This document is an asbestos survey report for Building 102 at the Bay Pines VA Medical Center in Florida. The report identifies asbestos-containing materials found throughout the building, including floor tiles and mastics in various rooms. Laboratory testing identified asbestos in samples of black mastic, olive floor tile with brown spots, dark red and black floor tile, generator exhaust pipefitting insulation, and other mastics. The report provides location and quantity details of the asbestos-containing materials, photographs of sample materials, laboratory certification documents, and inspector field notes. This information is relevant to federal solicitation number 36C24823R0153 issued by the Department of Veterans Affairs for renovation and abatement work involving flooring in three buildings at the Bay Pines VA Medical Center site.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS CONTAINING
BUILDING MATERIAL REPORT
BUILDING 102
Bay Pines VA Medical Center 10000 Bay Pines Boulevard
Bay Pines, Florida
Project No. 2009011.001
July 31, 2009
5 Alfred Circle Bedford, MA 01730-2318
Telephone: (781) 275-6050 Toll Free: (800) 877-6050 Facsimile: (781) 275-5651 info@mabbett.com www.mabbett.com
© 2009, Mabbett & Associates, Inc.
mailto:info@mabbett.com http://www.mabbett.com/
Building 102 July 2009 ©2009, Mabbett & Associates, Inc. iS:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
ACKNOWLEDGMENT
This Asbestos Building Survey/Analytical Report was prepared for the Department of Veteran Affairs Medical Center, Bay Pines, Florida in anticipation of potential future building renovations and in accordance with an established scope of work as defined in Contract Number VA248-P-1114. The information presented herein is based on the facts and information conveyed to or received by M&A during the preparation of this report. If any of the information provided to M&A that was used in preparing this plan is incorrect, incomplete, or subject to change, M&A would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to M&A as of the date of this report and considered applicable to this report.
This report was prepared by the following Mabbett & Associates, Inc. personnel:
Jody Freitas Environmental Engineer
Robert K. McKinley, CIH Director of Industrial Hygiene
This report has been reviewed and approved by:
BY:
Angelo Caparelli, MBA, B.Sc., CSP, FLAC Florida Licensed Asbestos Consultant (NEED NUMBER) Certified Asbestos Inspector EPA# 101796
Building 102 July 2009 ©2009, Mabbett & Associates, Inc. iiS:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
TABLE OF CONTENTS
Description Page
1.0 INTRODUCTION & EXECUTIVE SUMMARY 1
2.0 BUILDING DESCRIPTION 1
3.0 SAMPLING METHODOLOGY 1
4.0 ANALYTICAL METHODOLOGY 2
5.0 SUMMARY OF ASBESTOS CONTAINING MATERIALS (ACM) FINDINGS 2
6.0 LIMITATIONS 4
7.0 CLOSING REMARKS 4
Table Table of ACM Results
Photos Photos of Positive Representative Samples
Drawings 18” x 32" Floor Plan (with ACM survey information)
Appendices/Back-up Data
Appendix A Laboratory Certifications/Asbestos Laboratory Analysis Reports Appendix B Inspector Field Data Sheets
July 2009 Building 102 Page 1 of 4 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
1.0 INTRODUCTION & EXECUTIVE SUMMARY
Mabbett and Associates, Inc. (M&A) with ECS Florida, LLC (ECS) as a sub-contractor performed a pre-renovation asbestos-containing materials (ACM) inspection survey of the VA Medical Center located at 10000 Bay Pines Boulevard, Bay Pines, Florida under contract VA248-P-1114. Site survey work was performed during June and July, 2009, by appropriately credentialed personnel as required. There were 118 samples collected during the course of the survey phase. Samples collected were analyzed by a certified laboratory for asbestos content by polarized light microscopy (PLM) using stop positive methodology. Materials consisting of multiple layers were analyzed separately. The results of the survey indicated the presence of asbestos in the building.
