Ft. Wayne and Marion IN VAMC - Asbestos Reinspection Report - August 2016.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25020B0051
About this file
This federal solicitation seeks proposals for Correct Legionella Deficiencies and Provide Monitoring services at the Northern IN VA Healthcare System facilities in Fort Wayne, Indiana. The selected contractor will be responsible for providing all tools, equipment, parts, materials, labor and supervision to complete the required Legionella remediation and monitoring work according to the attached statement of work. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0051 0002.pdf | ||
| Consolidated Pre-bid RFIs_Answered.pdf | ||
| 36C25020B0051 0001.pdf | ||
| 610A4-18-104 PreBid Sign-In 20200715.pdf | ||
| RFI Responses.pdf | ||
| 05 Combined Specs.pdf | ||
| Wage Rate IN20200002.pdf | ||
| Contractor Certification Regarding Safety and Environmental.docx | DOCX document | |
| RFI Form.doc | DOC document | |
| 06 Drawings.pdf | ||
| 36C25020B0051.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS REINSPECTION REPORT
for the
DEPARTMENT OF VETERANS AFFAIRS
FT. WAYNE VAMC
FT. WAYNE, IN
MARION VAMC
MARION, IN
RFQ #:
VA251-16-Q-0346
INSPECTION DATES:
AUGUST 15-19, 2016
PRIME CONTRACTOR:
USFIN DEVELOPMENT, LLC.
7920 N. WOODBRIDGE RD.
MONCLOVA, OH 43542
419-382-9574
FT. WAYNE AND MARION, IN VAMC
AUGUST 2016
TABLE OF CONTENTS
1.0
2.0
ASBESTOS INSPECTION SUMMARY
APPENDICES
Appendix A – Asbestos Inventory by Building – Marion VAMC
Appendix B – Asbestos Inventory by Building – Ft. Wayne VAMC
Appendix C - Inspector Certifications
FT. WAYNE AND MARION, IN VAMC
AUGUST 2016
List of Acronyms
ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning IDEM Indiana Department of Environmental Management MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation USFin USFin Development, LLC VA United States Department of Veterans Affairs VAMC VA Medical Center XRD X-Ray Diffraction
1.0 ASBESTOS INSPECTION SUMMARY
EXECUTIVE SUMMARY
From August 15-19, 2016, USFin performed an asbestos reinspection Ft. Wayne and Marion, IN VAMC accordance with RFQ VA251-16-Q-0346. The purpose of the inspection was to update existing survey information from the previous asbestos reinspection conducted in 2013. All accessible functional areas in the facilities were surveyed. All previous asbestos survey information and sampling conducted at the facilities were evaluated and incorporated into this survey. All confirmed asbestos-containing materials were verified. This report can be incorporated into the facility’s management plan for asbestos-containing materials.
The inspection was conducted by Brett Brumbaugh and Sam Ansara (USFin). All USFin inspectors are EPA trained and state licensed to conduct asbestos inspections. The project manager was Mr. Brumbaugh who has been conducting asbestos surveys, sampling, and asbestos management planning work since 1987.
Previous sampling results and inventory spreadsheets from the previous survey and additional asbestos information provided by the current staff of the VAMC were used in this report. No additional samples of newly identified suspect materials were collected during this inspection.
Certain areas such as inaccessible pipe chases, areas above fixed permanent ceilings, and flooring materials located beneath carpeting were not inspected or tested.
2.0 ASBESTOS BACKGROUND
The term asbestos describes six naturally occurring fibrous minerals found in certain types of rock formations. The minerals chrysotile, amosite, and crocidolite have been most commonly used in building products such as floor tile, pipe insulation, boiler insulation, asbestos cement materials, roofing materials, and plasters. The minerals anthophyllite, actinolite, and tremolite are not frequently found in ACBM.
Intact and undisturbed ACBM do not pose a health risk. They may, however, become a health hazard if they are damaged, disturbed, or deteriorate over time and release fibers into the air. If released into the air, asbestos fibers may be inhaled. After prolonged or intense exposure, inhaled asbestos fibers may cause various types of lung disease. The health risks associated with asbestos exposure are greater for those who smoke.
3.0 REGULATORY BACKGROUND
3.1 Federal Regulations
The United States Environmental Protection Agency (EPA), the Occupational Safety and Health Administration (OSHA), and delegated states are responsible for regulating environmental exposure and protecting workers from asbestos exposure. OSHA is responsible for the health and safety of workers who may be exposed to asbestos in connection with their jobs (Occupational Exposure to Asbestos; Title 29, Code of Federal Regulations (CFR) Parts 1910.1001 and 1926.1101). The EPA and state regulators are responsible for developing and enforcing regulations necessary to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health.
