This document provides details for a federal contract solicitation to correct Legionella deficiencies and provide monitoring services at a Veterans Affairs medical center. The solicitation seeks to engage a contractor to provide all tools, equipment, parts, materials, labor and supervision necessary to complete corrective work and initiate monitoring services related to Legionella at the Northern IN VA Healthcare System located in Fort Wayne, Indiana. The solicitation references attachments and a statement of work that further outline the project requirements. The soliciting agency is identified as the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0051 0002.pdf | ||
| Consolidated Pre-bid RFIs_Answered.pdf | ||
| Ft. Wayne and Marion IN VAMC - Asbestos Reinspection Report - August 2016.pdf | ||
| 36C25020B0051 0001.pdf | ||
| 610A4-18-104 PreBid Sign-In 20200715.pdf | ||
| RFI Responses.pdf | ||
| 05 Combined Specs.pdf | ||
| Wage Rate IN20200002.pdf | ||
| Contractor Certification Regarding Safety and Environmental.docx | DOCX document | |
| RFI Form.doc | DOC document | |
| 36C25020B0051.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS CONTAINING MATERIAL (ACM) STATEMENT
(PLACE AN "X" IN THE APPROPRIATE BOX.)
THIS FACILITY CONTAINS NO KNOWN OR SUSPECTED ASBESTOS.
THIS FACILITY CONTAINS ASBESTOS THAT WILL BE REMOVED BY THE VAMC.
THIS FACILITY CONTAINS ASBESTOS THAT WILL BE REMOVED UNDER THIS
CONTRACT.
THIS FACILITY CONTAINS ASBESTOS THAT WILL BE REMOVED UNDER A
SEPARATE CONTRACT.
NOTES:
1. REFER TO SPECIFICATIONS FOR ABATEMENT PROCEDURES.
2. GENERAL CONTRACTOR SHALL REVIEW FACILITY ASBESTOS SURVEY AND HIRE AN
INDEPENDENT CIH TO VERIFY THE ABATEMENT QUANTITIES PRIOR TO THE START OF
ABATEMENT IN EACH CONTAINMENT AND ALSO CHECK IF ALL ASBESTOS HAS BEEN REMOVED
PRIOR TO CLEARANCE TESTING AND REMOVAL OF CONTAINMENT.
3. ASBESTOS CONTRACTOR SHALL COORDINATE ALL WORK WITH THE INSULATION
CONTRACTOR.
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
PROJECT SITE MAP PROJECT LOCATION MAP
PROJECT IMAGE
/1
/2
:2
:3
P
M
GI001
PROJECT COVER
1 1DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
CORRECT LEGIONELLA DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE SYSTEM
2121 Lake Avenue, Ft. Wayne, IN 46240
VA PROJECT #:
610A4-18-104
APOGEE PROJECT #: 17-283
DRAWING LIST
No. Description Dwg of Dwg
COVER
GI001 PROJECT COVER 1 1
PLUMBING
P-001 PLUMBING AND ARCHITECTURAL GENERAL INFORMATION 1 82
P-002 ELECTRICAL GENERAL INFORMATION 2 82
PD100 SUB-BASEMENT PLUMBING DEMOLITION PLAN 3 82
PD101 BASEMENT PLUMBING DEMOLITION PLAN - AREA A1 4 82
PD102 BASEMENT PLUMBING DEMOLITION PLAN - AREA A2 5 82
PD103 BASEMENT PLUMBING DEMOLITION PLAN - AREA B1 6 82
PD104 BASEMENT PLUMBING DEMOLITION PLAN - AREA B2 7 82
PD105 BASEMENT PLUMBING DEMOLITION PLAN - AREA C1 8 82
PD106 BASEMENT PLUMBING DEMOLITION PLAN - AREA C2 9 82
PD111 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A1 10 82
PD112 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A2 11 82
PD113 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A3 12 82
PD114 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A4 13 82
PD115 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA B1 14 82
PD116 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA B2 15 82
PD117 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA C1 16 82
PD118 FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA C2 17 82
PD121 SECOND FLOOR PLUMBING DEMOLITION PLAN - AREA A1 18 82
PD122 SECOND FLOOR PLUMBING DEMOLITION PLAN - AREA A2 19 82
PD123 SECOND FLOOR PLUMBING DEMOLITION PLAN - AREA B1 20 82
PD124 SECOND FLOOR PLUMBING DEMOLITION PLAN - AREA B2 21 82
PD125 SECOND FLOOR PLUMBING DEMOLIOTION PLAN - AREA C1 22 82
PD126 SECOND FLOOR PLUMBING DEMOLITION PLAN - AREA C2 23 82
PD131 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA A1 24 82
PD132 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA A2 25 82
PD133 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA B1 26 82
PD134 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA B2 27 82
PD135 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA C1 28 82
PD136 THIRD FLOOR PLUMBING DEMOLITION PLAN - AREA C2 29 82
