Inspection Sheets Montgomery.pdf
PDF 695 KB Posted
- Attached to
- J091--Natural Gas Line Leak & Detection Service
- Solicitation number
- 36C24726Q0105
About this file
This document is an Inspection & Leakage Repair Form for the Alabama VA Montgomery facility. The survey details a gas leak detected at a meter setting on the south side of Building #42, with a gas percentage of 4.6% and a PPM reading of 980. The leak is classified as a Class-3 leak, with the primary cause identified as a construction defect. The form recommends tightening the meter valve, and the leak was found using a CGI (Combustible Gas Indicator) detection method. The pipe system is primarily steel, and the survey was conducted with an average wind speed of 5 to 10 MPH. The precise location of the leak is noted with GPS coordinates 32°22'30.1"N 86°14'44.3"W.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02 Answer Questions 36C24726Q0105 0002.docx | DOCX document | |
| Gas Line - Tuskegee Campus.pdf | ||
| Gas Line - Montgomery Campus.pdf | ||
| S02 RFQ Site Visit in SOW 36C24726Q0105 0001 Amendment.docx | DOCX document | |
| S02 RFQ 36C24726Q0105_1.docx | DOCX document | |
| 36C24726Q0105.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INSPECTION & LEAKAGE REPAIR FORM
SURVEY PROVIDED FOR:
Alabama VA Montgomery
SURVEY CONDUCTED BY: DATE OF LEAK SURVEY:
Detected COVER LEAK INDICATION CGI Leak Remarks By APPEARS TO BE AT Test Grade
Mobile Flame Pack CONCRETE MAIN Gas Percent (%) 4.6 Class - 1 Leak #1
Flame Ionization ASPHALT SERVICE LEL Class - 2
CGI X BRICK PIPE TAP PPM 980 Class - 3 X
Bar Hole GRAVEL DRIP Negative
RMLD SOIL METER X Soap X
Odor ABOVE GROUND X CURB VALVE
Visual/Vegetation OTHER MAIN VALVE
Other OTHER
AVG WIND SPEED: 5 to 10 MPH
Pressure Leak Pipe Part Pipe Year Cause Condition Of System Type Size Inst.
Low X Corrosion Good X Main Steel X N/A
Intermediate Outside Force Fair Bldg. Riser Poly
High Const Defect X Poor Meter Set X PVC
Other Material Failure Bad Customer Side Other
Gath Line
Trans Line
Date of Repair: Repaired by whom: Date of Recheck:
Remarks:
Leak #1. Meter setting on South side of Bldg. #42. Flange appears to be good. Recommend tightening meter valve.
32°22'30.1"N 86°14'44.3"W
SKETCH OF LEAK LOCATION
PIPELINE REPAIR INFORMATION
LEAK IMAGES
File details come from the government source that posted it. Updated .