lattner instruction manual space saver july 2020.pdf
PDF 924 KB Posted
- Solicitation number
- 36C24724Q0633
About this file
This document is an Installation, Maintenance, and Service Instruction Manual for a Space Saver Electric Hot Water Boiler. It provides general information about the boiler, including its application, vessel, insulation, elements, and enclosure. The manual covers the controls, installation, startup instructions, maintenance procedures, and troubleshooting guidance. It also includes a limited warranty and standard terms and conditions.
The key details are:
- The boiler is UL listed, ASME Code Section IV "H" stamped, and National Board registered.
- It has a 160 psig and 250°F rating, with a 4" fiberglass blanket insulation.
- Controls include fuses, contactors, transformer, low water cutoff, operating controller, high temperature cutout, and control circuit switch.
- Installation requires following minimum clearances, piping the relief valve to a drain, and providing an expansion tank and circulating pump.
- Startup procedures include checking installation, piping, wiring, and control settings.
- Maintenance involves periodic checks of controls, safety devices, and pressure relief valve, as well as annual element inspection and replacement if needed.
- The warranty covers defects in material and workmanship for one year from shipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 41-M0.1- Gas Boiler.pdf | ||
| Mechanical-Heart Station.pdf | ||
| Mechanical-ORs.pdf | ||
| Mechanical- Dental.pdf | ||
| Mechanical-Ambulatory Clinic.pdf | ||
| Mechanical- Sterile Processing.pdf | ||
| AC6B-Heart Station AHU.pdf | ||
| Futera Fusion 750 Interactive Submittal Data Sheet SFTF 750 7_1.pdf | ||
| 36C24724Q0633_3.docx | DOCX document | |
| 49-M4.1-Gas boiler.pdf | ||
| Mechanical- Pharmacy.pdf | ||
| Updated Attachment A _ Revised May 27 2024.pdf | ||
| 36C24724Q0633_2.docx | DOCX document | |
| STATEMENT OF WORK.pdf | ||
| SCHEDULE.docx | DOCX document | |
| Site Visit Map.pdf | ||
| Wage Determination No 2015-4591 Rev 25.pdf | ||
| 36C24724Q0633_1.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INSTALLATION,
MAINTENANCE, AND
SERVICE INSTRUCTION
MANUAL
SPACE SAVER
ELECTRIC HOT WATER
BOILERS
General Information ….....………………………….Page 1 Typical Piping and Dimensions ............................Page 2 Controls and Installation .......................................Page 3 Start Up Instructions and Forms........................... Page 4 Maintenance ........................................................ Page 7 Troubleshooting ................................................... Page 8 Warranty .............................................................. Page 9 Terms & Conditions ............................................. Page 10
INDEX
GENERAL INFORMATION
Application UL Listed under File No. E30432 to 600 volts and 120 KW as primary heat source, secondary heat source, or as standby heat source for solar, hydronic, and water source heat pump systems.
Vessel ASME Code, Section IV “H” stamped, National Board registered, rated to 160 psig and 250 degrees Fahrenheit.
Insulation 4” fiberglass blanket on vessel.
Elements Incoloy sheathed, 75 watts per inch, mounted in 150 pound ASA steel flange, individually removable.
Enclosure Ventilated integral control panel constructed of heavy gauge steel contains line terminals, fuses, contactor(s), temperature controller, and safety high limit devices. All surfaces are phosphatized and protected against corrosion with factory applied finish.
Typical Boiler Piping Diagram
SPACE SAVER
BOILER
CONTROLS
Controls – All basic controls and terminals are located in an integral ventilated control cabinet, factory wired and functionally tested. Controls include Class K fuses with 50,000 ampere interrupting capacity, magnetic contactors UL Listed for 100,000 cycles, 120V control transformer with primary fuses, low water cutoff, operating controller, automatic reset high temperature cutout, and control circuit lighted switch.
Low Water Cutoff – In the event of a low water condition, low water cutoff interrupts control circuit to protect elements from damage caused by overheating.
Automatic Reset High Temperature Cutout(s)
– De-energizes control circuit in the event of a high temperature condition.
Control Circuit Lighted Switch – De-energizes control circuit (not main power).
Operating Controller – Maintains water temperature at predetermined setting.