PD141 FOURTH FLOOR PLUMBING DEMOLITION PLAN - AREA A1 30 82
PD142 FOURTH FLOOR PLUMBING DEMOLITION PLAN - AREA A2 31 82
PD143 FOURTH FLOOR PLUMBING DEMOLITION PLAN - AREA B1 32 82
PD144 FOURTH FLOOR PLUMBING DEMOLITION PLAN - AREA B2 33 82
PD145 FOURTH FLOOR PLUMBING DEMOLITION PLAN - AREA C1 34 82
PD151 FIFTH FLOOR PLUMBING DEMOLITION PLAN - AREA A1 35 82
PD152 FIFTH FLOOR PLUMBING DEMOLITION PLAN - AREA A2 36 82
PD153 FIFTH FLOOR PLUMBING DEMOLITION PLAN - AREA B1 37 82
PD154 FIFTH FLOOR PLUMBING DEMOLITION PLAN - AREA B2 38 82
PD155 FIFTH FLOOR PLUMBING DEMOLITION PLAN - AREA C1 39 82
PD161 PENTHOUSE PLUMBING DEMOLITION PLAN 40 82
PP100 SUB-BASEMENT PLUMBING PLAN 41 82
PP101 BASEMENT PLUMBING PLAN - AREA A1 42 82
PP102 BASEMENT PLUMBING PLAN - AREA A2 43 82
PP103 BASEMENT PLUMBING PLAN - AREA B1 44 82
PP104 BASEMENT PLUMBING PLAN - AREA B2 45 82
PP105 BASEMENT PLUMBING PLAN - AREA C1 46 82
PP106 BASEMENT PLUMBING PLAN - AREA C2 47 82
PP111 FIRST FLOOR PLUMBING PLAN - AREA A1 48 82
PP112 FIRST FLOOR PLUMBING PLAN - AREA A2 49 82
PP113 FIRST FLOOR PLUMBING PLAN - AREA A3 50 82
PP114 FIRST FLOOR PLUMBING PLAN - AREA A4 51 82
PP115 FIRST FLOOR PLUMBING PLAN - AREA B1 52 82
PP116 FIRST FLOOR PLUMBING PLAN - AREA B2 53 82
PP117 FIRST FLOOR PLUMBING PLAN - AREA C1 54 82
PP118 FIRST FLOOR PLUMBING PLAN - AREA C2 55 82
PP121 SECOND FLOOR PLUMBING PLAN - AREA A1 56 82
PP122 SECOND FLOOR PLUMBING PLAN - AREA A2 57 82
PP123 SECOND FLOOR PLUMBING PLAN - AREA B1 58 82
PP124 SECOND FLOOR PLUMBING PLAN - AREA B2 59 82
PP125 SECOND FLOOR PLUMBING PLAN - AREA C1 60 82
PP126 SECOND FLOOR PLUMBING PLAN - AREA C2 61 82
PP131 THIRD FLOOR PLUMBING PLAN - AREA A1 62 82
PP132 THIRD FLOOR PLUMBING PLAN - AREA A2 63 82
PP133 THIRD FLOOR PLUMBING PLAN - AREA B1 64 82
PP134 THIRD FLOOR PLUMBING PLAN - AREA B2 65 82
PP135 THIRD FLOOR PLUMBING PLAN - AREA C1 66 82
PP136 THIRD FLOOR PLUMBING PLAN - AREA C2 67 82
PP141 FOURTH FLOOR PLUMBING PLAN - AREA A1 68 82
PP142 FOURTH FLOOR PLUMBING PLAN - AREA A2 69 82
PP143 FOURTH FLOOR PLUMBING PLAN - AREA B1 70 82
PP144 FOURTH FLOOR PLUMBING PLAN - AREA B2 71 82
PP145 FOURTH FLOOR PLUMBING PLAN - AREA C1 72 82
PP151 FIFTH FLOOR PLUMBING PLAN - AREA A1 73 82
PP152 FIFTH FLOOR PLUMBING PLAN - AREA A2 74 82
PP153 FIFTH FLOOR PLUMBING PLAN - AREA B1 75 82
PP154 FIFTH FLOOR PLUMBING PLAN - AREA B2 76 82
PP155 FIFTH FLOOR PLUMBING PLAN - AREA C1 77 82
PP161 PENTHOUSE PLUMBING PLAN 78 82
P-401 PLUMBING SCHEDULES 79 82
P-501 PLUMBING DETAILS 80 82
P-601 PLUMBING CONTROLS 81 82
P-602 DOMESTIC WATER RISER DIAGRAM 82 82
SITE
BUILDING 1
EMERGENCY
ENTRANCE
MAIN ENTRANCE
DocuSign Envelope ID: D1B98FB9-32E9-49B1-B632-91616C54206C
3/17/2020
PLUMBING ABBREVIATIONS
3-WAY CONTROL VALVE
ANGLE GATE VALVE
ANGLE GLOBE VALVE
BALANCING/SHUTOFF VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CALIBRATED BALANCING VALVE
CONTROL VALVE
EXPANSION VALVE
GATE VALVE
GLOBE VALVE
QUICK OPEN VALVE
SAFETY RELIEF VALVE
SOLENOID VALVE
BACKFLOW PREVENTER
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLOW ARROW
HOSE BIB / SILLCOCK
VACUUM RELIEF VALVE
GAS COCK
PLUG VALVE
PLUMBING SYMBOLS
PRESSURE REDUCING VALVE (WATER)
PRESSURE REGULATOR (GAS)
PIPE ANCHOR
PIPE GUIDES
WALL CLEANOUT
SUSPENDED CLEANOUT
WCO
WYE STRAINER
WYE STRAINER WITH DRAIN VALVE
FLOOR DRAIN - ROUND OR SQUARE
FLOOR CLEANOUT - ROUND OR SQUARE
PIPE CAP
PIPE TURNING DOWN
PIPE TURNING UP
TEE UP
TEE DOWN
DROP AND RUN
DROP AND TURN
TEE OFF TOP
TEE OFF BOTTOM
CROSS AND RISER
PLAN 90° ELBOW
PIPE TEE
PIPE UNION
FLEXIBLE PIPE CONNECTOR
WATER METER
PUMP
AUTOMATIC AIR VENT
PRESSURE SWITCH
PRESSURE GAUGE
THERMOMETER
FLOW SWITCH
TEMPERATURE SWITCH
OR
OR
CO
PIPE SLOPE ARROW
F
P
T
M
PIPING SYSTEM
PLUMBING SYMBOLS
ANNOTATION SYMBOLS
(E)EXISTING
NEW KEYNOTE
DEMOLITION KEYNOTE
NEW BOLD TEXT INDICATES NEW ITEM
LIGHT ITALIC TEXT INDICATES EXISTING
ITEM
PLUMBING EQUIPMENT DESIGNATION
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER
CONNECT TO EXISTING
LIMITS OF DEMOLITION
P-###
PLUMBING AND ARCHITECTURAL GENERAL NOTES
PLUMBING AND ARCHITECTURAL DEMOLITION GENERAL NOTES
1. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE
PROCEEDING WITH WORK.
2. REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE FROM SITE ITEMS NOT BEING RETAINED BY GOVERNMENT OR REINSTALLED AS PART OF
THIS WORK.
3. DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.
4. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. RELOCATE, REMOVE AND
ADJUST MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO COORDINATE WITH NEW WORK.
5. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING ADJACENT CONDITIONS.
6. COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND
APPROVAL.
7. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES
DAMAGED AT NO ADDITIONAL COST.
8. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE W ORK.
9. SAWCUT CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE W ITH NEW
PLUMBING AND WORK OF OTHER TRADES.
10. REMOVE ACT CEILING TILES AND GRID AS REQUIRED TO PERFORM PLUMBING WORK IN SPACE. SALVAGE ACT
CEILING AND GRID FOR REINSTALLATION AFTER COMPLETION OF PLUMBING WORK.
11. REMOVE GYPSUM BOARD OR PLASTER WALLS AND CEILING, FLOORING AS REQUIRED TO PERFORM PLUMBING
WORK IN SPACE.
12. REMOVE GYPSUM BOARD OR PLASTER WALLS TO FRAMING, ACT CEILING TILE AND GRID, AND FLOORING AS REQUIRED TO PERFORM PLUMBING WORK IN SPACE. SALVAGE ACT CEILING AND GRID FOR REINSTALLATION
AFTER COMPLETION OF PLUMBING WORK.
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA
STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE
GRADE FOR THE PURPOSES INTENDED.
5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY
AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
6. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR
EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
7. AT EACH PLUMBING FIXTURE, PROVIDE A PISTON TYPE WATER HAMMER ARRESTOR SIZED ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS.
8. SANITARY DRAINAGE PIPING INDICATED IS LOCATED BELOW FLOOR SLAB OR WITHIN W ALLS UNLESS NOTED OTHERWISE. SANITARY VENT PIPING INDICATED IS ABOVE THE CEILING OR WITHIN WALLS UNLESS NOTED
OTHERWISE.
9. SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL CODES ALONG WITH
SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.
10. FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF
WALLS AND FLOORS.
11. TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND
APPLICABLE VA STANDARDS.
12. COORDINATE PLUMBING PIPING WITH W ORK OF OTHER DISCIPLINES.
13. DISINFECT DOMESTIC WATER SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE, AND NATIONAL
CODES AND APPLICABLE VA STANDARDS.
14. PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.
15. COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING
OF PIPING WITH EXISTING CONDITIONS.
16. PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND
ARRANGEMENT OF PIPING SYSTEMS.
17. CONTRACTOR SHALL SUBMIT SCHEDULE OF W ORK AND OUTAGES THREE WEEKS IN ADVANCE OF WORK ON
PARTICULAR AREAS.
18. CONTRACTOR SHALL PROVIDE POTABLE WATER FOR DRINKING AND WATER FOR FLUSHING FIXTURES
DURING SHUTDOWN.
19. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS
CONTRACT, UNLESS NOTED OTHERWISE.
20. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF
PROJECT.
21. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
22. DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.
23. REINSTALL ACT TILES AND GRID PER SPECIFICATION 095100 AS REQUIRED TO PERFORM PLUMBING WORK.
24. INSTALL GYPSUM BOARD ON EXISTING STUD WALL AND CEILING FRAMING. FEATHER EXISTING GYPSUM BOARD OR PLASTER FINISH INTO NEW GYPSUM BOARD AS REQUIRED TO PERFORM PLUMBING WORK. FINISH
AND PAINT TO MATCH ADJACENT EXISTING WALL AND CEILING.
