36C24920R0043-0006004.pdf
PDF Posted
- Solicitation number
- 36C24920R0043
About this file
This pre-solicitation notice describes an upcoming request for proposals from the Department of Veterans Affairs for elevator upgrade work at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The project magnitude is estimated between $2 million to $5 million, with responses due on or around January 24, 2020. The solicitation will be posted on SAM.gov. This requirement is fully set aside for service-disabled veteran-owned small businesses, which must be verified through the VA's Vendor Information Pages database prior to proposal submission. The construction work includes demolition, new construction, and upgrades for general trades as well as mechanical, electrical and other building systems. The project completion deadline is 360 calendar days following award.
36C24920R0043 0006 14 21 00 Traction Elevator Specs 20190711 RS Revised 20200506.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24920R0043-0008005.pdf | ||
| 36C24920R0043-0008004.pdf | ||
| 36C24920R0043-0008002.pdf | ||
| 36C24920R0043-0008001.pdf | ||
| 36C24920R0043-0008003.pdf | ||
| 36C24920R0043-0008000.docx | DOCX document | |
| 36C24920R0043-0007001.pdf | ||
| 36C24920R0043-0007000.docx | DOCX document | |
| 36C24920R0043-0006001.docx | DOCX document | |
| 36C24920R0043-0006000.docx | DOCX document | |
| 36C24920R0043-0006002.pdf | ||
| 36C24920R0043-0006003.pdf | ||
| 36C24920R0043-0005000.docx | DOCX document | |
| 36C24920R0043-0004000.docx | DOCX document | |
| 36C24920R0043-0003000.docx | DOCX document | |
| 36C24920R0043-0002000.docx | DOCX document | |
| 36C24920R0043-0001000.docx | DOCX document | |
| 36C24920R0043-006.xlsx | XLSX spreadsheet | |
| 36C24920R0043-003.docx | DOCX document | |
| 36C24920R0043-004.pdf | ||
| 36C24920R0043-005.pdf | ||
| 36C24920R0043-008.docx | DOCX document | |
| 36C24920R0043-007.pdf |
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Alvin C. York VAMC May 6, 2020
AE Upgrade Elevators Bldgs. 8 and 9 Addendum 1
Murfreesboro, TN 37129 Project No. 626A4-18-203
14 21 00-1
SECTION 14 21 00
TRACTION ELEVATORS
PART 1 GENERAL
1.1 DESCRIPTION
A. This section specifies the engineering, furnishing and installation of the complete electric traction elevator system as described herein and as indicated on the Contract drawings.
B. Items listed in the singular apply to each elevator in this specification except where noted.
C. Passenger Elevators for buildings 8 and 9 shall be overhead, gearless traction, microprocessor control system, power operated single-speed center opening car and hoistway doors with Class “A” load rated.
ELEVATOR SCHEDULE
Elevator Number
Overall Platform Size
Clear Inside Platform
Rated Load – kg (lb) 3500 lbs
Contract Speed - m/s (fpm) 200 fpm
Total Travel – m (ft)
Floors Served Three all in line
Number of Openings Three all in line
Entrance Type & Size Side opening two speed
Type of Roping
1.2 RELATED WORK
A. Section 01 33 23 SPECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR
52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL CONDITIONS.
B. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-rated construction.
C. SECTION 09 06 00, SCHEDULE FOR FINISHES: As a master format for construction projects, to identify interior and exterior material finishes for type, texture, patterns, color and placement.
D. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section.
E. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
(600 VOLTS AND BELOW): Low Voltage power and lighting wiring.
14 21 00-2
F. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.
G. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for cables and wiring.
H. Section 26 24 16, PANELBOARDS: Low voltage panelboards.
I. Section 26 51 00, INTERIOR LIGHTING: Fixture and ballast type for interior lighting.
J. Section 28 31 00 Fire Detection and Alarm
1.3 QUALIFICATIONS
A. Approval by the Contracting Officer is required for products and services of proposed manufacturers, suppliers and installers and shall be contingent upon submission of certificates by the Contractor stating the following:
1. Elevator contractor is currently and regularly engaged in the installation of elevator equipment as one of his principal products.
2. Elevator contractor shall have five (5) years of successful experience, trained supervisory personnel, and facilities to install elevator equipment specified herein.
3. Elevator Mechanic (Installer) shall have passed a Mechanic
Examination approved by the U.S. Department of Labor and have technical qualifications of at least five years of experience in the elevator industry or 10,000 hours of field experience working in the elevator industry with technical update training. Apprentices shall be actively pursuing Certified Elevator Mechanic status.
Certification shall be submitted for all workers employed in this capacity.
B. Welding at the project site shall be made by welders and welding operators who have previously qualified by test as prescribed in
American Welding Society Publications AWS Dl.1 to perform the type of work required. Certificates shall be submitted for all workers employed in this capacity. A welding or hot work permit is required for each day and shall be obtained from the VAMC safety department. Request permit one day in advance.
C. Electrical work shall be performed by a Licensed Master Electrician and
Licensed Journeymen Electricians as requirements by NEC. Certificates shall be submitted for all workers employed in this capacity.
14 21 00-3
D. Approval will not be given to elevator contractors and manufacturers who have established on prior projects, either government, municipal, or commercial, a record for unsatisfactory elevator installations, have failed to complete awarded contracts within the contract period, and do not have the requisite record of satisfactory performing elevator installations of similar type and magnitude.
E. Approval of Elevator Contractor’s equipment will be contingent upon their providing factory training, engineering and technical support, including all manuals, wiring diagrams, and tools necessary for adjusting, maintenance, repair, and testing of equipment to the VA for use by the VA’s designated Elevator Maintenance Service Provider.
