36C24726R0032 0003.docx
DOCX document 33 KB Posted
- Attached to
- Z2DA--Project 521-22-119 NRM Replace windows (VA-26-00016046) Federal contract opportunity
- Solicitation number
- 36C24726R0032
About this file
This document is a solicitation amendment for a window replacement project at the Birmingham VA Medical Center. The Department of Veterans Affairs (VA) is seeking a contractor to complete Phase III of a window replacement project on a firm fixed-price basis with a 491-calendar-day period of performance from Notice to Proceed. The scope of work includes demolition and removal of existing windows, installation of new non-operable windows per construction documents using exterior swing stage scaffolding, interior patching and painting, installation of window treatments and select windowsills, and asbestos and lead abatement for approximately 100 windows with proper removal and disposal. All work must comply with VA Design Guides, Infection Control Risk Assessment (ICRA) Level III containment standards, NFPA Life Safety Code, and applicable building codes. The facility will remain operational 24/7 during construction, requiring the contractor to develop and maintain a detailed phasing plan to minimize disruption.
The amendment extends the response due date to June 30, 2026, at 1:00 PM Central Daylight Time and announces a mandatory site visit on June 3, 2026, at 1:00 PM CDT at the Birmingham VA Medical Center located at 700 19th Street South, Birmingham, Alabama 35233, with additional visits available by coordinating with the Contracting Officer's Representative. The Request for Information (RFI) deadline is June 9, 2026, at 1:00 PM CDT, with submissions required to both listed email addresses. The government has issued initial responses to vendor questions submitted under the RFI to ensure consistent guidance to all interested parties. All other solicitation terms and conditions remain unchanged.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24726R0032 0005.docx | DOCX document | |
| 36C24726R0032 0004.docx | DOCX document | |
| Attachment 1 - WD No AL20260087-05.18.2026.pdf | ||
| 36C24726R0032 0002.docx | DOCX document | |
| 36C24726R0032 0001.docx | DOCX document | |
| Attachment 6 - SF24-23a Bid Bond.pdf | ||
| Attachment 4 - Performance Relevancy Questionnaire - PRQ.pdf | ||
| Attachment 1 - Wage Determination Number AL20260087.pdf | ||
| 36C24726R0032_1.docx | DOCX document | |
| Attachment 9 - Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 8 - Compliance with Executive Order 13899.pdf | ||
| Attachment 3 - SPECIFICATIONS - Project 521-22-119_Bid Document Specifications.pdf | ||
| Attachment 7 - Class Deviation from the Federal Acquisition Regulation.pdf | ||
| Attachment 5 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Deviation.pdf | ||
| Attachment 2 - DRAWINGS - Project 521-22-119_Bid Document Drawings .pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 06-22-2026 521-22-119 Department of Veterans Affairs VISN 7 Network Contracting Office 3 FL Directors Office 3700 Crestwood Parkway Duluth
GA
30096 Department of Veterans Affairs VISN 7 Network Contracting Office 3 FL Directors Office 3700 Crestwood Parkway Duluth
GA
30096 To all Offerors/Bidders
36C24726R0032
X X X The purpose of this amendment is to issue the Government’s initial responses to vendor questions under the Request for Information so all interested parties receive consistent guidance.
The Response Due Date remains June 30, 2026, at 1:00 p.m. Central Daylight Time, and all other terms and conditions remain unchanged.
Contracting Officer Kenyon Dulaney
REQUEST FOR INFORMATION: ANSWERS
1. Is ICRA containment required for all interior work areas occupied by the contractor, regardless of the scope of work being performed?
Yes. ICRA containment is required for all interior work performed inside the medical center in occupied or potentially occupied areas. The specific level of containment (Class I–IV) and the required infection control precautions will be determined by the project-specific Infection Control Risk Assessment (ICRA) and the associated ICRA Permit. Work cannot begin in any interior area until:
· The ICRA has been completed and approved, and
· The required containment measures are installed, inspected, and approved by the VA’s Infection Prevention and Safety teams.
· Since the original design was completed, the contractor shall no longer tie into the existing building return air system. Preferred Method: HEPA-filtered exhaust air shall be discharged directly to the exterior. Exhaust termination shall be located a minimum of 25 feet from building entrances, air intakes, and operable windows, in accordance with current VHA Infection Control Risk Assessment (ICRA) guidelines. If exterior exhaust is not feasible: A Certified Industrial Hygienist (CIH) shall be required to monitor interior discharge air. Prior to the start of work, HEPA filtration efficiency shall be verified by particulate measurement confirming no less than 99.97% efficiency at 0.3 microns. Exhaust shall not be directed into shared or recirculating HVAC systems. Monitoring shall occur at a minimum of three times per day (once every 8 hours) while negative air machines are operating.
