659-22-405 M-801-Blt 2.pdf

PDF 290 KB Posted

Attached to
Y1DZ--659-22-405 | Install Campus Generator | Salisbury VAMC
Solicitation number
36C24626B0011
Issued by

About this file

This document is a mechanical schedules drawing (M-801) for a Campus Generator Project at the VA Salisbury Station in Salisbury, North Carolina. The project, issued by the U.S. Department of Veterans Affairs Office of Construction and Facilities Management, contains detailed equipment specifications and requirements for a three-generator emergency power system with associated mechanical infrastructure.

The schedules specify multiple categories of equipment including three Greenheck rooftop downblast exhaust fans (EF-1, EF-2 rated at 2,500 CFM each, and EF-3 at 1,300 CFM), fuel oil pumping systems with Highland Tank fuel oil storage tanks (FOT-1 and FOT-2 at 20,000 gallons each), air control dampers from Greenheck for intake, exhaust, and recirculation functions across all three generators, and exhaust mufflers from Nett (NTHP-T1-R22 model) rated for hospital-grade sound attenuation at 65 dBA at 176 feet property line. Additional mechanical systems include split air conditioning units (IDU/ODU pairs), electric unit heaters (Modine HER50 and VE50 models), duct silencers from Vibro Acoustics designed to ASTM E477-20 standards, fuel oil day tanks with integral pumps (290-gallon capacity at 900 GPH), air filters (Camfill Farr MERV 8), and air distribution grilles. All equipment is specified with detailed operational parameters including CFM ratings, pressure drops, electrical requirements (predominantly 208/3/60V and 208/1/60V), and mounting specifications. The document includes professional engineer stamped calculations required for acoustical and pressure drop verification, with the contractor responsible for ensuring noise control solutions meet specified criteria.

View the file

Other files

File Type Posted
36C24626B0011 0003.docx DOCX document
01 91 00 VA Mark up.docx DOCX document
08 71 00.docx DOCX document
RFIs_Response_Rev2.docx DOCX document
36C24626B0011 0002.docx DOCX document
36C24626B0011 0001.docx DOCX document
01 32 16.15 - PROJECT SCHEDULES - Small Projects – DesignBidBuild.docx DOCX document
659-22-405_Install Campus Generator_Site Visit Sign In Sheet_03.17.2026.docx.pdf PDF
01 33 23 - SHOP DRAWINGS PRODUCT DATA SAMPLES.docx DOCX document
01 91 00 - VA Mark-up.docx DOCX document
01 91 00 - GEN_COMMISSIONING REQUIR.docx DOCX document
01 45 00 - QUALITY CONTROL.docx DOCX document
659-22-405_Bid Set Specifications_Rev 1_.docx DOCX document
36C24626B0011_2_Solicitation.docx DOCX document
657-22-405 Salisbury Emergency Generator Bid Set_.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s /0

V A

S a lis b u ry S ta ti o n

E m e rg e n c y G e n e ra to r/

V A

S a lis b u ry

G e n e ra to rs

R

M

E P

F A

F P

T .r v t

/3

/2

:4

:0

A

M

M-801

MECHANICAL SCHEDULES CAMPUS GENERATOR

PROJECT

SALISBURY NC

659-22-405

B44

10/04/2025 GSC WRH

BID DOCUMENTS

Geoffrey S. Chenoweth, P.E.

Maryland License #28835

NOTES:

1. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL

2. PROVIDE STEEL OPPOSED BLADE VOLUME DAMPER

3. FRONT BLADES PARALLEL TO SHORT DIMENSION

4. BLADES PARALLEL TO LONG (HORIZONTAL) DIMENSION, FIXED AT 35°

5. HORIZONTAL BLADES SET AT 22° ANGLE

6. CONCEALED FASTENING - NO SCREW HOLES

7. PROVIDE CONCEALED AIR TIGHT SEAL AROUND DIFFUSER TO PREVENT AIR LEAKAGE

8. FACTORY PAINTED FLAT BLACK INTERIOR

9. SIDEWALL SUPPLY GRILLE WITH INTEGRAL FIRE/SMOKE DAMPER

EXHAUST FAN SCHEDULE

MARK MANUFACTURER MODEL NO. TYPE CFM

ESP

(IN-WG) FAN RPM

ELECTRICAL DRIVE

TYPE

MAX

SONES NOTESAMPS/HP V/PH/HZ

EF-1 GREENHECK G-180-VG ROOFTOP DOWNBLAST 2500 0.65 888 7/1.0 208/1/60 DIRECT 9.4 2,3,4,5

EF-2 GREENHECK G-180-VG ROOFTOP DOWNBLAST 2500 0.65 888 7/1.0 208/1/60 DIRECT 9.4 2,3,4,5

EF-3 GREENHECK USF-13-B6 ROOFTOP UTILITY SET 1300 0.46 1160 4/0.25 208/1/60 BELT 13.6 1,2,6

NOTES:

1. SPARK A CONSTRUCTION.

2. PROVIDE 18" ROOF CURB.

3. PROVIDE BACKDRAFT DAMPER.

4. PROVIDE UNIT MOUNTED DISCONNECT.

5. PROVIDE UNIT MOUNTED VARIABLE SPEED CONTROL WITH SOFTSTART AND 2-SPEED CONTROL FUNCTION.

6. FURNISH COMBINATION MOTOR STARTER/DISCONNECT WITH BAS CONNECTIVITIY, INSTALLED BY DIVISION 26. CONTROLS BY DIVISION 23, REFER TO CONTROL DIAGRAMS FOR REQUIREMENTS.

FUEL OIL PUMP SCHEDULE

MARK MANUFACTURER MODEL NO. FLOW GPM FLOW PSI MOTOR HP MOTOR RPM VOLTS/PHASE/HZ DIMENSIONS (IN.)

FOSP-1/2 PREFERRED UTILITIES ATPSF-BGSG0716-Z1333-D-DP-L 13 GPM 50 0.75 1725 208/3/60 65.5x30.5x81

AIR CONTROL DAMPER SHEDULE

MARK MAKE MODEL NO. NUMBER OF MODULES SERVES TOTAL AIRFLOW MAX VELOCITY (FPM) MODULE SIZE (WxH) (IN)

ACD-1-1 GREENHECK HCD-230 4 GENERATOR 1 INTAKE 117,315 750 102x94

ACD-1-2 GREENHECK HCD-230 4 GENERATOR 1 EXHAUST 108,840 1050 82x94

ACD-1-2A GREENHECK VCD-33 6 GENERATOR 1 RECIRCULATION STEADY STATE 44,500 1000 36x64

ACD-1-2B GREENHECK VCD-33 3 GENERATOR 1 RECIRCULATION STARTUP 31,100 1250 36X56

ACD-2-1 GREENHECK HCD-230 4 GENERATOR 2 INTAKE 117,315 750 102x94

ACD-2-2 GREENHECK HCD-230 4 GENERATOR 2 EXHAUST 108,840 1050 82x94

ACD-2-2A GREENHECK VCD-33 6 GENERATOR 2 RECIRCULATION STEADY STATE 44,500 1000 36X64

ACD-2-2B GREENHECK VCD-33 3 GENERATOR 2 RECIRCULATION STARTUP 31,100 1250 36X56

ACD-3-1 GREENHECK HCD-230 4 GENERATOR 3 INTAKE 117,315 750 102x94

ACD-3-2 GREENHECK HCD-230 4 GENERATOR 3 EXHAUST 108,840 1050 82x94

ACD-3-2A GREENHECK VCD-33 6 GENERATOR 3 RECIRCULATION STEADY STATE 44,500 1000 36x64

ACD-3-2B GREENHECK VCD-33 3 GENERATOR 3 RECIRCULATION STARTUP 31,100 1250 36X56

EXHAUST MUFFLER SCHEDULE

MARK

BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL INLET SIZE (IN) OUTLET SIZE (IN)

SOUND RATING

(GRADE) SIZE (LxW) (IN) WEIGHT (LBS)

EM-1 NETT NTHP-T1-R22 22 22 HOSPITAL 156x96 2550

EM-2 NETT NTHP-T1-R22 22 22 HOSPITAL 156x96 2550

EM-3 NETT NTHP-T1-R22 22 22 HOSPITAL 156x96 2550

NOTES:

1. TO BE INSTALLED BY MECHANICAL CONTRACTOR.

2. CONTRACTOR RESPONSIBLE FOR COORDINATING CONNECTION SIZES AND INTERFACE WITH ENGINE.

3. CONNECT TO GENERATOR WITH FLEXIBLE CONNECTORS AS REQUIRED BY GENERATOR MANUFACTURER.

4. ARRANGMENT SHOWN IN PLAN AND SECTION REPRESENTS A CUSTOM OPTION FOR THREE (3) SEPARATE INLETS TO THE MUFFLER MATCHING

THE OUTLET OF THE BOD GENERATOR. THE CONTRACTOR SHALL INCLUDE THIS TYPE OF CUSTOM CONNECTION AS REQUIRED TO MATCH

INTENT OF DESIGN.