This building report consists of a summary of findings, floor plans indicating sample locations and findings information, detailed analytical findings for the specific surveyed building, photos of identified ACM positive homogenous samples; and Appendices/Back-up Data, including laboratory results and field data sheets.
2.0 BUILDING DESCRIPTION
According to information provided by VAMC Bay Pines and observations made during the field survey, Building 102 was a one-story Domiciliary built in 1971-1981. Building 102 was approximately 90,000 square feet (ft2).
3.0 SAMPLING METHODOLOGY
Samples of suspected ACM including floor tile, mastic, plaster, etc. were collected from accessible building locations according to the scope of work, Pinellas County Code Chapter 58, National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61 and other applicable state and Federal guidelines.
Bulk material sampling was conducted according to the following sampling plan:
a) Surfacing material:
(1) At least three bulk samples shall be collected from each homogeneous area that is 1,000 ft2 or less.
(2) At least five bulk samples shall be collected from each homogeneous area that is greater than 1,000 ft2 but less than or equal to 5,000 ft2.
(3) At least seven bulk samples shall be collected from each homogeneous area that is greater than 5,000 ft2.
(b) Thermal system insulation:
(1) At least three bulk samples from each homogeneous area of thermal system insulation
(2) At least one bulk sample from each homogeneous area of patched area of thermal system insulation.
(3) Sufficient samples from elbows and fittings to determine if it contains ACM.
(4) Bulk samples were not collected from any homogeneous area where the accredited inspector determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-
ACBM.
Building 102 Page 2 of 4 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
(c) Miscellaneous material:
(1) At least one bulk sample shall be collected from each homogeneous area that is less than 100 ft2
(2) At least three bulk samples shall be collected from each homogeneous area that is greater than
100 ft2
A visual screening inspection was conducted by Florida Licensed Asbestos Inspectors throughout the entire Building 102 to determine the locations of suspect ACM. Only areas that were accessible during the field work phase were inspected. Many offices, patient care areas, and other sensitive areas were not accessible by the survey teams. Any suspect ACM that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, that was not inspected should be assumed to contain asbestos if discovered during any renovation process or until otherwise verified.
4.0 ANALYTICAL METHODOLOGY
The bulk asbestos samples collected including available layers were analyzed by polarized light microscopy (PLM). Sampling results are summarized in the enclosed Building Results Table. The PLM analytical protocol requires each layer of the sample to be analyzed separately. The quantity of analyses will vary based on the number of layers in a sample and whether a "positive stop" is employed. Note: when one sample of a homogeneous area is positive, the remainder of the samples was not analyzed because the entire homogeneous area is considered positive, as indicated on the results tables and drawings.
Samples were submitted to EMSL Analytical, Inc., of Beltsville, MD for PLM analysis of bulk materials via EPA 600/R-93/116 Method. PLM analysis was conducted in conjunction with dispersion staining as outlined by 40 CFR 63, Subpart F dated January 1987. EMSL Analytical is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program (NVLAP License 101151-0). Copies of the laboratory accreditations are included in Appendix A.
For purposes of this report and consistent with county and Federal regulations, asbestos containing materials are any materials containing more than one percent (1%) asbestos as determined by PLM.
5.0 SUMMARY OF ASBESTOS CONTAINING MATERIALS (ACM) FINDINGS
A table with all available sample results for this building is enclosed with a summary of positive sample locations below. Where a sample was found positive, a representative photo of the material is provided in the Photos section of this report. Analytical results and Inspector Field Notes are provided in Appendix A and Appendix B respectively.
The CADD drawing for this building shows approximate asbestos sample locations and shortened sample numbers. The floor plan legend shows positive sample numbers and associated positive (stop positives) in blue on the drawing. Building areas containing ACM are shown on the drawing in red with markings to indicate the kind of material (e.g., floor title).
Building 102 Page 3 of 4 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Summary of Positive ACM Samples
Sample# Sample Location
ACM
Location
Description of Material
Percent and Type of Asbestos
Condition Estimated Quantity
NESHAP
Category
1A Room 112 112 Black Mastic 5% Chrysotile Good 250 SF I 4 Throughout
Building 112 12" x 12"
Olive w/ Brown Spots Floor Tile
4% Chrysotile Good 90,700 SF I
4A Throughout Building
112 Black Mastic 10% Chrysotile
Good 90,700 SF I
7 Room 112 112 12" x 12" Dark Red and Black Floor Tile
5% Chrysotile Good 230 SF I
7A Room 112 112 Black Mastic 3% Chrysotile Good 230 SF I 50 Room 122 122 Generator
Exhaust Pipefitting Insulation
5% Chrysotile Good 50 LF Friable
62A Hallway Unit A Hallway
Black Mastic to Red and Black Floor Tile
10% Chrysotile
Good 700 SF I
89A Room C-140 Room C-140 Brown Mastic 2% Chrysotile Good 240 SF I 92A Room C-101 C-101 Black Mastic 5% Chrysotile Good 200 SF I 104A Room D-101 D-101 Black Mastic 3% Chrysotile Good 160 SF I 110A Entry 84 Entry Unit B Black Mastic 4% Chrysotile Good 220 SF I
SF – Square Feet LF – Linear Feet
Category I – non-friable asbestos-containing material (ACM) – means asbestos-containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1 percent asbestos as determined using the method specified in Appendix A, Subpart F, 40 CFR part 763, Section 1, Polarized Light Microscopy.
Category II – non-friable ACM – means any material, excluding Category I non-friable ACM, containing more than 1 percent asbestos as determined using the methods specified in Appendix A, Subpart F, 40 CFR part 763, Section I, Polarized Light Microscopy that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Friable asbestos material – means any material containing more than 1 percent asbestos as determined using the method specified in Appendix A, Subpart F, 40 CFR part 763 Section I, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
Building 102 Page 4 of 4 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
6.0 LIMITATIONS
This inspection report is the result of a diligent search of the building for asbestos containing building materials. The purpose of this inspection was to identify ACM. Only materials that were accessible were sampled and submitted to the laboratory for asbestos analysis. However comprehensive this inspection appears, it does not claim to have identified all of the asbestos-containing materials present in the facility.
M&A’s evaluation was performed with limitations inherent to visual inspections. M&A has conducted this assessment with reasonable care and has performed this study within general industry standards. As with any study of this nature, limitations are inherent. There can be no assurances, and M&A makes no assurances, that the said information, research, and technology may not change in the future, thus affecting the services provided. M&A understands that you will be the sole recipient of our report and will not distribute the report to any other party without prior written approval.
7.0 CLOSING REMARKS
The VAMC should assume materials not previously sampled due to accessibility, etc. which will be impacted by any future renovation activities to be asbestos-containing materials unless proved otherwise.
Only Florida Licensed Asbestos Consultants can state that a building material is presumed to be asbestos-containing. If asbestos-containing materials must be disturbed as a part of the renovations, all ACMs must be removed by a State of Florida licensed asbestos abatement contractor. If proposed renovations will not disturb asbestos-containing materials, continuous monitoring of ACMs should be conducted throughout renovation activities to ensure the ACMs remain in an intact condition. Additionally, prior to commencing renovations, all contractors involved with the renovations should be made aware of the location and quantity of ACM within the building in which they will be working.
If any asbestos-containing material is damaged or becomes damaged it should be repaired, if possible, or removed entirely.
Prior to initiating any renovation or demolition project, Federal Law requires that the local EPA representative's office be notified in writing at least 10 working days prior to the onset of the project. The State Asbestos Coordinator's Office also requires a copy of the notification (address to State Asbestos Coordinator, State of Florida Environmental Regulation, 2600 Blare Stone Road, Tallahassee, Florida 32399-2400).
