This is a technical specification document (Section 08 90 00) for louvers and vents as part of a HEPA Filter Installation project at the Atlanta VA Health Care System's Pharmacy Cleanroom Suite. The document details requirements for fixed and operable wall louvers, door louvers, and wall vents.

The specification outlines material requirements including aluminum (ASTM B221M), stainless steel (ASTM A240/A240M Type 302B), and galvanized steel (ASTM A653/A653M G90). Weather louvers must have a minimum 50% free area and pass specific performance criteria for air velocity and water penetration per AMCA Standard 500-L. Key requirements include wire guards on exterior louvers, blank-off panels with insulating cores, and specific finish requirements including anodized finish AA-M10C22A42 for aluminum components. The document also mandates protection against galvanic action between dissimilar materials and includes detailed installation and cleaning requirements. The project number is 508-21-107 with bid documents dated September 27, 2024.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Atlanta VA Health Care System September 27, 2024 HEPA Filter Installation Pharmacy Cleanroom Suite 100% Bid Documents Add. 1 Atlanta, GA 30024 Project No: 508-21-107

08 90 00 - 1

SECTION 08 90 00

LOUVERS AND VENTS

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies fixed and operable wall louvers, door louvers and wall vents.

1.2 RELATED WORK

A. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES: Louvers in Steel

Doors.

B. Section 09 06 00, SCHEDULE FOR FINISHES: Color of finish.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Shop Drawings:

1. Each type, showing material, finish, size of members, method of assembly, and installation and anchorage details.

C. Manufacturer's Literature and Data:

1. Each type of louver and vent.

D. Samples: Submit two samples 2 by 2 inches (50 by 50 mm) in size illustrating finish and color of exterior surfaces.

E. Color samples.

F. Test Reports: Independent agency reports showing compliance with specified performance criteria.

G. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.

H. Maintenance Data: Include lubrication schedules, adjustment requirements.

1.4 APPLICABLE PUBLICATIONS:

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. The Master Painters Institute (MPI):

Approved Product List – Updated Monthly

C. ASTM International (ASTM):

A240/A240M-20...........Chromium and Chromium-Nickel Stainless Steel

Plate, Sheet, and Strip for Pressure Vessels and for General Applications

08 90 00 - 2

A653/A653M-20...........Steel Sheet Zinc-Coated (Galvanized) or Zinc-

Iron Alloy Coated (Galvannealed) by the Hot Dip

Process

A1008/A1008M-20.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved

Formability

B209-14.................Aluminum and Aluminum Alloy, Sheet and Plate

B209M-14................Aluminum and Aluminum Alloy, Sheet and Plate

(Metric)

B221-14.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes

B221M-13................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)

D1187/D1187M-97(2018)...Asphalt-Base Emulsions for Use as Protective

Coatings for Metal

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual

E. National Fire Protection Association (NFPA):

90A-15..................Installation of Air Conditioning and

Ventilating Systems

F. American Architectural Manufacturers Association (AAMA):

2605-13.................High Performance Organic Coatings on

Architectural Extrusions and Panels

G. Air Movement and Control Association, Inc. (AMCA):

500-L-07 Testing Louvers

H Department of Veterans Affairs:

1. VA Physical Security Design Manual for Life Safety Protected Facilities January 2015.

2. VA Physical Security Design Manual for Mission Critical Protected Facilities January 2015.

I. Protective Design Center PDC-TR-08 Single Degree of Freedom Structural Response Limits for

Antiterrorism Design

08 90 00 - 3

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products of the type specified in this section, with minimum three years of documented experience.

B. Installer Qualifications: Company specializing in performing work of type specified and with at least three years of documented experience.

1.6 WARRANTY

A. Construction Warranty: FAR clause 52.246 21, "Warranty of

Construction."

B. Provide five year manufacturer's warranty against distortion, metal degradation, and connection failures of louver components.

