RFI_Answer-Contego_RFI_2.pdf
PDF 201 KB Posted
- Solicitation number
- 36C24922B0027
About this file
This request for information pertains to a renovation project at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project involves removing pneumatic controls from the VAV system in Building 200, including the pneumatic actuator, thermostat, controller, and air lines from rooms. Main control air lines must be removed from rooms and capped with brass plugs above drop ceilings in corridors. Lines bent over or tapped will not be accepted. Contractors are requested to submit any questions regarding specifications or drawings by July 20, 2022, referencing the relevant section. The related federal contract opportunity is a solicitation for the renovation of VAV controls in Building 200 Wings B1, D1, and select rooms in Wings C and E.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
(RFI) 36C24922B0027
PROJECT NUMBER: 621-22-144 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.
When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Bldg 200, 1st Flr. Wings B,C,D,E PROJECT LOCATION: James H. Quillen VA Medical
Center Lamont and Veterans Way Mt Home, TN 37684
TO:
Craig Ziegemeier, Contracting Officer craig.ziegemeier@va.gov
RFI NO.: DATE: SPEC/DWG. REFERENCE:
REPLY NEEDED BY:
INFORMATION NEEDED:
REPLY:
REPLY FROM: DATE:
ATTACHMENTS: COPY TO:
SUBMITTED BY: City/State:
PHONE NO.:
"Demo" of VAV pneumatics is assumed to be removal of devices at the VAV and the associated thermostat, with main air lines capped.
Are there any special, or additional, requirements associated with the pneumatics, such as complete removal on the floor or removals of lines "back to" point, or standards?
02 41 00 pneumatic demo 07/20/222
Contego Environmental 423-523-2650
Panama City, FL mailto:diana.grube@va.gov VHAMOUPageD Text Box Demo of the VAV pneumatics means removal of the VAV pneumatic actuator, pneumatic thermostat, the pneumatic VAV controller, and all pneumatic control air line. The main control air lines (20-30psi) are to be removed from the rooms and capped with a brass plug above the drop ceiling in the corridor. Pneumatic lines bent over and tapped will not be accepted as a capped line.
VHAMOUPageD Text Box 07/20/22
| 2022-07-20T12:30:47-0400 | |
| DANIEL PAGE |
File details come from the government source that posted it. Updated .