERTICAL AND 24" O.C.
HORIZONTAL
STANDARD BRICK - 3/8" JOINT
2" RIGID INSULATION.
5/8" TYPE X GYPSUM BOARD.
1/2" GYPSUM SHEATHING.
3" AIRSPACE
1" AIRSPACE
CONTINUOUS LIQUID-APPLIED
AIR & MOISTURE BARRIER
VAPOR BARRIER.
8" METAL STUDS AT CORNER
BUMP-OUT.
6" METAL STUDS AT 16" O.C.
3'-3 3/4"3/8"
STRUCTURAL FRAMING - SEE
STRUCTURAL DRAWINGS.
A530 A602
J
1" AIRSPACE
3" AIRSPACE
STANDARD BRICK - 3/8" JOINT
ADJUSTABLE BRICK TIE 16"
O.C. VERTICAL AND 24" O.C.
HORIZONTAL
2" RIGID INSULATION.
1/2" GYPSUM SHEATHING.
2-1/2" X 7-1/2" ALUMINUM BLAST-
RESISTANT WINDOWS SYSTEM
W/FINISH TO MATCH EXISTING
WINDOWS ON BUILDING. NEW
GLASS TO BE LAMINATED,
INSULATING…