25. INSTALL FLOOR TILE AS REQUIRED TO PERFORM PLUMBING WORK IN SPACE TO MATCH EXISTING.
A/E ARCHITECT/ENGINEER
AC ABOVE CEILING
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
AFG ABOVE FINISHED GRADE
ASD ADJUSTABLE SPEED DRIVE
ASHRAE AMERICAN SOCIETY HEATING,
REFRIGERATING, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BAS BUILDING AUTOMATION SYSTEM
BF BELOW FLOOR
BFP BACKFLOW PREVENTER
BG BELOW GRADE
BH BOOSTER HEATER
BHP BREAK HORSEPOWER
BJ BETWEEN JOISTS
BOP BOTTOM OF PIPE
BSP BLACK STEEL PIPE
BT BATHTUB
BTUH BRITISH THERMAL UNITS PER HOUR
C CELSIUS
CF COMBINATION FIXTURE
CGA COMPRESSED GAS ASSOCIATION
CI CAST IRON
CO CLEANOUT
COND CONDENSATE
CP CONDENSATE PUMP
CS CLINICAL SINK
CV CONTROL VALVE
CW COLD WATER
DCWS DOMESTIC COLD WATER SUPPLY
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DF DRINKING FOUNTAIN
DI DEIONIZED WATER
DN DOW N
DOE DEPARTMENT OF ENERGY
DS DOW NSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EC ELECTRICAL CONTRACTOR
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL
SYSTEM
EPA ENVIRONMENTAL PROTECTION
AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYEWASH STATION
EX EXISTING
F FAHRENHEIT
FA FROM ABOVE
FB FROM BELOW
FBO FURNISHED BY OTHERS
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE)
CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FU FIXTURE UNITS
G GALLON
GC GENERAL CONTRACTOR
GCO GRADE CLEANOUTS
GD GARBAGE DISPOSAL
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB (INTERIOR)
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK
(DOMESTIC)
HW HOT WATER
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ICRA INFECTION CONTROL RISK ASSESMENT
ICW INDUSTRIAL COLD WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS W ATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWHR KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD W ATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SINK BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PACAL
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAUGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF
VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RO REVERSE OSMOSIS
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SCFM STANDARD CUBIC FOOT/MIN
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT SQUARE FOOT
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TDL TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
THRU THROUGH
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TW R TEMPERED WATER RETURN
TW S TEMPERED WATER SUPPLY
TYP TYPICAL
UPC UNIFORM PLUMBING CODE
V SANITARY VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VTR VENT THROUGH ROOF
W WASTE
W\ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAUGE
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
WHD WALL HYDRANT
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
YCO YARD CLEANOUT
YH YARD HYDRANT
PHASING NOTES
1. THIS FACILITY OPERATES 24 HOURS PER DAY, 7 DAYS PER WEEK. CONSTRUCTION WORK SHALL BE PHASED TO MINIMIZE BOTH QUANTITY AND DURATION OF SHUTDOW NS. SCHEDULE ALL SHUTDOW NS W ITH THE CONTRACTING OFFICER'S
REPRESENTATIVE (COR) A MINIMUM OF THREE (3) W EEKS IN ADVANCE.
2. SUBMIT A DETAILED PHASING PLAN FOR REVIEW BY THE COR, ARCHITECT AND ENGINEER. PHASING PLAN SHALL INCLUDE, BUT NOT BE LIMITED TO, START AND END DATES OF ALL TASKS THROUGHOUT THE ENTIRE PROJECT, AND DATE
AND DURATION OF SUGGESTED SHUTDOWNS.
3. TO MINIMIZE SHUTDOWNS, MAKE CONNECTIONS TO EXISTING PIPING VIA "HOT TAPPING" WHEREVER POSSIBLE, IN ORDER
TO ALLOW S THE PIPING TO REMAIN ACTIVE.
4. OLD PIPING MAINS SHALL BE DEMOLISHED AFTER NEW MAINS HAVE BEEN BROUGHT INTO OPERATION.
5. WORK IN OFFICES, CONFERENCE ROOMS, EXAM ROOMS, CONSULTATION ROOMS, AND OTHER SIMILAR AREAS THAT ARE OCCUPIED ON A REGULAR BASIS DURING BUSINESS HOURS SHALL BE PERFORMED AFTER BUSINESS HOURS.
GENERALLY, AFTER HOURS MEANS FROM 6 P.M. UNTIL 5 A.M. COORDINATE EXACT HOURS WITH THE COR. SPECIFIC APPROVAL FROM THE COR IS REQUIRED TO PERFORM WORK IN THESE AREAS DURING BUSINESS HOURS.
6. ALL MEANS OF EGRESS SHALL BE MAINTAINED DURING CONSTRUCTION. ACCESSIBLE ICRA BARRIERS SHALL BE ERECTED
AND TAKEN DOWN AS REQUIRED TO MEET THE VA SCHEDULING REQUIREMENTS.
7. TEMPORARILY REMOVE CEILINGS, LIGHT FIXTURES, AIR DEVICES, CEILING-MOUNTED FIRE ALARM DEVICES AND SMOKE DETECTORS, CEILING-MOUNTED WIRELESS ACCESS POINTS, AND ALL OTHER CEILING-MOUNTED IN ORDER TO ACCOMPLISH WORK. CEILING REMOVAL INCLUDES, BUT IS NOT LIMITED TO, REMOVING CEILING TILES, CEILING T-BAR GRID, AND PARTIALLY OR FULLY REMOVING HARD SURFACE CEILINGS. SPRINKLER HEADS SHALL BE TURNED UP W ITHIN THE AREA OF WORK. THERE ARE BOTH LAY-IN CEILINGS AND HARD SURFACE CEILINGS IN THE AREAS OF WORK. AFTER WORK ABOVE CEILINGS IS COMPLETED, REINSTALL CEILINGS AND REINSTALL ALL CEILING-MOUNTED DEVICES AND EQUIPMENT. TURN SPRINKLER HEADS BACK DOW N AND REINSTALL IN CEILING. ANY ITEMS DAMAGED AS A RESULT OF THE DEMOLITION OR NEW W ORK SHALL BE REPLACED AT NO ADDITIONAL COST TO THE GOVERNMENT.
PIPE RISER MARK
RISER NUMBER
RISER PIPING SYSTEM TYPE
DEAD LEG PIPING MARK
DEAD LEG SCHEDULE NUMBER
PIPE DEAD LEG
DL
BID ALTERNATES
1. DEDUCT ALTERNATE NO. 1: OMIT SCOPE OF WORK INDICATED ON THE PLANS AS "BID ALTERNATE 1" FOR THIRD
FLOOR AREAS B1, AND B2.
2. DEDUCT ALTERNATE NO. 2: OMIT SCOPE OF WORK INDICATED ON THE PLANS AS "BID ALTERNATE 2" FOR THIRD
FLOOR AREAS A1, AND A2.