TABLE
FINAL
JULY 31, 2009
Asbestos Screening Results VA Medical Center - Bay Pines, FL
Building 102 Estimated
Room # Area Designation Description of Material Asbestos % Type Quantity Location Condition NESHAP Category
102JWM 1 112 12" x 12" Light Red Floor Tile NAD 102JWM 2 112 12" x 12" Light Red Floor Tile NAD 102JWM 3 112 12" x 12" Light Red Floor Tile NAD 102JWM 1A 112 Black Mastic 5% Chrysotile 230 Square Feet Room 112 Good I 102JWM 2A 112 Black Mastic stop positive 230 Square Feet Room 112 Good I 102JWM 3A 112 Black Mastic stop positive 230 Square Feet Room 112 Good I 102JWM 4 112 12" x 12" Olive w/ Brown Spots Floor Tile 4% Chrysotile 90,700 Square Feet Throughout Building Good I 102JWM 5 112 12" x 12" Olive w/ Brown Spots Floor Tile stop positive 90,700 Square Feet Throughout Building Good I 102JWM 6 112 12" x 12" Olive w/ Brown Spots Floor Tile stop positive 90,700 Square Feet Throughout Building Good I 102JWM 4A 112 Black Mastic 10% Chrysotile 90,700 Square Feet Throughout Building Good I 102JWM 5A 112 Black Mastic stop positive 90,700 Square Feet Throughout Building Good I 102JWM 6A 112 Black Mastic stop positive 90,700 Square Feet Throughout Building Good I 102JWM 7 112 12" x 12" Dark Red and Black Floor Tile 5% Chrysotile 230 Square Feet Room 112 Good I 102JWM 8 112 12" x 12" Dark Red and Black Floor Tile stop positive 230 Square Feet Room 112 Good I 102JWM 9 112 12" x 12" Dark Red and Black Floor Tile stop positive 230 Square Feet Room 112 Good I 102JWM 7A 112 Black Mastic 3% Chrysotile 230 Square Feet Room 112 Good I 102JWM 8A 112 Black Mastic stop positive 230 Square Feet Room 112 Good I 102JWM 9A 112 Black Mastic stop positive 230 Square Feet Room 112 Good I 102JWM 10 112 Cream AC Duct Mastic NAD 102JWM 11 112 Cream AC Duct Mastic NAD 102JWM 12 112 Cream AC Duct Mastic NAD 102JWM 13 112 2' x4' Pinhole Ceiling Tile NAD 102JWM 14 112 2' x4' Pinhole Ceiling Tile NAD 102JWM 15 112 2' x4' Pinhole Ceiling Tile NAD 102JWM 16 112 2' x 4' Yellowed Ceiling Tile NAD 102JWM 17 112 2' x 4' Yellowed Ceiling Tile NAD 102JWM 18 112 2' x 4' Yellowed Ceiling Tile NAD 102JWM 19 112 12" x 12" White Tile w/ Tan Spots NAD 102JWM 20 112 12" x 12" White Tile w/ Tan Spots NAD 102JWM 21 112 12" x 12" White Tile w/ Tan Spots NAD 102JWM 22 112 Tan Baseboard Mastic NAD 102JWM 23 107 Tan Baseboard Mastic NAD 102JWM 24 CE-4 Tan Baseboard Mastic NAD 102JWM 25 107 12" x 12" Grey and Black Spots Floor Tile NAD 102JWM 26 107 12" x 12" Grey and Black Spots Floor Tile NAD 102JWM 27 107 12" x 12" Grey and Black Spots Floor Tile NAD 102JWM 25A 107 Yellow Mastic NAD 102JWM 26A 107 Yellow Mastic NAD 102JWM 27A 107 Yellow Mastic NAD 102JWM 28 112 Brown Duct Mastic NAD 102JWM 29 112 Brown Duct Mastic NAD 102JWM 30 112 Brown Duct Mastic NAD 102JWM 31 CE-4 Brown Baseboard Mastic NAD 102JWM 32 112A Brown Baseboard Mastic NAD 102JWM 33 Hallway Brown Baseboard