In 1979, EPA began an asbestos technical assistance program for building owners, environmental groups, contractors, and industry. In May 1982, EPA issued the first regulation intended to control asbestos in schools under the authority of the Toxic Substances Control Act (TSCA); this regulation is known as the Asbestos-in-Schools Rule.
Two EPA regulations govern asbestos: the Asbestos Hazard Emergency Response Act (AHERA) and the National Emission Standards for Hazardous Air Pollutants (NESHAP).
AHERA
In 1986, Congress enacted AHERA (Title 40, CFR Part 763) which mandated a regulatory program to address the asbestos hazards in schools. A part of AHERA deals with the mandatory training and accreditation of persons who perform certain types of asbestos-related work in schools.
Subsequently, in 1990 Congress amended AHERA to extend some of the training and accreditation requirements to persons performing such work in public and commercial buildings.
AHERA requires inspections of school buildings to determine the conditions of ACBM and preparation of management plans which recommend the best way to reduce the asbestos hazards.
The United States Veterans Administration (VA) has adopted many of the requirements of AHERA for surveys performed at VA facilities. The methods may include removal, encapsulation, enclosure, repair, and operations and maintenance to protect human health and the environment from ACBM.
NESHAP
The Clean Air Act (CAA) of 1970 required EPA to develop and enforce regulations to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health; therefore, EPA promulgated NESHAP (Title 40, CFR Part 61) on April 6, 1973.
NESHAP is intended to minimize the release of asbestos fibers during certain activities (i.e., renovations, demolition, and installations). It specifies work practices to be followed during renovations of buildings (except apartment buildings that have no more than four dwelling units) which contain a specific amount of friable asbestos. NESHAP requires that buildings be inspected for ACBM prior to renovation/demolition projects.
NESHAP also requires owners and operators subject to the asbestos rules to notify delegated state and local agencies and/or the regional EPA offices before demolition or renovation activities begin. In addition, NESHAP requires the removal of all friable ACBM prior to demolition.
OSHA
OSHA began regulating workplace asbestos exposure in 1970, adopting a permissible exposure limit (PEL) to regulate worker exposure. The original asbestos standard has been revised several times to better protect workers. On August 10, 1994, OSHA issued a revised final standard regulating asbestos exposure in all industries. The newly revised standard for the construction industry lowers the PEL. The revised standard also establishes a new classification system for asbestos construction work, which clearly spells out mandatory work practices to follow to reduce worker exposures (see Occupational Exposure to Asbestos, Title 29, CFR 1926.1101).
3.2 State and Local Regulations
Indiana state regulations are similar to the Federal regulations. In many instances state and local asbestos regulations are more stringent, therefore, it is recommended that the applicable state asbestos regulation(s) be reviewed before the start of any renovation/demolition projects.
State asbestos regulations include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.
4.0 ANALYTICAL METHODS AND LIMITATIONS
4.1 Bulk Sampling Protocol
EPA and OSHA define an ACBM as any material which contains greater than 1percent asbestos (some state regulations may be more stringent). The ACBM inspection and bulk sampling were performed in accordance with the methods outlined in the EPA guidance document titled Guidance for Controlling Asbestos-Containing Materials in Buildings (Document No. 560/5-85/024). In addition, bulk sampling of asbestos was performed in accordance with 40 CFR Part 763, AHERA requirements for number of samples and types of ACBM to be sampled. According to these requirements, materials are classified as either surfacing (e.g., decorative plaster, spray-applied fireproofing), thermal system insulation (e.g., pipe insulation, pipe fitting insulation, boiler insulation), or miscellaneous materials (e.g., floor tile, ceiling tile, plaster, wallboard, mastics).
The number of samples collected from each material varies based on the classification of the material and increases as the potential for a non-uniform mixture of asbestos in the material increases. Typically, regulations require a minimum number of samples to be collected from the different classifications of suspect ACBM, as follows:
• Surfacing Material
a) Three samples from homogeneous areas up to 1,000 square feet
b) Five samples from homogeneous areas between 1,000 and 5,000 square feet
c) Seven samples from homogeneous areas over 5,000 square feet
• Thermal System Insulation
a) Minimum of three samples per homogeneous area
• Miscellaneous Material
a) Minimum of two samples per homogeneous area, but must be sufficient to determine asbestos content
5.0 SUMMARY OF FINDINGS
5.1 Survey Access Limitations
All accessible areas within the facilities were inspected for ACBM, including access panels to chases, areas above suspended ceilings, and crawl spaces. Any areas not inspected included non-accessible pipe chases, areas above plaster ceilings, areas above patient-care operations, secured areas, and areas occupied by patients where access could not be gained.
