Ft. Wayne and Marion IN VAMC - Asbestos Reinspection Report - August 2016.pdf

PDF 2 MB Posted

Attached to
Amendment 02 -Correct Legionella Deficiencies & Provide Monitoring - 610A4-18-104
Solicitation number
36C25020B0051
Issued by

About this file

This federal solicitation seeks proposals for Correct Legionella Deficiencies and Provide Monitoring services at the Northern IN VA Healthcare System facilities in Fort Wayne, Indiana. The selected contractor will be responsible for providing all tools, equipment, parts, materials, labor and supervision to complete the required Legionella remediation and monitoring work according to the attached statement of work. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
36C25020B0051 0002.pdf PDF
Consolidated Pre-bid RFIs_Answered.pdf PDF
36C25020B0051 0001.pdf PDF
610A4-18-104 PreBid Sign-In 20200715.pdf PDF
RFI Responses.pdf PDF
05 Combined Specs.pdf PDF
Wage Rate IN20200002.pdf PDF
Contractor Certification Regarding Safety and Environmental.docx DOCX document
RFI Form.doc DOC document
06 Drawings.pdf PDF
36C25020B0051.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS REINSPECTION REPORT

for the

DEPARTMENT OF VETERANS AFFAIRS

FT. WAYNE VAMC

FT. WAYNE, IN

MARION VAMC

MARION, IN

RFQ #:

VA251-16-Q-0346

INSPECTION DATES:

AUGUST 15-19, 2016

PRIME CONTRACTOR:

USFIN DEVELOPMENT, LLC.

7920 N. WOODBRIDGE RD.

MONCLOVA, OH 43542

419-382-9574

FT. WAYNE AND MARION, IN VAMC

AUGUST 2016

TABLE OF CONTENTS

1.0

2.0

ASBESTOS INSPECTION SUMMARY

APPENDICES

Appendix A – Asbestos Inventory by Building – Marion VAMC

Appendix B – Asbestos Inventory by Building – Ft. Wayne VAMC

Appendix C - Inspector Certifications

FT. WAYNE AND MARION, IN VAMC

AUGUST 2016

List of Acronyms

ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning IDEM Indiana Department of Environmental Management MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation USFin USFin Development, LLC VA United States Department of Veterans Affairs VAMC VA Medical Center XRD X-Ray Diffraction

1.0 ASBESTOS INSPECTION SUMMARY

EXECUTIVE SUMMARY

From August 15-19, 2016, USFin performed an asbestos reinspection Ft. Wayne and Marion, IN VAMC accordance with RFQ VA251-16-Q-0346. The purpose of the inspection was to update existing survey information from the previous asbestos reinspection conducted in 2013. All accessible functional areas in the facilities were surveyed. All previous asbestos survey information and sampling conducted at the facilities were evaluated and incorporated into this survey. All confirmed asbestos-containing materials were verified. This report can be incorporated into the facility’s management plan for asbestos-containing materials.

The inspection was conducted by Brett Brumbaugh and Sam Ansara (USFin). All USFin inspectors are EPA trained and state licensed to conduct asbestos inspections. The project manager was Mr. Brumbaugh who has been conducting asbestos surveys, sampling, and asbestos management planning work since 1987.

Previous sampling results and inventory spreadsheets from the previous survey and additional asbestos information provided by the current staff of the VAMC were used in this report. No additional samples of newly identified suspect materials were collected during this inspection.

Certain areas such as inaccessible pipe chases, areas above fixed permanent ceilings, and flooring materials located beneath carpeting were not inspected or tested.

2.0 ASBESTOS BACKGROUND

The term asbestos describes six naturally occurring fibrous minerals found in certain types of rock formations. The minerals chrysotile, amosite, and crocidolite have been most commonly used in building products such as floor tile, pipe insulation, boiler insulation, asbestos cement materials, roofing materials, and plasters. The minerals anthophyllite, actinolite, and tremolite are not frequently found in ACBM.

Intact and undisturbed ACBM do not pose a health risk. They may, however, become a health hazard if they are damaged, disturbed, or deteriorate over time and release fibers into the air. If released into the air, asbestos fibers may be inhaled. After prolonged or intense exposure, inhaled asbestos fibers may cause various types of lung disease. The health risks associated with asbestos exposure are greater for those who smoke.