Mastic NAD 102JWM 34 112 Pipe Wrap on Fiberglass NAD 102JWM 35 Hallway Pipe Wrap on Fiberglass NAD 102JWM 36 Hallway Pipe Wrap on Fiberglass NAD 102JWM 37 A-112 Ten/Green Carpet Mastic NAD 102JWM 38 A-112 Ten/Green Carpet Mastic NAD 102JWM 39 A-112 Ten/Green Carpet Mastic NAD 102JWM 40 117 Cementitious Floor Covering NAD 102JWM 41 117 Cementitious Floor Covering NAD 102JWM 42 117 Cementitious Floor Covering NAD 102JWM 43 117 Tan Sink Base Coating NAD 102JWM 44 117 Tan Sink Base Coating NAD 102JWM 45 117 Tan Sink Base Coating NAD 102JWM 46 122 Vibration Dampaner NAD
Sample #
(c) 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Buildings_Asbestos_Tables_VABP 7-23-09 JF
Asbestos Screening Results VA Medical Center - Bay Pines, FL
Building 102 Estimated
Room # Area Designation Description of Material Asbestos % Type Quantity Location Condition NESHAP Category
Sample # 102JWM 47 122 Vibration Dampaner NAD 102JWM 48 122 Vibration Dampaner NAD 102JWM 49 122 Generator Exhaust Pipefitting Insulation NAD 50 Linear Feet Room 122 Good Friable 102JWM 50 122 Generator Exhaust Pipefitting Insulation 5% Chrysotile 50 Linear Feet Room 122 Good Friable 102JWM 51 122 Generator Exhaust Pipefitting Insulation stop positive 50 Linear Feet Room 122 Good Friable 102JWM 52 122 Generator Exhaust Pipe Insulation NAD 102JWM 53 122 Generator Exhaust Pipe Insulation NAD 102JWM 54 122 Generator Exhaust Pipe Insulation NAD 102JWM 55 Exterior Exterior Stucco NAD 102JWM 56 Exterior Exterior Stucco NAD 102JWM 57 Exterior Exterior Stucco NAD 102JWM 58 Exterior Exterior Stucco NAD 102JWM 59 Exterior Exterior Stucco NAD 102JWM 60 Exterior Exterior Stucco NAD 102JWM 61 Exterior Exterior Stucco NAD 102JWM 62 Hallway - Unit A 12" x 12" Black Floor Tile NAD 102JWM 63 Hallway - Unit A 12" x 12" Black Floor Tile NAD 102JWM 64 Hallway - Unit A 12" x 12" Black Floor Tile NAD 102SJM 62A* Hallway - Unit A Black Mastic 10% Chrysotile 700 Square Feet Hallway Good I 102SJM 63A* Hallway - Unit A Black Mastic 10% Chrysotile 700 Square Feet Hallway Good I 102SJM 64A* Hallway - Unit A Black Mastic 10% Chrysotile 700 Square Feet Hallway Good I
102JWM 65 Hallway - Unit A 12" x 12" Yellow Floor Tile NAD 102JWM 66 Hallway - Unit A 12" x 12" Yellow Floor Tile NAD 102JWM 67 Hallway - Unit A 12" x 12" Yellow Floor Tile NAD 102JWM 65A Hallway - Unit A Brown Mastic NAD 102JWM 66A Hallway - Unit A Brown Mastic NAD 102JWM 67A Hallway - Unit A Brown Mastic NAD 102JWM 68 Hallway (SF to A) Sheetrock NAD 102JWM 69 Hallway (A to SF) Sheetrock NAD 102JWM 70 Hallway (SF to C) Sheetrock NAD 102SJM 68A* Hallway (SF to A) Joint Compound NAD 102SJM 69A* Hallway (A to SF) Joint Compound NAD 102SJM 70A* Hallway (SF to C) Joint Compound NAD