Identifying an elevator maintenance service provider that shall render services within two hours of receipt of notification, together with certification that the quantity and quality of replacement parts stock is sufficient to warranty continued operation of the elevator installation.
F. Equipment within a group of electric traction elevators shall be the product of the same manufacturer.
G. The Contractor shall provide and install safety devices that have been subjected to tests witnessed and certified by an independent professional testing laboratory that is not a subsidiary of the firm that manufactures supplies or installs the equipment.
1.4 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification.
Elevator installation shall meet the requirements of the latest editions published and adopted by the United States Department of
Veterans Affairs on the date contract is signed.
B. Federal Specifications (Fed. Spec.):
J-C-30B.................Cable and Wire, Electrical (Power, Fixed
Installation)
J-C-580.................Cord, Flexible, and Wire, Fixture
W-S-610.................Splice Connectors
W-C-596F................Connector, Plug, Electrical; Connector, Receptacle, Electrical
W-F-406E................Fittings for Cable, Power, Electrical and
Conduit, Metal, Flexible
14 21 00-4
HH-I-558C...............Insulation, Blankets, Thermal (Mineral Fiber, Industrial Type)
W-F-408E................Fittings for Conduit, Metal, Rigid (Thick-Wall and Thin-wall Type)
RR-W-410................Wire Rope and Strand
TT-E-489J...............Enamel, Alkyd, Gloss, Low VOC Content
QQ-S-766................Steel, Stainless and Heat Resisting, Alloys, Plate, Sheet and Strip
C. American Society of Mechanical Engineers (ASME):
A17.1...................Safety Code for Elevators and Escalators
A17.2...................Inspectors Manual for Electric Elevators and
Escalators
D. National Fire Protection Association:
NFPA 13.................Standard for the Installation of Sprinkler
Systems
NFPA 70.................National Electrical Code (NEC)
NFPA 72.................National Fire Alarm and Signaling Code
NFPA 101................Life Safety Code
NFPA 252................Fire Test of Door Assemblies
E. International Building Code (IBC).
F. American Society for Testing and Materials (ASTM):
A1008/A1008M-09.........Steel, Sheet, Cold Rolled, Carbon, Structural, High-Strength Low-Alloy and High Strength Low-
Alloy with Improved Formability
E1042-02................Acoustically Absorptive Materials Applied by
Trowel or Spray
G. Manufacturer's Standardization Society of the Valve and Fittings
Industry (MSS):
SP-58...................Pipe Hangers and Supports
H. Society of Automotive Engineers, Inc. (SAE):
J517-91.................Hydraulic Hose, Standard
I. Gauges:
Sheet and Plate: U.S. Standard (USS)
Wire: American Wire Gauge (AWG)
J. American Welding Society (AWS):
D1.1....................Structured Welding Code Steel
14 21 00-5
K. National Electrical Manufacturers Association (NEMA):
LD-3....................High-Pressure Decorative Laminates
L. Underwriter's Laboratories (UL):
486A....................Safety Wire Connectors for Copper Conductors
797.....................Safety Electrical Metallic Tubing
M. Institute of Electrical and Electronic Engineers (IEEE)
N. Regulatory Standards:
VA Barrier Free Design Handbook H-18-13
VA Seismic Design Manual H-18-8
1.5 SUBMITTALS
A. Submit in accordance with Specification Section 01 33 23, SHOP
DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Before execution of work, furnish information to evidence full compliance with contract requirements for proposed items. Such information shall include, as required: Manufacturer's Name, Trade
Names, Model or Catalog Number, Nameplate Data (size, capacity, and rating) and corresponding specification reference (Federal or project specification number and paragraph). All submitted drawings and related elevator material shall be forwarded to the Contracting Officer.
C. Shop Drawings:
1. Complete scaled and dimensioned layout in plan and section view showing the arrangement of equipment and all details of each elevator unit specified including:
a. Hoisting machines, controllers, power conversion devices, governors, and all other components located in machine room.
b. Car, counterweight, sheaves, supporting beams, guide rails, brackets, buffers, and size of car platform, car frame members, and other components located in hoistway.
c. Rail bracket spacing and maximum vertical forces on guide rails in accordance with H 18-8 for Seismic Risk Zone 2 or greater.
d. Reaction at points of support and buffer impact loads.
e. Weight of principal parts.
f. Top and bottom clearances and over travel of car and counterweight.
g. Location of main line switch/shunt trip circuit breaker, switchboard panel, light switch, and feeder extension points in the machine room.
14 21 00-6
h. Fire alarm connection
2. Drawings of hoistway entrances and doors showing details of construction and method of fastening to the structural members of the building.
a. If drywall construction is used to enclose hoistway, submit details of interface fastenings between entrance frames and drywall.
b. Sill details including sill support.
D. Samples:
1. One each of stainless steel, 75 mm x 125 mm (3 in. x 5 in.).
2. One each of baked enamel, 75 mm x 125 mm (3 in. x 5 in.).
3. One each of color floor covering.
4. One each of protection pads, 75 mm x 125 mm (3 in. x 5 in.) if used.
5. One each car and hoistway Braille plate sample.
6. One each car and hall button sample.
7. One each car and hall lantern/position indicator sample.
8. One each wall and ceiling material finish sample.
9. One each car lighting sample.
E. Name of manufacturer, type or style designation, and applicable data of the following equipment shall be shown on the elevator layouts:
1. Hoisting Machine.
2. Hoisting Machine Motor, HP and RPM ratings, Voltage, Starting and
Full Load Ampere, and Number of Phases.