3.0 REGULATORY BACKGROUND

3.1 Federal Regulations

The United States Environmental Protection Agency (EPA), the Occupational Safety and Health Administration (OSHA), and delegated states are responsible for regulating environmental exposure and protecting workers from asbestos exposure. OSHA is responsible for the health and safety of workers who may be exposed to asbestos in connection with their jobs (Occupational Exposure to Asbestos; Title 29, Code of Federal Regulations (CFR) Parts 1910.1001 and 1926.1101). The EPA and state regulators are responsible for developing and enforcing regulations necessary to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health.

In 1979, EPA began an asbestos technical assistance program for building owners, environmental groups, contractors, and industry. In May 1982, EPA issued the first regulation intended to control asbestos in schools under the authority of the Toxic Substances Control Act (TSCA); this regulation is known as the Asbestos-in-Schools Rule.

Two EPA regulations govern asbestos: the Asbestos Hazard Emergency Response Act (AHERA) and the National Emission Standards for Hazardous Air Pollutants (NESHAP).

AHERA

In 1986, Congress enacted AHERA (Title 40, CFR Part 763) which mandated a regulatory program to address the asbestos hazards in schools. A part of AHERA deals with the mandatory training and accreditation of persons who perform certain types of asbestos-related work in schools.

Subsequently, in 1990 Congress amended AHERA to extend some of the training and accreditation requirements to persons performing such work in public and commercial buildings.

AHERA requires inspections of school buildings to determine the conditions of ACBM and preparation of management plans which recommend the best way to reduce the asbestos hazards.

The United States Veterans Administration (VA) has adopted many of the requirements of AHERA for surveys performed at VA facilities. The methods may include removal, encapsulation, enclosure, repair, and operations and maintenance to protect human health and the environment from ACBM.

NESHAP

The Clean Air Act (CAA) of 1970 required EPA to develop and enforce regulations to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health; therefore, EPA promulgated NESHAP (Title 40, CFR Part 61) on April 6, 1973.

NESHAP is intended to minimize the release of asbestos fibers during certain activities (i.e., renovations, demolition, and installations). It specifies work practices to be followed during renovations of buildings (except apartment buildings that have no more than four dwelling units) which contain a specific amount of friable asbestos. NESHAP requires that buildings be inspected for ACBM prior to renovation/demolition projects.

NESHAP also requires owners and operators subject to the asbestos rules to notify delegated state and local agencies and/or the regional EPA offices before demolition or renovation activities begin. In addition, NESHAP requires the removal of all friable ACBM prior to demolition.

OSHA

OSHA began regulating workplace asbestos exposure in 1970, adopting a permissible exposure limit (PEL) to regulate worker exposure. The original asbestos standard has been revised several times to better protect workers. On August 10, 1994, OSHA issued a revised final standard regulating asbestos exposure in all industries. The newly revised standard for the construction industry lowers the PEL. The revised standard also establishes a new classification system for asbestos construction work, which clearly spells out mandatory work practices to follow to reduce worker exposures (see Occupational Exposure to Asbestos, Title 29, CFR 1926.1101).

3.2 State and Local Regulations

Indiana state regulations are similar to the Federal regulations. In many instances state and local asbestos regulations are more stringent, therefore, it is recommended that the applicable state asbestos regulation(s) be reviewed before the start of any renovation/demolition projects.

State asbestos regulations include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.

4.0 ANALYTICAL METHODS AND LIMITATIONS

4.1 Bulk Sampling Protocol

EPA and OSHA define an ACBM as any material which contains greater than 1percent asbestos (some state regulations may be more stringent). The ACBM inspection and bulk sampling were performed in accordance with the methods outlined in the EPA guidance document titled Guidance for Controlling Asbestos-Containing Materials in Buildings (Document No. 560/5-85/024). In addition, bulk sampling of asbestos was performed in accordance with 40 CFR Part 763, AHERA requirements for number of samples and types of ACBM to be sampled. According to these requirements, materials are classified as either surfacing (e.g., decorative plaster, spray-applied fireproofing), thermal system insulation (e.g., pipe insulation, pipe fitting insulation, boiler insulation), or miscellaneous materials (e.g., floor tile, ceiling tile, plaster, wallboard, mastics).