Pressure Relief Valve – Vents pressure to atmosphere in the even of high pressure in excess of relief valve setting.
Pressure/Temperature Gauge – Combination gauge provides visual indication of water temperature and pressure. Mounted on outlet pipe.
Optional Accessories – Optional built-in or remote accessories may be included as called for in job specifications. Instructions covering adjustments and servicing of these accessories are supplied with the unit.
INSTALLATION
1. Install drain valve furnished with boiler.
2. Set boiler in position to conform to local codes. Minimum clearances: Front – 6 inches to door or 3 feet to wall; back – 1 inch; left side – 1 inch; right side – 10 inches. A minimum distance of 34 inches must be maintained above the boiler for element removal.
3. Suitable for closet installation. Subject to minimum spacing requirements shown below.
Closet door must be vented at the top and bottom of the door with 24 by 12 inch openings.
4. Be certain unit is installed on a level, non-combustible surface.
5.5. Connect the supply and return piping
according to applicable codes. Pipe relief valve discharge to nearest floor drain or downward, away from any potential hazard to other equipment or personnel.
6.6. Boiler feed connection may be tee’d into
return connection.
7.7. Electrical knockouts are provided for wiring
access. All wiring must conform to applicable codes and conductors cannot be smaller than sixes listed on wiring diagrams located inside the control panel door.
8.8. Provide expansion tank and circulating pump
for boiler piping system; install to conform to applicable codes. Installation of flow switch is recommended. Connect vent tube to (top of vessel) to expansion tank.
START‐UP FORM FOR LATTNER ELECTRIC HOT WATER BOILER
Job __________________________________ Date _____________________________
Location ______________________________ Serial No. _________________________
______________________________ Model No. ________________________
______________________________ NB # _____________________________
Contact _______________________________ Phone ____________________________
Fax _______________________________
Please check to verify the following.
1. ___ Disconnect power to boiler and controls per lockout/tag out procedure.
2. ___ Verify incoming service breaker size and ground.
3. ___ Review installation, operation manual provided for boiler.
4. ___ Check installation:
a. ___ Piping service
b. ___ Wiring completed
5. ___ Check piping:
a. ___ Water makeup
b. ___ Bottom drain closed
c. ___ Inlet valve open
d. ___ Safety valve outlet piping
e. ___ Safety valve set pressure _____ psi
f. ___ Water outlet
g. ___ City water makeup open
6. ___ Open softener bypass valve for initial fill with city water.
7. ___ Tighten all wiring connections.
8. See page 6.
9. ___ Review wiring diagram. Note remote interlock terminals with jumpers.
10. ___ With the boiler switch “OFF” energize the main disconnect. (optional)
11. ___ Verify incoming voltage is correct.
12. ___ Press the manual reset on the high pressure switch.
13. ___ Press the manual reset on the low water cutoff (6 seconds).
14. ___ Set operating control to desired operating temperature.
15. ___ Set automatic reset high temperature limit to 10o F higher than operating temperature.
16. ___ Set manual reset high temperature limit to 5o F higher than automatic high temperature limit.
17. ___ Set 2nd stage control or progressive sequencer (if applicable). ___ time delay = ___ sec. (verify dip sw’s)
18. ___ Energize power and control circuits.
19. ___ Verify amber safety circuit light is “ON.” (all safeties proven)
20. ___ check all fitting for leaks. Tighten/repair as needed.
21. ___ Test high temperature limit switch and reset
22. ___ Test low water cutoff using test switch and reset
23. ___ Operating pressure ____ min. ____max.
24. ___ Instruct owner/operator to check temperature, pressure and number of operating stages for three (3) days of operation.
25. ___ Instruct owner/operator to disconnect power and recheck all power terminals for tightness after 30 days of operation.
26. ___ Flow switch test (hot water only)
27. ___ Observe unit for proper operation. Keep log of procedure and performance.
NOTES:______________________________________________________________
Startup Technician Owner’s Approval Signature
Tele. No. ___________________ Print Name _______________________
Company ________________________
Date ____________________________
WARRANTY VALIDATION & BOILER START UP REPORT
Start-up information must be verified for each boiler returned to Lattner Boiler Manufacturing Co. P.O. box 1527 cedar rapids, IA 52406 for warranty validation. If this information is not returned, warranty consideration may not be extended.