3. Controller.
4. Starters and Overload Current Protection Devices.
5. Car Safety Device; Type “B” safeties and Governor.
6. Electric Door Operator; HP, RPM, Voltage, and Ampere rating of motor.
7. Hoistway Door Interlocks.
8. Car and Counterweight Buffers; maximum and minimum rated loads, maximum rated striking speed and stroke.
9. Cab Ventilation Unit; HP rating and CFM rating.
10. Hoist and Compensation Ropes; breaking strength, allowable working load, and actual working load.
F. Complete construction drawings of elevator car enclosure showing dimensioned details, fastenings to platform, car lighting, ventilation, ceiling framing, top exits, and location of car equipment.
14 21 00-7
G. Complete dimensioned detail of vibration isolating foundations for traction hoisting machines.
H. Dimensioned drawings showing details of:
1. All signal and operating fixtures.
2. Car and counterweight roller guides.
3. Hoistway door tracks, hangers, and sills.
4. Door operator, infrared curtain units.
I. Cut sheets and drawings showing details of controllers and supervisory panels.
J. Furnish certificates as required under: Paragraph "QUALIFICATIONS".
1.6 WIRING DIAGRAMS
A. Provide three complete sets of paper and one electronic set field wiring and straight-line wiring diagrams showing all electrical circuits in the hoistway, machine room and fixtures and fire alarm relays. Install one set coated with an approved plastic sealer and mounted in the elevator machine room as directed by the COR.
B. In the event field modifications are necessary during installation, diagrams shall be revised to include all corrections made prior to and during the final inspection. Corrected diagrams shall be delivered to the COR within thirty (30) days of final acceptance.
C. Provide the following information relating to the specific type of microprocessor controls installed:
1. Owner's information manual, containing job specific data on major components, maintenance, and adjustment.
2. System logic description.
3. Complete wiring diagrams needed for field troubleshooting, adjustment, repair and replacement of components. Diagrams shall be base diagrams, containing all changes and additions made to the equipment during the design and construction period.
4. Changes made during the warranty period shall be noted on the drawings in adequate time to have the finalized drawings reproduced for mounting in the machine room no later than six months prior to the expiration of the warranty period.
1.7 ADDITIONAL EQUIPMENT
A. Additional equipment required to operate the specified equipment manufactured and supplied for this installation shall be furnished and
14 21 00-8 installed by the contractor. The cost of the equipment shall be included in the base bid.
1.8 TOOL CABINET
A. Provide a metal parts/tool cabinet, having two shelves and hinged doors. Cabinet size shall be 1200 mm (48 in.) high, 750 mm (30 in.)
wide, and 450 mm (18 in.) deep.
1.9 PERFORMANCE STANDARDS
A. The elevators shall meet the highest standards of the industry and specifically the following:
1. Contract speed is high speed in either direction of travel with rated capacity load in the elevator. Speed variation under all load conditions, regardless of direction of travel, shall not vary more than three (3) percent.
2. The controlled rate of change of acceleration and retardation of the car shall not exceed 0.1G per ft/s/s and the maximum acceleration and retardation shall not exceed 0.2G per ft/s/s.
3. Starting, stopping, and leveling shall be smooth and comfortable without appreciable steps of acceleration and deceleration.
B. Passenger door operator shall open the car door and hoistway door at 75 cm (2.5 ft) per second and close at 30 cm (1 ft) per second.
C. Floor level stopping accuracy shall be within 3 mm (.125 in.) above or below the floor, regardless of load condition.
D. Noise and Vibration Isolation: All elevator equipment including their supports and fastenings to the building, shall be mechanically and electrically isolated from the building structure to minimize objectionable noise and vibration transmission to car, building structure, or adjacent occupied areas of building.
E. Sound Isolation: Noise level relating to elevator equipment operation in the machine room shall not exceed 80 decibels. All db readings shall be taken 90 cm (3 ft) off the floor and 90 cm (3 ft) from equipment.
F. Airborne Noise: Measured noise level of elevator equipment during operation shall not exceed 50 decibels in elevator lobbies and 60 decibels inside car under any condition including door operation and car ventilation exhaust blower on its highest speed.
1.10 WARRANTY
A. Submit all labor and materials furnished regarding elevator system and installation to terms of "Warranty of Construction" articles of FAR
14 21 00-9 clause 52.246-21. The one-year Warranty shall commence after final inspection, completion of performance test, and upon full acceptance of the installation and run concurrent with the guarantee period of service.
B. During warranty period if a device is not functioning properly in accordance with specification requirements, more maintenance than the contract requires keeping device operational, device shall be removed and a new device meeting all requirements shall be installed as part of work until satisfactory operation of installation is obtained. Period of warranty shall start anew for such parts from date of completion of each new installation performed, in accordance with foregoing requirements.
1.11 POWER SUPPLY
A. For power supply in each machine room, see Specification 26 05 19, Electrical specifications, and Electrical drawings.
B. Main Line Fused Disconnect Switch/Shunt Trip Circuit Breaker for each controller shall be located inside the machine room at the strike jamb side of the machine room door and lockable in the “Off” position.
C. Surge Suppressors to protect the elevator equipment.
1.12 EMERGENCY POWER SUPPLY
A. Emergency power supply, its starting means, transfer switch for transfer of elevator supply from normal to emergency power, two pair of conductors in a conduit from an auxiliary contact on the transfer switch (open or close contacts as required by Controller Manufacturer) to terminals in the group elevator controller and other related work shall be provided by the Electrical Contractor.
B. Upon loss of normal power supply there shall be a delay before transferring to emergency power of 10 seconds minimum to 45 seconds maximum, the delay shall be accomplished through an adjustable timing device.
C. Prior to the return of normal power an adjustable timed circuit shall be activated that will cause all elevators to remain at a floor if already there or stop and remain at the next floor if in flight. Actual transfer of power from emergency power to normal building power shall take place after all elevators are stopped at a floor with doors open.
D. Car lighting circuits shall be connected to the emergency power panel.
14 21 00-10
1.13 ELEVATOR MACHINE ROOM AND MACHINE SPACE
A. Provide a machine room that meets the requirements of latest edition of
ASME A17.1, NEC, and IBC.
