Attachment 3 Project Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24825R0168
About this file
These are architectural and structural engineering drawings for a temporary shoring installation project at the Bay Pines VA Medical Center in Florida. The project (Number 516-23-604) involves repairing structural concrete deficiencies in the crawl space of Building 1, including spall repairs, epoxy injection, and carbon fiber reinforced polymer (CFRP) wrap applications. The drawings detail specific repair areas across four zones, documenting concrete deterioration, reinforcement exposure, and recommended repair techniques. The final submission is dated 08-25-2025 and is prepared by Innovative Engineering, Inc. for the U.S. Department of Veterans Affairs Office of Construction and Facilities Management, with design codes following the 2021 International Building Code and Florida Building Code 2023.
The technical specifications include detailed repair procedures such as removing loose concrete, cleaning and treating exposed reinforcing steel, applying corrosion inhibitors, using high-strength structural cementitious repair materials, and installing CFRP wraps. The project requires precise surface preparation, careful concrete removal to specified depths, and specific attention to reinforcement condition, with instructions to stop and contact the Contracting Officer Representative (COR) if reinforcing steel has lost more than 10% of its cross-sectional area. Shoring requirements are explicitly defined, with factored loads specified for different structural elements like joists, beams, and floor areas.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF DRAWINGS
GI001
SHEET
NO.
DRAWING
TITLE
GENERAL
COVER SHEET
INSTALL TEMP SHORING IN CRAWL SPACE
AT BUILDING 1
PROJECT NUMBER: 516-23-604
FINAL SUBMISSION
10000 BAY PINES BOULEVARD,
BAY PINES, FL 33744
LOCATION MAP
NOT TO SCALE
AREA MAP
NOT TO SCALE
TRUE
NORTH
PLAN
NORTH
BUILDING 1
PROJECT LOCATION
PROJECT LOCATION
TRUE
NORTH
PLAN
NORTH
STRUCTURCAL
STRUCTURAL NOTESS001
ENLAGED REPAIR AREA PLANSS101
S102
S103
OVERALL CRITICAL AREA PLAN FROM JS HELD REPORTS104
CONCRETE DETAILSS105
ENLAGED REPAIR AREA PLANS
ENLAGED REPAIR AREA PLANS
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FINAL SUBMISSION
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
JM SJ
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
516-23-604
BAY PINES VAMC, FLORIDA
08-25-2025REVISIONS:
COVER SHEET
GI001
STAMP
DESIGN CODES
1.01 2021 INTERNATIONAL BUILDING CODE (IBC) AS MODIFIED BY:
A. ANSI/ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
B. FLORIDA BUILDING CODE 2023
C. PG-18-10 VA STRUCTURAL DESIGN MANUAL FOR HOSPITALS, OCTOBER 1, 2022
1.02 AMERICAN CONCRETE INSTITUTE (ACI)
A. ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
DESIGN LOADS
1.01 DESIGN LOADS ARE AS FOLLOWS:
A. ROOF:
1. DEAD LOADS:
a. ACTUAL WEIGHT OF MATERIALS.
2. LIVE LOADS:
a. 20 PSF
3. RAIN LOADS:
a. N/A: NO ACCUMULATION
4. FLOOD LOADS:
a. N/A: NOT IN FLOOD HAZARD AREA
5. SNOW LOADS: GROUND SNOW LOAD
a. 0 PSF
B. FLOOR:
1. DEAD LOADS:
c. ACTUAL WEIGHT OF MATERIALS
2. LIVE LOADS:
a. CORRIDORS AT MAIN LEVEL = 100 PSF
b. MECHANICAL AREAS = MAXIMUM OF ACTUAL EQUIPMENT WEIGHT OR 100 PSF
c. PROCEDURE ROOMS, EXAM ROOMS = 80PSF INCLUDING 20PSF PARTITION LOAD
C. WIND LOADS:
1. ULTIMATE DESIGN WIND SPEED Vult = 155 MPH
2. NOMINAL DESIGN WIND SPEED Vasd = 120.1 MPH
3. RISK CATEGORY = III
4. WIND EXPOSURE = C
D. EARTHQUAKE LOADS:
1. OCCUPANCY CATEGORY = III
2. SPECTRAL RESPONSE COEFFICIENT:
a. SS = 0.060
b. S1 = 0.030
3. SPECTRAL RESPONSE ACCELERATION:
a. Sds = 0.067
b. Sd1 = 0.046
4. SEISMIC DESIGN CATEGORY = A
5. SITE CLASS = D
1.02 DEFLECTION CRITERIA: REFER TO TABLE 1604.3 FOR DEFLECTION LIMITS
GENERAL STRUCTURAL NOTES
1.01 WHERE A DETAIL, TYPICAL DETAIL, SECTION, TYPICAL SECTION OR NOTE IS SHOWN FOR ONE CONDITION, IT SHALL APPLY FOR ALL SIMILAR OR LIKE CONDITIONS UNLESS OTHERWISE NOTED.
1.02 THE STRUCTURAL DESIGN OF THE BUILDING IS BASED ON THE FULL INTERACTION OF ALL ITS COMPONENT PARTS, WITH NO PROVISION MADE FOR CONDITIONS OCCURRING DURING CONSTRUCTION. THEREFORE, CONTRACTOR SHALL PROVIDE ADEQUATE BRACING AND TEMPORARY SHORING DURING CONSTRUCTION
IN ACCORDANCE WITH APPLICABLE STANDARDS.
1.03 CONTRACTOR IS RESPONSIBLE FOR ALL JOB SITE SAFETY INCLUDING THE SAFE RIGGING, LIFTING, SHORING, BRACING AND SETTING OF MATERIALS AND EQUIPMENT IN ACCORDANCE WITH APPLICABLE
STANDARDS.
1.04 FURNISH AND INSTALL ALL NECESSARY ATTACHMENTS, ANCHORAGES AND ACCESSORIES TO PROVIDE A
COMPLETE STRUCTURALLY SOUND STRUCTURE WITH A CONTINUOUS LOAD PATH. BRING ANY
DISCONTINUITIES TO THE ATTENTION OF THE COR VIA RFI IMMEDIATELY.
1.05 FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF FABRICATION OR CONSTRUCTION.
BRING ANY DISCREPANCIES ALONG WITH DETAILED FIELD SKETCHES OF AS-BUILT CONDITIONS TO THE
ATTENTION OF THE COR VIA RFI IMMEDIATELY.
1.06 COORDINATE AND VERIFY ALL DIMENSIONS AND DETAILS WITH THE EXISTING, CIVIL, PROCESS, ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, SHOP, AND
SUBMITTAL DRAWINGS. NOTIFY THE COR IMMEDIATELY OF ANY DISCREPANCIES VIA RFI.
EXISTING CONDITIONS
1.01 AS WITH ANY WORK AFFECTING EXISTING CONSTRUCTION, UNFORESEEN CONDITIONS ARE
UNAVOIDABLE WITHOUT DEMOLISHING OTHERWISE SERVICEABLE CONSTRUCTION, DISRUPTING
OCCUPIED OPERATIONS AND INCURRING SIGNIFICANT COST FOR CLOSE UP EXAMINATION AND NON-
DESTRUCTIVE TESTING DURING THE DESIGN STAGE.
1.02 CONTRACTOR SHALL VISIT SITE PRIOR TO SUBMITTING BID TO REVIEW EXISTING CONDITIONS IN WORK
AREAS.
1.03 CONTRACTOR SHALL PROVIDE UNIT PRICES FOR ADDITIONAL WORK THAT MAY ARISE DUE TO
UNFORSEEN CONDITIONS OR ADDITIONAL DETERIORATION.
1.04 WITH THE PASSAGE OF TIME SINCE THE CREATION OF AS-BUILT DRAWINGS AND/OR THE DESIGNERS SURVEY, BOTH CONCEALED AND VISIBLE CONDITIONS MAY HAVE CHANGED DUE TO ALTERATIONS, ADDITIONS, RENOVATIONS, AND DETERIORATION.
1.05 PRIOR TO THE COMMENCEMENT OF ANY WORK IN PREPARATION OF CONSTRUCTION RELATED ACTIVITIES, INCLUDING BUT NOT LIMITED TO SHOP DRAWING PREPARATION, ALL EMBEDDED OR CONCEALED ITEMS LIKELY TO BE ENCOUNTERED DURING CONSTRUCTION SHALL BE LOCATED AND MARKED ON THE SURFACE. THIS WORK SHALL BE ACCOMPLISHED BY DESTRUCTIVE AND/OR NON-
DESTRUCTIVE MEANS WITHOUT IMPAIRING THE STRUCTURAL INTEGRITY OF THE ASSOCIATED
MEMBERS. SHORING AS REQUIRED SHALL BE DESIGNED BY A PROFESSIONAL STRUCTURAL ENGINEER, LICENSED IN THE STATE OF THE PROJECT, AND FURNISHED AND INSTALLED AT NO ADDITIONAL COST.
1.06 EXISTING CONDITIONS THAT INTERFERE OR OTHERWISE AFFECT THE DESIGN, CONSTRUCTION OR
SERVICEABILITY OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE COR VIA RFI,
INCLUDING PLAN AND SECTION SKETCHES, IMMEDIATELY FOR RESOLUTION. THE CONTRACTOR SHALL ALLOW TWO CALENDAR WEEKS IN THE SCHEDULE FOR DESIGN RESOLUTION THE INTERFERENCE AFTER ALL INFORMATION ABOUT THE INTERFERENCE, INCLUDING SIZE, LOCATION, AND FUNCTION OF THE
EMBEDMENT, HAS BEEN RECEIVED BY THE COR.
DEMOLITION AND REMOVAL:
1.01 GENERAL
A. PERFORM ALL DEMOLITION WORK INCLUDING REMOVAL, TRANSPORT, AND DISPOSAL PER ALL
FEDERAL, STATE AND LOCAL RULES AND REGULATIONS.
1.02 EXISTING CONDITIONS
A. BEFORE BEGINNING ANY DEMOLITION WORK, SURVEY THE SITE AND EXAMINE THE DRAWINGS AND
SPECIFICATIONS TO DETERMINE THE EXTENT OF THE WORK. PHOTOGRAPH EXISTING CONDITIONS.
RECORD LOCATION AND EXTENT OF EXISTING CRACKS AND OTHER DAMAGE. PRIOR TO STARTING
WORK SUBMIT EXISTING CONDITION PHOTOS AND RECORDS TO THE GOVERNMENT.
1.03 DUST, DEBRIS AND NOISE CONTROL
A. CONFINE NOISE AND DUST TO IMMEDIATE WORK AREA.
B. CONTRACTOR SHALL REMOVE AND DISPOSE OFF-SITE ALL MATERIALS INDICATED TO BE DEMOLISHED
AND REMOVED, RUBBISH AND DEBRIS DAILY INCLUDING DUST AND DIRT.
1.04 TRAFFIC CONTROL
A. WHERE PEDESTRIAN AND DRIVER SAFETY IS ENDANGERED IN THE AREA OF THE WORK, USE
BARRICADES ANCHORED IN A MANNER TO PREVENT DISPLACEMENT BY WIND.
1.05 ITEMS TO REMAIN IN PLACE
A. TAKE PRECAUTIONS TO AVOID DAMAGE TO EXISTING ITEMS TO REMAIN IN PLACE, TO BE REUSED OR
TO REMAIN THE PROPERTY OF THE OWNER.
B. DO NOT DISTURB EXISTING CONSTRUCTION BEYOND THE EXTENT INDICATED OR NECESSARY FOR
INSTALLATION OF THE NEW WORK.
C. PROTECT NEW WORK FROM DAMAGE AS A RESULT OF SUBSEQUENT WORK.
D. DO NOT OVERLOAD EXISTING STRUCTURAL ELEMENTS, PAVEMENT, FOUNDATIONS, OR WORK TO
REMAIN.
E. INCREASE STRUCTURAL SUPPORT OR ADD NEW SUPPORTS AS MAY BE REQUIRED AS A RESULT OF
DEMOLITION WORK INCLUDING BUT NOT LIMITED TO CUTTING, REMOVAL, AND DECONSTRUCTION.
F. PROVIDE NEW SUPPORTS AND REINFORCEMENT FOR EXISTING CONSTRUCTION WEAKENED BY
DEMOLITION, DECONSTRUCTION, OR REMOVAL WORK.
G. PROVIDE TEMPORARY SHORING AND BRACING FOR SUPPORT OF BUILDING COMPONENTS TO
PREVENT SETTLEMENT OR OTHER MOVEMENT.
H. REPAIR OR REPLACE DAMAGED ITEMS AT NO COST TO THE GOVERNMENT. STRUCTURAL REPAIRS, REINFORCEMENT OR REPLACEMENT REQUIRE AN ENGINEERED PLAN AND CALCULATIONS SEALED BY A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT, AND PAID
FOR BY THE CONTRACTOR, AND PRIOR APPROVAL BY THE GOVERNMENT.
1.06 UTILITIES AND RELATED EQUIPMENT
A. DO NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED OR USED FACILITIES WITHOUT FIRST
COORDINATING WITH AND RECEIVING WRITTEN AUTHORIZATION FROM THE GOVERNMENT.
REINFORCED CONCRETE NOTES
1.01 CONCRETE DESIGN IS IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE, ACI 318.
1.02 CONCRETE WORK SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH THE FIELD REFERENCE MANUAL: STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE ACI 301 WITH SELECTED ACI AND
ASTM REFERENCES ( SP-15 )
1.03 ALL CONCRETE SHALL COMPLY TO THE REQUIREMENTS OF THE SPECIFICATIONS AND MATERIALS SHALL BE USED IN A MANNER COMPLYING WITH ALL OF THE MANUFACTURER REQUIREMENTS AND
RECOMMENDATIONS.
1.04 ALL CONCRETE SHALL BE NORMAL WEIGHT (145PCF) AND HAVE A MINIMUM 28-DAY COMPRESSIVE
STRENGTH AS FOLLOWS UNLESS NOTED OTHERWISE:
A. F'c = 5000 PSI FOR SLABS, JOISTS, COLUMNS, BEAMS, AND LOCATIONS NOT OTHERWISE NOTED.
1.05 CONCRETE SHALL BE TESTED IN ACCORDANCE WITH ACI 301 AND THE SPECIFICATIONS, WHEN
PROVIDED, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS. AT A MINIMUM, CONCRETE
SPECIMENS SHALL BE TAKEN FOR EVERY 100 YARDS OR PORTION THEREOF FOR EACH MIX DESIGN PLACED IN A DAY. CONCRETE TEST REPORTS SHALL BE AVAILABLE ON SITE FOR INSPECTION.
1.06 ALL STEEL REINFORCEMENT SHALL CONFORM WITH THE FOLLOWING:
A. DEFORMED BARS SHALL CONFORM WITH ASTM A 615 GRADE 60.
1.07 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE. SPLICE ONLY AS SHOWN OR
APPROVED. STAGGER SPLICES WHERE POSSIBLE. DOWELS SHALL MATCH SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE LAPPED WITH TENSION SPLICES. UNLESS OTHERWISE NOTED, ALL REINFORCING SHALL BE CONTACT LAP SPLICED WITH A CLASS B SPLICE IN ACCORDANCE WITH ACI 318-05. FOR BARS WITH A MINIMUM COVER AND SPACING GREATER THAN 2.0DB AND 3.0DB (DB = BAR DIAMETER) RESPECTIVELY, THE MINIMUM SPLICE LENGTH, EXPRESSED IN BAR DIAMETERS, SHALL NOT BE LESS THAN SPECIFIED IN THE REBAR SPLICE SCHEDULE. SPLICE LENGTHS SHALL BE
INCREASED BY A FACTOR OF 1.3 FOR TOP REINFORCEMENT.
1.08 ALL HORIZONTAL REINFORCING SHALL BE CONTINUOUS AROUND CORNERS, THROUGH CONTROL
JOINTS, AND THROUGH CONSTRUCTION JOINTS UNO.
1.09 ALL DOWELS AND TERMINATING BARS SHALL HAVE A STANDARD 90-DEG HOOK UNO.
1.10 CONCRETE COVER AT REINFORCEMENT:
A. FORMED CONCRETE NOT EXPOSED TO WEATHER OR EARTH:
1. SLABS, WALL, AND JOISTS:
a. # 11 BARS & SMALLER - 3/4".
2. BEAMS AND COLUMNS - 1½ IN.
1.11 CORNER EDGES OF CONCRETE TO BE LEFT EXPOSED TO VIEW SHALL HAVE A CHAMFER OR RADIUS OR
AS INDICATED ON THE DRAWINGS.
1.12 CHECK FOR EMBEDDED ITEMS AND PENETRATIONS PRIOR TO CONCRETE PLACEMENT
1.13 ALL CONCRETE SHALL BE CONSOLIDATED BY VIBRATION, SPADING, RODDING, OR FORKING SO THAT
THE CONCRETE IS THOROUGHLY WORKED AROUND THE REINFORCEMENT, AROUND EMBEDDED ITEMS, AND INTO CORNERS OF FORMS, ELIMINATING ALL AIR OR STONE POCKETS WHICH MAY CAUSE
HONEYCOMBING, PITTING, OR PLANES OF WEAKNESS. IF VIBRATORS, OF ADEQUATE SIZE, ARE USED THEY SHALL BE INSERTED AND WITHDRAWN AT POINTS APPROXIMATELY 18 INCHES APART. AT EACH
INSERTION, THE DURATION SHALL BE SUFFICIENT TO CONSOLIDATE THE CONCRETE BUT NOT
SUFFICIENT TO CAUSE SEGREGATION (GENERALLY FROM 5 TO 15 SECONDS).
1.14 FOLLOW ALL MANUFACTURER'S RECOMMENDED CURING GUIDELINES. IN THE ABSENCE OF SPECIFIC GUIDELINES, MAINTAIN CONCRETE AFTER PLACEMENT WITH MINIMAL MOISTURE LOSS AT RELATIVELY CONSTANT TEMPERATURE FOR THE PERIOD NECESSARY FOR HYDRATION OF CEMENT AND HARDENING OF CONCRETE (NOT LESS THAN 7 DAYS). COMPLY WITH THE REQUIREMENTS OF ACI 308 - STANDARD PRACTICE FOR CURING CONCRETE; AMERICAN CONCRETE INSTITUTE. A COMBINATION CURING AND SEALING COMPOUND SHALL BE APPLIED AFTER THE CONCRETE HAS BEEN FINISHED OR THE FORMS REMOVED. COMPOUND SHALL BE IN ACCORDANCE WITH ASTM C309, LATEST ADOPTED EDITION, TYPE I, CLASS B. (W.R. MEADOWS CS-309).
REINFORCED CONCRETE NOTES (CTD)
1.15 SPALL REPAIR NOTES
A. REMOVE ALL LOOSE CONCRETE TO SOUND SUBSTRATE 1/4" BEYOND REINFORCING.
B. CLEAN REINFORCING STEEL ENCOUNTERED TO A BRIGHT METAL FINISH.
C. ANY REINFORCING ENCOUNTERED SHOULD BE COMPLETELY EXPOSED AND NOT LEFT PARTIALLY
EMBEDDED IN CONCRETE.
1. SHORE REPAIR AREAS THAT REQUIRE AN ANNULAR SPACE AROUND REINFORCEMENT. FACTORED
SHORING LOADS ARE AS FOLLOWS:
a. JOIST: 5 KIP
b. BEAM: 58 KIP
c. FLOOR AREA: 241 PSF
2. LEAVE SHORES IN PLACE UNTIL REPAIRS HAVE REACHED A MINIMUM COMPRESSIVE STRENGTH
OF 4,000 PSI.
D. IF REINFORCING HAS LOST MORE THAN 10% OF ITS CROSS SECTIONAL AREA STOP AND CONTACT
THE COR IMMEDIATELY.
E. PROVIDE A MINIMUM DEPTH EXCAVATION, AS DEFINED IN CONCRETE REPAIR DETAILS, IN THE AREA
TO BE PATCHED. PROVIDE SAW-CUT, GROUND, OR CHIPPED EDGES. DO NOT FEATHER EDGES.
F. CLEAN AREA IN ACCORDANCE WITH BONDING AGENT MANUFACTURER'S RECOMMENDATIONS.
G. INJECT ANY VISIBLE CRACKS WITH EPOXY. SEE PLANS FOR LOCATIONS.
H. APPLY CORROSION INHIBITOR/ BONDING AGENT TO REINFORCING STEEL AND THE CONCRETE
SUBSTRATE.
I. REFORM SPALL WITH A HIGH STRENGTH STRUCTURAL CEMENTITIOUS REPAIR MATERIAL (NON-
METALLIC), ADD AGGREGATE AS SPECIFIED BY MANUFACTURER, CONSOLIDATE THE REPAIR
MATERIAL, FINISH, AND CURE IN ACCORDANCE WITH A MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS.
STRUCTURAL DRAWING ABBREVIATIONS:
BOT BOTTOM
B/STL BOTTOM OF STEEL
CFRP CARBON FIBER REINFORCED POLYMER
C.J. CONSTRUCTION OR CONTROL JOINT
CONN CONNECTION
DIAG DIAGONAL
EA EACH
EF EACH FACE
EL ELEVATION
EMBED EMBEDMENT
EOD EDGE OF DECK
EOS EDGE OF SLAB
EW EACH WAY
EXF EXISTING FOOTING
HORIZ HORIZONTAL
IFW INSIDE FACE OF WALL
MAX. MAXIMUM
MIN. MINIMUM
OC ON CENTER
OFW OUTSIDE FACE OF WALL
PLF POUNDS PER LINEAR FOOT
SOG SLAB-ON-GROUND
STD STANDARD
T&B TOP AND BOTTOM
T/FTG TOP OF FOOTING
T/STL TOP OF STEEL
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL
VOH VERTICAL / OVERHEAD
SPECIAL INSPECTION NOTES
1.01 CONDUCT SPECIAL INSPECTIONS IN ACCORDANCE WITH CHAPTER 17 SPECIAL INSPECTIONS AND TESTS OF THE 2021 IBC AS SUMMARIZED IN THE SCHEDULE OF SPECIAL INSPECTIONS. SPECIAL INSPECTOR SHALL BE REGISTERED IN THE STATE OF FLORIDA AND BE ON THE STATE SPECIAL
INSPECTOR'S LIST.
CONFINEMENT WRAP CONSTRUCTION SEQUENCE
1.01 INSTALLATION OF ALL MATERIALS SHALL BE PERFORMED IN ACCORDANCE WITH ALL OF THE
MANUFACTURER INSTRUCTIONS AND RECOMMENDATIONS.
1.02 SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
1.03 SURFACE PREPARATION:
A. WHERE CFRP IS TO BE WRAPPED AROUND CORNERS, CORNERS SHALL BE ROUNDED TO 1/2" MIN.
RADIUS. ROUGH CORNERS SHALL BE SMOOTHED WITH PUTTY.
B. SUBSTRATE MUST BE CLEAN, SOUND, AND FREE OF SURFACE MOISTURE.
C. REMOVE DUST, LAITANCE, GREASE, OILS, CURING COMPOUNDS, WAXES, IMPREGNATIONS, FOREIGN
PARTICLES, COATINGS AND DISINTEGRATED MATERIALS BY MECHANICAL MEANS (I.E. SANDBLASTING).
D. PREPARE SURFACE IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
1.04 CARBON FIBER WRAP MAY BE APPLIED IN A WET OR DRY LAYUP METHOD. IN THE WET LAY-UP PROCEDURE, IMPREGNATION RESIN SHOULD BE APPLIED ONTO BOTH SIDES OF THE FABRIC USING A BRUSH OR ROLLER. AFTER SATURATING, EXCESS RESIN SHOULD BE REMOVED FROM THE WET OUT FABRIC USING A
SQUEEGEE.
1.05 APPLY 1 TOPCOAT OF WATER DISPERSED ACRYLIC PROTECTIVE COATING BY BRUSH, ROLLER, OR
SPRAY OVER ENTIRE AREA MOVING IN ONE DIRECTION.
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
STRUCTURAL NOTES
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
BAY PINES VAMC, FLORIDA
S001
516-23-604
JTT EJB08-25-2025
FINAL SUBMISSION
B B
E E
5.1
5.1
5.9
5.9
2.3
2.3
6.9
6.9
6.5
6.5
4.9
4.9
C.90 C.90
C.1 C.1
15' - 0 1/2" REF 20' - 1 1/2" REF 12' - 9" REF 4' - 4 1/2" REF 9' - 7" REF 7' - 6 1/2" REF 6' - 5" REF
/2
R E
F 9'
0"
R E
F
/2
R
E F
50 51 52 53
70 71 72 73
88 89 90 91
PLAN
NORTH
TRUE
NORTH
AREA 1
BLDG A
BLDG B
AREA 3
AREA 2
AREA 4
1. SEE SHEET S104 "OVERALL CRITICAL AREA PLAN FROM JS HELD REPORT" FOR
REFERENCE TO SCOPE AREAS TYP.
2. ALL REPAIRS ARE VERTICAL OR OVERHEAD, UNO.
3. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS INCLUDING
DIMENSIONS OF INSTALLED CONSTRUCTION PRIOR TO COMMENCING THE
WORK. IN THE EVENT THAT ANY DISCREPANCIES BETWEEN THE INDICATED
WORK AND EXISTING CONDITIONS ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE COR VIA RFI FOR INTERPRETATION AND DIRECTION PRIOR
TO PROCEEDING WITH THE WORK.
4. QUANTITIES ARE FOR REFERENCE ONLY AND SHALL BE VERIFIED BY
CONTRACTOR.
5. CONTRACTOR SHALL BECOME FAMILIAR WITH SPECIFICATION REQUIREMENTS
AND MAINTAIN A COPY OF SPECIFICATIONS ON SITE DURING ALL REPAIR
ACTIVITIES.
6. SHORE EXISTING MECHANICAL/ELECTRICAL/PLUMBING/ETC INFRASTRUCTURE
AS REQUIRED DURING REPAIRS. REPLACE EXISTING ANCHORAGES IN KIND AS
REQUIRED TO FACILITATE STRUCTURAL REPAIRS.
7. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY.
8. EXISTING SHORING/ MEP SUPPORTS INCLUDING STRUCTURAL STEEL FRAMING
NOT SHOWN FOR CLARITY.
9. IMAGES ARE PROVIDED TO HELP LOCATE SOME DEFICIENCIES. IMAGES OF
DEFICIENT CONDITIONS MAY NOT SHOW ALL DETERIORATION PRESENT ON
MEMBERS.
10. SEE SHEET S102 FOR REPRESENTATIVE PHOTOS OF TYPICAL DEFICIENCIES.
11. CLEAN CORROSION OFF ALL EMBEDDED STEEL COMPONENTS EXPOSED
DURING REPAIR PROCEDURES.
UNDERSIDE OF SLAB SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
JOIST SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
BEAM SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
COLUMN SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
EPOXY INJECTION - LINEAR FOOT QUANTITY - SEE 3/S105.
CFRP WRAP - EACH QUANTITY - SEE 5/S105.
DEFICIENCY TYPE
DEFICIENCY QUANTITY
NOTE (IF ANY)
A
B
C
D
E
X
COLUMN NUMBER (TYPICALLY MARKED
ON COLUMNS WITHIN CRAWLSPACE)
F
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
ENLARGED REPAIR AREA PLANS
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
BAY PINES VAMC, FLORIDA
S101
516-23-604
JTT EJB08-25-2025
FINAL SUBMISSION
1/4" = 1'-0"S101
1 AREA 1 ENLARGED REPAIR PLAN
KEY PLAN
ENLARGED REPAIR PLAN NOTES
DEFICIENCY LEGEND
C
C
C
C
C
D
C
D
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
A
THIS BAY
B
B
B
B
B
B
A
THIS BAY
A
THIS BAY
B
A
THIS BAY
A
THIS BAY
A
THIS BAY
A
THIS BAY
B
C
B
B
B
B
B
B
B
B
C
D
D
C
D
C
B
B
B
B
B
B
C
D
B
B
B
B
B
B
D
B
B
B
B
B
B
A
THIS BAY
A
THIS BAY
B B
13.1
13.1
C.1 C.1
14.3
14.3
18' - 0" REF
/2
R E
F
AREA 1
BLDG A
BLDG B
AREA 3
AREA 2
AREA 4
PLAN
NORTH
TRUE
NORTH
1. SEE SHEET S104 "OVERALL CRITICAL AREA PLAN FROM JS HELD REPORT" FOR
REFERENCE TO SCOPE AREAS TYP.
2. ALL REPAIRS ARE VERTICAL OR OVERHEAD, UNO.
3. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS INCLUDING
DIMENSIONS OF INSTALLED CONSTRUCTION PRIOR TO COMMENCING THE
WORK. IN THE EVENT THAT ANY DISCREPANCIES BETWEEN THE INDICATED
WORK AND EXISTING CONDITIONS ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE COR VIA RFI FOR INTERPRETATION AND DIRECTION PRIOR
TO PROCEEDING WITH THE WORK.
4. QUANTITIES ARE FOR REFERENCE ONLY AND SHALL BE VERIFIED BY
CONTRACTOR.
5. CONTRACTOR SHALL BECOME FAMILIAR WITH SPECIFICATION REQUIREMENTS
AND MAINTAIN A COPY OF SPECIFICATIONS ON SITE DURING ALL REPAIR
ACTIVITIES.
6. SHORE EXISTING MECHANICAL/ELECTRICAL/PLUMBING/ETC INFRASTRUCTURE
AS REQUIRED DURING REPAIRS. REPLACE EXISTING ANCHORAGES IN KIND AS
REQUIRED TO FACILITATE STRUCTURAL REPAIRS.
7. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY.
8. EXISTING SHORING/ MEP SUPPORTS INCLUDING STRUCTURAL STEEL FRAMING
NOT SHOWN FOR CLARITY.
9. IMAGES ARE PROVIDED TO HELP LOCATE SOME DEFICIENCIES. IMAGES OF
DEFICIENT CONDITIONS MAY NOT SHOW ALL DETERIORATION PRESENT ON
MEMBERS.
10. SEE SHEET S102 FOR REPRESENTATIVE PHOTOS OF TYPICAL DEFICIENCIES.
11. CLEAN CORROSION OFF ALL EMBEDDED STEEL COMPONENTS EXPOSED
DURING REPAIR PROCEDURES.
UNDERSIDE OF SLAB SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
JOIST SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
BEAM SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
COLUMN SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
EPOXY INJECTION - LINEAR FOOT QUANTITY - SEE 3/S105.
CFRP WRAP - EACH QUANTITY - SEE 5/S105.
DEFICIENCY TYPE
DEFICIENCY QUANTITY
NOTE (IF ANY)
A
B
C
D
E
X
COLUMN NUMBER (TYPICALLY MARKED
ON COLUMNS WITHIN CRAWLSPACE)
F
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
ENLARGED REPAIR AREA PLANS
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
BAY PINES VAMC, FLORIDA
S102
516-23-604
JTT EJB08-25-2025
FINAL SUBMISSION
3/8" = 1'-0"S102
1 AREA 2 ENLARGED REPAIR PLAN
KEY PLAN
ENLARGED REPAIR PLAN NOTES
D
D
B
B
B
A
B
B
TYPICAL BEAM SPALL
TYPICAL SLAB SPALL
TYPICAL JOIST SPALL
TYPICAL COLUMN SPALL
DEFICIENCY LEGEND
79 90
97 98
L L
M M
N N
M.6 M.6
13.5
13.5
13.7
13.7
N.4 N.4
N.5 N.5
N.50 N.50
M.7 M.7
L.4 L.4
L.2 L.2
15.1
15.1
14.5
14.5
8' - 1" REF 3' - 6" REF 9' 3 1/2" REF 8' - 7" REF
R E
F
R E
F
1'
1/
2"
7'
1" R
E F
6'
/2
R E
F
R E
F
/2
R
E F
R E
F
R E
F
2'
2"
R E
F
3'
AREA 1
BLDG A
BLDG B
AREA 3
AREA 2
AREA 4
PLAN
NORTH
TRUE
NORTH
1. SEE SHEET S104 "OVERALL CRITICAL AREA PLAN FROM JS HELD REPORT" FOR
REFERENCE TO SCOPE AREAS TYP.
2. ALL REPAIRS ARE VERTICAL OR OVERHEAD, UNO.
3. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS INCLUDING
DIMENSIONS OF INSTALLED CONSTRUCTION PRIOR TO COMMENCING THE
WORK. IN THE EVENT THAT ANY DISCREPANCIES BETWEEN THE INDICATED
WORK AND EXISTING CONDITIONS ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE COR VIA RFI FOR INTERPRETATION AND DIRECTION PRIOR
TO PROCEEDING WITH THE WORK.
4. QUANTITIES ARE FOR REFERENCE ONLY AND SHALL BE VERIFIED BY
CONTRACTOR.
5. CONTRACTOR SHALL BECOME FAMILIAR WITH SPECIFICATION REQUIREMENTS
AND MAINTAIN A COPY OF SPECIFICATIONS ON SITE DURING ALL REPAIR
ACTIVITIES.
6. SHORE EXISTING MECHANICAL/ELECTRICAL/PLUMBING/ETC INFRASTRUCTURE
AS REQUIRED DURING REPAIRS. REPLACE EXISTING ANCHORAGES IN KIND AS
REQUIRED TO FACILITATE STRUCTURAL REPAIRS.
7. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY.
8. EXISTING SHORING/ MEP SUPPORTS INCLUDING STRUCTURAL STEEL FRAMING
NOT SHOWN FOR CLARITY.
9. IMAGES ARE PROVIDED TO HELP LOCATE SOME DEFICIENCIES. IMAGES OF
DEFICIENT CONDITIONS MAY NOT SHOW ALL DETERIORATION PRESENT ON
MEMBERS.
10. SEE SHEET S102 FOR REPRESENTATIVE PHOTOS OF TYPICAL DEFICIENCIES.
11. CLEAN CORROSION OFF ALL EMBEDDED STEEL COMPONENTS EXPOSED
DURING REPAIR PROCEDURES.
UNDERSIDE OF SLAB SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
JOIST SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
BEAM SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
COLUMN SPALL - SQUARE FOOT QUANTITY - SEE 1/S105 & 2/S105.
EPOXY INJECTION - LINEAR FOOT QUANTITY - SEE 3/S105.
CFRP WRAP - EACH QUANTITY - SEE 5/S105.
DEFICIENCY TYPE
DEFICIENCY QUANTITY
NOTE (IF ANY)
A
B
C
D
E
X
COLUMN NUMBER (TYPICALLY MARKED
ON COLUMNS WITHIN CRAWLSPACE)
F
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
ENLARGED REPAIR AREA PLANS
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
BAY PINES VAMC, FLORIDA
S103
516-23-604
JTT EJB08-25-2025
FINAL SUBMISSION
1/4" = 1'-0"S103
1 AREA 3 & 4 ENLARGED REPAIR PLAN
KEY PLAN
ENLARGED REPAIR PLAN NOTES
D
D
D
D
A
THIS BAY
C
C
C
D
D
A
C
C
C
D
C
C
D
C
E
B
A
C
B
A
THIS BAY
A
THIS BAY
B
B
B
B
PERFORM 10LF HYDROPHILIC
POLYURETHANE GROUT INJECTION AT
UNDERSIDE OF FIRST FLOOR SLAB WHERE
ACTIVE MOISTURE IS PRESENT.
DEFICIENCY LEGEND
180 181
171168163
173A
170 174
172A
F
REMOVE LOOSE/SPALLED
CONCRETE BY CHIPPING AND
APPLY NEW EPOXY/MATERIAL
PATCH
EXISTING
CONCRETE
SURFACE
EXISTING
REINFORCING
NOTES:
1. PRIOR TO PLACING EPOXY/MATERIAL PATCH:
A. CONCRETE SURFACE MUST BE FREE FROM PAINT, DUST, LOOSE MATERIAL, SURFACE
CONTAMINATION, AND MATERIALS WHICH REDUCE BOND OR PREVENT WETTING BY REPAIR
MATERIALS. DELAMINATED, WEAK, DAMAGED AND DETERIORATED CONCRETE, AND WHERE
NECESSARY, SOUND CONCRETE SHALL BE REMOVED BY CHIPPING OR OTHER SUITABLE MEANS.
B. STEEL REINFORCEMENT SHALL BE FREE OF RUST, SCALE, MORTAR, CONCRETE, DUST AND OTHER
LOOSE DELETERIOUS MATERIAL THAT WOULD REDUCE BOND OR CONTRIBUTE TO
CORROSION. FOLLOW BONDING AGENT MANUFACTURER'S RECOMMENDATIONS AND
REQUIREMENTS FOR SURFACE PREPARATION REQUIREMENTS.
2. WHERE INSUFFICIENT COVER EXISTS OVER REINFORCEMENT USE EPOXY MATERIAL PATCH TO
PROVIDE REQUIRED COVER.
3/4" MAX CLEAR
EXISTING CONCRETE
MEMBER
REMOVE UNSOUND CONCRETE FROM
REPAIR AREA. CAST TO RESTORE
CROSS-SECTION.
EXISTING REINFORCING BARS: CLEAN ACCORDING TO REPAIR
MATERIAL INSTRUCTIONS AND RECOMMENDATIONS AND COAT
WITH CORROSION INHIBITOR WHERE BARS ARE EXPOSED. WHERE
REINFORCEMENT IS FOUND TO BE SEVERELY CORRODED OR HAS
LOST 10% OR MORE OF ITS CROSS SECTIONAL AREA,
SUPPLEMENTARY REINFORCEMENT MAY BE REQUIRED.
CHIP CONCRETE TO A MIN. DEPTH
OF 3/4" BELOW REINFORCING STEEL
3/4" SAWCUT AROUND
PERIMETER OF PATCH
AREA - BEVEL SAWCUT
AWAY FROM CENTER OF
PATCH AREA
NOTES:
1. LARGE AND/OR DEEP AREAS OF REMOVAL MAY REQUIRE SHORING. SEE
CONCRETE NOTES FOR SHORING LOADS.
C
LE
A R
A N
C E
3/ /4
M
IN
M
IN
5/ 8"
C
LR
CORROSION DAMAGED REINFORCING
1" MIN. CLEARANCE BEYOND
B Y
M A
N U
F A
C T
U R
E R
S P
A C
IN
G
A S
R E
Q U
IR
E
D
EPOXY INJECTION PORT,
SEE SPECIFICATIONS
EPOXY PASTE
SURFACE SEALANT
EXISTING CONCRETE
SUBSTRATE
CONCRETE CRACK.
PREP AS REQUIRED BY
MANUFACTURER FOR
INJECTION PROCESS
AFFECTED LENGTH
CROSS SECTION
LOSS OF 10% OR MORE
REQUIRED LAP REQUIRED LAP
AFFECTED LENGTH
SUPPLEMENTAL BAR
EXIST CONCRETE
JOISTS/BEAMS TYP
AFTER PERFORMING CEMENTITIOUS
REPAIRS, PLACE CFRP WRAP AT EXTENTS OF
COLUMN INCLUDING PREVIOUSLY REPAIRED
AREAS FOLLOWING APPLICATION OF NEW
CEMENTITIOUS REPAIRS. PLACE WRAP WITH
PRIMARY FIBERS ORIENTED HORIZONTALLY.
SEE CONFINEMENT WRAP NOTES AND
SPECIFICATIONS.
EXIST COLUMN
EXIST PEDESTAL
REMOVE AND REINSTALL
EXISTING PIPE
SUPPORTS, CONDUIT, OR
OTHER MECHANICAL
COMPONENTS TO
FACILITATE CFRP
INSTALLATION.
MAINTAIN 1/2" CLR FROM
EXIST STRUCTURAL STEEL
FRAMING TYP.
EXIST STRUCTURAL
STEEL FRAMING TYP
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date Checked
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
CONCRETE DETAILS
INSTALL TEMP SHORING IN CRAWL
SPACE AT BUILDING 1
BAY PINES VAMC, FLORIDA
S105
516-23-604
JTT EJB08-25-2025
FINAL SUBMISSION
6" = 1'-0"S105
LOW CONCRETE COVER REPAIR DETAIL
(≤ 3/4" CLEAR COVER)
1 1/2" = 1'-0"S105
2 TYPICAL CONCRETE REPAIR DETAIL
1 1/2" = 1'-0"S105
3 EPOXY INJECTION CRACK REPAIR
3" = 1'-0"S105
REPAIR OF DAMAGED/DETERIORATED
REINFORCING
CONCRETE REBAR LAP SPLICE SCHEDULE
BAR SIZE CLASS
NORMAL WEIGHT CONCRETE 28 DAY f'c (PSI)
5,000
#6 or Smaller B 44 Dia.
#7 or Larger B 55 Dia.
1" = 1'-0"S105
5 CONFINEMENT WRAP DETAIL
| 1 General Drawings - Final Submission |
| 2 Structural Drawings - Final Submission |
| S001 - STRUCTURAL NOTES |
| S101 - ENLARGED REPAIR AREA PLANS |
| S102 - ENLARGED REPAIR AREA PLANS |
| S103 - ENLARGED REPAIR AREA PLANS |
| S105 - CONCRETE DETAILS |
File details come from the government source that posted it. Updated .