8. ___ POWER OFF. Check the OHMS of resistance on each leg of each circuit at the contactor.
Circuit #1 Circuit #2 Circuit #3 Circuit #4 Circuit #5 Circuit #6 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #7 Circuit #8 Circuit #9 Circuit #10 Circuit #11 Circuit #12 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #13 Circuit #14 Circuit #15 Circuit #16 Circuit #17 Circuit #18 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #19 Circuit #20 Circuit #21 Circuit #22 Circuit #23 Circuit #24 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #25 Circuit #26 Circuit #27 Circuit #28 Circuit #29 Circuit #30 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3
Circuit #31 Circuit #32 Circuit #33 Circuit #34 Circuit #35 Circuit #36 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #37 Circuit #38 Circuit #39 Circuit #40 Circuit #41 Circuit #42 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #43 Circuit #44 Circuit #45 Circuit #46 Circuit #47 Circuit #48 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #49 Circuit #50 Circuit #51 Circuit #52 Circuit #53 Circuit #54 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 Circuit #55 Circuit #56 Circuit #57 Circuit #58 Circuit #59 Circuit #60 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T2 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T1 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3 T2 to T3
MAINTENANCE
A periodic check of all control components will ensure proper operation.
1. Check wiring and terminations for tightness.
2. Check all controls and safety devises for proper operation.
3. Check pressure relief valve to ensure that it is not leaking and that no corrosion exists.
4. Check circulator pump and lubricate according to manufacturer’s instructions.
At least once a year, boiler elements should be checked.
1. Disconnect all power to boiler.
2. If a faulty open element is indicated, the element may be replaced in the following manner:
a. Isolate boiler from system by closing hand valves in supply and return piping.
b. Drain boiler completely of water.
c. Remove ALL wiring from the elements, tagging both the wires and element terminals.
d. Mark element flange position with respect to the vessel flange for proper alignment upon reinstallation; remove flange bolts.
e. Remove the element flange from the vessel.
f. Remove element retaining nut using a 11/16 socket wrench.
g. Remove ferrules (2 compressed rings) from the element ends and remove element from back side of flange.
h. Insert new element and ferrules and tighten element retaining nuts into flange.
i. Replace flange in boiler vessel using new gasket. Align previously made marks on flanges and install flange bolts, torqueing each bolt to 70 foot pounds (minimum).
j. Reconnect electrical wiring, making sure all wiring is connected to the proper element termination.
k. Refill boiler following procedure listed in INSTALLATION section.
l. Check elements and flanges for leaks.
m. Replace vessel enclosure cover.
n. Turn disconnect on.
SERVICE INSTRUCTIONS
Disconnect all sources of power before servicing unit. If it is necessary to replace a factory installed part, be sure to use Lattner replacement part. Replacement parts are available through authorized Lattner representatives or directly from the factory. When ordering replacement parts, always include the model and serial numbers.
LOCATING TROUBLE
Problem Possible Cause
1. Unit does not operate Disconnect or control circuit switched off, low water condition, high temperature condition, improper setting of operating control.
2. Water temperature too low Operating control set too low or not operating properly, oversized circulator pump, or faulty elements/fuses/contactors/wiring.
3. Water temperature is too high
Operating control is set too high or not operating properly, undersized circulator pump or not operating properly.
4. Water temperature correct but building is cold
Circulator pump not operating properly, air blocks in piping or radiation, control valve in supply or return piping not fully open.
5. Excess pressure causing relief valve to open
System head pressure exceeds relief valve setting or expansion tank water logged.
Lattner Boiler Company 1411 9th St. SW
Cedar Rapids, IA 52404 Telephone: (800) 345-1527
Fax: (319) 366-0770 Web: www.lattnerboiler.com
Form W01-17
LATTNER BOILER LIMITED WARRANTY
A Lattner boiler shell is guaranteed to be constructed in accordance with the ASME Code. An independent ASME boiler inspector inspects the construction of each boiler and: (1) checks mill test reports on all materials used to ensure that the chemical and physical analysis of such materials complies with the ASME Code; (2) inspects each boiler shell during construction to see that workmanship complies with the Code;
and (3) witnesses the final hydrostatic test and then places the ASME stamp on the boiler shell and signs an ASME data report certifying the boiler is ASME approved.