There were several buildings on the Marion VAMC campus that were fenced-in and no deemed safe for entry. These buildings are slated for demolition and include:
Building 7
Building 10
Building 13
Building 18
Building 24
Building 25
Building 35
Building 42
Building 50
Building 122
The areas not inspected, or where access could not be obtained, must be assumed to contain asbestos and be inspected prior to any renovation or demolition activities.
6.0 CONCLUSION/RECOMMENDATIONS
An operations and maintenance (O&M) program has been developed by the VAMC specifically for the positively identified ACBM in the facilities. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and VA-approved personnel and contractors. Since demolition was not performed as part of the inspection work at the facilities, certain areas such as pipe chases and areas above fixed permanent ceilings, fire-door interiors, and vault/safe wall and door linings were not inspected or tested. Prior to renovation and alteration work which could impact these areas, USFin recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed. USFin recommends sampling of roofing materials, duct mastics, laboratory equipment and electrical components (not specifically examined as part of this survey) if renovation activities are planned which may disturb these materials.
Project Manager:
Brett L. Brumbaugh – Project Manager
APPENDIX A
ASBESTOS INVENTORY BY BUILDING
MARION VAMC
Abreviation Material Identified
BT Black Tar
MCB Mastic on Cove base
FD Fire Door
ED Elevator Doors
ERT Exterior Roof Tar
EWC Exterior Window Caulk
IWC or IWG Interior Window Caulk / Glazing
FT Floor Tile
FT & MFT Floor Tile & Mastic on Floor Tile
MFT Mastic on Floor tile
PI Pipe Insulation
PJ Pipe Joist
DWC Drywall Compund
MCT Mastic on Ceiling Tile
Explanation of Survey
This column identifies asbestos containing (or assumed asbestos containing) material in the room.
This column identifies The quantity of material
This column contains notes on materials observed in the room
See chart below for an explanation of abreviations
Each tab at the bottom of this document is the survey for an individual building. Within each tab the room number and material identified is listed as seen below.
Bldg 1
Room/Area Material Description Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 90 SF Contain & Remove
Fire Door FD 1 door Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 32 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White /Gray Floor Tile w/Associated
Mastic Mastic Positive
MFT 32 SF
Mastic Associated w/ Floor Tile Positive on Previous Report.
Material not identified on Previous Report Good Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 170 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 144 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 120 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 80 SF Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
Hall outside Room
102 and 105
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 240 SF
Mastic Associated w/ Floor Tile Positive on Previous Report.
Material not identified on Previous Report Good Contain & Remove
106 - 4 Plaster Walls, Plaster Ceiling and Concrete Floor
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 260 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 2 door Material not identified on Previous Report Good Wrap & Remove
Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on
Previous Report
Mastic Associated w/ Floor Tile Positive on Previous Report.
Material not identified on Previous Report
Mastic Associated w/ Floor Tile Positive on Previous Report. Fire
Door not identified on Previous Report
Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data
Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on
Previous Report st
Floor
Mastic Associated w/ Floor Tile Positive and Fire Door Assumed on
Previous Report.
Good
100A
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data Hall outside Room
107 & Room 108
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 330 SF
Mastic Associated w/ Floor Tile Positive on Previous Report.
Material not identified on Previous Report Good Contain & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT Material not identified on Previous Report Good Contain & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 130 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 50 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Material not identified on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 120 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 224 SF Good Contain & Remove
TransiteBlackboard BB 2 blackboar d Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report. Area identified as 1-C-2 Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 78 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Contain & Remove
Pipe Insulation PI 10 LF Wall Chase in room s approximately 10lin.ft. of pipe Contain, Glove Bag &
Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 140 SF Material identified not on Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report. Area identified as 1-C-2 Good Wrap & Remove
Material not identified on Previous Report. 2 blackboards, one green and one black.
Good
Hallway outside
Room115
Hallway outside
Room113
70 SF
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 116 Exterior Window Caulk EWC 26 windows
Plaster Ceiling, Floor Tile and Mastic identified not on Previous
Report.
Good Regulated Area
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT Good
1x1 White/Gray Floor Tile w/Associated
Mastic Mastic Positive MFT Good
Fire Door FD 1 door Fire Door Assumed Material identified not on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 120 SF Floor Tile and Mastic identified not on Previous Report. Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
119 Fire Door FD 1 door Fire Door Assumed Material identified not on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 324 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
120A 1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT 20 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive
MFT 15 SF
Material identified on Previous Report was not found during inspection Good Contain & Remove
200 Fire Door FD 1 door Fire Door Assumed on Previous Report
204 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 White with Tan Splotches Floor Tile w/Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Wrap & Remove
Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data nd
Floor and Attic
1899 SF
Drywall Ceiling, Mastic Associated w/ Floor Tile Positive on
Previous Report.