B. Provide stairs and landing for access to the machine room. The landing shall be large enough to accommodate full opening of the door plus 60 cm (24 in.).
C. Locate the light switch on the lock side of the door inside the machine room.
D. Locate sprinkler pipes to provide seven 210 cm (7 ft) head clearance.
Do not locate sprinkler heads, heat detectors, and smoke detectors directly over elevator equipment.
1.14 HOISTWAY LIGHTING
A. Provide lighting with 3-way switches at the top and bottom of the hoistway accessible from elevator hoistway entrance prior to entering the pit or stepping onto the car top.
B. Lighting shall illuminate top of elevator cab when it is at the top floor and the pit when at the bottom floor.
PART 2 – PRODUCTS
2.1 MATERIALS
A. Where stainless steel is specified, it shall be corrosion resisting steel complying with Fed. Spec. QQ-S-766, Class 302 or 304, Condition A with Number 4 finish on exposed surfaces. Stainless steel shall have the grain of belting in the direction of the longest dimension and surfaces shall be smooth and without waves. During installation stainless-steel surfaces shall be protected with suitable material.
B. Where cold rolled steel is specified it shall be low-carbon steel rolled to stretcher level standard flatness, complying with ASTM A109.
2.2 MANUFACTURED PRODUCTS
A. Materials, devices, and equipment furnished shall be of current production by manufacturers regularly engaged in the manufacture of such items. The elevator equipment, including controllers, door operators, and supervisory system shall be the product of manufacturers of established reputation, provided such items are capably engineered and produced under coordinated specifications to ensure compatibility with the total operating system.
B. Manufacturers of equipment assemblies which include components made by others shall assume complete responsibility for the final assembled
14 21 00-11 unit. Components shall be compatible with each other and with the total assembly for the intended service.
C. Mixing of manufactures related to a single system or group of components shall be identified in the submittals.
D. If key operated switches are furnished in conjunction with component of this elevator installation, furnish four (4) keys for each individual switch or lock. Provide different key tumblers for different switch and lock functions. Each key shall have a tag bearing a stamped or etched legend identifying its purpose.
2.3 CONDUIT AND WIREWAY
A. Install electrical conductors, except traveling cable, in rigid zinc-coated steel or aluminum conduit, electrical metallic tubing or metal wireways. Rigid conduit smaller than 18.75 mm (.75 in.) or electrical metallic tubing smaller than 12.5 mm (.50 in.) electrical trade size shall not be used. All raceways completely embedded in concrete slabs, walls, or floor fill shall be rigid steel conduit. Wireway (duct) shall be installed in the hoistway and to the controller and between similar apparatus in the elevator machine room. Fully protect self-supporting connections, where approved, from abrasion or other mechanical injury. Flexible metal conduit not less than 9.375 mm (.375 in.) electrical trade size may be used, not exceeding 45 cm (18 in.) in length unsupported, for short connections between risers and limit switches, interlocks, and for other applications permitted by NEC.
B. All conduit terminating in steel cabinets, junction boxes, wireways, switch boxes, outlet boxes and similar locations shall have approved insulation bushings. Install a steel lock nut under the bushings if they are constructed completely of insulating materials. Protect the conductors at ends of conduits not terminating in steel cabinets or boxes by terminal fittings having an insulated opening for the conductors.
C. Rigid conduit and EMT fittings using set screws or indentations as a means of attachment shall not be used.
D. Connect motor or other items subject to movement, vibration or removal to the conduit or EMT systems with flexible, steel conduits.
2.4 CONDUCTORS
A. Conductors shall be stranded or solid coated annealed copper in accordance with Federal Specification J-C-30B for Type RHW or THW.
14 21 00-12
Where 16 and 18 AWG are permitted by NEC, single conductors or multiple conductor cables in accordance with Federal Specification J-C-580 for
Type TF may be used provided the insulation of single conductor cable and outer jacket of multiple conductor cable is flame retardant and moisture resistant. Multiple conductor cable shall have color or number coding for each conductor. Conductors for control boards shall be in accordance with NEC. Joints or splices are not permitted in wiring except at outlets. Tap connectors may be used in wireways provided they meet all UL requirements.
B. Provide all conduit and wiring between machine room, hoistway and fixtures.
C. All wiring must test free from short circuits or ground faults.
Insulation resistance between individual external conductors and between conductors and ground shall be a minimum of one megohm.
D. Where size of conductor is not given, voltage and amperes shall not exceed limits set by NEC.
E. Provide equipment grounding. Ground the conduits, supports, controller enclosure, motor, platform and car frame, and all other non-current conducting metal enclosures for electrical equipment in accordance with
NEC. The ground wires shall be copper, green insulated and sized as required by NEC. Bond the grounding wires to all junction boxes, cabinets, and wire raceways.
F. Terminal connections for all conductors used for external wiring between various items of elevator equipment shall be solderless pressure wire connectors in accordance with Federal Specification W-S-
610. The Elevator Contractor may, at his option, make these terminal connections on #10 gauge or smaller conductors with approved terminal eyelets set on the conductor with a special setting tool, or with an approved pressure type terminal block. Terminal blocks using pierce-through serrated washers are not acceptable.
2.5 TRAVELING CABLES
A. All conductors to the car shall consist of flexible traveling cables conforming to the requirements of NEC. Traveling cables shall run from the junction box on the car directly to the controller. Junction boxes on the car shall be equipped with terminal blocks. Terminal blocks having pressure wire connectors of the clamp type that meet UL 486A requirements for stranded wire may be used in lieu of terminal eyelet
14 21 00-13 connections. Terminal blocks shall have permanent indelible identifying numbers for each connection. Cables shall be securely anchored to avoid strain on individual terminal connections. Flame and moisture resistant outer covering must remain intact between junction boxes. Abrupt bending, twisting and distortion of the cables shall not be permitted.