Lattner warrants the boiler and any other equipment of its manufacture to be free from defects in material and workmanship for one (1) year from the date of shipment from the factory, provided the boiler is operated under the normal use and service for which it was intended, and only if the boiler has been properly installed by a qualified technician in accordance with but not limited to ASME, ANSI, and NFPA Codes and applicable local, state, and national codes.
Lattner’s obligation under this Warranty is limited, at Lattner’s option, to replacing or repairing any defective part of the boiler or other equipment it manufactures. No allowance will be made for labor, transportation, or other charges incurred in the replacement or repair of defective parts. Merchandise not manufactured by the Company, supplied in one piece or in component assemblies, is not covered by the above warranty, but the Company will give the Purchaser the benefit of such adjustment as it can make with the manufacturer of such items.
Lattner shall not be liable for special, indirect, or consequential damages. Lattner shall not be liable for any loss or damage resulting, directly or indirectly, from the use or loss of use of the boiler. This exclusion from liability includes the Purchaser’s expenses for downtime or for making up downtime, damages for which the Purchaser may be liable to other persons, or damages to property.
The remedies set forth in this Warranty are exclusive, and the liability of Lattner with respect to any contract or sale shall not exceed the cost of repair or replacement of the boiler or other equipment manufactured by Lattner.
The above Warranty shall not apply to any boiler or other equipment manufactured by Lattner which:
1) has been repaired or altered without Lattner’s written consent;
2) has been altered in any way so as, in the judgment of Lattner, to adversely affect the stability or reliability of the boiler;
3) has been subject to improper water treatment, scale, corrosion, misuse, negligence, or accident;
4) has not been operated in accordance with Lattner’s printed instructions or specifications;
5) has been operated under conditions more severe than or otherwise exceeding those set forth in the specifications for such boiler; or
6) has not been properly installed by a qualified technical in accordance with but not limited to
ASME, ANSI and NFPA Codes and all applicable local, state and national codes.
THIS WARRANTY IS EXPRESSLY MADE IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED. LATTNER MAKES NO WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR ANY
PARTICULAR PURPOSE.
Purchaser must notify Lattner of a breach of Warranty within thirty (30) days after discovery thereof, but not later than the one-year guarantee period; otherwise, such claims shall be deemed waived. No allowance will be granted for any repairs or alterations made by Purchaser without Lattner’s prior verbal or written consent. Items returned to Lattner must be accompanied by a factory-supplied return goods authorization (RGA). Such authorization may be obtained by calling the factory at 319/366-0778 or by writing to P.O. Box 1527, Cedar Rapids, IA 52406.
Lattner neither assumes nor authorizes any person to assume for it any other liability in connection with the sale or use of the boiler or other equipment manufactured by Lattner, and there are no oral agreements or warranties collateral to or affecting this Agreement.
LATTNER BOILER COMPANY
Cedar Rapids, IA USA
TC17
STANDARD TERMS & CONDITIONS
LIMITATION ON QUOTATION
Unless otherwise stated in the quotation, the quotation will remain valid for a period of thirty (30) days from the date hereof, at which time it will automatically expire unless extended by a signed document issued by the Company, from its headquarters in Cedar Rapids, IA.
EQUIPMENT SELECTION
The Purchasers selection of sizes, types, capacities, and specifications and suitability thereof for the specific application shall be the unshared responsibility of the Purchaser or Purchaser’s representative or consultant.
PRICES
Unless defined otherwise in the quotation, prices are F.O.B. Cedar Rapids, IA – USA, exclusive of freight, storage, off-loading, installation, service, start-up, extended warranty or local delivery charges, if any.
TAXES
Purchaser shall be liable for all Federal, State, and local taxes with respect to the purchase of the equipment proposed, unless exclusively exempted from any taxes and proof thereof is on file with the Company.
PAYMENT
Purchaser shall pay with US funds, the full amount of the invoiced purchase price within thirty (30) days of the Company’s invoice, whether the equipment has shipped or has been delayed through no fault of the Company and subject to approved credit. Beginning thirty (30) days after the invoice date, Purchaser shall pay a late payment charge of two percent (2%) per month, which is an annual rate of 24%, on any unpaid portion of the purchase price. The Company reserves the right to revoke or modify these credit terms.