Contain & Remove
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 1 is no longer accessible and fenced in. All assessments are based on the prior reinspection data
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 White & Beige Mottled Floor Tile w/
Associated Mastic Mastic Positive MFT SF Mastic Associated w/ Floor Tile Positive on Previous Report. damaged Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
Attic Exterior Window Caulk EWC 12 windows Exterior Window Caulk Positive Good Regulated Area
Bldg 2
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
001 Fire Door FD 1 door Concrete Floor, partial Plaster wall and ceiling. Fiberglass pipe lines, Fire Door Assumed Good Wrap & Remove
002 Fire Door FD 1 door Brick Walls, Concrete Floor and Fiberglass pipe lines, Fire Door
Assumed Good Wrap & Remove
003 Fire Door FD 1 door Concrete Floor and Partial Drywall on 3 walls. Fire Door Assumed Good Wrap & Remove
004 Fire Door FD 1 door Concrete Floor and Plaster Ceiling. Fiberglass line and Aircell insulation visible at ceiling. Fire Door Assumed Good Wrap & Remove
005A Fire Door FD 1 door Concrete Floor and Plaster with Skim coat walls. Fire Door Assumed Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 144 SF
Mastic Associated w/ Floor Tile Assumed to be Positive on Previous
Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 135 SF Floor Tile Assumed to be Positive on Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 30 SF Floor Tile Assumed to be Positive on Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 312 SF Floor Tile Assumed to be Positive on Previous Report F Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 153 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 342 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 32 SF FT1 not identified during inspection as noted on previous report; Good Contain & Remove
Basement
1st Floor
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Basement
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 140 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Fire door not identified during inspection as noted on previous report
Good Contain & Remove
109 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 84 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report; Fire door not identified during inspection as noted on previous report
Good Contain & Remove
111 Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 120 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 110 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report;
Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 180 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 208 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 208 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 28 SF
Drywall Ceiling, Mastic Associated w/ Floor Tile Positive on Previous
Report.
Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 108 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 198 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Basement
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 324 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 323 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 202 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1-S-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 99 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1-C-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 180 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1-C-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 357 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1-C-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 225 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 190 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 70 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
201 Fire Door FD 1 door Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 120 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Fire Door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1-S-1
1-C-4 nd
Floor
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Basement 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 120 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Fire door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 108 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Fire door FD 1 door Fire Door Assumed on Previous Report Good Wrap & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 108 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 156 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 120 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 140 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 96 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive MFT 187 SF Mastic Associated w/ Floor Tile Positive on Previous Report. Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 180 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 180 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 340 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Basement
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 90 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 200 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 168 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 224 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 250 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 100 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 126 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 126 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 150 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
2-S-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 60 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
2-S-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 60 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Basement
2-S-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 80 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
2-C-1 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 450 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
2-C-2 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 220 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report Good Contain & Remove
2-C-3 1x1 Gray with White Splotches Floor Tile w/Associated Mastic Mastic Positive
MFT 225 SF
Floor Tile with Associated Mastic Assumed to be Positive on
Previous Report. Quantity Includes hall outside Room 206 Good Contain & Remove st Floor EWC 32 windows Good Regulated Area nd
Floor EWC 40 windows Good Regulated Area
Attic EWC 16 windows Good Regulated Area
Exterior Black Window Caulk Exterior Black Window Caulk Positive
Bldg 3
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
1 Interior Window Caulk IWC 2 windows Interior window caulk positive Good Contain & Remove
2 Interior Window Caulk IWC 4 windows Interior window caulk positive Good Contain & Remove
2A Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove
3 Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove
4 Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove
5 Interior Window Caulk IWC 5 windows Interior window caulk positive Good Contain & Remove
5A Interior Window Caulk IWC 1 window Interior window caulk positive Good Contain & Remove
6 Interior Window Caulk IWC 2 windows Interior window caulk positive Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 95 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 80 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 162 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 120 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Basement st
Floor
Mastic Associated w/ Floor Tile Positive on Previous Report
Fire Door Assumed on previous report.
100A Mastic Associated w/ Floor Tile Positive on Previous Report
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report: Interior
Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door
Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 120 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 84.5 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 76.5 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 36 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 20 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove
Interior Window Caulk IWC 3 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 252 SF Good Contain & Remove
Interior Window Caulk IWC 3 windows Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 63 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Mastic Associated w/ Floor Tile Positive on Previous Report:
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Fire Door Assumed on previous Report Mastic Associated w/ Floor
Tile Positive on Previous Report Fire Door Assumed on previous report.