2. Regarding Detail 2 on Drawing A-303, is the specified cleaning agent only required to be applied to the stone windowsill and the sealant surrounding the existing window?
Per Detail 2 on Drawing A-303, the contractor shall supply a cleaning agent that works like Sure Klean for each type of surface. Manufacture recommended cleaning agent shall be applied to the stone windowsill and the existing structure, brick, metal, aluminum, concrete surrounding the window as part of surface preparation. The cleaner is intended to remove pollution, dirt, contaminants, and old sealant residue to ensure proper adhesion of the new flashing, backer rod, sealant primer, and sealant. Apply the correct surface cleaner in accordance with the manufacturer’s recommendations (including dwell time) and thoroughly rinse or wipe the surface clean before proceeding with new work.
For each cleaning cycle or area perform a PH test or approved manufacture test to ensure the manufactures cleaning agent has been fully removed. Do not install on surfaces that have not been fully cleaned.
3. Regarding the phasing requirements outlined in the Statement of Work, can any activities be performed during the initial 60-day period outside of the window replacement scope? Examples include, but are not limited to, installation of roof protection, roof access door installation, scaffolding, window cleaning, material staging, and other preparatory activities.
The 60 calendar days referenced in the Statement of Work / Section 01 00 00 are allocated primarily for submittal processing, creating an approved project schedule and getting any mockup items completed. During this period, the Contractor may perform limited preparatory activities, provided they are:
· Non-disruptive to Medical Center operations,
· Coordinated in advance with the COR, and
· Approved through the appropriate submittals and Infection Control / Safety reviews where required.
Examples of activities generally permitted during the 60-day period (with COR approval):
· Submittal preparation, review, and approval process (primary intent of the 60 days)
· Material ordering, fabrication, and off-site preparation
· Material staging in approved exterior or designated areas
· Installation of roof protection
· Installation of roof access doors (exterior work)
· Erection of exterior scaffolding and swing stage systems
· Exterior windowsill and wall cleaning
· Site survey and layout work
Temporary protection measures that do not require ICRA containment Activities that are generally NOT permitted during the 60-day period without specific written approval:
· Actual window removal or replacement
· Any interior work that generates dust or requires ICRA containment
· Work inside patient care or occupied areas
· Any activity that could impact building operations or life safety systems
All work during this period must be shown on the project schedule and coordinated with the COR, Infection Prevention, and Safety Office as applicable.
4. Regarding the phasing requirements outlined in the Statement of Work, each phase is shown as 21 days in duration. With a total of 23 phases, this equates to 483 days, not including the initial 60-day period required for measurements, submittals, scheduling, procurement, and other preconstruction activities. Given that the current Period of Performance (POP) is 491 days, can the Government consider a revision or extension to the POP to account for the phasing requirements and associated overlap constraints?
The Government does not intend to revise or extend the Period of Performance at this time. The phasing durations shown on the drawings and in the Statement of Work are not intended to be performed entirely sequentially with no overlap. The 21-day duration per phase represents the approximate time required to complete the full cycle of work in that area (including demolition, installation, sealing, cleaning, and ICRA release).
However, overlap between phases is expected and permitted, provided it complies with ICRA requirements, life safety, and coordination with Medical Center operations. The Contractor is responsible for developing a realistic Critical Path Method (CPM) schedule that incorporates reasonable overlap between phases while meeting the contract completion date. During the baseline schedule review process, the Government will evaluate the proposed phasing and overlap. Any request for additional time must be justified through the normal change order process and supported by a detailed schedule analysis.
5. Regarding the roof access door shown on Drawing GI200, Elevation 7 on Drawing A-203 does not depict the roof access door. Can the exact location of the roof access door be clarified?
Unit 3336.E-SF1 shown on A-107 “STORE FRONT DOOR SEE DETAIL 1/A305” also shows ships ladder to access this area on print. Detail 1/A305 shows the offset pulls, ladder, locks, associated hardware and accessories.
All frames and glazing shall be blast resistant. Blast resistant glass shall meet the performance requirements of UFC 4-010-01 (or latest edition) and VA Master Specification Section 08 80 00, including minimum blast pressure and impulse criteria as applicable to this facility. All glass types, including insulated glass units, shall incorporate a laminated interlayer designed to resist blast loads. Submit shop drawings and product data demonstrating compliance for review and approval
6. Regarding project logistics, can all windows required for a particular phase be lifted to the roof during a single crane mobilization and temporarily stored on the roof to minimize the number of crane mobilizations required throughout the project?
Crane Mobilization and Roof Storage of Windows Yes, with limitations. Windows for a particular phase may be lifted to the roof in a single crane mobilization and temporarily stored on the roof, provided the following conditions are met:
· The roof structure can safely support the concentrated and uniform loads from the stored windows (see dead load question below).