SHIPMENT
Any shipping date shown in the body of the quotation or order acknowledgement, represents the Company’s approximated schedule as of the date of the quotation, and is subject o change as determined by shop loading if and when this quotation should be realized as an actual sale. The Company shall no incur any liability of any kind for failure to ship on any particular date unless a firm shipping date has been expressly agreed to by an officer of the Company, in a separate written document.
CANCELLATION AND DELAYS
Subsequent to the receipt of Purchaser’s Purchase Order and the Company’s issued order acknowledgement, the Purchaser may not change nor cancel the order in whole or in part, without the written approval and acceptance by the Company of such cancellation or change. The price change to reflect the Company’s cost to implement the change, or to offset costs incurred by the Company in order preparation, engineering, purchasing, and or in actual production of the order in the event of a cancellation. In the event that Purchaser delays shipment of the equipment up the Company’s notice to ship, the equipment shall be place in storage at the Purchaser’s risk and expense, and transfer to storage shall occasion shipment and the order shall be invoice as if shipped.
RETURNS AND RESTOCKING
Equipment may be returned to Lattner at 1411 9th Street SW, Cedar Rapids, IA 52406, only upon prior written authorization of the Company. Consent, if given, will be upon the condition the purchaser assumes all carrier charges, responsibility for damages in transit, and a minimum 15% restocking charge, and the only if the so authorized material is in new and .unused condition and returned within one year from original date of shipment. The credit will be based on the original invoice price or the current price; whichever is lower, less the applicable restocking charge.
SECURITY INTEREST
For the purposes of securing payment, the Company may issue a lien on the equipment, following the invoice 30 days time, and until such time that payment has been received in full. Upon receipt of payment in full, the Company will rescind the lien.
FORCE MAJEURE
In no event shall the Company be liable for loss or damage resulting from any delay or failure to ship or other failure, loss or damage that is the proximate result of any act of government authority, revolution, riot, civil disorder, art of war, delay or default in transportation, inability to obtain materials or facilities from normal sources, fire, flood, act of God, or any cause not within the reasonable control of the Company. The Company may, without causing a breach or incurring liability, allocate goods which are in short supply irrespective of the reasons therefore among customers in any manner which the Company in its sole discretion deems advisable. If an event occurs that is beyond the control of the Company, and that even delays the Company’s performance and causes its cost of production to increase because of the delay, the Company may pass such increased cost(s) on to the Purchaser.
DAMAGE LIMITATION
Under no circumstance shall the Company be held liable for any loss of profits, down time, or any incidental or consequential damages of any kind with respect to its products or the transaction by which its products are sold.
WARRANTY AND PERFORMANCE
Products shall be warranted in accordance with the Company’s standard warranty statement, form No. W01 - 17.
The Company’s warranty shall be voiced by any abuse, misuse, neglect, unauthorized modification or service, lack of maintenance and service, or use not in accordance with the Company’s instructions. Warranty shall also be voided if water treatment has not been provided or by improper start-up of the equipment. The Company’s sole warranty statement and this paragraph contain the Company’s sole warranty and the Company makes no implied warranty, and there is no implied warranty of merchantability or fitness for any particular purpose.
SERVICE
Unless otherwise noted herein, the cost of the equipment does not include service or installation. All services performed by the Company are subject to purchaser’s payment of the Company’s prevailing charges plus necessary travel and living expenses.
Whenever service is quoted, please refer to Lattner’s Service Policy for specific details.
EXCLUSION OF OTHER TERMS
This constitutes an offer on behalf of Lattner Boiler Manufacturing (the Company); to sell the goods described in the quotation, exclusively on the terms and conditions stated. Acceptance of this by the Purchaser is hereby expressly limited to these Terms and Conditions and shall be applicable to any order issued by the Purchaser unless other terms have been agreed to in a written document issued by the Company.
GOVERNING LAW
The transaction with respect to the goods, which are subject hereof, shall be governed by the interpreted and construed in accordance with the laws of the State of Iowa. The Courts in the State of the Iowa. The Courts in the State of Iowa will have the sole jurisdiction over any claim arising under this contract of sale.
ASSIGNMENT
All sales as evidenced by the Company’s acknowledgement hall be binding up on and inure to the benefit of the Purchaser and the Company and their respective heirs, successors, or assigns.
LATTNER BOILER COMPANY
Cedar Rapids, IA USA