B. Provide spare conductors equal to 10 percent of the total number of conductors furnished, but not less than 5 spare conductors in each traveling cable.
C. Provide shielded wires (2-Cat 6)for the auto dial telephone system within the traveling cable, five (5) pair shielded wires for card reader, one (1) the CAT 6 Ethernet cable for Wi-Fi, two (2) pair 14-gauge wires for 110 Volt power supply, one CAT 6 for future cameras, one CAT 6 for future Code condition and wire for video display monitor if specified.
D. If traveling cables contact the hoistway or elevator due to sway or change in position, provide shields or pads to the elevator and hoistway to prevent damage to the traveling cables.
E. Hardware cloth may be installed from the hoistway suspension point to the elevator pit to prevent traveling cables from rubbing or chafing and securely fastened and tensioned to prevent buckling. Hardware cloth is not required when traveling cable is hung against a flat wall.
2.6 CONTROLLER AND SUPERVISORY PANEL
A. UL/CSA Labeled Controller: Mount all assemblies, power supplies, chassis switches, and relays on a steel frame in a NEMA Type 1 General
Purpose Enclosure. Cabinet shall be securely attached to the building structure.
B. Properly identify each device on all panels by name, letter, or standard symbol which shall be neatly stencil painted or decaled in an indelible and legible manner. Identification markings shall be coordinated with identical markings used on wiring diagrams. The ampere rating shall be marked adjacent to all fuse holders. All spare conductors to controller and supervisory panel shall be neatly formed, laced, and identified.
C. Controller shall be provided with wiring and components for additional future travel if required.
14 21 00-14
2.7 MICROPROCESSOR CONTROL SYSTEM
A. Provide a microprocessor control system with absolute position/speed feedback to control dispatching, signal functions, door operation, and
VVVF Drive for hoist motor control. Complete details of the components and printed circuit boards, together with a complete operational description, shall be submitted for approval. Add Regenerative Drive when economically advantages to the VA.
B. Controller manufacturer shall provide factory training, engineering and technical support, including all manuals, wiring diagrams, and tools necessary for adjusting, maintenance, repair, and testing of equipment to the VA for use by the VA’s designated Elevator Maintenance Service
Provider.
2.8 EMERGENCY POWER OPERATION
A. The control system for Elevator(s) shall provide for the operation of at least one car per elevator group on emergency power upon failure of the normal power supply.
B. Auxiliary equipment on elevator controllers, wiring between associated elevator controllers and wiring between elevator controllers and remote selector panel as required to permit the elevators to operate as detailed, shall be provided by the Elevator Contractor.
C. Upon loss of normal power supply there shall be a delay before transferring to emergency power of 10 seconds minimum to 45 seconds maximum, the delay shall be accomplished through an adjustable timing device. After adjusting delay, the associated elevators shall function as follows:
2.9 MACHINE ROOM MONITOR
A. Provide a monitor in each machine room, separate monitors for each passenger elevator group, and each service elevator group. Provide a separate keyboard for each monitor.
B. The monitor shall contain indicators to provide the following information:
1. The floor where each elevator is currently located.
2. The direction that each elevator is currently traveling or is scheduled to travel.
3. The location and direction of currently registered hall calls.
4. Elevators that are currently out of service.
5. Elevators that are currently bypassing hall calls.
14 21 00-15
6. Elevators that are currently engaged in passenger transfers.
7. Operations program under which entire group is currently operating.
8. Zone divisions of the entire group.
9. Door positions.
10. Status indication for elevators on independent service, car top inspection, fire service, earthquake protection, and activated stop switch and alarm bell.
C. The maintenance terminal shall be suitable for all troubleshooting procedures related to the specific type microprocessor installed on this project.
2.10 FIREFIGHTER’S SERVICE
A. Provide Firefighter’s Service.
1. Main Floor
2. Alternate Floor
3. Verify main and alternate floors with Contract Officer’s
Representative.
2.11 INDEPENDENT SERVICE
A. Provide a legibly and indelibly labeled "INDEPENDENT SERVICE", two-position key operated switch that shall have its positions marked "ON" and "OFF". When the switch is in the "ON" position, the car shall respond only to calls registered on its car dispatch buttons and shall bypass all calls registered on landing push buttons. The car shall start when a car call is registered, car call button or door close button is pressed, car and hoistway doors are closed, and interlock circuits are made. When switch is returned to "OFF" position, normal service shall be resumed.
2.12 MEDICAL EMERGENCY SERVICE
A. Provisions shall be made for calling elevator(s) to any floor served by the elevator on an emergency basis, operating independently from the dispatch signals and landing call signals.
B. Provide key switches in the floor landing push button fixture above the push buttons and provide key switch in each elevator car.
C. Provide a call registered light indicator adjacent to key switch. The ckey switch at the landings and in the car, shall only be operable by authorized personnel with a valid VA ID badge/key.
D. When key switch is activated at any floor, the call register light indicator shall illuminate at the call floor and inside the elevator
14 21 00-16 only. The elevator control system shall instantly select an elevator to respond to the medical emergency call. Immediately upon selection, all car calls shall be cancelled. If car is traveling away from the medical emergency call, it shall slow down and stop at the nearest floor, maintain closed doors, reverse direction and proceed nonstop to the medical emergency call floor. If the car is traveling toward the medical emergency call floor, it shall proceed to that floor nonstop.
If at the time of selection, it is slowing down for a stop, the car shall stop, maintain doors closed, and start immediately toward the medical emergency floor.
E. Arriving at the medical emergency floor, the car shall remain with doors open for 30 seconds. After this interval has expired and the car has not been placed on medical emergency operation inside the car, the car shall automatically return to normal service.
F. Provide an key switch the same size as the Fire Service indicator.
1. Locate a “Medical Emergency” key switch above call buttons in the main car operating panel for selecting medical emergency service.
Activation of the card reader will allow the car to accept a car call for any floor, close doors, and proceed nonstop to the floor desired.
2. After medical emergency call has been completed the elevator shall return to normal operation after an adjustable time of 30 to 90 seconds has expired.
G. In the center of the rear cab panel provide a back lighted "MEDICAL
EMERGENCY" LED illuminated display that shall flash on and off continuously when the car is assigned to this operation and until it is restored to normal service. "MEDICAL EMERGENCY" indicator shall be a photographic negative type 1800 mm (72 in.) to center above the floor, 150 mm (6 in.) wide X 75 mm (3 in.) high, with 12.5 mm (.50 in.) high letters legible only when illuminated.
H. If the car being operated on “Independent Service”, the medical emergency service indicator lights in the car operating panel and rear wall shall be illuminated, buzzer shall sound, and the “Audio Voice” system shall direct the attendant to return the car to automatic operation.
I. If the car is out of service and unable to answer medical emergency calls, the call register light shall not illuminate.
14 21 00-17
J. Each key switch shall have its identity legible and indelible engraved in faceplates. All lettering shall be 6 mm (.25 in.) high, filled with black paint.
K. When Phase I firefighter’s recall is activated it shall over-ride elevators on medical emergency service and return them to the main or alternate fire service recall floor. When the fire emergency floor has been identified the attendants may complete their medical emergency run on Phase II firefighter’s operation if life safety is not affected.
2.13 LOAD WEIGHING
A. Provide means for weighing car load for each elevator. When load in a car reaches an adjustable predetermined level of the rated capacity, that car shall bypass registered landing calls until the load in the car drops below the predetermined level. Calls bypassed in this manner shall remain registered for the next car. The initial adjustment of the load weighting bypass setting shall be 60 to 100 percent.
2.14 ANTI-NUISANCE FEATURE
A. If weight in the car is not commensurate with the number of registered car calls, cancel car calls. Systems that employ either load weighing or door protective device for activation of this feature are acceptable.
2.15 SEISMIC REQUIREMENTS
A. Meet the requirements of VA Seismic Design Manual H-18-8.
2.16 ELEVATOR MACHINE BEAMS
A. Overhead beams shall support machines and machinery in place to prevent movement under any conditions imposed in service.
2.17 TRACTION HOIST MACHINE
A. Provide gearless traction machine with an AC motor, brake, drive sheave, and deflector sheave mounted in proper alignment on an isolated bedplate.
B. Provide hoist machine mounted direct drive, digital, closed-loop velocity encoder.
C. Drive sheaves shall be free from cracks, sand holes, and other imperfections that would tend to injure the hoist ropes. Sheave shall be turned smooth and true with rope grooves of proper design to insure maximum traction and maximum life of the hoist ropes.
D. Hoisting machine brake shall be drum or disc type and shall stop and hold the elevator with 125 percent of rated load.
14 21 00-18
2.18 SHEAVES
A. Provide deflector sheaves with a metal basket type guard mounted below the sheave and a guard to prevent ropes from jumping out of grooves.
Securely fasten guard to sheave support beams.
B. Two-to-one idler sheaves on car and counterweight, if used, shall be provided with metal guards that prevent foreign objects from falling between ropes and sheave grooves and to prevent ropes from jumping out of grooves.
C. Securely mount overhead sheaves on overhead beams in proper alignment with basement traction sheave, car and counterweight rope hitches or sheaves. Provide blocking beams where sheaves are installed on two or more levels.
2.19 HOIST ROPES
A. Provide elevator with the required number and size of ropes to insure adequate traction and required safety factor. Hoisting ropes shall be pre-formed 8 x 19 or 8 x 25 traction steel, conforming to Federal
Specification RR-W-410 with minimum nominal diameter of 12.5 mm (.50 in.).
B. Securely attach a corrosion resistant metal data tag to one hoisting rope fastening on top of the elevator.
2.20 HOIST ROPE COMPENSATION
A. Provide compensation when required by controller manufacturer.
Compensation shall consist of a necessary number and size of encapsulated chains attached to the underside of car and counterweight frames.
1. Provide guide(s) in pit to minimize chain sway.
2. Provide take-up adjustment to compensate for hoist rope stretch.
3. Pad areas where compensation may strike car or hoistway items.
2.21 GOVERNOR ROPE
A. Governor Rope shall be 6 x 19 or 8 x 19 wire rope, preformed traction steel, uncoated, fiber core, conforming to Federal Specification RR-W-
410 with minimum nominal diameter of 9.375 mm (.375 in.) having a minimum safety factor of 5. Tiller rope construction is not acceptable.
B. Under normal operation rope shall run free and clear of governor jaws, rope guards, and other stationary parts.
C. Securely attach governor rope tag to governor rope releasing carrier.
14 21 00-19
2.22 SPEED GOVERNOR
A. Provide Centrifugal car driven governor to operate the car safety device shall be complete with weighted pit tension sheave, governor release carrier and mounting base with protected cable sleeves.
B. Furnish overspeed switch and speed reducing switches when required.
C. The governor rope clamping device shall be designed to prevent appreciable damage to or deformation of the governor rope that results from the stopping action of the device operating the safety.
D. Provide metal guard over top of governor rope and sheaves.
E. Where the elevator travel does not exceed 100 feet, the weight tension sheave may be mounted on a pivoted steel arm in lieu of operating in steel guides.
2.23 CAR SAFETY DEVICE
A. Provide “Type B Safeties” on the elevator.
2.24 ASCENDING CAR OVERSPEED PROTECTION
A. Provide a device to prevent ascending over speed and unintended motion away from the landing in either direction when the doors are not locked.
2.25 CAR AND COUNTERWEIGHT BUFFERS
A. Provide buffer(s) for each car and each counterweight. Securely fasten buffers and supports to the pit channels and in the alignment with striker plates on car and counterweight. Each installed buffer shall have a permanently attached metal plate indicating its stroke and load rating. Buffer anchorage shall not puncture pit waterproofing.
2.26 COUNTERWEIGHTS
A. Elevator shall be counterweighted with the weight of the car plus 40-50 percent of the rated capacity load as required by the controller manufacturer.
B. Furnish two (2) tie rods with cotter pins and double nuts at top and bottom. Install counterweight retainer plates or other approved means on tie rods to prevent counterweight sub-weights from jumping and/or rattling. Both ends of tie-rods shall be visible and accessible.
2.27 GUIDE RAILS, SUPPORTS, AND FASTENINGS
A. Guide rails for car shall be planed steel T-sections and weigh 27.5 kg/m (18.5 lb/ft) Guide rails for counterweight shall be planed steel
T-sections and weigh 22.5 kg/m (15 lb/ft.
14 21 00-20
B. Securely fasten guide rails to the brackets or other supports by heavy duty steel rail clips.
C. Provide car and counterweight rail brackets and counterweight spreader brackets of sufficient size and design to secure substantial rigidity to prevent spreading or distortion of rails under any condition.
D. Guide rails shall extend from channels on pit floor to within 75 mm (3 in.) of the underside of the concrete slab or grating at top of hoistway with a maximum deviation of 3.2 mm (.125 in.) from plumb in all directions. Provide a minimum of 18.5 mm (.75 in.) clearance between bottom of rails and top of pit channels.
E. Guide rail anchorages in pit shall be made in a manner that will not reduce effectiveness of the pit waterproofing.
F. In the event inserts or bond blocks are required for the attachment of guide rails, the Contractor shall furnish such inserts or bond blocks and shall install them in the forms before the concrete is poured. Use inserts or bond blocks only in concrete or block work where steel framing is not available for support of guide rails. Expansion-type bolting for guide rail brackets will not be permitted.
G. Guide rails shall be clean and free of any signs of rust, grease, or abrasion before final inspection. Paint the shank and base of the T-section with one field coat of manufacturer’s standard enamel.
2.28 NORMAL AND FINAL TERMINAL STOPPING DEVICES
A. Mount terminal slowdown switches and direction limit switches on the elevator or in hoistway to reduce speed and bring car to an automatic stop at the terminal landings.
1. Switches shall function with any load up to and including 125 percent of rated elevator capacity at any speed obtained in normal operation.
2. Switches, when opened, shall permit operation of elevator in reverse direction of travel.
B. Mount final terminal stopping switches in the hoistway.
1. Switches shall be positively opened should the car travel beyond the terminal direction limit switches.
2. Switches shall be independent of other stopping devices.
3. Switches, when opened, shall remove power from hoist motor, apply hoist machine brake, and prevent operation of car in either direction.
14 21 00-21
2.29 CROSSHEAD DATA PLATE AND CODE DATA PLATE
A. Permanently attach a non-corrosive metal Data Plate to car crosshead.
B. Permanently attach a non-corrosive Code Data Plate to the controller.
2.30 WORKMAN'S LIGHTS AND OUTLETS
A. Provide duplex GFCI protected type receptacles and lamps with guards on top of each elevator car and beneath the platform. The receptacles shall be in accordance with Fed. Spec. W-C-596 for Type D7, 2-pole, 3-wire grounded type, rated for 15 amperes and 125 volts.
2.31 CARTOP OPERATING DEVICE
A. Provide a cartop operating device.
B. The device shall be activated by a toggle switch mounted in the device.
The switch shall be clearly marked "INSPECTION" and "NORMAL" on the faceplate, with 6 mm (.25 in.) letters.
C. Movement of the elevator shall be accomplished by the continuous pressure on a direction button and a safety button.
D. Provide an emergency stop switch, push to stop/pull to run.
E. Provide permanent identification for the operation of all components in the device.
F. The device shall be permanently attached to the elevator crosshead on the side of the elevator nearest to the hoistway doors used for accessing the top of the car.
2.32 CAR LEVELING DEVICE
A. Car shall be equipped with a two-way leveling device to automatically bring the car to within 3 mm (.125 in.) of exact level with the landing for which a stop is initiated regardless of load in car or direction.
B. If the car stops short or travels beyond the floor, the leveling device, within its zone shall automatically correct this condition and maintain the car within 3 mm (.125 in.) of level with the floor landing regardless of the load carried.
2.33 EMERGENCY STOP SWITCHES
A. Provide an emergency stop switch, push to stop/pull to run, for each cartop device, pit, machine spaces, service panel and firefighter’s control panel inside the elevator. Mount stop switches in the pit adjacent to pit access door, at top of the pit ladder 1200 mm (48 in.)
above the bottom landing sill and 1200 mm (48 in.) above the pit floor adjacent to the pit ladder.
14 21 00-22
B. Each stop switch shall be red in color and shall have "STOP" and "RUN" positions legibly and indelibly identified.
2.34 MAIN CAR OPERATING PANEL
A. Locate the main car operating panel in the car enclosure on the front return panel for passenger/service elevators and the front of the side wall for freight elevators. The top floor car call push button shall not be more than 1200 mm (48 in.) above the finished floor. Car call push buttons and indicator lights shall be LED illuminated, round with a minimum diameter of 25 mm (1 in.). Each button shall contain an integral registration LED white light which shall illuminate upon registration of a call and shall extinguish when that call is answered.
B. One-piece front faceplate with edges beveled 15 degrees hinged, swing return panel, or tilt shall have the firefighter’s service panel recessed into the upper section and the service operation panel recessed into the lower section fitted with hinged doors. Doors shall have concealed hinges, be in the same front plane as the faceplate and fitted with key operated locks. Secure the faceplate with stainless steel tamperproof screws.
C. All terminology and tactile symbols on the faceplate shall be on square or rectangular plates recessed into the faceplate with its surface flush with the surface of the faceplate. Use 6 mm (.25 in.) letters to identify all devices in the faceplate. The tactile symbols with contrasting background shall be 12.5 mm (0.5 in.) high raised .075 mm
(.030 in.) on the plate. Surface mounted plates are not acceptable.
D. The upper section shall contain the following items in order listed from top to bottom:
1. Elevator number, 12.5 mm (.50 in.) high with black paint for contrast.
2. Capacity plate information with black paint for contrast with freight loading class and number of passengers allowed.
3. LED illuminated digital car position indicator with direction arrows.
4. Emergency car lighting system consisting of a rechargeable battery, charger, controls, and LED illuminated light fixture. The system shall automatically provide emergency light in the car upon failure or interruption of the normal car lighting service, and function irrespective of the position of the light control switch in the car.
14 21 00-23
The system shall maintain a minimum illumination of 1.0 foot-candle when measured 1200 mm (48 in.) above the car floor and approximately
300 mm (12 in.) in front of the car operating panel, for not less than four (4) hours.
5. Firefighter’s Emergency Operation Panel shall be 1650 mm (66 in.)
minimum to 1800 mm (72 in.) maximum to the top of the panel above finished floor.
6. Firefighter’s Emergency Indicator Light shall be round with a minimum diameter of 25 mm (1 in.).
7. Medical Emergency key switch marked “MEDICAL EMERGENCY” with two positions labeled “ON” and “OFF” and Medical Emergency Indicator
Light located next to the key switch shall be round with a minimum diameter of 25 mm (1 in.). Instruction for Medical Emergency operation shall be engraved below the key switch and light.
8. Key operated Independent Service Switch or switch inside service panel.
9. Provide a Door Hold Button on the faceplate next to the Independent
Service Key Switch. It shall have “DOOR HOLD” indelibly marked on the button. Button shall light when activated. When activated, the door shall stay open for a maximum of one minute. To override hold timer, push a car call button or door close button.
10. Complete set of round car call push buttons, minimum diameter of 25 mm (1 in.), and LED white light illuminated, corresponding to the floors served. Car call buttons shall be legibly and indelibly identified by a floor number and/or letter not less than 12.5 mm
(.50 in.) high in the face of the call button.
11. Door Open and Door Close buttons shall be located below the car call buttons. They shall have “OPEN” and “CLOSE” legibly and indelibly identified by letters in the face of the respective button. The
Door Open button shall be located closest to the door jamb.
a. Rear Door Open and Rear Door Close buttons shall be located below the Front Door Open and Front Door Close buttons. They shall have “REAR OPEN” and “REAR CLOSE” legibly and indelibly identified by letters in the face of the respective button.
12. Red Emergency Alarm button that shall be located below the car operating buttons. Mount the emergency alarm button not lower than
875 mm (35 in.) above the finished floor. It shall be connected to
14 21 00-24 audible signaling devices. Provide audible signaling devices including the necessary wiring.
13. Emergency Help push button shall activate two-way communications by
Auto Dial telephone system that is compatible with the VAMC’s telephone system. Help button shall be LED white light illuminated and flash when call is acknowledged. Legibly and indelibly label the button “HELP” in the face of the button with 12.5 mm (.50 in.) high letters.
E. The service operation panel, in the lower section shall contain the following items:
1. Light switch labeled “LIGHTS” for controlling interior car lighting with its two positions marked “ON” and “OFF”.
2. Inspection switch that will disconnect normal operation and activate hoistway access switches at terminal landings. Switch shall be labeled “ACCESS ENABLE” with its two positions marked “ON” and
“OFF”.
3. Three-position switch labeled “FAN” with its positions marked
“HIGH”, “LOW” and “OFF” for controlling car ventilating blower.
4. Two-position, spring return, toggle switch or push button to test the emergency light and alarm device. It shall be labeled “TEST
EMERGENCY LIGHT AND ALARM”.
5. Two-position emergency stop switch, when operated, shall interrupt power supply and stop the elevator independently of regular operating devices. Emergency stop switch shall be marked “PUSH TO
STOP” and “PULL TO RUN”.
2.35 AUXILIARY CAR OPERATING PANEL
A. Provide an auxiliary car operating panel in the side wall of the elevator between the handrails immediately adjacent to the front entrance column strike jamb. The auxiliary car operating panel shall contain only those controls essential to passenger (public) operation. The auxiliary car operating panel faceplate shall match the main car operating panel faceplate in material and general design.
Secure the faceplate with stainless steel tamperproof screws.
1. Complete set of round car call push buttons, minimum diameter 25 mm
(1 in.), and LED white light illuminated, corresponding to the floors served. Car call button shall be legibly and indelibly identified by a floor number and/or letter not less than 12.5 mm
14 21 00-25
(.50 in.) high in the face of the call button corresponding to the numbers of the main car operating buttons.
2. Mount door "OPEN" and door "CLOSE" buttons closest to the door jamb and mount the alarm button no lower than 875 mm (35 in.) above the finished floor. The Door Open button shall be located closest to the door.
3. Cross-connect all buttons in the auxiliary car operating panels to their corresponding buttons in the main car operating panel.
Registration of a car call shall cause the corresponding button to illuminate in the main and auxiliary car operating panel.
4. Emergency Help push button shall activate two-way communications by auto dial telephone that is compatible with the…