The number of samples collected from each material varies based on the classification of the material and increases as the potential for a non-uniform mixture of asbestos in the material increases. Typically, regulations require a minimum number of samples to be collected from the different classifications of suspect ACBM, as follows:

• Surfacing Material

a) Three samples from homogeneous areas up to 1,000 square feet

b) Five samples from homogeneous areas between 1,000 and 5,000 square feet

c) Seven samples from homogeneous areas over 5,000 square feet

• Thermal System Insulation

a) Minimum of three samples per homogeneous area

• Miscellaneous Material

a) Minimum of two samples per homogeneous area, but must be sufficient to determine asbestos content

5.0 SUMMARY OF FINDINGS

5.1 Survey Access Limitations

All accessible areas within the facilities were inspected for ACBM, including access panels to chases, areas above suspended ceilings, and crawl spaces. Any areas not inspected included non-accessible pipe chases, areas above plaster ceilings, areas above patient-care operations, secured areas, and areas occupied by patients where access could not be gained.

There were several buildings on the Marion VAMC campus that were fenced-in and no deemed safe for entry. These buildings are slated for demolition and include:

Building 7

Building 10

Building 13

Building 18

Building 24

Building 25

Building 35

Building 42

Building 50

Building 122

The areas not inspected, or where access could not be obtained, must be assumed to contain asbestos and be inspected prior to any renovation or demolition activities.

6.0 CONCLUSION/RECOMMENDATIONS

An operations and maintenance (O&M) program has been developed by the VAMC specifically for the positively identified ACBM in the facilities. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and VA-approved personnel and contractors. Since demolition was not performed as part of the inspection work at the facilities, certain areas such as pipe chases and areas above fixed permanent ceilings, fire-door interiors, and vault/safe wall and door linings were not inspected or tested. Prior to renovation and alteration work which could impact these areas, USFin recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed. USFin recommends sampling of roofing materials, duct mastics, laboratory equipment and electrical components (not specifically examined as part of this survey) if renovation activities are planned which may disturb these materials.

Project Manager:

Brett L. Brumbaugh – Project Manager

APPENDIX A

ASBESTOS INVENTORY BY BUILDING

MARION VAMC

Abreviation Material Identified

BT Black Tar

MCB Mastic on Cove base

FD Fire Door

ED Elevator Doors

ERT Exterior Roof Tar

EWC Exterior Window Caulk

IWC or IWG Interior Window Caulk / Glazing

FT Floor Tile

FT & MFT Floor Tile & Mastic on Floor Tile

MFT Mastic on Floor tile

PI Pipe Insulation

PJ Pipe Joist

DWC Drywall Compund

MCT Mastic on Ceiling Tile

Explanation of Survey

This column identifies asbestos containing (or assumed asbestos containing) material in the room.

This column identifies The quantity of material

This column contains notes on materials observed in the room

See chart below for an explanation of abreviations

Each tab at the bottom of this document is the survey for an individual building. Within each tab the room number and material identified is listed as seen below.

Bldg 1

Room/Area Material Description Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 90 SF Contain & Remove

Fire Door FD 1 door Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 32 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White /Gray Floor Tile w/Associated

Mastic Mastic Positive

MFT 32 SF

Mastic Associated w/ Floor Tile Positive on Previous Report.

Material not identified on Previous Report Good Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 170 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 144 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 120 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 80 SF Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

Hall outside Room

102 and 105

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 240 SF

Mastic Associated w/ Floor Tile Positive on Previous Report.

Material not identified on Previous Report Good Contain & Remove

106 - 4 Plaster Walls, Plaster Ceiling and Concrete Floor

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 260 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 2 door Material not identified on Previous Report Good Wrap & Remove

Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on

Previous Report

Mastic Associated w/ Floor Tile Positive on Previous Report.

Material not identified on Previous Report

Mastic Associated w/ Floor Tile Positive on Previous Report. Fire

Door not identified on Previous Report

Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data

Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on

Previous Report st

Floor

Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on

Previous Report.

Good

100A

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data Hall outside Room

107 & Room 108

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 330 SF

Mastic Associated w/ Floor Tile Positive on Previous Report.

Material not identified on Previous Report Good Contain & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT Material not identified on Previous Report Good Contain & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 50 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 120 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 224 SF Good Contain & Remove

TransiteBlackboard BB 2 blackboar d Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report. Area identified as 1-C-2 Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 78 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Contain & Remove

Pipe Insulation PI 10 LF Wall Chase in room s approximately 10lin.ft. of pipe Contain, Glove Bag &

Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 140 SF Material identified not on Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report. Area identified as 1-C-2 Good Wrap & Remove

Material not identified on Previous Report. 2 blackboards, one green and one black.