3. DEDUCT ALTERNATE NO 3: OMIT SCOPE OF WORK INDICATED ON THE PLANS AS "BID ALTERNATE 3" FOR
BASEMENT FLOOR AREAS C1, AND C2.
DCWR
DHWS
NG NATURAL GAS
ST STORM
PD PUMP DISCHARGE
OFD OVERFLOW STORM DRAIN
GW GREASE WASTE
OW OIL WASTE
SAN SANITARY WASTE
CD CONDENSATE DRAIN
CA COMPRESSED AIR
AW ACID WASTE
N2 NITROGEN
N2O NITROUS OXIDE
MA MEDICAL AIR
O2 OXYGEN
WAGD WASTE ANESTHETIC GAS DISPOSAL
VAC VACUUM
V SANITARY VENT
OV OIL VENT
AV ACID VENT
NPCW NONPOTABLE COLD WATER
DI DE-IONIZED WATER
SCW SOFTENED COLD WATER
DCWS DOMESTIC COLD WATER
RO REVERSE OSMOSIS WATER
DOMESTIC CW RECIRCULATION
DOMESTIC HOT WATER
CO2 CARBON DIOXIDE
HW 140 DOMESTIC HOT WATER (OTHER TEMP)
PG PROPANE GAS
DHWR DOMESTIC HW RECIRCULATION
NG
ST
PD
OFD
GW
OW
SAN
CD
CA
AW
N2
N2O
MA
O2
WAGD
VAC
CO2
PG
V
OV
AV
HW 140
SCW
NPCW
DI
RO
NON-INSULATED PIPING MARK
NON-INSULATED SCHEDULE NUMBER
NON-INSULATED PIPE
NI
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:3
P
M
P-001
PLUMBING AND ARCHITECTURAL
GENERAL INFORMATION
1 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
L
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TW ISTED PAIR
TPS TW ISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERW RITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TW O-CONDUCTOR (3/C, 4/C, ETC.)
W2 TW O-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALTALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORDCOORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMIELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMCINTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MICMICROPHONE
MINMINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SW ITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SW ITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES W ALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW .
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: W ALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' W ITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE
WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL
APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND W ITH THE LATEST
EDITION OF THE NATIONAL ELECTRICAL CODE.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH
THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE
APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID
CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS
MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS
NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC
CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROW NOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT W ITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE OWNER, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. ALL ELECTRICAL W ORK IS INDICATED ON THE PLUMBING PLANS.
SHORT CIRCUIT CURRENT CALCULATIONS WILL BE
PERFORMED ON THE ELECTRICAL SYSTEM USING A
BOLTED THREE PHASE FAULT CONDITION FOR
CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND
MECHANICAL STRESS TO THE SYSTEM FOR
CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT
VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR
THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT
CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY
CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM
PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS
TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO
AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP
OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP
CALCULATIONS
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:3
P
M
P-002
ELECTRICAL GENERAL INFORMATION
2 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
K
18 19 20 21 22
TO HX
TO HX
1" DHWS
1/2" DHWS
1" DHWS
1" DHWS
3/4" DHWS
2" DHWR
3" DHWS
D L
DL
DL
DL
DL
DL
SUB-BASEMENT
SB-01
STAIRS
SB-02
SUB-BASEMENT
SB-01
STAIRS
SB-02
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:0
P
M
PD100
SUB-BASEMENT PLUMBING
DEMOLITION PLAN
3 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
SUB-BASEMENT PLUMBING DEMOLITION PLAN 0 2 4 8
NORTH
TRUE
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1" DHWS AND 1"DCWS UP TO BASEMENT.
CONTINUED ON PD105.
04 1/2" DCWS UP TO BASEMENT. CONTINUED ON
PD105.
05 3" DHWS AND 3" DCWS UP FROM
RECIRCULATION STATION AND WATER
HEATER.
06 1/2" DHW AND 1" DCW UP TO BASEMENT.
CONTINUED ON PD105.
07 1" DHWS UP TO BASEMENT. CONTINUED ON
PD105.
08 4" DCWS, 3" DHWS, AND 2" DHWR UP TO
BASEMENT. CONTINUED ON SHEET PD105.
C
G
H
2 3 3A 4 5 6
P D
P
D
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
D L
DL
DL
DL
DL
DL
DL
1" DCWS
1 1/2" DCWS
1 1/4" DHWS
DL
DL
TO HX
3/4" DHWS
1" DCWS
1" DCWS
1/2" DHWS
1/2" DHWS
1/2" DCWS
3/4" DCWS
3/4" DHWS
1 1/2" DCWS
1" DHWS
1 1/2" DCWS
DL
DL
2" DHWS
4" DCWS
4" DCWS
3" DHWS
1 1/2" DHWR
1/2" DCWS
1/2" DHWS
1" DCWS
3/4" DHWS
2" DCWS
3/4" DHWS
3/4" DHWR
1 1/4" DHWS
2" DCWS
1" DCWS
3/4" DHWS
2" DCWS
2" DCWS
1 1/4" DHWS
1/2" DHWS 3/4" DCWS
1/2" DCWS
1/2" DHWS
1/2" DHWS
1/2" DHWS
3/4" DCWS
1" DHWS
1" DCWS
1" DCWS
1/2" DCWS
1/2" DHWS
1/2" DCWS
1" DCWS
1" DHWS
1/2" DCWS
1/2" DHWS
3" DCWS
2" DHWS
DHWS
9-2
DCWS
9-1
D L
DL
DHWR
10-3
DHWS
10-2
DCWS
10-1
D L
DL
2" DCWS
LINEN STORAGE
30B
EMS CHIEF OFFICE
30C
Room
EMS SUPPLY STORAGE
30D
EMS SUPERVISORS
30A
MECHANICAL
EMS EQUIPMENT STORAGE
Room
WOMEN'S BATHROOM
CORRIDOR
MEN'S BATHROOM
MECHANICAL
D L
D L
2 1/2" DHWS
1 1/2" DHWR
3" DCWS
DL
DL
1210 1109
111009
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:1
P
M
PD101
BASEMENT PLUMBING DEMOLITION
PLAN - AREA A1
4 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA A1 0 2 4 8
NORTH
TRUE
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1/2" DCWS AND DHWS UP TO FIXTURE ON
FIRST FLOOR. CONTINUED ON PD111.