105A Mastic Associated w/ Floor Tile Positive on Previous Report
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report:
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
108 A/B
Mastic Associated w/ Floor Tile Positive on Previous Report: Interior
Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door
Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report : Interior
Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door
Assumed on previous report.
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 112.5 SF Contain & Remove
Interior Window Caulk IWC 1 window Contain & Remove
Fire Door FD 1 door Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 117 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 130.5 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 104 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 98 SF Good Contain & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
115 Interior Window Caulk IWC 1 window Interior Window Caulk not identified on previous report. Good Contain & Remove
Interior Window Caulk IWC 27 windows Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 696 SF Good Contain & Remove
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report: Interior
Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door
Assumed on previous report.
Good
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
116/Porch Interior Window Caulk not identified on previous report: Mastic
Associated w/ Floor Tile Positive on Previous Report .
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 1450 SF Good Contain & Remove
Interior Window Caulk IWC 7 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 168 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 340 SF Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 30 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Fire Door FD 1 door Good Wrap & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 35 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Fire Door FD 1 door Good Wrap & Remove
Interior Window Caulk IWC 1 window Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 180 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 250 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Mastic Associated w/ Floor Tile Positive on Previous Report :
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report: Interior
Window Caulk not identified on previous report. Sample collected during current inspection Positive. Fire Door
Assumed on previous report.
Mastic Associated w/Floor Tile Positive on Previous Report. Fire
Door Assumed on previous report.
120A Mastic Associated w/ Floor Tile Positive on Previous Report : Fire
Door Assumed on previous report.
1-S-1 Fire Door Assumed on previous report.
1-S-2 Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
1-S-3 Fire Door Assumed on previous report. Interior Window
Caulk not identified on previous report
1-C-1 Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
1-C-1A Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 144 SF Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 224 SF Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 384 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 340 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 300 SF Good Contain & Remove
Interior Window Caulk IWC 5 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ Mottled White/Gray Floor Tile w/Associated Mastic Mastic Positive MFT 55 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 340 SF Good Contain & Remove
Interior Window Caulk IWC 3 windows Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 153 SF Good Contain & Remove
Interior Window Caulk IWC 1 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Mastic Associated w/Floor Tile Positive on Previous Report.
Interior Window Caulk not identified on previous report
Mastic Associated w/Floor Tile Positive on Previous Report.
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive
1-C-1B Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
1-C-2 Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
nd
Floor
Mastic Associated w/Floor Tile Positive on Previous Report.
Interior Window Caulk not identified on previous report
Mastic Associated w/ Floor Tile Positive on Previous Report
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/Floor Tile Positive on Previous Report. Fire
Door Assumed on previous report.
Mastic Associated w/Floor Tile Positive on Previous Report.
Fire Door Assumed on previous report.
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 52 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove
208 Fire Door FD 1 door Fire Door Assumed on previous report Good Wrap & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 50 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
Interior Window Caulk IWC 5 windows Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 425 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 320 SF Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 384 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 280 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
Fire Door FD 1 door Good Wrap & Remove
213A 1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 42 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove
1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 7 SF Mastic Associated w/ Floor Tile Positive on Previous Report Good Contain & Remove
Fire Door Assumed on previous report. Mastic Associated w/ Floor
Tile Positive on Previous Report
Fire Door Assumed on previous report. Interior Window Caulk not identified on previous report. Sample collected during current inspection. Positive Mastic Associated w/ Floor Tile Positive on
Previous Report
Mastic Associated w/ Floor Tile Positive on Previous Report
Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive.
Fire Door Assumed on previous report.
Mastic Associated w/ Floor Tile Positive on Previous Report
Fire Door Assumed on previous report.
Fire Door Assumed on previous report. Interior Window Caulk not identified on previous report. Sample collected during current inspection Positive Mastic Associated w/ Floor Tile Positive on
Previous Report
Material
Abbr.
Material
Quantity
Unit of
Measure Comments Condition Method of Abatement
Note: Building 3 is no longer accessible and fenced in. All assessments are based on the prior reinspection data 1’x1’ White with Brown Splotches Floor
Tile w/ Associated Mastic Mastic
Positive
MFT 750 SF Good Contain & Remove
Interior Window Caulk IWC 2 windows Good Contain & Remove
Fire Door FD 2 doors Good Wrap & Remove
2-C-2 1’x1’ White with Brown Splotches Floor
Tile w/Associated Mastic Mastic Positive MFT 468 SF Mastic…