Good

Hallway outside

Room115

Hallway outside

Room113

70 SF

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 116 Exterior Window Caulk EWC 26 windows

Plaster Ceiling, Floor Tile and Mastic identified not on Previous

Report.

Good Regulated Area

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT Good

1x1 White/Gray Floor Tile w/Associated

Mastic Mastic Positive MFT Good

Fire Door FD 1 door Fire Door Assumed Material identified not on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 120 SF Floor Tile and Mastic identified not on Previous Report. Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

119 Fire Door FD 1 door Fire Door Assumed Material identified not on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 324 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

120A 1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT 20 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive

MFT 15 SF

Material identified on Previous Report was not found during inspection Good Contain & Remove

200 Fire Door FD 1 door Fire Door Assumed on Previous Report

204 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Wrap & Remove

Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data nd

Floor and Attic

1899 SF

Drywall Ceiling, Mastic Associated w/ Floor Tile Positive on

Previous Report.

Contain & Remove

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 White & Beige Mottled Floor Tile w/

Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

Attic Exterior Window Caulk EWC 12 windows Exterior Window Caulk Positive Good Regulated Area

Bldg 2

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

001 Fire Door FD 1 door Concrete Floor, partial Plaster wall and ceiling. Fiberglass pipe lines, Fire Door Assumed Good Wrap & Remove

002 Fire Door FD 1 door Brick Walls, Concrete Floor and Fiberglass pipe lines, Fire Door

Assumed Good Wrap & Remove

003 Fire Door FD 1 door Concrete Floor and Partial Drywall on 3 walls. Fire Door Assumed Good Wrap & Remove

004 Fire Door FD 1 door Concrete Floor and Plaster Ceiling. Fiberglass line and Aircell insulation visible at ceiling. Fire Door Assumed Good Wrap & Remove

005A Fire Door FD 1 door Concrete Floor and Plaster with Skim coat walls. Fire Door Assumed Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 144 SF

Mastic Associated w/ Floor Tile Assumed to be Positive on Previous

Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 135 SF Floor Tile Assumed to be Positive on Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 30 SF Floor Tile Assumed to be Positive on Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 312 SF Floor Tile Assumed to be Positive on Previous Report F Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 153 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 342 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 32 SF FT1 not identified during inspection as noted on previous report; Good Contain & Remove

Basement

1st Floor

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Basement

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 140 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Fire door not identified during inspection as noted on previous report

Good Contain & Remove

109 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 84 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report; Fire door not identified during inspection as noted on previous report

Good Contain & Remove

111 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 120 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 110 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report;

Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 180 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 208 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 208 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 28 SF

Drywall Ceiling, Mastic Associated w/ Floor Tile Positive on Previous

Report.

Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 108 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 198 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Basement

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 324 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 323 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 202 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1-S-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 99 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1-C-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 180 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1-C-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 357 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1-C-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 225 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 190 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 70 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

201 Fire Door FD 1 door Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 120 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1-S-1

1-C-4 nd

Floor

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Basement 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 120 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Fire door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 108 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Fire door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 108 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 156 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 120 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 140 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 96 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 187 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 180 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 180 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 340 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Basement

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 90 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 200 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 168 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 224 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 250 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 100 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 126 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 126 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 150 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

2-S-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 60 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

2-S-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 60 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Basement

2-S-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 80 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

2-C-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 450 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

2-C-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 220 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report Good Contain & Remove

2-C-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive

MFT 225 SF

Floor Tile with Associated Mastic Assumed to be Positive on

Previous Report. Quantity Includes hall outside Room 206 Good Contain & Remove st Floor EWC 32 windows Good Regulated Area nd

Floor EWC 40 windows Good Regulated Area

Attic EWC 16 windows Good Regulated Area

Exterior Black Window Caulk Exterior Black Window Caulk Positive

Bldg 3

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

1 Interior Window Caulk IWC 2 windows Interior window caulk positive Good Contain & Remove

2 Interior Window Caulk IWC 4 windows Interior window caulk positive Good Contain & Remove

2A Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove

3 Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove

4 Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove

5 Interior Window Caulk IWC 5 windows Interior window caulk positive Good Contain & Remove

5A Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove

6 Interior Window Caulk IWC 2 windows Interior window caulk positive Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 95 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 80 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 162 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 120 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Basement st

Floor

Mastic Associated w/ Floor Tile Positive on Previous Report

Fire Door Assumed on previous report.