04 2" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD111.
05 1/2" DHWS AND DCWS DOWN TO FIXTURE.
06 1/2" DCWS AND DHWS UP TO FIRST FLOOR.
CONTINUED ON PD111.
07 DEAD LEG UP TO FIRST FLOOR. CONTINUED
ON SHEET PD111.
08 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN. SIZE AND SERVICE AS INDICATED.
09 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
10 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID
FOR REINSTALLATION AFTER COMPLETION
OF PLUMBING WORK.
11 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
12 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
A
G
H
7 8 9 10 11 12 13 14 15 18 1916
P D
P
D
P D
/1 PD105
/1 PD105
/1 PD103
DHWS
8-2
DHWR
8-3
DCWS
8-1
DL
DL
D L
D L
DL
DL
DL
DL
DL
DL
DL
D L
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
1/2" DCWS
1/2" DHWS
2" DHWS
2" DCWS
2" DCWS
2" DHWS
2" DHWS
2" DCWS
3" DHWS
1 1/2" DHWR
4" DCWS
4" DCWS
3/4" DHWR
3/4" DHWS
1 1/2" DCWS
3/4" DHWS
3/4" DCWS
3/4" DHWR
1" DHWR
1" DCWS
1" DHWS
1" DHWR
1" DCWS
1" DHWS
1" DCWS
1" DHWS
1" DHWR
1" DHWS
1 1/2" DCWS
1" DHWR
1" DCWS
1" DHWS
1 1/2" DCWS
3/4" DHWS
3" DHWS
1 1/2" DHWR
4" DCWS
1" DHWR
3" DHWS
3" DCWS
1" DCWS
1" DHWS
1" DHWS
1" DCWS
3/4" DHWS
3/4" DCWS
2" DCWS
3" DCWS
2 1/2" DHWS
1" DHWS
2" DCWS
4" DCWS
2" DCWS
2" DHWS
01 01
3/4" DCWS
MECHANICAL
Room
HAC
ELECTRICAL
FILE ROOM
ELECTRICAL
42A
MECHANICAL
Room
Room
Room
Room
MEDICAL SURGICAL
LOGISTICS OFFICE
MECHANICAL
Room
Room
HAC
ELECTRICAL
FILE ROOM
ELECTRICAL
42A
MECHANICAL
Room
VESTIBULE
Room
MEDICAL SURGICAL
LOGISTIC
MEDICAL SURGICAL
LOGISTIC
MECHANICAL
Room
Room
Room
MEDICAL SURGICAL
LOGISTIC
DL
DL
D
LD
L
DL
DL
STORAGE
STORAGE
44A
11 12 13 14
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:2
P
M
PD102
BASEMENT PLUMBING DEMOLITION
PLAN - AREA A2
5 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA A2
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1" DHWS AND DCWS UP TO FIRST FLOOR.
CONTINUED ON PD112.
04 2" DHWS AND DCWS UP TO FIRST FLOOR.
CONTINUED ON PD112.
05 POSSIBLE CAP. NO FIXTURE OBSERVED.
06 1" DCWS UP TO FIRST FLOOR. CONTINUED ON
PD112.
07 1 1/2" DCWS, 3/4" DHWS, AND 3/4" DHWR UP
TO FIRST FLOOR. CONTINUED ON PD112.
08 3/4" DCWS AND DHWS UP TO FIRST FLOOR.
CONTINUED ON PD112.
09 3/4" DHWS UP TO FIRST FLOOR. CONTINUED
ON PD112.
10 6" BUILDING FIRE SERVICE ENTRANCE.
11 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
12 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID FOR
REINSTALLATION AFTER COMPLETION OF
PLUMBING WORK.
13 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
14 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
0 2 4 8
NORTH
TRUE
G
H
19 20 21 23 2422 25 26 27 28 29 30
BACKFLOW
PREVENTER ON BOTH
RUNOUTS
P D
P D
P
D
/1 PD105 /1 PD105
P D
/1 PD102
DL
DL
DL
DL
D L
D L
DL
DL
DL
2" DCWS
1 1/2" DHWR
3" DHWS
4" DHWS
4" DCWS
4" DHWS
4" DCWS
1 1/2" DHWR
3" DHWS
1" DHWS
2" DCWS
2" DHWS
4" DCWS
1" DHWS
4" DCWS
3" DHWS
4" DCWS
3" DCWS
2" DCWS
2" DHWR
1 1/4" DHWS
3" DHWS
3" DCWS
1/2" DHWS
1/2" DCWS
2" DCWS
1" DHWS
1" DCWS
1" DHWR
1" DHWR
1" DHWR
1" DHWS
1" DCWS
1" DCWS
4" DCWS
1" DHWS
2" DCWS
1" DHWR
2 1/2" DHWS
3" DCWS
1 1/2" DHWS
1 1/2" DCWS
1 1/2" DCWS
1 1/2" DHWR
3" DHWS
DHWS
6-2
1" DHW TO SINK
DHWR
6-3
WOMEN'S LOCKER ROOM
59C
Room
Room
HAC
P-501
DHWR
5-3
DHWS
5-2
DCWS
5-1
DL
STORAGE
STORAGE
44A
EMS EQUIPMENT STORAGE
63A
COVERED LOADING DOCK
Room
TOILETS
45A
MEN'S LOCKER ROOM
Room
45B
EMS STORAGE
SOILED UTILITY
TOILET
60B
Room
Room
60A
MECHANICAL
MECHANICAL
LOCKERS
59B
TOILETS
59A
DCWS
6-1
07 08 09
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:3
P
M
PD103
BASEMENT PLUMBING DEMOLITION
PLAN - AREA B1
6 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA B1
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 2" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD103.