102JWM 71 Hallway (door from SF Red Flex Patch NAD 102JWM 72 Hallway (door from SF Red Flex Patch NAD 102JWM 73 Hallway (door from SF Red Flex Patch NAD 102JWM 74 Hallway (SF to A) Black Pipe Insulation NAD 102JWM 75 Hallway (SF to A) Black Pipe Insulation NAD 102JWM 76 Hallway (SF to C) Black Pipe Insulation NAD 102JWM 77 Hallway (SF to A) Light Blue Firestop NAD 102JWM 78 Hallway (SF to C) Light Blue Firestop NAD 102JWM 79 Hallway (SF to C) Light Blue Firestop NAD 102JWM 80 A-148 Grey Sink Base Coating NAD 102JWM 81 A-148 Grey Sink Base Coating NAD 102JWM 82 A-107 Grey Sink Base Coating NAD 102JWM 83 Hallway (SF to A) Grey Plaster NAD 102JWM 84 Hallway (SF to A) Grey Plaster NAD 102JWM 85 Hallway (SF to A) Grey Plaster NAD 102JWM 86 Hallway 6" Pipefitting Insulation NAD 102JWM 87 Hallway 6" Pipefitting Insulation NAD 102JWM 88 Hallway 6" Pipefitting Insulation NAD 102JWM 89 C-140 12" x 12" Light Brown Floor Tile NAD 102JWM 90 C-140 12" x 12" Light Brown Floor Tile NAD 102JWM 91 C-140 12" x 12" Light Brown Floor Tile NAD 102SJM 89A* C-140 Brown Mastic 2% Chrysotile 240 Square Feet Room C-104 Good I 102SJM 90A* C-140 Brown Mastic 2% Chrysotile 240 Square Feet Room C-104 Good I 102SJM 91A* C-140 Brown Mastic 2% Chrysotile 240 Square Feet Room C-104 Good I
102JWM 92 C-101 12" x 12" Mustard Brown Floor Tile NAD
(c) 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Buildings_Asbestos_Tables_VABP 7-23-09 JF
Asbestos Screening Results VA Medical Center - Bay Pines, FL
Building 102 Estimated
Room # Area Designation Description of Material Asbestos % Type Quantity Location Condition NESHAP Category
Sample # 102JWM 93 C-101 12" x 12" Mustard Brown Floor Tile NAD 102JWM 94 C-101 12" x 12" Mustard Brown Floor Tile NAD 102JWM 92A C-101 Black Mastic 5% Chrysotile 200 Square Feet Room C-101 Good I 102JWM 93A C-101 Black Mastic stop positive 200 Square Feet Room C-101 Good I 102JWM 94A C-101 Black Mastic stop positive 200 Square Feet Room C-101 Good I 102JWM 95 C-105 Tan Carpet Mastic NAD 102JWM 96 C-105 Tan Carpet Mastic NAD 102JWM 97 C-105 Tan Carpet Mastic NAD 102JWM 98 Hallway (SF to C) Red Firestop NAD 102JWM 99 Hallway (SF to D) Red Firestop NAD 102JWM 100 Hallway (SF to D) Red Firestop NAD 102JWM 101 Hallway (SF to D) Pink Firestop NAD 102JWM 102 Hallway (SF to D) Pink Firestop NAD 102JWM 103 Hallway (SF to D) Pink Firestop NAD 102JWM 104 D-101 12" x 12" Blue Floor Tile NAD 102JWM 105 D-101 12" x 12" Blue Floor Tile NAD 102JWM 106 D-101 12" x 12" Blue Floor Tile NAD 102JWM 104A D-101 Black Mastic 3% Chrysotile 160 Square Feet Room D101 Good I 102JWM 105A D-101 Black Mastic stop positive 160 Square Feet Room D101 Good I 102JWM 106A D-101 Black Mastic stop positive 160 Square Feet Room D101 Good I 102JWM 107 D-170 Leveling Compound NAD 102JWM 108 D-170 Leveling Compound NAD 102JWM 109 D-170 Leveling Compound NAD 102JWM 110 84 Entry - Unit B 12" x 12" Green Floor Tile NAD 102JWM 111 84 Entry - Unit B 12" x 12" Green Floor Tile NAD 102JWM 112 84 Entry - Unit B 12" x 12" Green Floor Tile NAD 102JWM 110A 84 Entry - Unit B Black Mastic 4% Chrysotile 220 Square Feet Entry 84 Good I 102JWM 111A 84 Entry - Unit B Black Mastic stop positive 220 Square Feet Entry 84 Good I 102JWM 112A 84 Entry - Unit B Black Mastic stop positive 220 Square Feet Entry 84 Good I 102JWM 113 84 Entry - Unit B Duct Insulation NAD 102JWM 114 84 Entry - Unit B Duct Insulation NAD 102JWM 115 84 Entry - Unit B Duct Insulation NAD 102JWM 116 B-118 12" x 12" Lime Green Floor Tile NAD 102JWM 117 B-118 12" x 12" Lime Green Floor Tile NAD 102JWM 118 B-118 12" x 12" Lime Green Floor Tile NAD 102JWM 116A B-118 Clear Mastic NAD 102JWM 117A B-118 Clear Mastic NAD 102JWM 118A B-118 Clear Mastic NAD 102SRG 1 Roof Membrane NAD 102SRG 2 Roof Membrane NAD 102SRG 3 Roof Membrane N/A 102SRG 4 Roof Flashing NAD 102SRG 5 Roof Flashing NAD 102SRG 6 Roof Flashing NAD 102SRG 7 Roof Pitch Post NAD 102SRG 8 Roof Pitch Post NAD 102SRG 9 Roof Pitch Post NAD
Note: Positive Asbestos and "Stop Positive" samples in Red Note: NAD - No Asbestos Detected Note: N/A - Analysis Not Applicable
* Resampled material analysis
(c) 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Buildings_Asbestos_Tables_VABP 7-23-09 JF
PHOTOS
Building 102 Photos - Page 1 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Building 102 Sample 1A - Black Mastic to 12” x 12” Red Floor Tile
Building 102 Photos - Page 2 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Dra
Building 102 Photos - Page 2 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 4 - 12" x 12" Olive with Brown Spots Floor Tile
Sample 4A - Black Mastic Sample 110A – Black Mastic to 12” x 12” Olive Dark Green Floor Tile
Building 102 Photos - Page 3 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 7 - 12" x 12" Dark Red and Black Floor Tile
Sample 7A - Black Mastic
Building 102 Photos - Page 4 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 50 - Generator Exhaust Pipefitting Insulation
Building 102 Photos - Page 5 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 62A – Black Mastic to 12" x 12" Red and Black Floor Tile
Building 102 Photos - Page 6 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 89A – Brown Mastic to 12” x 12” Light Brown Floor Tile
Sample 92A – Black Mastic to 12” x 12” Mustard Brown Floor Tile
Building 102 Photos - Page 7 of 7 © 2009, Mabbett & Associates, Inc. S:\STAFF\VA Bay Pines Asbestos\Draft Reports\Building 102\Building 102 Rpt.doc
Sample 104A – Black Mastic to 12” x 12” Dark Blue Floor Tile
DRAWINGS
APPENDIX A
LAB REPORTS
APPENDIX B
FIELD NOTES
| 1.0 INTRODUCTION & EXECUTIVE SUMMARY |
| 2.0 BUILDING DESCRIPTION |
| 3.0 SAMPLING METHODOLOGY |
| 4.0 ANALYTICAL METHODOLOGY |
| 5.0 SUMMARY OF ASBESTOS CONTAINING MATERIALS (ACM) FINDINGS |
| 6.0 LIMITATIONS |
| 7.0 CLOSING REMARKS |
| Buildings_Asbestos_Tables_VABP 7-23-09 JF.pdf |
| Bldg 102 |
File details come from the government source that posted it. Updated .