2025-02-03_229004_AE002.pdf

PDF 317 KB Posted

Attached to
Y1FD--Project: 508-22-102, Renovate Nutrition and Food Service and Freezers
Solicitation number
36C24725R0015
Issued by

About this file

This is an architectural wall types drawing detailing construction specifications for various wall assemblies as part of VA Atlanta's Nutrition and Food Service Kitchen & Freezers renovation project (508-22-102). The drawing provides comprehensive details for wall construction including fire ratings, sound ratings, material specifications, and construction methods.

The drawing includes wall type schedules showing different configurations (CH4A.2Fi, F1D.GIMR, F2D.GiMR, F3D.G, S3A.2F, S3C.G, S6A.1Fi, S6C.GiMR), detailed sections for deflection tracks and corner framing, and tables for non-composite steel studs in various gauges (25GA, 22GA, 20GA, 18GA). Key requirements include specifications for fire-rated assemblies (1-hour and 2-hour ratings), smoke barriers, sound attenuation requirements (STC ratings), and moisture/mold resistant gypsum board applications. The drawing also contains general notes covering stud spacing (16" O.C.), deflection criteria (L/240 or L/360 for fragile finishes), and requirements for fire stopping and acoustical treatments.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. ALL WALLS WILL BE WALL TYPES S3A.G UNLESS OTHERWISE NOTED.

B. ALL WALL TYPE INDICATORS REFER TO THIS SHEET UNLESS OTHERWISE

NOTED.

C. REFER TO DIMENSION PLANS FOR PARTITION TYPE LOCATIONS.

PARTITIONS ARE DISTINGUISHED ON PLANS BY SYMBOL DESIGNATION

GRAPHIC DESIGNATION, OR A COMBINATION OF BOTH. NOT ALL

PARTITIONS ON THIS SHEET MAY BE USED. REFER TO PARTITION TYPE

SCHEDULE ON THIS SHEET FOR PARTITIONS USED ON THIS PROJECT.

D. ALL DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD, OR TO FACE

OF BLOCK. REFER TO PARTITION TYPES FOR PARTITION WIDTH

DIMENSIONS.

E. ALL WALLS TO BE 16" O.C. UNLESS OTHERWISE NOTED.

F. REFER TO SPECIFICATIONS AND TO TABLE ON THIS SHEET FOR MINIMUM

STUD GAUGE, MAXIMUM SPACING AND ALLOWABLE LIMITING HEIGHT

DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES AND REQUIRED

FINISHES. FOR WALLS WHERE STUDS ARE ATTACHED TO STRUCTURE

ABOVE, PROVIDE CROSS BRACING AS NECESSARY MEETING THE CRITERIA

INDICATED TO ACCOMMODATE THE SPECIFIED DEFLECTION CRITERIA OF

THE WALL.

G. ALL INTERIOR NON-BEARING STUDS TO BE DESIGNED FOR A DEFLECTION

EQUAL TO BUT NOT GREATER THAN L/240, UNLESS FULL HEIGHT FINISH IS

DETERMINED TO BE FRAGILE OR BRITTLE, THEN DEFLECTION TO BE L/360.

EXAMPLES OF FRAGILE FINISHES WOULD INCLUDE BUT NOT LIMITED TO

ANY TYPE OF WALL TILE, PLASTER OR PLASTER SKIM COAT.

H. ALTHOUGH WALL STUD SIZES ARE LISTED ON PLANS, IN AREAS WHERE

STUDS ARE TO STRUCTURE ABOVE OR HIGH AREAS, CONTRACTOR TO

VERIFY SIZE INDICATED IS ADEQUATE FOR HEIGHT LISTED. PROVIDE

ADEQUATE SIZE STEEL STUD FRAMING AND NOTIFY ARCHITECT OF ANY

DISCREPANCY PRIOR TO FABRICATION OR INSTALLATION.

I. KING STUDS AT DOOR FRAMES TO BE 18 GA. UNLESS OTHERWISE NOTED.

J. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD FOR ALL OTHER WALL

CONSTRUCTION, UNLESS OTHERWISE NOTED.

K. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD IN BULKHEAD CONSTRUCTION.

L. REFER TO LIFE SAFETY PLANS FOR LOCATIONS AND RATINGS OF SMOKE

AND FIRE RATED PARTITIONS. REFERENCE TEST NUMBERS APPLY ONLY TO

PARTITIONS INDICATED TO BE RATED.

M. FIRE RATING TEST NUMBERS ARE FOR UNDERWRITER'S LABORATORIES

(UL) ASSEMBLIES UNLESS OTHERWISE NOTED.