04 1" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD115.
05 1/2" DHWS AND DCWS UP TO FIRST FLOOR.
CONTINUED ON PD103.
06 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
07 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID
FOR REINSTALLATION AFTER COMPLETION
OF PLUMBING WORK.
08 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
09 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
0 2 4 8
NORTH
TRUE
G
H
31 32 33 33A 34 35 36
P D
P
D
DL
DL
DL
DL
DL
DL
DL
DL DL
DL
DL
DL
DL
DL
1 1/2" DHWR
1" DCWS
4" DCWS
1 1/2" DCWS
2" DHWS
3" DCWS
1" DHWR
1" DCWS
3/4" DHWS
3" DCWS
3/4" DHWS
3/4" DCWS
1/2" DHWS
1/2" DCWS
1/2" DCWS
1/2" DHWS
2" DHWS
3/4" DHWR
2 1/2" DCWS
05 05 05
DHWS
7-2
DCWS
7-1
01 01
MAIL ROOM
49A
ARMAMENTARIUM
REINTEGRATION
STORAGE
Room
53A
MAIL ROOM
49A
ARMAMENTARIUM
REINTEGRATION
WET VAC STORAGE
Room
STORAGE
Room
53A
RESTROOM
Room
53B
OFFICE
MATERIALS MANAGEMENT
SECTION
WOMEN'S LOCKER ROOM
59C
DHWR
7-3
10090807
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:4
P
M
PD104
BASEMENT PLUMBING DEMOLITION
PLAN - AREA B2
7 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA B2
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1/2" DCWS AND DHWS UP TO FIRST FLOOR.
CONTINUED ON PD114.
04 3/4" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD114.
05 NEW SPS AREA IS NOT PART OF THIS
PROJECT.
06 1" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD114.
07 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
08 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID
FOR REINSTALLATION AFTER COMPLETION
OF PLUMBING WORK.
09 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
10 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
0 2 4 8
NORTH
TRUE
H
I
J
K
L
M
N
13 14 15 18 19 20 21 232216
/1 PD102
/1 PD103
/1 PD106/1 PD106
/1 PD103/1 PD102
1/2" DHWS
1/2" DHWS
3/4" DHWS
D H W S
3/4" DHWS
1" DHWS
3/4" DHWS
D H W S
2" DHWS
1" DHWS
TO STEAMER
TO SPRAY HOSE
3/4" DCWS
3/4" DHWS
DL
D L
DL
1/2" DCWS
1/2" DHWS
2" DHWS
2" DCWS
DL
D L
DL
DL
DL
DL
DL
DL
D L
D L
D L
DL
DL
1" DHWS
2" DCWS
4" DCWS
3" DCWS
3" DHWS
2" DHWR
1" DCWS
1" DHWS
1" DHWR
1" DCWS
3" DHWR
3" DHWS
1" DHWS
1" DCWS
1 1/2" DHWS
1 1/2" DCWS
1 1/2" DCWS
1 1/4" DHWS
1 1/2" DCWS
1 1/2" DHWR
3" DHWS
2" DHWS
2" DCWS
3" DCWS
2" DHWS
DHWS
3-2
DCWS
3-1
DHWR
3-3
1" DHWR
1" DHWR
DHWR
2-3
DL
DL
1" DHW TO SINK
1" DHWS
DHWS
2-2
DCWS
2-1
Room
Room
KITCHEN
STAIRS
SB-02
COVERED LOADING DOCK
SPS
Room
Room
Room
22A
WALK-IN REFRIGERATOR
R1
Room
COVERED LOADING DOCK
Room
WALK-IN REFRIGERATOR
R2
COVERED LOADING DOCK
KITCHEN
COVERED LOADING DOCK
KITCHEN
COVERED LOADING DOCK
EXTERIOR LOADING DOCK
-DRFY FOOD STORAGE
15141312
1312 14 15
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:4
P
M
PD105
BASEMENT PLUMBING DEMOLITION
PLAN - AREA C1
8 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA C1
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1" DHWS AND DCWS FROM SUB-BASEMENT
CONNECTED TO SINK.
04 DCWS AND DHWS UP TO FIXTURE ON FIRST
FLOOR. CONTINUED ON SHEET PD117.
05 2" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD115.
06 1" DHWS DOWN TO FIXTURE.
07 3/4" DHWS AND DCWS DOWN TO FIXTURE.
08 1/2" DHWS AND 1 1/2" DCWS DOWN TO
FIXTURES.
09 3" DHWS, 4" DCWS, AND 2" DHWR UP FROM
SUB-BASEMENT. CONNECTED TO MAINS.
10 3/4" DHWS AND DCWS UP TO FIRST FLOOR.
CONTINUED ON PD115.
11 FILLED REGION PART OF BID ALTERNATE NO.
12 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
13 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID
FOR REINSTALLATION AFTER COMPLETION
OF PLUMBING WORK.