100A Mastic Associated w/ Floor Tile Positive on Previous Report

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report: Interior

Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door

Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 120 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 84.5 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 76.5 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 36 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 20 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove

Interior Window Caulk IWC 3 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 252 SF Good Contain & Remove

Interior Window Caulk IWC 3 windows Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 63 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Mastic Associated w/ Floor Tile Positive on Previous Report:

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Fire Door Assumed on previous Report Mastic Associated w/ Floor

Tile Positive on Previous Report Fire Door Assumed on previous report.

105A Mastic Associated w/ Floor Tile Positive on Previous Report

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report:

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

108 A/B

Mastic Associated w/ Floor Tile Positive on Previous Report: Interior

Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door

Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report : Interior

Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door

Assumed on previous report.

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 112.5 SF Contain & Remove

Interior Window Caulk IWC 1 window Contain & Remove

Fire Door FD 1 door Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 117 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 130.5 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 104 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 98 SF Good Contain & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

115 Interior Window Caulk IWC 1 window Interior Window Caulk not identified on previous report. Good Contain & Remove

Interior Window Caulk IWC 27 windows Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 696 SF Good Contain & Remove

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report: Interior

Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door

Assumed on previous report.

Good

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

116/Porch Interior Window Caulk not identified on previous report: Mastic

Associated w/ Floor Tile Positive on Previous Report .

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 1450 SF Good Contain & Remove

Interior Window Caulk IWC 7 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 168 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 340 SF Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 30 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Fire Door FD 1 door Good Wrap & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 35 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Fire Door FD 1 door Good Wrap & Remove

Interior Window Caulk IWC 1 window Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 250 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Mastic Associated w/ Floor Tile Positive on Previous Report :

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report: Interior

Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door

Assumed on previous report.

Mastic Associated w/Floor Tile Positive on Previous Report. Fire

Door Assumed on previous report.

120A Mastic Associated w/ Floor Tile Positive on Previous Report : Fire

Door Assumed on previous report.

1-S-1 Fire Door Assumed on previous report.

1-S-2 Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

1-S-3 Fire Door Assumed on previous report. Interior Window

Caulk not identified on previous report

1-C-1 Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

1-C-1A Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 144 SF Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 224 SF Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 384 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 340 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 300 SF Good Contain & Remove

Interior Window Caulk IWC 5 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 55 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 340 SF Good Contain & Remove

Interior Window Caulk IWC 3 windows Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 153 SF Good Contain & Remove

Interior Window Caulk IWC 1 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Mastic Associated w/Floor Tile Positive on Previous Report.

Interior Window Caulk not identified on previous report

Mastic Associated w/Floor Tile Positive on Previous Report.

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive

1-C-1B Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

1-C-2 Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

nd

Floor

Mastic Associated w/Floor Tile Positive on Previous Report.

Interior Window Caulk not identified on previous report

Mastic Associated w/ Floor Tile Positive on Previous Report

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/Floor Tile Positive on Previous Report. Fire

Door Assumed on previous report.

Mastic Associated w/Floor Tile Positive on Previous Report.

Fire Door Assumed on previous report.

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 52 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove

208 Fire Door FD 1 door Fire Door Assumed on previous report Good Wrap & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 50 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

Interior Window Caulk IWC 5 windows Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 425 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 320 SF Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 384 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 280 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

Fire Door FD 1 door Good Wrap & Remove

213A 1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 42 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove

1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 7 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove

Fire Door Assumed on previous report. Mastic Associated w/ Floor

Tile Positive on Previous Report

Fire Door Assumed on previous report. Interior Window Caulk not identified on previous report. Sample collected during current inspection. Positive Mastic Associated w/ Floor Tile Positive on

Previous Report

Mastic Associated w/ Floor Tile Positive on Previous Report

Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.

Fire Door Assumed on previous report.

Mastic Associated w/ Floor Tile Positive on Previous Report

Fire Door Assumed on previous report.

Fire Door Assumed on previous report. Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive Mastic Associated w/ Floor Tile Positive on

Previous Report

Material

Abbr.

Material

Quantity

Unit of

Measure Comments Condition Method of Abatement

Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor

Tile w/ Associated Mastic Mastic

Positive

MFT 750 SF Good Contain & Remove

Interior Window Caulk IWC 2 windows Good Contain & Remove

Fire Door FD 2 doors Good Wrap & Remove

2-C-2 1’x1’ White with Brown Splotches Floor

Tile w/Associated Mastic Mastic Positive MFT 468 SF Mastic…