N. FIRE RESISTANT RATED PARTITIONS SHALL EXTEND TO THE INSIDE FACE

OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.

O. SEAL ALL OPENINGS, GAPS, PENETRATIONS, AND JOINTS IN PARTITIONS

TYPES AS FOLLOWS:

a. FIRE RATED PARTITIONS: SEAL IN ACCORDANCE WITH THE

REQUIREMENTS SPECIFIED FOR THROUGH PENETRATION

FIRESTOP SYSTEMS AND FIRE RESISTIVE JOINT SYSTEMS.

b. SMOKE TIGHT PARTITIONS: SEAL COMPLETELY WITH

ELASTOMERIC SEALANT. FOR THE LOCATION AND EXTENT OF

PARTITIONS, DESIGNATED AS "SMOKE TIGHT", REFER TO THE LIFE

SAFETY DRAWINGS.

c. ALL OTHER LOCATIONS: SEAL AS INDICATED AND REQUIRED

ELSEWHERE BY THE CONTRACT DOCUMENTS.

P. INSULATION HEAD CONDITIONS AT FLOOR / ROOF DECK:

a. FIRE RESISTANT RATED PARTITIONS SHALL USE MINERAL WOOL

INSULATION AND APPROPRIATE FIRE RATED SEALANT.

b. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL

USE SOUND ATTENUATION BATTS (SAB).

Q. PROVIDE STENCILED IDENTIFICATION FOR RATED PARTITIONS.

R. STC RATING APPLIES WHERE PARTION TAG QUALIFIER INDICATES WITH AN

"i". PROVIDE SOUND ATTENUATION BATTS OF THICKNESS INDICATED ON

SCHEDULE WHERE INDICATED BY QUALIFIER.

S. FOR PARTITIONS WITH STC RATINGS INDICATED SOUND ATTENUATION

BATTS TO EXTEND FULL HEIGHT OF PARTITION UNLESS OTHERWISE

NOTED. FLOOR TRACK TO BE SET IN A CONTINUOUS BED OF SEALANT.

T. WHERE PARTITION TYPE INDICATES SOUND ACOUSTICAL BATT, WITH FINISH

BOARD GOING TO DECK ON ONE SIDE ONLY, PROVIDE VAPOR BARRIER TO

SECURE INSULATION IN PLACE.

U. PROVIDE 5/8" MOISTURE/MOLD RESISTANT GYPSUM BOARD IN ALL WET

LOCATIONS WITHIN SCOPE OF WORK.

V. PROVIDE 5/8" CEMENTITIOUS BACKER BOARD BEHIND CERAMIC WALL TILE.

COORDINATE LOCATIONS WITH FINISH WALL PLANS.

W. PROVIDE CORNER AND END WALL FRAMING AS DETAILED ON 3/AE002.

WALL TYPES LEGEND AND GENERAL NOTES

X#X.#

INDICATES STRUCTURAL MATERIAL

CH = SHAFT WALL

F = FURRING

S = STEEL

M = MASONRY

W = WOOD

INDICATES NOMINAL SIZE

INDICATES STRUCTURE AND

FINISH HEIGHTS

QUALIFIER'S (X-X-X)

G GYPSUM BOARD FINISH

1SB 1 HR RATED SMOKE BARRIER

2SB 2 HR RATED SMOKE BARRIER

1F 1 HR FIRE RATED

2F 2 HR FIRE RATED

i SOUND INSULATION t THERMAL INSULATION

B BULLET RESISTANT

L LEAD LINED

M MESH (STEEL SECURITY MESH)

MR MOIST/MOLD RESISTANT GYPSUM

SP SMOKE PARTITION

TB TILE BACKER CEMENT BOARD

A = STRUCTURE TO DECK, FINISH TO DECK

B = STRUCTURE TO DECK, FINISH ONE SIDE TO DECK

C = STRUCTURE TO DECK, FINISH TO ABOVE CEILING

D = STRUCTURE TO ABOVE CEILING, FINISH TO ABOVE CEILING

P = PARTIAL HEIGHT WALL

U = STRUCTURE TO UNDERSIDE OF CELING, FINISH TO UNDERSIDE OF CEILING

*SEE WALL TYPES FOR PROJECT SPECIFIC CONSTRUCTION

CH

2 1/2" 4" 6"

F 7/8

1 1/2" 2 1/2" 3 5/8"

4" 6" 8" 12"

S

2 1/2" 3 5/8"

4" 6" 8" 12"

M

2 5/8" 3 5/8" 5 5/8" 7 5/8" 11 5/8"

W

3/4"

3 1/2"

5 1/2" 7 1/4" 11 1/4"

" 1 HR FIRE/SMOKE

10'-0" MAX 10'-0" MAX

A. LETTERED STENCILS SHALL BE APPLIED TO EACH SIDE OF RATED PARTITIONS

AT 10'-0" INTERVALS; BUT NO LESS THAN ONCE PER PARTITION LENGTH.

B. USE THE FOLLOWING LANGUAGE FOR STENCILS:

"1 HR FIRE/SMOKE" "1 HR FIRE"

"2 HR FIRE/SMOKE" "2 HR FIRE"

"LIMIT TRANSFER OF SMOKE"

PERMANENT RED PAINT

LETTERING, TYP.

CEILING LINE

STENCILING NOTES

WALL TAG LEGEND

S2C.G 2 1/2"

WALL TAG

STRUCTURAL

SIZE

FINISH DIM FIRE RATING UL DESIGN

MIN STC

RATING

3 3/4" NA NA NA

COMMENTS

S3C.G 3 5/8" 4 7/8"

NA

NANANANA

S6C.GiMR 6" 7 1/4" NANANANA

LINE OF STRUCTURE ABOVE

LINE OF CEILING

LINE OF STRUCTURE BELOW

PLAN

5/8"

STRUCTURAL SIZE

5/8"

FINISH DIMENSION

STEEL STUD BRACING @ 4'-0" O.C.

CEILING

6"

5/8" TYPE X GYP BD

BEAD OF CONT. SEALANT

STEEL STUDS @ 16" O.C.

INSULATION PRESENT WITH QUALIFER (i OR t)

F2D.G 2 1/2"

WALL TAG

STRUCTURAL

SIZE

FINISH DIM FIRE RATING UL DESIGN

MIN STC

RATING

3 1/8" NA NA NA

COMMENTS

F3D.G 3 5/8" 4 1/4"

NA

NANANANA

F6D.G 6" 6 5/8" NANANANA

LINE OF STRUCTURE ABOVE

LINE OF CEILING

LINE OF STRUCTURE BELOW

PLAN

STRUCTURAL DIMENSION

5/8"

FINISH DIMENSION

STEEL STUD BRACING @ 4'-0" O.C.

CEILING

6"

5/8" TYPE X GYP BD

BEAD OF CONT. SEALANT

STEEL STUDS @ 16" O.C.

INSULATION PRESENT WITH QUALIFER (i OR t)

EXISTING WALL / COLUMN, VIF.

F0D.G 7/8" 1 1/2" NA NA NA

F1D.GiMR 1 1/2" 2 1/8"

HAT CHANNEL @ 24" O.C.

NANANA HAT CHANNEL @ 24" O.C.

WALL TYPES

CH2A.2F 2 1/2"

WALL TAG

STRUCTURAL

SIZE

FINISH DIM FIRE RATING UL DESIGN

MIN STC

RATING

3 3/4" 2 HR. U415 37

COMMENTS

CH4A.2Fi 4" 5 1/4"

NA

NA48U4152 HR.

CH6A.2F 6" 7 1/4" NA48U4152 HR.

LINE OF STRUCTURE ABOVE

LINE OF CEILING

LINE OF STRUCTURE BELOW

PLAN

STRUCTURAL SIZE

1 1/4"

FINISH DIMENSION

5/8" TYPE X GYP BD (2 LAYERS)

BEAD OF CONT. SEALANT

CH STEEL STUDS @ 24" O.C.

CEILING

DEEP LEG SLIP TRACK AT DECK

HOLD GYPSUM BACK FROM DECK FOR

DEFLECTION

FILL FLUTES OF DECK WITH FIRE SAFING

AT FIRE RATED WALLS

1" TYPE C GYP LINER PANEL

1"

INSULATION PRESENT WITH QUALIFER (i OR t)

WALL TAG

STRUCTURAL

SIZE

FINISH DIM FIRE RATING UL DESIGN

MIN STC

RATING

COMMENTS

S3A.1Fi 3 5/8" 4 7/8" NA40U4651 HR.

S6A.1Fi 6" 7 1/4" NA40U4651 HR.

LINE OF STRUCTURE ABOVE

LINE OF CEILING

LINE OF STRUCTURE BELOW

PLAN

5/8"

STRUCTURAL SIZE

5/8"

FINISH DIMENSION

5/8" TYPE X GYP BD

BEAD OF CONT. SEALANT

STEEL STUDS @ 16" O.C.

STEEL STUD BRACING @ 4'-0" O.C.

CEILING

DEEP LEG SLIP TRACK AT DECK

HOLD GYPSUM BACK FROM DECK FOR

DEFLECTION

FILL FLUTES OF DECK WITH FIRE SAFING

AT FIRE RATED WALLS

INSULATION PRESENT WITH QUALIFER (i OR t)

F2D.GiMR 2 1/2" 3 1/8" NA NA NA NA

WALL TAG

STRUCTURAL

SIZE

FINISH DIM FIRE RATING UL DESIGN

MIN STC

RATING

COMMENTS

S3A.2F 3 5/8" 6 1/8" NA40U4192 HR.

S6A.2F 6" 8 1/2" NA40U4192 HR.

LINE OF STRUCTURE ABOVE

LINE OF CEILING

LINE OF STRUCTURE BELOW

PLAN

1 1/4"

STRUCTURAL SIZE

1 1/4"

FINISH DIMENSION

5/8" TYPE X GYP BD (2 LAYERS EACH SIDE)

BEAD OF CONT. SEALANT

STEEL STUDS @ 16" O.C.

STEEL STUD BRACING @ 4'-0" O.C.

CEILING

DEEP LEG SLIP TRACK AT DECK

HOLD GYPSUM BACK FROM DECK FOR

DEFLECTION

FILL FLUTES OF DECK WITH FIRE SAFING

AT FIRE RATED WALLS

INSULATION PRESENT WITH QUALIFER (i OR t)

NOTE:

• TYPICAL LIMITING HEIGHTS-INTERIOR PARTITIONS, L/240 (5 PSF), WITH 5/8"GYPSUM BOARD EACH SIDE.

• PROVIDE DIAGONAL STUD BRACING AT ALL NON FULL HEIGHT INTERIOR PARTITIONS STAGGERED AT 48" O.C. TO DECK ABOVE. PROVIDE

STUD ATTACHMENT TO DECK W/ MIN. SPAN OF 2 DECK FLUTES. BRACING TO BE THE SAME SIZE AND GAUGE AS VERTICAL STUDS.

25 GA. STUDS (NON-COMPOSITE)

STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT

16" L/240 6'-11"1-5/8"

24" L/240 6'-0"162S125-18

16" L/240 9'-6"2-1/2"

24" L/240 8'-4"250S125-18

16" L/240 12'-5"3-5/8"

24" L/240 10'-10"362S125-18

16" L/240 13'-9"4"

24" L/240 12'-0"400S125-18

22 GA. STUDS (NON-COMPOSITE)

STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT

16" L/240 8'-1"1-5/8"

24" L/240 7'-1"162S125-27

16" L/240 11'-2"2-1/2"

24" L/240 9'-9"250S125-27

16" L/240 14'-6"3-5/8"

24" L/240 12'-8"362S125-27

16" L/240 16'-1"4"

24" L/240 14'-0"400S125-27

20 GA. STUDS (NON-COMPOSITE)

STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT

16" L/240 8'-4"1-5/8"

24" L/240 7'-3"162S125-30

16" L/240 11'-7"2-1/2"

24" L/240 10'-1"250S125-30

16" L/240 15'-0"3-5/8"

24" L/240 13'-1"362S125-30

16" L/240 16'-8"4"

24" L/240 14'-7"400S125-30

16" L/240 22'-4"6"

24" L/240 19'-6"600S125-27

16" L/240 23'-1"6"

24" L/240 20'-2"600S125-30

18 GA. STUDS (NON-COMPOSITE)

STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT

16" L/240 13'-0"2-1/2"

24" L/240 11'-5"250S125-43

16" L/240 17'-5"3-5/8"

24" L/240 15'-3"362S125-43

16" L/240 18'-10"4"

24" L/240 16'-5"400S125-43

16" L/240 26'-1"6"

24" L/240 22'-10"600S125-43

SSMA NON-COMPOSITE STUDS

HIGH PRIORITY PARTITION

LOWER PRIORITY PARTITION

HIGH PRIORITY CEILING /

ROOF ASSEMBLY

LOWER PRIORITY PARTITION

RATING

3 HOUR ASSEMBLY

2 HOUR ASSEMBLY

1 HOUR ASSEMBLY

SMOKE-RATED ASSEMBLY

NON-RATED ASSEMBLY

PRIORITY

NOTE: LOWER NUMBER, HIGHER PRIORITY

TOP OF METAL DECK OR CONCRETE

FIRE CAULKING AS REQUIRED BY UL# HWS0001

(BY FRAMING CONTRACTOR)

PACK FLUTES OF DECK WITH FIRE SAFING AS

REQUIRED PER UL# HWS0001

Z-CLIPS 2" WIDTH

BOTTOM OF METAL DECK

LIGHT GAUGE FRAMING DEFLECTION TRAK,

CONFORMING TO UL# HW-D-0060

5/8" TYPE X GYP. BD. EACH SIDE OF STUD

SCRIBED TO DECK UL# U465

METAL STUD

PARALLEL NOTE:

NON-RATED CONSTRUCTION SIMILAR W/O

FIRE SAFING & SCRIBING BYP. BD. TO DECK

6"

TOP OF METAL DECK OR CONCRETE

FIRE CAULKING AS REQUIRED BY UL# HWS0001

(BY FRAMING CONTRACTOR)

PACK FLUTES OF DECK WITH FIRE SAFING AS

REQUIRED PER UL# HWS0001

Z-CLIPS 2" WIDTH

BOTTOM OF METAL DECK

LIGHT GAUGE FRAMING DEFLECTION TRAK,

CONFORMING TO UL# HW-D-0060

5/8" TYPE X GYP. BD. EACH SIDE OF STUD

SCRIBED TO DECK UL# U465

METAL STUD

PERPENDICULAR NOTE:

NON-RATED CONSTRUCTION SIMILAR W/O

FIRE SAFING & SCRIBING BYP. BD. TO DECK

INSULATION STUFFED INSIDE BOX

METAL STUD FRAMING

CORNER BEAD AT ALL

OUTSIDE CORNERS (TYPICAL)

20 GA. METAL STUDS WRAPPED WITH

20 GA. TRACK ON BOTH SIDES,

CONTINUOUS FROM FLOOR TO DECK

INSULATION STUFFED INSIDE BOX

METAL STUD FRAMING

CORNER BEAD AT ALL

OUTSIDE CORNERS (TYPICAL)

20 GA. METAL STUDS WRAPPED WITH

20 GA. TRACK ON BOTH SIDES,

CONTINUOUS FROM FLOOR TO DECK

3 HR FIRE RATED

2 HR FIRE RATED

1 HR FIRE RATED

1 HR SMOKE BARRIER

SMOKE PARTITION

2 HR SMOKE BARRIER

3 HR SMOKE BARRIER

WALL RATING LEGEND

LINE OF STRUCTURE BELOW

PLAN

5/8" 6" 5/8"

FINISH DIMENSION

5/8" TYPE X GYP BD

BEAD OF CONT. SEALANT

6" STEEL STUDS @ 16" O.C.

INSULATION PRESENT WITH QUALIFIER (i OR t)

4'

A F

F

5/8" TYPE X GYP BD

STEEL STUD RUNNER

STEEL STUD RUNNER

PROVIDE WALL FINISH ON

TOP OF PARTITION

3 X 3 X 1/4" TUBE STEEL. MOUNT TO FLR

W/ LIGHT GAUGE STEEL ANGLE. ATTACH

STEEL STUDS TO TUBE STEEL FOR WALL

STABILIZATION.

LIGHT GUAGE STEEL ANGLE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

NOT F

OR

CONSTRUCTIO

N

ARCHITECT/ENGINEER OF RECORD

CIVIL ENGINEER, ARCHITECT, STRUCTURAL ENGINEER FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER

A u to d e s k D o c s

/2

.9

V

A A tl a n ta

R e n o v a te

N F

S K it c h e n

F re e z e rs

G u id o n

-C h a rl o tt e

E n g in e e rs /2

.9

A v

.r v t

/3

/2

:4

:5

P

M

AE002

WALL TYPES Renovate NFS Kitchen & Freezers -

Guidon-Charlotte Engineers

SDVOSB JV LLC

DECATUR, GA

508-22-102

BUILDING C

02/03/2025 AO TA

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLEREDGUIDON - CHARLOTTE ENGINEERS SDVOSB JV LLC

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

SCALE: 1 1/2" = 1'-0"AE002

1 RATED WALL PRIORITY

SCALE: 1 1/2" = 1'-0"AE002

2 DEFLECTION TRACK

WALL TYPE SCHEDULE

WALL TYPES USED IN THIS PROJECT

CH4A.2Fi

F1D.GIMR

F2D.GiMR

F3D.G

S3A.2F

S3C.G

S6A.1Fi

S6C.GiMR

SCALE: 3" = 1'-0"AE002

3 TYPICAL CORNER FRAMING DETAIL

SCALE: 1 1/2" = 1'-0"AE002

4 PARTIAL HEIGHT WALL SECTION

Revisions: Date:

Sheets
AE002 - WALL TYPES