14 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
15 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
0 2 4 8
NORTH
TRUE
N
O
P
Q
R
S
13 14 15 18 19 20 21 232216
/1 PD105/1 PD105
3/4" D H
W S
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
DL
D L
DL
DL
DL
DL
D L
D L
DL
DL
1" DHWR
3" DCWS
1" DHWS
4" DCWS
2" DCWS
2" DHWS
1" DCWS
1" DHWS
3/4" DCWS
1 1/4" DHWS
3/4" DHWR
1/2" DCWS
1 1/2" DHWS
3/4" DCWS
1" DCWS
1 1/4" DHWS
2" DHWR
2" DHWS
3" DCWS
3/4" DCWS
3/4" DCWS
3/4" DCWS
1" DCWS
1" DHWS
3/4" DHWS
3/4" DHWS
1 1/4" DHWS
1/2" DHWS
DHWR
1-3
DHWS
1-2
DCWS
1-1
D L
DL
EXTERIOR LOADING DOCK
WALK-IN REFRIGERATOR
R2
MECHANICAL
MECHANICAL
HAC
OFFICE
MANAGEMENT OFFICE
SUPERVISORS OFFICE
FOOD PANTRY
8B
VESTIBULE
CANTEEN STORAGE
8A
WALK-IN FREEZER
F1
EXTERIOR LOADING DOCK
-DRFY FOOD STORAGE
11 12 1310
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:5
P
M
PD106
BASEMENT PLUMBING DEMOLITION
PLAN - AREA C2
9 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A1 A2 B1 B2
C1
C2
BASEMENT
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - AREA C2 0 2 4 8
NORTH
TRUE
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1 1/14" DHWS UP TO FIRST FLOOR.
CONTINUED ON PD116.
04 1/2" DHWS AND 1" DCWS UP TO FIRST FLOOR.
CONTINUED ON PD116.
05 1 1/14" DHWS AND 3/4" DCWS UP TO FIRST
FLOOR. CONTINUED ON PD116.
06 3/4" DCWS AND DHWS UP TO FIRST FLOOR.
CONTINUED ON PD116.
07 4" DCWS UP TO FIRST FLOOR. CONTINUED
ON PD116.
08 HOSE END DRAIN VALVE.
09 FILLED REGION PART OF BID ALTERNATE NO.
10 DEMOLISH RISER PIPING, FITTINGS, AND
INSULATION COMPLETE.
11 REMOVE ACT CEILING TILES AND GRID AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE. SALVAGE ACT CEILING AND GRID
FOR REINSTALLATION AFTER COMPLETION
OF PLUMBING WORK.
12 REMOVE GYPSUM BOARD OR PLASTER
WALLS AND CEILING, FLOORING AS
REQUIRED TO PERFORM PLUMBING WORK IN
SPACE.
13 REMOVE GYPSUM BOARD OR PLASTER
WALLS TO FRAMING, ACT CEILING TILE AND
GRID, AND FLOORING AS REQUIRED TO
PERFORM PLUMBING WORK IN SPACE.
SALVAGE ACT CEILING AND GRID FOR
REINSTLLATION AFTER COMPLETION OF
PLUMBING WORK.
E
C
G
H
2 3 3A 4 5 6
P D
P
D
/1 PD113 /1 PD113
DL
DL
DL
DL
DL
DL
DL
DL
D L
D L
1 1/2" DCWS
1" DHWR
1 1/4" DHWS
1 1/2" DHWS
1 1/2" DCWS
1" DHWS
1" DCWS
1 1/2" DCWS
1 1/2" DHWS
1" DHWS
1" DCWS
1" DCWS
1" DHWS
1 1/2" DCWS
1 1/2" DHWS
1 1/2" DCWS
1 1/2" DHWS
1 1/2" DHWR 1 1/2" DCWS
1" DHWR
1" DHWS
1 1/2" DCWS
1 1/2" DHWS
1 1/2" DHWS
1 1/2" DCWS
DL
DL
DCWS
10-1
DHWS
10-2
DHWS
9-2
DCWS
9-1
1 1/2" DHWS
1 1/2" DCWS
DL
DL
DL
DHWR
10-3
Room
109C
Room
109D
Room
Room
110B
Room
Room
Room
Room
Room
Room
Room
119A
Room
Room
120A
Room
120B
Room
Room
121A
Room
121B
Room
121C
Room
121E
Room
Room
121F
Room
121G
Room
A157
Room
A158
Room
A159
Room
110A
Room
Room
121D
Room
Room
A157
Room
A158
Room
A159
D L
D L
05 06 07
05 06 07
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs#
/1
/2
:2
:0
P
M
PD111
FIRST FLOOR PLUMBING DEMOLITION
PLAN - AREA A1
10 82DJR WLF
CORRECT LEGIONELLA
DEFICIENCIES
VA NORTHERN INDIANA HEALTH CARE
SYSTEM
2121 Lake Avenue, Ft. W ayne, IN 46240 03/20/2020
BID DOCUMENTS
610A4-18-10417-283
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
MAIN
ENTRANCE
A1 A2 B1 B2
C1
C2
A3
A4
FIRST FLOOR
Scale: 1/4" = 1'-0"
FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A1 0 2 4 8
NORTH
TRUE
01 REMOVE DEAD LEG AND CAP PIPE AT ACTIVE
MAIN WITHIN 2.5 PIPE DIAMETERS. SIZE AND
SERVICE AS INDICATED.
02 SUSPECTED ASBESTOS CONTAINING PIPE
INSULATION.
03 1 1/2" DHWS AND DCWS UP TO FIXTURE ON
SECOND FLOOR.