· Proper roof protection is installed as shown on the drawings
· The Contractor must submit a roof loading / material staging plan for review and approval by the COR and Structural Engineer prior to any material being placed on the roof.
· All stored materials must be secured against wind uplift and properly protected from weather.
· Crane operations must be coordinated with the Medical Center (swing radius, safety, noise, and patient/staff impact).
Note: The Government generally prefers to minimize the number of crane mobilizations, so this approach is acceptable if the structural capacity and protection requirements are satisfied. All crane setups shall be a task on the project schedule.
The drawings identify Wausau as the basis of design for the windows. Are Traco, Kawneer, or Winco acceptable approved equal manufacturers?
Wausau is listed as the Basis of Design manufacturer in the drawings and specifications (Section 08 51 13 – Aluminum Windows).
· Kawneer is considered an acceptable manufacturer on this project, provided the proposed system meets or exceeds all performance requirements (thermal, structural, air/water infiltration, warranty, etc.).
· Traco and Winco are not pre-approved equals. They may be submitted for consideration as “or equal” manufacturers; however, they will be subject to review and approval by the Government.
Any proposed alternate manufacturer must be submitted with complete supporting documentation demonstrating compliance with all requirements. The Government reserves the right to reject any proposed equal that does not meet the specified performance criteria.
All frames and glazing to be blast resistant. The selected window system must meet the blast performance criteria and be capable of addressing the installation conditions for each opening across the building. This includes a wide range of window sizes, configurations, and mounting conditions.
While many manufactures offer some blast-resistant products, they may not meet the project requirements in all configurations. The approved Manufacture must provide blast-resistant frames and glazing that satisfy the performance, structural, and installation demands of this project.
If you wish to propose an “or equal,” you must submit complete documentation demonstrating that the proposed systems fully comply with the blast resistance requirements for every window type and opening condition on this project. This documentation should include, at a minimum:
· Blast test reports meeting the project’s required pressure and impulse criteria
· Structural calculations for each window configuration
· Details showing how the system will be anchored and installed at all conditions
· Confirmation that both the frame and glazing are blast resistant
The VAMC reserves the right to reject any proposed alternate that does not clearly demonstrate full compliance.
WINDOW REPLACEMENT DESIGN CRITERIA – SHELTER-IN-PLACE HOSPITAL
Birmingham VA Medical Center
· Risk Category: IV (Essential Facility)
· Basic Wind Speed: Per ASCE 7 (Risk Category IV)
· Exposure Category: B
· Wind-Borne Debris Region: No (Birmingham, AL)
· Blast / Hazard Mitigation: ASTM F1642 (latest edition) with laminated glazing –
· Hazard Rating per VA Physical Security and Resiliency Design Manual
· Glazing Type: Insulating Glass Units with laminated inner lite (minimum 0.030" PVB interlayer)
· Impact Resistance: Not required
· Mental Health Areas: No hardware
· Thermal Performance: Maximum whole-window U-factor 0.35 and SHGC
· 0.35 (NFRC-rated)
· Air / Water Infiltration: ASTM E283 / E331 (0.1 – 0.2 cfm/ft² @ 6.24 psf)
· Acoustic Performance: STC 35 minimum
· Forced Entry Resistance: All windows are fixed units
· Structural Requirements:
· Design glass per ASTM E1300
· Maximum center-of-glass deflection 1” COG Deflection.
· Balanced design (glazing fails before frame/mullions) in accordance with the minimum prescriptive requirements of the VA physical Security and Resiliency Design Manual.
· Structural silicone wet glazing at perimeter for blast performance. Per VA PSRDM Section 6.3.2.3
· Warranty: 10-year glass / 10-year finish / 2-year installation (starting at Substantial Completion)
7. Regarding Drawing GI300, what are the requirements for the labeling system used in the photographic documentation process? Is a handwritten label using paper and permanent marker acceptable, or are stenciled labels required?
Drawing GI300 – Quality Assurance, Recording outlines the photographic documentation requirements for this project. The labeling on photographs must be clear, legible, and permanent. A handwritten label using paper and a permanent marker is acceptable provided the label is clearly visible in the photograph and contains the required information (date, location/window number, and description of the work shown). Stenciled labels are not required. However, all photographs must be uploaded daily into the approved cloud-based software (Procore or equal) with proper metadata and indexing as required by the specifications and Drawings. The Contractor should ensure that labels do not obstruct the view of the work being documented.
The purpose of this amendment is to issue the Government’s initial responses to vendor questions submitted under the Request for Information, ensuring all interested parties receive consistent guidance. The Response Due Date remains June 30, 2026, at 1:00 p.m. Central Daylight Time, and all other terms and conditions of the RFI remain unchanged.