Futera Fusion 750 Interactive Submittal Data Sheet SFTF 750 7_1.pdf

PDF 209 KB Posted

Attached to
J045-- 521-24-3-5125-0022-HVAC & MEDICAL AIR/VACUUM SYSTEMS MAINTENANCE
Solicitation number
36C24724Q0633
Issued by

About this file

This document is a combined synopsis/solicitation for commercial services related to Heating, Ventilation, Air Conditioning (HVAC) & heating hot water heaters, compressed air, and medical air/vacuum systems preventative maintenance and repair at the Department of Veterans Affairs (VA) Birmingham Medical Center.

The solicitation is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) with a NAICS code of 238220. The service contract will consist of a base period and four one-year option periods. Responses are due by May 28, 2024 at 5:00 PM EST. The government will evaluate quotes based on technical capability, past performance, and price. A site visit is scheduled for May 14, 2024 and questions are due by May 17, 2024.

View the file

Other files

File Type Posted
41-M0.1- Gas Boiler.pdf PDF
Mechanical-Heart Station.pdf PDF
lattner instruction manual space saver july 2020.pdf PDF
Mechanical-ORs.pdf PDF
Mechanical- Dental.pdf PDF
Mechanical-Ambulatory Clinic.pdf PDF
Mechanical- Sterile Processing.pdf PDF
AC6B-Heart Station AHU.pdf PDF
36C24724Q0633_3.docx DOCX document
49-M4.1-Gas boiler.pdf PDF
Mechanical- Pharmacy.pdf PDF
Updated Attachment A _ Revised May 27 2024.pdf PDF
36C24724Q0633_2.docx DOCX document
STATEMENT OF WORK.pdf PDF
SCHEDULE.docx DOCX document
Site Visit Map.pdf PDF
Wage Determination No 2015-4591 Rev 25.pdf PDF
36C24724Q0633_1.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

FUTERA FUSION 750

Category II or IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.

Westfield, MA 01085

(413) 568-9571

SFTF-750-7

SIDE VIEW

TOP VIEW

BACK VIEW

CENTER OF

GRAVITY

CENTER OF

GRAVITY

Ø8 AIR INTAKE

2 NPT

WATER INLET

CIRCULATOR

PUMP

DIVERTER

VALVE 1 NPT

NG GAS INLET

Ø7 CAT. II/IV

FLUE OUTLET

CONDENSATE DRAIN 1/2 NPT

CONDENSATE DRAIN

OUTLET

2 NPT

WATER OUTLET

12 1/2 [318]

25 1/8 [638]

26 15/16 [684]

51 1/8 [1299]

[1499]

25 13/16 [656]

54 15/16 [1396]

29 3/8 [745]

45 11/16 [1160]

26 1/8 [664]

7 1/8 [181]

33 7/16 [849]

46 13/16 [1188]

7 1/8 [181]

15 13/16 [402]

16 7/8 [429]

9 1/2 [241]

16 3/8 [415]

4 5/8 [117]

12 9/16 [319]

18 5/8 [473]

4X � .4375 [11]

4X3/4 [19]

[508]

[281]

[281]

2 1/2 [64]

BOTTOM VIEW

NOTES:

1.) SYMBOL INDICATES CENTER OF GRAVITY

2.) DIMENSIONS ARE NOMINAL AND SUBJECT TO

MANUFACTURING VARIATION AND SHOULD NOT

BE USED FOR "ROUGH IN".

3.) ALL DIMENSIONS ARE INCHES[MM].

BOILER CERTIFIED RATINGS & CAPACITIES

Fuel Type Natural/Propane Gas Total FLA 9.2*

Input BTU/hr. 750,000 / 220 kW Min. Gas Pressure Required 2" W.C.**

Output BTU/hr. 713,250 / 209 kW Max. Gas Pressure Allowed 14" W.C.

Electrical Requirements (L1, NEU, GND) Operating Weight 793 lbs. / 360 kg.

120 VAC / 1 ph / 60 hz

BOILER / WATER HEATER TRIM & CONTROLS

Main Gas Valve Dungs MBC-SE Air Switch Cleveland NS2

Firing Valve 1” Blower Motor Fasco 1/2 hp

Ignition Control Honeywell RM7895C Relief Valve - CW 3/4" x 3/4" set @ 125 psi

Operating Control HeatNet® Relief Valve - CB 3/4" x 3/4" set @ 50 psi

High Limit Jumo Flow Switch TACO

Main Ball Valve 1" Pilot Regulator White-Rodgers 25m

Economizer RBI-1000 Circulator B&G PL-130 - FLA - 5

Mixing Valve 2" By-Pass Piping 2"

A.S.M.E.

ASME Sect IV Htg Surface 97.79 Sq. Ft. / 9.08 Sq. M. Design Data Max. 125 psig & 250°F

Water Volume 3.7 gal. / 14.01 Liters

Water Volume Secondary HX 4.5 gal. / 17.03 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP

20°F / 11.1°C 25°F / 13.9°C

Flow Rate*** Total Loss**** Flow Rate*** Total Loss****

GPM L/s Ft kPa GPM L/s Ft kPa

65.3 4.1 10.5 31.4 52.2 3.3 7.7 23.0

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)

40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

2,168 8,194 1,445 5,462 1,084 4,097 867 3,277 723 2,731 619 2,341

Notes:

1. Dimensions are approximate and should not be used to "rough-in" equipment.

2. Dimensions are subject to change without notice.

* Includes pump ** For incoming gas pressures lower than 2" W.C. natural or propane, consult factory.

RSUB-97 REV H

*** Primary heat exchanger.

**** Includes primary, secondary, mixing valve and piping.

CODE OPTIONS

CSD-1 Manual Reset LWCO

INDOOR UNIT

FUTERA FUSION 750

OUTDOOR UNIT

CENTER OF

GRAVITY

56 1/2 [1435]

13 1/16 [332]

26 3/16 [664]

30 7/8 [784]

CENTER OF

GRAVITY

2 3/16 [56]

[1499]

[25]

61 7/16 [1560]

57 3/16 [1452]

39 15/16 [1015]

28 1/16 [713]

69 11/16 [1771]

2 NPT

WATER OUTLET

Ø7 [179]

VENT ASSEMBLY

1 NPT

NG GAS INLET

2 NPT

WATER INLET

16 3/8 [415]

12 9/16 [319]

9 1/2 [241]

4 5/8 [117]

33 7/16 [849]

21 1/16 [535]

7 3/8 [187]

45 11/16 [1160]

77 5/16 [1964]

25 5/8 [651]

60 3/16 [1528]

FRONT VIEW

SIDE VIEW

REAR VIEW

TOP VIEW

BOTTOM VIEW

[279]

[279]

4X 3/4 [19]

4X � .4375 [11]

2 1/2 [64]

[508]

NOTES:

1.) SYMBOL INDICATES CENTER OF GRAVITY

2.) DIMENSIONS ARE NOMINAL AND SUBJECT TO

MANUFACTURING VARIATION AND SHOULD NOT

BE USED FOR "ROUGH IN".

3.) ALL DIMENSIONS ARE INCHES[MM].

RSUB-123 REV D

Notes:

1. Dimensions are approximate and should not be used to "rough-in" equipment.

2. Dimensions are subject to change without notice.

Text8:
Text9:
Text10:
Text11:
Text12:
Text13:
Text14: