RFI 1 answered 2.docx

DOCX document 23 KB Posted

Attached to
Resolve HVAC Issues in Building 15 Federal contract opportunity
Solicitation number
36C25020B0031
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document contains a request for information (RFI) related to a federal contract opportunity to resolve HVAC issues in Building 15 at the Department of Veterans Affairs Cincinnati VA Medical Center. The RFI seeks information on the basis of design for an equipment access platform and fume hood venturi valves. It also requests extending the replacement date for air handling unit 15-AHU-31 to November 30th and the basis of design for the replacement unit. The reply provides Daikin as the basis of design for the air handling unit and notes the contractor will be responsible for re-certifying the fume hoods after the work. It also includes responses to the other questions and notes changes to relevant drawings.

The related federal contract opportunity is a solicitation to resolve HVAC issues in Building 15 at the Department of Veterans Affairs Indianapolis Network Contracting Office for between $100,000 to $200,000. It is a 100% set-aside for service-disabled veteran-owned small businesses. Interested parties should register at SAM.gov and VIP.vetbiz.gov and monitor FBO.gov for the solicitation release on or around July 15th, 2018 with a proposal due date approximately 30 days later. The work must be completed within 365 days of notice to proceed.

View the file

Other files for this federal contract opportunity

Other files attached to Resolve HVAC Issues in Building 15, newest first.
File Type Posted
sight visit signin sheet.jpg JPG image
RFI answered 3.docx DOCX document
M-001 ADDENDUM.pdf PDF
RFI Form answered.docx DOCX document
15-A101 -2020.0723.pdf PDF
36C25020B0031 0001_1.docx DOCX document
36C25020B0031 0001.docx DOCX document
Honeywell Fire Alarm Sole Source Justification 1.pdf PDF
RFI Form.docx DOCX document
539-20-212 bldg 15 specs 2020 0401.pdf PDF
36C25020B0031.docx DOCX document
539-20-212 bldg 15 drawings 2020.0312.pdf PDF
Contractor Certification Regarding EMR.docx DOCX document
WAGE DETERMINATIONS.6.23.20.docx DOCX document
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI) 36C25019B0022

PROJECT NUMBER:
539-20-212
Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE:
Resolve HVAC Issues in Bldg. 15
PROJECT LOCATION:
Department of Veterans Affairs

Cincinnati VA Medical Center 3200 Vine Street Cincinnati, OH 45220

SUBMITTED BY:
Jeffrey Jett
City/State:
Paducah, KY
PHONE NO.:
270-564-0351

TO: Contract Specialist Patrice Scott (email: Patrice.Richardson-Scott@va.gov)

RFI NO.:1
DATE:7/21/2020
REFERENCE:

REPLY NEEDED BY:

INFORMATION NEEDED: Who is the basis of design on the Modular Equipment access platform note 8 on drawing number 15-A101?

What brand is the basis of design for the Fume Hood Venturi Valves on Drawing Number 15-M601?

Can the replacement of 15-AHU-31 be extended to November 30th as it will not be possible to get the AHU in that amount of time.

What brand is the basis of design for the AHU on this project that it to be replaced? Daikin is the basis of design.

Will the fume hoods have to be re-certified after the new work is completed and if so who is responsible for this?

REPLY:

The equipment platform is fabricated with bar grating and steel support as specified on section 05 50 00. There will be a change in drawing 15-A101, Note 8 to read “equipment platform with 1”X3/16” bar grating on Steel supports.” See amended 15-A101.

Phoenix Controls is the basis of design of the Fume Hood Venturi Air Valves.

The designer checked if 12-ton rental heat pumps were available that could extend the time of the year that the AHU installation could occur. Only 24-ton rentals were available which would require a re-design of the electrical hook up. As a result, the original dates will have to stay.

Daikin is the basis of design for the AHU.

The contractor will re-certify the fume hoods. See amended drawing M-001.

REPLY FROM:
DATE:
ATTACHMENTS:
COPY TO: