546-22-121 Miami VA CLC 1st and 2nd Floor Addendum 1.pdf

PDF 12 MB Posted

Attached to
Renovate Community Living Center (CLC) - 1st & 2nd Floor
Solicitation number
36C24825R0033
Issued by

About this file

This is Addendum No. 1 for the Community Living Center (CLC) 1st and 2nd Floor Renovation project at the Miami VA Medical Center (TOPR 546-22-121). The addendum modifies the original drawings and specifications with several key changes, including the addition of specification 02 82 13.19 for Asbestos Floor Tile and Mastic Abatement, an environmental report containing asbestos survey and lead paint findings, and multiple drawing revisions.

The drawing revisions include updates to the Bid Item Plan (G101), modifications to demolition plans (AD101/AD102) with revised keynote 2.40, changes to note plans (A101-N/A102-N) including a new column closure detail and revised keynotes, and updates to interior elevations (A401) with the addition of missing tag HR-1. The addendum provides detailed specifications across multiple divisions including general requirements, existing conditions, concrete, wood/plastics/composites, thermal/moisture protection, openings, finishes, specialties, plumbing, electrical, and communications. The drawings show extensive interior renovations to patient rooms, corridors, and support spaces on both floors of the CLC facility.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

524 Fernwood Drive, Altamonte Springs, Florida 32701 | rdcjpa.com | 800.362.1523

DATE: 2/19/2025

Addendum No. 1

CLC Renovation 1st & 2nd Floors TOPR 546-22-121

Miami VA

This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders and all appropriate building code authorities. This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract

Documents.

Receipt of this Addendum must be acknowledged on the Form of Proposal.

This addendum consists of 7 Drawing sheets, revised TOC, responses to RFI’s, and the environmental report.

General:

1. Responses to “Requests for Information” (RFI’s)

2. Environmental report containing Asbestos Survey and Lead Paint. See attached H8227090 - VA Hospital - CLC 1st and 2nd Floor document.

Specifications:

1. Revised TOC.

a. Specification 02 82 13 .19 Asbestos Floor Tile and Mastic Abatement added to the Table of Contents.

Drawings:

1. G101 – BID ITEM PLAN

2. AD101 - DEMOLITION PLAN & AD102 - DEMOLITION PLAN

a. Revised keynote 2.40

3. A101-N – NOTE PLAN & A102-N – NOTE PLAN

a. Column closure detail added.

b. Keynote 9.43 revised.

524 Fernwood Drive, Altamonte Springs, Florida 32701 | rdcjpa.com | 800.362.1523

c. Keynotes 9.05, 9.2, and 9.44 added.

4. A401 – INTERIOR ELEVATIONS & AF101-P WALL PROTECTION PLAN – L – 1

a. Missing tag (HR-1) added.

End of Addendum No. [1]

CLC Renovation 1st and 2nd Floors TOPR 02-01-23 VAMC Miami, Florida 546-22-121

00 01 10-1

DEPARTMENT OF VETERANS AFFAIRS

VHA MASTER SPECIFICATIONS

TABLE OF CONTENTS

Section 00 01 10

SECTION NO. DIVISION AND SECTION TITLES DATE

DIVISION 00 - SPECIAL SECTIONS

00 01 15 List of Drawing Sheets 05-20

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 General Requirements 11-21

01 31 00.01 Project Management and Coordination 09-19

01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 11-21

01 33 23 Shop Drawings, Product Data, and Samples 02-23

01 35 26 Safety Requirements 10-22

01 42 19 Reference Standards 11-20

01 45 00 Quality Control 02-21

01 57 19 Temporary Environmental Controls 01-21

01 58 16 Temporary Interior Signage 07-15

01 74 19 Construction Waste Management 04-22

DIVISION 02 – EXISTING CONDITIONS

02 41 00 Demolition 08-17

02 82 13 .19 Asbestos Floor Tile and Mastic Abatement 01-21

DIVISION 03 – CONCRETE

03 54 16 Moisture Mitigation System

DIVISION 06 – WOOD, PLASTICS AND COMPOSITES

06 20 00 Finish Carpentry 01-21

06 41 16 Plastic Laminate Clad Architectural Cabinets 06-20

Division 07 – Thermal and Moisture Protection

07 92 00 Joint Sealants 04-22

DIVISION 08 - OPENINGS

08 14 00 Interior Wood Doors 01-21

08 71 00 Door Hardware 05-22

DIVISION 09 – FINISHES

09 05 16 Subsurface Preparation for Floor Finishes 01-21

09 22 16 Non-Structural Metal Framing 06-18

CLC Renovation 1st and 2nd Floors TOPR 02-01-23 VAMC Miami, Florida 546-22-121

00 01 10-2

SECTION NO. DIVISION AND SECTION TITLES DATE

09 29 00 Gypsum Board 04-20

09 30 13 Ceramic/Porcelain Tiling 01-21

09 51 00 Acoustical Ceilings 12-18

09 65 13 Resilient Base and Accessories 01-21

09 65 16 Resilient Sheet Flooring 06-22

09 65 19 Resilient Tile Flooring 05-18

09 91 00 Painting 01-21

DIVISION 10 – SPECIALTIES

10 26 00 Wall and Door Protection 01-21

10 28 00 Toilet, Bath, and Laundry Accessories 01-21

10 30 90 Manufactured Electric Fireplaces and Mantles 01-21

DIVISION 22 – PLUMBING

22 05 11 Common Work Results for Plumbing 01-23

22 11 00 Facility Water Distribution 05-21

22 40 00 Plumbing Fixtures 12-22

DIVISION 26 – ELECTRICAL

26 05 11 Requirements for Electrical Installations 11-22

26 05 19 Low-Voltage Electrical Power Conductors and Cables 11-22

26 05 26 Grounding and Bonding for Electrical Systems 11-22

26 05 33 Raceway and Boxes for Electrical Systems 11-22

26 27 26 Wiring Devices 11-22

DIVISION 27 – COMMUNICATIONS

27 05 11 Requirements for Communications Installations 09-19

27 05 26 Grounding and Bonding for Communications Systems 06-15

27 05 33 Raceways and Boxes for Communications Systems 10-18

27 15 00 Communications Structured Cabling 01-16

SRQPN

LJGEC M OKHFDBA

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

BID ITEM 2

BID ITEM 3 Excludes doors and hardware

BID ITEM 1 (BASE BID)

Area not in scope

AREAS IN BID ITEM 3

AREAS IN BID ITEM 2

SRQPN

LJGEC M OKHFDBA

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

BID ITEM 2

BID ITEM 3 Excludes doors and hardware

BID ITEM 1 (BASE BID)

Area not in scope

AREAS IN BID ITEM 3

AREAS IN BID ITEM 2

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

9:

:0

AM

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

BID ITEM PLAN

G101 DesignerApprover

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

N.T.S.Scale:

BID ITEM PLAN FIRST FLOOR

N.T.S.Scale:

BID ITEM PLAN SECOND FLOOR

Revisions Date

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

3 Addendum #1 02/19/2025

L

J

J

G

G

E

E

C

C M OKHFDBA

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

TOILET

125A

PATIENT

BATH

CLEAN

UTILITY

TOILET

122A

TOILET

123A

RESTROOM

MALE

Room

Mechanical Room

MEA-2

MALE

TOILETS

STAFF

107A

FEMALE

TOILETS

STAFF

TOILET

FEMALE

PATIENT

RESTROOMS

TOILET

141A

E1-1 E1-1

T1-1 T1-1

TOILET

159A

TOILET

143A

TOILET

146A

TOILET

147A

TOILET

148A

TOILET

155A

TOILET

151A

TOILET

153A

GERIATRICS

AND

EXTENDED

CARE

GENERAL

STORAGE

100A

CONTROL

ROOM

GERIATRIC

DIRECTOR'S

OFFICE

SOCIAL

WORKER

PSYCHOLOGY

SERVICE

BARBER

SHOP

RECREATION

THERAPY

DINING ROOM

RECREATION

THERAPY

110B

STAIR

S1-1

MECH. ROOM

MEA-3A

SWITCH GEAR

MEA-2B ELEVATOR

MACHINE RM.

MEA-2C

CORRIDOR

C1-3-10

HORTICULTURAL

THERAPY

110A

VENDING

111A

NFS

111B

HOUSEKEEPING

CORRIDOR

C1-2A-10

CORRIDOR

C1-5A-10

MECHANICAL

ROOM

EMS

STORAGE

EMS

STORAGE

MED ROOM

NURSE

MANAGER

RECEPTION /

LOUNGE

3 BED ROOM

3 BED ROOM

3 BED ROOM

2 BED ROOM

2 BED RM.

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

H.A.C.

STAFF TOILET

CLEAN

SUPPLY

TOILET

128A

TOILET

126A

CONG. TOILET

137A

TOILET

132A

TOILET

130A

MECH./OXYGEN

ROOM

MEA-1

CORRIDOR

C1-4-10

LAUNDRY

MULTIPURPOSE

ROOM

EMS

LIBRARY

1 BED ROOM

1 BED ROOM

1 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

159SOILED

UTILITY

ATTENDING

PHYSICIAN

CORRIDOR

C1-7-10

CORRIDOR

C1-6-10

TOILET

145A

TOILET

150A

TOILET

149A

TOILET

157A

STAIR

S1-2

STAIR

S1-3

CORRIDOR

C1-5-10

2 BED ROOM

1 BED ROOM

2 BED ROOM

CLEAN

SUPPLY

121A

CORRIDOR

C1-2-10

AD101

1BED TYPICAL

AD101

3BED TYPICAL

AD101

2BED TYPICAL

2.07 2.10

2.162.16

2.07 2.10

2.16

2.07 2.10

2.16

2.07 2.10

2.16

2.07 2.10

2.09 2.10

2.07

2.10 2.122.12

2.22

2.22

2.22

2.232.23 2.22

2.07 2.10

2.242.242.22

2.09 2.10

2.16

2.22

2.22

2.10 2.25

2.25

2.23

2.22

2.28

2.07 2.10

2.05

2.05

2.09 2.10

2.12

2.26 2.26

2.04

2.05

2.05

2.05

2.052.05 2.07

2.10 2.13

2.27

2.05 2.06 2.072.10

2.13 2.20

2.16

2.28 2.23

2.05

2.05 2.25 2.31 2.10

2.05 2.05

2.16

2.07 2.102.04

2.05

2.16

2.09 2.10

2.28 2.25

2.22 2.10

2.05

2.05

2.05

2.05

2.05

2.04

2.04

2.07

2.10

2.30

2.042.04 2.042.04

2.09 2.09

2.09 2.10

2.04 2.10

2.10 2.10

2.04

2.09 2.10

2.09 2.10

2.09 2.102.04

2.04

2.09 2.10

2.04

2.09 2.10

2.25

2.28

2.13

2.05

2.13 2.09

2.10

2.10

2.16

2.04

2.09 2.10

2.09 2.09 2.09

2.32

2.28 2.25

2.10

2.22 2.07

2.10

2.05

2.25

2.28

2.10

2.50 2.50 2.50 2.50

2.50

2.51 2.51 2.51 2.51 2.51

2.512.512.512.512.512.512.512.512.51

2.52

2.52

2.51

2.51

2.51

2.51 2.51

2.51

2.51

2.51

2.07

2.10

2.07 2.10

2.10 2.07

2.25 2.11

2.07

2.10 2.10

2.10 2.07 2.102.11

2.11

2.12

2.38

2.14

2.15

2.37

2.37

2.40

2.40

2.40

2.40 Typ.

Typ.

Typ.

2.40

2.40

2.40

2.40

Typ.

Typ.

Typ.

Typ.

2.40

Typ.

Typ.

2.16

2.16

2.05

2.05 2.072.07

2.17

2.21

2.12

2.52 2.13

2.18

2.06

2.31

2.04

2.40 Typ.

2.05

2.16

2.17

2.21

2.06

2.18

2.12

2.05

2.072.07

2.51 2.13

2.04

2.12

2.31

2.40 Typ.

2.05

2.50 2.13

2.16

2.06

2.06

2.07

2.05

2.18

2.04

2.13

2.07

2.40 Typ.

DEMOLITION LEGEND

Existing wall to remain Door slab to be demolished, frame to remain.

No work unless otherwise noted.

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

:1 5:

P

M

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

DEMOLITION PLAN

AD101

JWSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

A. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.

B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.

C. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.

D. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.

E. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.

F. Prepare walls and floor slabs as required to receive new finish materials where existing finish is indicated to be removed.

G. Remove existing corner guards.

H. Existing lights, diffusers, sprinkler heads, and other MEPFS items to remain. Protect during construction.

J. Remove and reinstall existing signage.

N Scale: 3/32" = 1'-0"

DEMOLITION PLAN - FIRST FLOOR

2.04 Remove existing half height wall protection, handrail, chairrail, and wood door casing. Reskim wall and prepare surfaces.

2.05 Existing door slab and existing vinyl door frame protection product to be removed. Existing HM frame to remain. Prep frame as required for new vinyl frame protection product.

2.06 Remove existing ceiling tiles, grid to remain. Paint grid P-6. Install new ceiling tiles in existing grid.

2.07 Remove existing VCT and rubber base. Prepare slab for new finishes.

2.09 Remove existing welded sheet vinyl flooring and integral base.

Prepare slab for new finishes.

2.10 Remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accessories, corner protection, and equipment.

2.11 Remove existing wall protection.

2.12 Remove existing casework. Prepare for new installation.

2.13 Remove existing half height wall protection and upper wall covering. Reskim wall and prep surface.

2.14 Existing fire extinguisher cabinet to remain.

2.15 Remove existing fire extinguisher cabinet. Patch wall as required to match adjacent finish.

2.16 Remove and reinstall existing window covering.

2.17 Existing wall tile to remain. Protect during construction.

2.18 Existing patient lift and cubicle curtains to remain. Protect in place during construction.

2.20 Existing ACT ceiling to remain.

2.21 Existing gypsum ceiling to remain.

2.22 Existing casework to remain. Protect in place during construction.

2.23 Existing plumbing fixture to remain. Protect in place during construction.

2.24 Remove and reinstall existing lockers.

2.25 Remove existing ceramic tile flooring and base. Prepare slab for new finishes.

2.26 Remove existing column furring walls.

2.27 Existing wall mounted equipment to remain. Protect in place during construction.

2.28 Remove existing wall tile. Prepare wall for new finishes.

2.30 Remove and reinstall existing water fountain as required to install new finishes.

2.31 Remove existing plumbing fixtures. See plumbing drawings.

2.32 Remove wood trim at elevators. Remove and reinstall floor indicator as required for removal and installation of finishes.

2.37 Remove existing wall mounted nurse workstations. Prepare for installation of new stations.

2.38 Existing fire extinguisher cabinet to be reset as required to be flush flush with new finish face.,

2.40 Remove existing interior gypsum board at exterior walls. Existing framing and window trim to remain. Protect during construction.

2.50 Typical 1-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See detail 5 & 6 on sheet a405.

2.51 Typical 2-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See deatil 3 & 4 sheet a405

2.52 Typical 3-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See details 1 & 2 sheet a405

PLAN NOTES

GENERAL DEMOLITION NOTES

Scale: 1/4" = 1'-0"

TYPICAL 3 BED ROOM

Scale: 1/4" = 1'-0"

TYPICAL 2 BED ROOM

Scale: 1/4" = 1'-0"

TYPICAL 1 BED ROOM

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

3 Addendum #1 02/19/2025

L

J

J

G

G

E

E

C

C M OKHFDBA

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

W/C.B.

246A

W/C.B.

247A

W/C.B.

248A

W/C.T.

243A

1 BED ROOM

1 BED ROOM

1 BED ROOM

1 BED ROOM

LOUNGE

NURSE

MANAGER

OXYGEN

STORE

240A W/C.T.

241A

CORRIDOR

C2-7-10

CORRIDOR

C2-4-10

ELECTRICAL

CLOSET

E2-1

TELEPHONE

CLOSET

T2-1 W/C.B.

259A

W/C.T.

257A

W/C.T.

255A

W/C.T.

253A

W/C.T.

251A

1 BED ROOM

W/C.B.

250A

W/C.B.

249A

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

CORRIDOR

C2-6-10

SOILED UTIL

MD/ARNP

STAIR

S2-2HOUSEKEEPING

NOUR. KIT

263A

COPY

221A

LAUNDRY

RECEPTION /

LOUNGE

CORRIDOR

C2-2-10

W/C.T.

222A

W/C.T.

223A

MED

STORAGE

SOIL LINEN

218EMS STORE

3 BED ROOM

3 BED ROOM

3 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

W/C.T.

228A

W/C.T.

230A

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

W/C.T.

232A

W/C.T.

226A

W/C.T.

225A

HOUSEKEEPING

CLOSET

STAFF TOILET

LOUNGE

LINEN

STORAGE

PATIENT

BATH

CONG. TOILET

237A

CLEAN

SUPPLY

MECHANICAL

ROOM

MEA-8

REEF CAFE

LOUNGE

MECHANICAL

ROOM

MECHANICAL

ROOM

MEA-9

CORRIDOR

C2-5-10

CORRIDOR

C2-5A-10

OFFICE

207A4

DIRECTORY

GRECC

207A3

PROGRAM

ASSISTANT

207A2

ADMINISTRATIVE

OFFICER

207A1

CLINICAL

CENTER

207A

OFFICE

207C1

OFFICE

207C2

OFFICE

207C3

OFFICE

207C

DIRECTOR

A.G.U.

207B

CORRIDOR

207-10

RESEARCH

DIRECTOR,

GRECC

207H

STAFF TOILET

LABORATORY

#1

205B

CORRIDOR

205-10

LABORATORY

#2

205A

LAB

205A2

LAB

205A1

LABORATORY

#3

DARK ROOM

204A

GENERAL

STORAGE

SECRETARY

207G

STAIR

S2-1

CORRIDOR

C2-3-10

DOCTOR'S

OFFICE

207F

SENIOR

STAFF

ASSISTANT

207E

CONFERENCE

ROOM

207D

2.28

2.09

2.05

2.05

2.05

2.05

2.05

2.05

2.22 2.10

2.25 2.29

2.05

2.05

2.05

2.05 2.05

2.05

2.05

2.05

2.05 2.05 2.05

2.05 2.05

2.05

2.05

2.12

2.10

2.262.26 2.04

2.09

2.22 2.23

2.07

2.10

AD102

1BED TYPICAL

AD102

3BED TYPICAL

AD102

2BED TYPICAL

2.16 2.07

2.10 2.13

2.31 2.25

2.29

2.07 2.10

2.34

2.05

2.16

2.07

2.13 2.10

2.23 2.12

2.07

2.28 2.10

2.16

2.09 2.10

2.34

2.22 2.23

2.07

2.10

2.09 2.09 2.09

2.322.32

2.09 2.04

2.10

2.13 2.10

2.28 2.30

2.10

2.04

2.09 2.10

2.35

2.05

2.04 2.09

2.10

2.34

2.10

2.04

2.10 2.07

2.04

2.25 2.28

2.10

2.50

2.51

2.51

2.51

2.51

2.51

2.51

2.51

2.52

2.52

2.52

2.50 2.50 2.50 2.50

2.50 2.51 2.51 2.51 2.51

2.50

2.512.512.512.512.512.512.512.512.51

2.29 2.25

2.10

2.08 2.04

2.34

2.07 2.10

2.10

2.25

2.29

2.15

2.15

2.37

2.37

2.38

2.38

2.40 Typ.

2.40 Typ.

2.40 Typ.

2.40 Typ.

2.40 Typ.

2.40 Typ.

2.40 Typ.

2.40

2.40

2.40 3

Typ.

Typ.

Typ.

2.312.05

2.122.12

2.17

2.21 2.072.07

2.16

2.16

2.52 2.13

2.06

2.18 2.05

2.042.04

2.40 Typ.

2.05

2.05

2.31

2.17

2.21

2.51 2.13

2.18

2.12

2.12 2.16

2.042.04

2.06

2.072.07

2.40 Typ.

2.05

2.05

2.042.04

2.06

2.13

2.072.07

2.16

2.06 2.50

2.13 2.18

2.40 Typ.

DEMOLITION LEGEND

Existing wall to remain Door slab to be demolished, frame to remain.

No work unless otherwise noted.

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

:1 5:

P

M

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

DEMOLITION PLAN

AD102

JWSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

N Scale: 3/32" = 1'-0"

DEMOLITION PLAN - SECOND FLOOR

2.04 Remove existing half height wall protection, handrail, chairrail, and wood door casing. Reskim wall and prepare surfaces.

2.05 Existing door slab and existing vinyl door frame protection product to be removed. Existing HM frame to remain. Prep frame as required for new vinyl frame protection product.

2.06 Remove existing ceiling tiles, grid to remain. Paint grid P-6. Install new ceiling tiles in existing grid.

2.07 Remove existing VCT and rubber base. Prepare slab for new finishes.

2.08 Remove existing LVT flooring and rubber base. Prepare slab for new finishes.

2.09 Remove existing welded sheet vinyl flooring and integral base.

Prepare slab for new finishes.

2.10 Remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accessories, corner protection, and equipment.

2.12 Remove existing casework. Prepare for new installation.

2.13 Remove existing half height wall protection and upper wall covering.

Reskim wall and prep surface.

2.15 Remove existing fire extinguisher cabinet. Patch wall as required to match adjacent finish.

2.16 Remove and reinstall existing window covering.

2.17 Existing wall tile to remain. Protect during construction.

2.18 Existing patient lift and cubicle curtains to remain. Protect in place during construction.

2.21 Existing gypsum ceiling to remain.

2.22 Existing casework to remain. Protect in place during construction.

2.23 Existing plumbing fixture to remain. Protect in place during construction.

2.25 Remove existing ceramic tile flooring and base. Prepare slab for new finishes.

2.26 Remove existing column furring walls.

2.28 Remove existing wall tile. Prepare wall for new finishes.

2.29 Remove existing half height wall tile and cove base. Prepare wall for new finishes.

2.30 Remove and reinstall existing water fountain as required to install new finishes.

2.31 Remove existing plumbing fixtures. See plumbing drawings.

2.32 Remove wood trim at elevators. Remove and reinstall floor indicator as required for removal and installation of finishes.

2.34 Remove existing wall covering. Reskim wall and prep surface.

2.35 Remove existing handrail. Prepare for new installation.

2.37 Remove existing wall mounted nurse workstations. Prepare for installation of new stations.

2.38 Existing fire extinguisher cabinet to be reset as required to be flush flush with new finish face.,

2.40 Remove existing interior gypsum board at exterior walls. Existing framing and window trim to remain. Protect during construction.

2.50 Typical 1-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See detail 5 & 6 on sheet a405.

2.51 Typical 2-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See deatil 3 & 4 sheet a405

2.52 Typical 3-bed room: remove and reinstall existing wall mounted lights, light switches, receptacles, device covers, accesories, corner protection, and equipment. See details 1 & 2 sheet a405

A. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.

B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.

C. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.

D. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.

E. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.

F. Prepare walls and floor slabs as required to receive new finish materials where existing finish is indicated to be removed.

G. Remove existing corner guards.

H. Existing lights, diffusers, sprinkler heads, and other MEPFS items to remain. Protect during construction.

J. Remove and reinstall existing signage.

GENERAL DEMOLITION NOTES

PLAN NOTES

Scale: 1/4" = 1'-0"

TYPICAL 3 BED ROOM DEMO

Scale: 1/4" = 1'-0"

TYPICAL 2 BED ROOM DEMO

Scale: 1/4" = 1'-0"

TYPICAL 1 BED ROOM DEMO

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

A401

A402

TOILET

125A

PATIENT

BATH

CLEAN

UTILITY

TOILET

122A

TOILET

123A

RESTROOM

MALE

Room

Mechanical Room

MEA-2

MALE

TOILETS

STAFF

107A

FEMALE

TOILETS

STAFF

TOILET

FEMALE

PATIENT

RESTROOMS

TOILET

141A

E1-1 E1-1

T1-1

T1-1 TOILET

159A

TOILET

143A TOILET

146A

TOILET

147A

TOILET

148A

TOILET

155A

TOILET

151A

TOILET

153A

GERIATRICS

AND

EXTENDED

CARE

GENERAL

STORAGE

100A

CONTROL

ROOM

GERIATRIC

DIRECTOR'S

OFFICE

SOCIAL

WORKER

PSYCHOLOGY

SERVICE

BARBER

SHOP

RECREATION

THERAPY

110 DINING ROOM

RECREATION

THERAPY

110B

STAIR

S1-1

MECH. ROOM

MEA-3A

SWITCH GEAR

MEA-2B

ELEVATOR

MACHINE RM.

MEA-2C

CORRIDOR

C1-3-10

HORTICULTURAL

THERAPY

110A

VENDING

111A

NFS

111BHOUSEKEEPING

CORRIDOR

C1-2A-10

CORRIDOR

C1-5A-10

MECHANICAL

ROOM

EMS

STORAGE

EMS

STORAGE

MED ROOM

NURSE

MANAGER

RECEPTION /

LOUNGE

3 BED ROOM

3 BED ROOM

3 BED ROOM

2 BED ROOM

2 BED RM.

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

H.A.C.

STAFF TOILET

CLEAN

SUPPLY

TOILET

128A

TOILET

126A

CONG. TOILET

137A

TOILET

132A

TOILET

130A

MECH./OXYGEN

ROOM

MEA-1

CORRIDOR

C1-4-10

LAUNDRY

MULTIPURPOSE

ROOM

EMS

LIBRARY

1 BED ROOM

1 BED ROOM

1 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

147 2 BED ROOM

2 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

SOILED

UTILITY

ATTENDING

PHYSICIAN

CORRIDOR

C1-7-10

CORRIDOR

C1-6-10

TOILET

145A

TOILET

150A

TOILET

149A

TOILET

157A

STAIR

S1-2

STAIR

S1-3

CORRIDOR

C1-5-10

2 BED ROOM

1 BED ROOM

2 BED ROOM

CLEAN

SUPPLY

121A

CORRIDOR

C1-2-10

C1-7

142 146 147145144143141 148

151152153154155156157158

150149

121A

129 130

128 131

132127

126 133

1-MEA

A4 02 11 A4

A4011-T1

4A4

3 A4

A405

A405

A402

A402

141A 142A 144A143A

145A

147A 148A

149A

150A

151A152A153A154A155A156A157A158A

123A

122A

125A

126A

127A

128A

129A 130A

131A

132A

133A

137A

146A

159A

A404 A

3 A4

5A4

4 A4

A403

A403

A403

2A4

A403

9.20 Typ.

9.20 Typ.

9.20 Typ.

9.20 Typ.

9.20 Typ.

9.20 Typ.

9.20 Typ.

A513

A513

6.10 Typ.

6.10 Typ.

6.10 Typ.

6.10 Typ.

6.10 Typ.

6.10 Typ.

6.10 Typ.

1-E1-1

6 A4

4A4

2.38

2.38

5 A4

6A4

4 A4

2.38

10.18

137B

9.1

A404

10.23

10.23

3A4

5A4

9.43

9.43

9.43

9.43 Typ.

Typ.

Typ.

9.43

9.43

Typ.

Typ.

Typ.

9.43 Typ.

9.43 Typ.

A101-N

TYP.

A101-N

Sim

9.43

9.43

9.43 Typ.

Typ.

Typ.

2.42

9.05

9.21

9.44

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

:1 4:

P

M

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

NOTE PLAN

A101-N

SOSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

N Scale: 3/32" = 1'-0"

NOTE PLAN - FIRST FLOOR

A. All dimensions are taken to face of gypsum wallboard or unit masonry.

B. All wood blocking to be fire retardent treated.

2.38 Existing fire extinguisher cabinet to be reset as required to be flush flush with new finish face.,

2.42 Existing concrete column to remain.

6.10 Patient Closet Casework.

9.05 7/8ing furring channel @ 16" o.C.

9.20 Moisture mitigiation system. Install throughout first floor where new finishes are being located.

9.21 5/8" Type X gypsum board.

9.43 Install new 5/8" water resistant gypsum board with level 4 finish over existing metal studs at all interior sides of exterior walls.

9.44 WP-5 adhered to gypsum board substrate on all sides.

10.18 Semi-recessed Fire Extinguisher Cabinet. Align with new finish.

10.23 Wall mounted work station equivalent to SHS-3254-FD-A.

Finish to be selected by architect from manufacturer's full range.

PLAN NOTES

GENERAL NOTES

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

3 Addendum #1 02/19/2025

Scale: 1 1/2" = 1'-0"2 Column Closure - 1st & 2nd Floor

M.1

9.1

9.3

K.1

7.1

9.2

T

1.A

D.1 F.1

12.1

A402

GENERAL

STORAGE

LABORATORY

#3

DARK ROOM

204A

CORRIDOR

205-10

LABORATORY

#2

205A

LAB

205A1

LAB

205A2

LABORATORY

#1

205B

STAFF TOILET

CLINICAL

CENTER

207A

DIRECTOR

A.G.U.

207B

OFFICE

207C

DOCTOR'S

OFFICE

207F

SECRETARY

207G

RESEARCH

DIRECTOR,

GRECC

207H

ADMINISTRATIVE

OFFICER

207A1

PROGRAM

ASSISTANT

207A2

DIRECTORY

GRECC

207A3

OFFICE

207A4

SECRETARY

207A5

OFFICE

207C1

OFFICE

207C2

OFFICE

207C3

CORRIDOR

207-10

CORRIDOR

C2-3-10

STAIR

S2-1

CORRIDOR

C2-5-10

CORRIDOR

C2-5A-10

MECHANICAL

ROOM

MEA-9

MECHANICAL

ROOM

EMS STORE

SOIL LINEN

MED

STORAGE

LAUNDRY

RECEPTION /

LOUNGE

COPY

221A

CORRIDOR

C2-4-10

ELECTRICAL

CLOSET

E2-1

TELEPHONE

CLOSET

T2-1

MECHANICAL

ROOM

MEA-8

3 BED ROOM

3 BED ROOM

LINEN

STORAGE

3 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

LOUNGE

HOUSEKEEPING

CLOSET

STAFF TOILET

PATIENT

BATH

CLEAN

SUPPLY

NURSE

MANAGER

LOUNGE

W/C.T.

222A

W/C.T.

223A

W/C.T.

225A

W/C.T.

226A

W/C.T.

228A

STAIR

S2-3

W/C.T.

230A

W/C.T.

232A

CONG. TOILET

237A

CORRIDOR

C2-2-10

1 BED ROOM

1 BED ROOM

1 BED ROOM

1 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

OXYGEN

STORE

240A

W/C.T.

241A

W/C.T.

243A

W/C.B.

245A

W/C.B.

246A

W/C.B.

247A

W/C.B.

248A

W/C.B.

250A

W/C.B.

249A

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

SOILED UTIL

MD/ARNP

HOUSEKEEPING

NOUR. KIT

263A

REEF CAFE

LOUNGE

STAIR

S2-2

CORRIDOR

C2-7-10

CORRIDOR

C2-6-10 W/C.T.

251A W/C.T.

253A

W/C.T.

255A

W/C.T.

257A

W/C.B.

259A

CONFERENCE

ROOM

207DSENIOR

STAFF

ASSISTANT

207E

258 257

251252

253254

246 249245

243241240

233226

228 231

230229

244242

MEA-8

C2-7

E2-1 T2-1

221A

259A

258A 257A 256A 255A 254A 253A 252A 251A

241A 242A

240A

243A 244A

245A

246A 247A 248A

250A

249A

225A

226A 233A

232A227A

228A 231A

230A229A

237A

223A

222A

7A4

A404

A404

3A4 04 1 A4

A404

A404

5A4

6.10

TYP.

6.10

TYP.

6.10

TYP.6.10

Typ.

6.10Typ.

6.10

6.10 Typ.

Typ.

10 A4

9 A4

8A4

221A

10.18

A401 sim

A401

3 A4 014A4 sim sim sim 10.18

A404 B

A404 C

10.23

10.23

A402

5 A4

A101-N

Sim

A101-N

Sim

9.43

9.43

9.43

9.43

9.43

9.43

9.43

9.43 9.43

9.43

3 3

Typ.

Typ.

Typ.

Typ.

Typ.

Typ. Typ.

Typ.

Typ.

Typ.

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

:1 5:

P

M

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

NOTE PLAN

A102-N

SOSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

A. All dimensions are taken to face of gypsum wallboard or unit masonry.

B. All wood blocking to be fire retardent treated.

6.10 Patient Closet Casework.

9.43 Install new 5/8" water resistant gypsum board with level 4 finish over existing metal studs at all interior sides of exterior walls.

10.18 Semi-recessed Fire Extinguisher Cabinet. Align with new finish.

10.23 Wall mounted work station equivalent to SHS-3254-FD-A.

Finish to be selected by architect from manufacturer's full range.

PLAN NOTES

GENERAL NOTES

N Scale: 3/32" = 1'-0"

NOTE PLAN - SECOND FLOOR

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

X

X

Toilet Accessory

Equipment

Keynote

Material Finish

SYMBOL LEGEND

RB-1

RWP-1

HR-1

P-2

P-2

P-2

RWP-1

1'-0" 1'-8"

WP-1

1'-8"1'-0" 1'-8"1'-0"

10.03

HR-1

RWP-1

WP-1 RWP-1

HR-1

RB-1

WP-1WP-1WP-1 WP-1 WP-1

150149148146 147144 145142 143141

1'-8" 1'-0"

RB-1

1'-8"1'-0"

RB-1

WP-1RB-1

10.03 10.03

RB-1 RWP-1

HR-1WP-1

10.03

Typ.

Typ.

Typ.

Typ.

Typ.

Typ.Typ.

Typ.

Typ.

RWP-1

HR-1

RB-1

Typ.

Typ. Typ.

P-1P-1P-2 P-2P-2P-2P-2 Typ.

Typ.

P-2P-210.03

4' -0

301130863013030113030301130301130306301 31 6 8 630 325

10.182.38

1'-8" 1'-8"1'-0" 1'-0"1'-8" 1'-8"1'-0"

10.0310.03

HR-1

WP-1

RB-1

HR-1WP-1

P-2 WP-1P-2WP-1WP-1

RB-1

HR-1 CG-2

151 152 153 155154 158157156 1-T1

CG-2

9 11/256" P-2

WP-1

HR-1

RB-1

Typ. Typ.

Typ.

Typ.Typ.Typ.

Typ.

Typ.

Typ.

RWP-1

RB-1

HR-1

RB-1 WP-6

Typ.

Typ.

?WP-6

Typ.

P-2 P-2 P-2

P-2

P-2

OPEN

RWP-210.20

Typ.

Typ.

30130

301130103011303030113030

10.20

10.23

Typ.

1'-8" 1'-0" 1'-4 1/2"1'-0" 1'-8" 1'-8" 1'-0" 1'-0"

10.03WP-1 P-2 P-2

HR-1

RWP-1

RB-1

WP-1

WP-1

RWP-1

HR-1

RWP-1

RWP-1

HR-1WP-1 CG-2

120138133 134 135 136 137131 132130

4' -0

4' -0

9 1/4"

HR-1

RWP-1

RB-1

RWP-1RB-1

RB-1

Typ.

Typ.

Typ.

Typ.

Typ.

P-1WP-6

Typ.

WP-6

Typ.

P-2 P-2

1'-0" 1'-4"

OPEN

CG-2

OPEN

WP-5

RB-3

WP-5WP-1 RWP-2 301930 593030303011111 30

RB-1

2530 30 30 10 5

12WP-5

10.23

HR-1

1'-0" 1'-8"1'-8" 1'-0"

10.03 10.03 WP-1P-2

HR-1

RWP-1

RB-1

WP-1WP-1 P-2

WP-1HR-1

P-2WP-1

RB-1

HR-1

RB-1

119 122 125124123 126 127 128 129

4' -0

HR-1

1'-0" 1'-8"1'-8" 1'-0"

RWP-1 RWP-1 RWP-1

8"

10.03WP-1 WP-1P-2 P-2

Typ. Typ.

HR-1

RWP-1

RB-1

Typ.

HR-1

RWP-1

RB-1

WP-6

Typ. Typ.

Typ.

10.03 Typ.

10.20 10.03

Typ.

Typ.

10.03

Typ.

19 30 1 830 30 6 1 30 30 30 1 30 6 8 1 30 30 1 1 30 6 30 1 Typ.

WP-1

4130 30 30 3535 25 2530 25 25 Typ.

2.14 10.18

Typ.

OPEN

HR-1

RWP-1

RB-1

4' -0

25 30 1

4' -0

OPEN

HR-1

RWP-1

RB-1

CG-2

306 25

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

9:

:4

AM

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

INTERIOR ELEVATIONS

A401

SMSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

A. RWP in corridors to stop at 4' to meet the top of the CG-2.

B. See sheet A511 for Casework Details.

C. See sheet AF603 for Finish Materials Legend.

D. All handrails to stop 2" before wall or door frame. Handrail height to match existing.

2.14 Existing fire extinguisher cabinet to remain.

2.38 Existing fire extinguisher cabinet to be reset as required to be flush flush with new finish face.,

10.03 All existing signages to be removed and reinstalled In the renovated areas.

10.18 Semi-recessed Fire Extinguisher Cabinet. Align with new finish.

10.20 Contractor to remove and reinstall.

10.23 Wall mounted work station equivalent to SHS-3254-FD-A.

Finish to be selected by architect from manufacturer's full range.

ELEVATION NOTES

GENERAL INT. ELEVATION NOTES

Scale: 1/4" = 1'-0"

Typ. Patient Rooms Corridor

Scale: 1/4" = 1'-0"

Corridor - C1-6-10

Wall Mounted Item Schedule

Type Mark Device Name Comments

1 Nurse Call Dome Light Remove. Provide junction box extension and reinstall device.

2 Med Gas Alarm Remove and reinstall device cover.

3 Manual Fire Alarm Pull Remove and reinstall device cover.

4 Fire Alarm Remove and reinstall device cover.

5 Thermostat Remove and reinstall device cover.

6 Fire Alarm Strobe Remove and reinstall device cover.

8 Fire Extinguisher Sign Remove and reinstall.

9 Flatscreen TV Remove and reinstall.

10 Nurse Phone Remove. Provide junction box extension and reinstall device.

11 Telecommunication Outlet Remove and reinstall device cover.

12 Electric Outlet Remove and reinstall device cover.

13 Light Switch Remove and reinstall device cover.

14 Patient Room Light Fixture Remove and reinstall.

15 Intercom - Room to Room Remove. Provide junction box extension and reinstall device.

16 Clock Remove and reinstall.

17 TV Wall Bracket Adjustable Remove and reinstall.

18 Speaker Cover Remove and reinstall device cover.

19 Door Actuator Remove and reinstall device cover.

20 Patient Lift 3-Bed Room To remain.

Wall Mounted Item Schedule

Type Mark Device Name Comments

21 Patient Lift 2-Bed Room To remain.

22 Patient Lift 1-Bed Room To remain.

23 Window Treatment To remain.

24 White Board Remove and reinstall.

25 Artwork Remove and reinstall.

26 Track To remain.

27 Bulletin Board Remove and reinstall.

28 Sharps Container Remove and reinstall.

29 Combo Whiteboard/Bulletin Remove and reinstall.

30 Signage Remove and reinstall.

31 Convex Mirror Remove and reinstall.

32 Key Pad Remove and reinstall device cover.

33 Elevator Call Button Remove and reinstall device cover.

34 Elevator Floor Indicator Remove. Provide junction box extension and reinstall device.

35 Device Remove and reinstall.

36 Control Panel To remain.

37 Wall Sconce Remove and reinstall.

38 Medication Cabinet Remove and reinstall.

39 Glove Dispenser Remove and reinstall.

40 Hand Sanitizer Dispenser Remove and reinstall.

41 Exit Sign Lighted Remove and reinstall.

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

RWP-1 RWP-1 RWP-1 RWP-1RWP-1 RWP-1 RWP-1 RWP-1RWP-1

RWP-1RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1 RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1

RWP-1 RWP-1

RWP-1

RWP-1

CORRIDOR

C1-5-10

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED RM.

2 BED ROOM

3 BED ROOM

3 BED ROOM

3 BED ROOM

LIBRARY

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

H.A.C.

STAFF TOILET

CLEAN

SUPPLY

MECH./OXYGEN

ROOM

MEA-1

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

156 2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

CORRIDOR

C1-7-10

CORRIDOR

C1-6-10

SOILED

UTILITY

MULTIPURPOSE

ROOM

NFS

111B

VENDING

111A

HOUSEKEEPING

DINING ROOM

RECREATION

THERAPY

110B

RECREATION

THERAPY

BARBER

SHOP

HORTICULTURAL

THERAPY

110A

CORRIDOR

C1-2A-10

CORRIDOR

C1-3-10

PSYCHOLOGY

SERVICE

SOCIAL

WORKER

GERIATRIC

DIRECTOR'S

OFFICE

GERIATRICS

AND

EXTENDED

CARE

GENERAL

STORAGE

100A

CONTROL

ROOM

CORRIDOR

C1-5A-10

LAUNDRY

164NURSE

MANAGER

EMS

STORAGE

EMS

STORAGE

CLEAN

SUPPLY

121A

CORRIDOR

C1-4-10

RECEPTION /

LOUNGE

ATTENDING

PHYSICIAN

EMS

1 BED ROOM

1 BED ROOM

1 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

2 BED ROOM

1 BED ROOM

RWP-1

CLEAN

UTILITY

RWP-1

CG-2

CG-2 CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2 CG-2

CG-2

CG-2 CG-2 CG-2 CG-2 CG-2

CG-2

CG-2

CG-2

CG-1

CG-2

CG-2

CG-2

CG-2

CG-2CG-2 CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-1

CG-2

CG-2

HR-1HR-1HR-1HR-1HR-1HR-1HR-1HR-1HR-1

HR-1

HR-1HR-1HR-1

HR-1

HR-1

HR-1HR-1HR-1

HR-1HR-1

?HR-1

HR-1

CORRIDOR

C1-2-10

CG-2

CG-2

CG-1

CG-1

HR-1HR-1HR-1

HR-1

HR-1Sign

HR-1

HR-1

HR-1HR-1

HR-1HR-1

HR-1HR-1HR-1

HR-1

HR-1

HR-1HR-1HR-1

HR-1HR-1HR-1

HR-1 HR-1HR-1

HR-1HR-1

HR-1

CG-2

CG-2

HR-1

RWP-1

?HR-1HR-1HR-1

HR-1HR-1HR-1

CG-2

CG-2

CG-2

CG-3

RWP-1

RWP-1

CG-2

CG-2

CG-2CG-2

CG-2

CG-2CG-2

CG-2CG-2

CG-2

RWP-1

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2

CG-2CG-2

CG-2CG-2CG-2

HR-1HR-1

CG-2 CG-2HR-1

RWP-1

CG-2

CG-2

CG-2

RWP-2

RWP-3

HR-1

CG-2

RWP-2

RWP-2CG-2

WP-7

RWP-1

RWP-1

RWP-1

RWP-1 RWP-1

RWP-1

RWP-1

RWP-1

HR-1

HR-1

HR-1

HR-1

HR-1HR-1

HR-1

HR-1

HR-1HR-1

HR-1

ST

AT

E O

F MICHIGA

LICENSED ARCH

IT

EC

T

NROGER

A.

REPSTIEN

1301066948 No.

ARCHITECT

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

2/

/2

9:

:0

AM

VA Miami - CLC Renovation 1st and 2nd floors TOPR

05/12/2023

WALL PROTECTION PLAN - L-1

AF101-P

SMSO

546-22-121

MIAMI VA

ALBINO WISELL

CONSTRUCTION

DOCUMENTS

22015.00

Scale: 3/32" = 1'-0"1 WALL PROTECTION PLAN - FIRST FLOOR

A. All walls to be painted P-1 unless notes otherwise.

B. All handrails to stop at 2" before wall or door frame. Refer to Wall

Protection Plan.

C. RB-1 to be installed at all walls and RB-2 to be installed at BT-1 in wainscoting walls unless noted otherwise. See Interior Elevations for further details

D. Patient Room walls, Nurse Station, Dining room, and Reef Cafe tagged with RWP-1 are to also have the BT-1, WP-2, WP-3, and WP-4 applied as well. See Interior Elevations for further details.

E. All new doors to have P-5 finish unless noted otherwise.

F. All door frames to be painted P-4 unless noted otherwise.

PLAN NOTES

GENERAL FINISH PLAN NOTES

RWP-1

Revisions Date

1 95% CONSTRUCTION DRAWINGS 03/08/2023

2 100% CONSTRUCTION DOCUMENT SET 05/12/2023

File details come from the government source that posted it. Updated .