C. Finish: Include ten year coverage against degradation of exterior finish.

PART 2 - PRODUCTS

2.1 MATERIALS:

A. Aluminum, Extruded: ASTM B221M (B221).

B. Stainless Steel: ASTM A240/A240M, Type 302B.

C. Galvanized Steel Sheet: ASTM A653/A653M; G90 min.

D. Carbon Steel and Sheet: ASTM A1008/A1008M (interior use louvers only).

E. Aluminum, Plate and Sheet: ASTM B209M (B209); alloy 3003 or 5005 with temper as required for forming.

F. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or indicated in construction documents, to be toggle or expansion bolts of size and type as required for each specific type of installation and service condition.

1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.

2. Fasteners for louvers, louver frames, and wire guards to be of stainless steel or aluminum with same finish as louvers.

3. Fasteners for louvers, louver frames and wire guards within mental health areas to be non-removable/tamper-proof type.

G. Inorganic Zinc Primer: MPI No. 19.

H. Bituminous Coating: ASTM D1187/D1187M; cold applied asphalt mastic emulsion.

08 90 00 - 4

2.2 EXTERIOR WALL LOUVERS:

A. General:

1. Provide fixed type louvers of size and design shown.

2. Heads, sills and jamb sections are to have formed caulking slots or be designed to retain caulking. Head sections are to have exterior drip lip, and sill sections an integral water stop.

3. Furnish louvers with sill extension or separate sill as shown.

4. Frame is to be mechanically fastened or welded construction with welds dressed smooth and flush.

B. Performance Characteristics:

1. Weather louvers are to have a minimum of 50 percent free area and to pass .075 fpm free area velocity at a pressure drop not exceeding

1000 fpm (305 m/min): 0.20" (0.05 kPA) water gauge and carry not more than .01 ounces of water per square foot of free area for 15 minutes when tested per AMCA Standard 500-L.

2. Louvers are to bear AMCA certified rating seals for air performance and water penetration ratings.

C. Aluminum Louvers:

1. General: Frames, blades, sills and mullions (sliding interlocking type); 2 mm (0.078-inch) thick extruded 6063-T5 or –T52 aluminum.

Blades to be drainable type and have reinforcing bosses.

2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames are not to exceed 1676 mm (66 inches) wide. When openings exceed 1676 mm (66 inches), provide twin louvers separated by mullion members.

3. Louvers are to withstand the effects or gravity loads and the following wind loads and stresses within limits and under conditions indicated without permanent deformation of louver components, noise or metal fatigue caused by louver-blade rattle or flutter, or permanent damage to fasteners and anchors.

a. Wind load acting inward or outward of not less than 1436 Pa (30 pound per square foot.).

2.3 CLOSURE ANGLES AND CLOSURE PLATES:

A. Fabricate from 2 mm (0.078-inch) thick stainless steel or aluminum.

B. Provide continuous closure angles and closure plates on inside head, jambs and sill of exterior wall louvers.

08 90 00 - 5

C. Secure angles and plates to louver frames with screws, and to masonry or concrete with fasteners as indicated in construction documents.

2.4 WIRE GUARDS:

A. Provide wire guards on outside of all exterior louvers, except on exhaust air louvers unless access doors are provided for cleanout.

B. Fabricate frames from 2 mm (0.078-inch) thick extruded or sheet aluminum designed to retain wire mesh.

C. Wire mesh to be woven from not less than 1.6 mm (0.063-inch) diameter aluminum wire in 13 mm (1/2-inch) square mesh.

D. Miter corners and join by concealed corner clips or locks extending not less than 57 mm (2-1/4 inches) into rails and stiles. Equip wire guards over 1219 mm (4 feet) in height with a mid-rail constructed as specified for frame components.

E. Fasten frames to outside of louvers with aluminum or stainless steel devices of same finish as louvers designed to allow removal and replacement without damage to the wire guard or the louver.

2.5 BLANK-OFF PANELS:

A. Insulated laminated panels consisting of an insulating core surfaced on back and front with metal sheets and attached to back of louver with clips on screws and gasketed or sealant sealed perimeter. Panel finish is to be same type of finish applied to louvers but black color.

1. Thickness: 25 mm (1 inch).

2. Aluminum sheet for aluminum louver 0.81 mm (0.032 inch) minimum.

3. Galvanized-steel sheet for galvanized-steel louver 0.71 mm (0.028 inch) minimum.

4. Stainless-steel sheet for stainless-steel louvers 0.79 mm (0.031 inch) minimum.

5. Insulating Core: extruded-polystyrene foam.

2.6 EXTERIOR DOOR LOUVERS:

A. Fabricate of 1.6 mm (0.063-inch) thick extruded aluminum. Miter frames at corners and join by concealed corner brackets. Louvers are to be weather resistant type.

B. Equip louvers on outside with wire guards, except omit wire guards for louvers in doors located completely below enclosed areaways.

2.7 FINISH:

A. In accordance with NAAMM Metal Finishes Manual: AMP 500-505 B. Aluminum Louvers Blank Off Panels:

08 90 00 - 6

1. Anodized finish

a. AA-M10C22A42, Chemically etched medium matte, with integrally colored anodic coating, Class I Architectural, 0.17 mm (0.7 mils) thick.

2. Manufacturer finished louvers and blank-off panels are to have color as indicated in Section 09 06 00, SCHEDULE FOR FINISHES.

C. Steel: Surfaces of steel work, for which no other finish is specified, are to be cleaned free from scale, rust, oil and grease, and then given a light colored prime paint after fabrication, except ferrous metals concealed in finished work. Paint all contact surfaces of assembled work (except welded contact surfaces) with an additional shop coat of similar paint.

2.8 PROTECTION:

A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with a heavy coat of bituminous coating

(complete coverage), or by separating the contact surfaces with a performed synthetic rubber tape having pressure sensitive adhesive coating on one side.

B. Isolate the aluminum from plaster, concrete and masonry by coating aluminum with zinc-chromate primer.

C. Protect finished surfaces from damage during fabrication, erection, and after completion of the work. Strippable plastic coating on colored anodized organic finish is not approved.

PART 3 - EXECUTION

3.1 INSTALLATION:

A. Set work accurately, in alignment and where indicated in construction documents. Install plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.

B. Furnish setting drawings and instructions for installation of anchors and for the positioning of items having anchors to be built into masonry construction. Provide temporary bracing for such items until masonry is set.

C. Provide anchoring devices and fasteners as shown and as necessary for securing louvers to building construction as specified. Power actuated

08 90 00 - 7 drive pins may be used, except for removal items and where members would be deformed or substrate damaged by their use.

D. Set wall louvers in masonry walls during progress of the work. If wall louvers are not delivered to job in time for installation in prepared openings, make provision for later installation. Set in cast-in-place concrete in prepared openings.

3.2 CLEANING AND ADJUSTING:

A. After installation, all exposed prefinished and plated items and all items fabricated from stainless steel and aluminum are to be cleaned as recommended by the manufacturer and protected from damage until completion of the project.

B. All movable parts, including hardware, are to be cleaned and adjusted to operate as designed without binding or deformation of the members, so as to be centered in the opening of frame, and where applicable, to have all contact surfaces fit tight and even without forcing or warping the components.

C. Restore louvers and vents damaged during installation and construction so no evidence remains of corrective work. If results of restoration are unsuccessful, as determined by Contracting Officer

Representative (COR) damaged units and replace with new units.

- - - E N D - - -

08 90 00 - 8

--- INTENTIONALLY BLANK ---

SECTION 08 90 00
LOUVERS AND VENTS
PART 1 - GENERAL
1.1 DESCRIPTION
1.2 RELATED WORK
1.3 SUBMITTALS
1.4 APPLICABLE PUBLICATIONS:
PART 2 - PRODUCTS
2.1 MATERIALS:
2.2 EXTERIOR WALL LOUVERS:
2.3 CLOSURE ANGLES AND CLOSURE PLATES:
2.4 WIRE GUARDS:
2.5 BLANK-OFF PANELS:
2.6 EXTERIOR DOOR LOUVERS:
2.7 FINISH:
2.8 PROTECTION:
PART 3 - EXECUTION
3.1 INSTALLATION:
3.2 CLEANING AND ADJUSTING:

File details come from the government source that posted it. Updated .