AIR DISTRIBUTION SCHEDULE

MARK CFM

NECK

SIZE

FACE SIZE

LENGTH DESCRIPTION

E1 0-500 12X20 12X20 SIDEWALL EXHAUST GRILLE

BASIS OF DESIGN: PRICE

COLOR: MATCH WALL

MATERIAL: ALUMINUM

OPPOSED BLADE DAMPER: YES

R20 0-1360 30X8 30X8 SIDEWALL RETURN GRILLE

BASIS OF DESIGN: PRICE - 635

COLOR: MATCH WALL

MATERIAL: ALUMINUM

OPPOSED BLADE DAMPER: YES

S20 0-340 12X6 12X6 SIDEWALL SUPPLY GRILLE

BASIS OF DESIGN: PRICE - 620

COLOR: WHITE

MATERIAL: ALUMINUM

OPPOSED BLADE DAMPER: NO

FUEL OIL TANK SCHEDULE

MARK MANUFACTURER MODEL NO. CAPACITY (G) LENGTH DIAMETER

FOT-1 HIGHLAND TANK 120" AG DW HORIZONTAL 20,000 34' 10'

FOT-2 HIGHLAND TANK 120" AG DW HORIZONTAL 20,000 34' 10'

FUEL OIL FILTER SCHEDULE

MARK MANUFACTURER MODEL FLOW (GPH) FLOW (PSI) PUMP HP VOLTS/PHASE/HZ

FOF-1 PREFERRED UTLITIES PFBG-505-Z1333 1200 50 3/4 120/1/60

AIR FILTER SCHEDULE

MARK MAKE MODEL IND FILTER SIZE (DXWXH) FILTER EFFICIENCY

FACE VELOCITY

(FPM)

INITIAL ADP (IN

WG)

MAX. APD (IN

WG) QUANTITY MAX TOTAL CFM

FLT-1 CAMFILL FARR 30/30 4"x24"x24" MERV 8 401 FPM 0.27 1.0 196 314505

FLT-2 CAMFILL FARR 30/30 4"x24"x20" MERV 8 401 FPM 0.27 1.0 28 37440

UNIT HEATER SCHEDULE

MARK MANUFACTURER MODEL

AIRFLOW

(CFM)

HEATING

CAPACITY (KW) TEMP RISE (°F)

HEAT THROW

(FT)

MAX MOUNTING

HEIGHT (FT) V/PH/HZ

UH-1 MODINE HER50 380 5 42 12 8 208/3/60

UH-2 MODINE HER50 380 5 42 12 8 208/3/60

UH-3 MODINE HER50 380 5 42 12 8 208/3/60

UH-4 MODINE HER50 380 5 42 12 8 208/3/60

UH-5 MODINE VE50 800 5 21 20 13 208/3/60

NOTES:

1. PROVIDE FILTER FRAME TYPE 8 ASSEMBLY FOR SCHEDULED FILTERS AND HAVE SIMILAR CONFIGURATION TO THAT SHOWN IN THE DRAWINGS.

MANUFACTURER SHALL PROVIDE COORDINATION AND INSTALLATION DRAWINGS OF FILTERS AND FILTER ASSEMBLY SPECIFICALLY FOR THIS PROJECT.

SUBMIT FOR REVIEW WITH FILTER SYSTEM SUBMITTAL.

2. FINAL RESISTANCE IS FILTER CHANGE OUT POINT. INITIAL RESISTANCE IS BRAND NEW FILTER.

NOTES:

1. DAMPER ACTUATOR BASIS OF DESIGN: BELIMO EFCX SPRING RETURN DAMPER ACTUATOR. DAMPER SHALL FAIL OPEN ON LOSS OF POWER OR SIGNAL.

2. FRONT FLANGE MOUNTING OPTION FOR PLENUM MOUNTING.

3. PROVIDE 120V OR 24V AC DAMPER ACTUATOR AS REQUIRED BY CONTROL CONTRACTOR. DIVISION 26 SHALL PROVIDE 120VAC CIRCUIT FOR EACH DAMPER BANK, REFER TO

ELECTRICAL DRAWINGS. PROVIDE CONTROL POWER TRANSFORMER AND LOCAL ENCLOSURE IF 24 VAC IS PROVIDED.

DUCT SILENCER SCHEDULE

MARK MANUFACTURER MODEL NO. SERVICE

SIZE

(W"xH"xL")

AIRFLOW

(CFM)

VELOCITY

(FPM)

PRESSURE DROP

(IN. W.C.)

DYNAMIC INSERTION LOSS

63 125 250 500 1000 2000 4000 8000

SL-1 VIBRO ACOUSTICS RD-MLV-3167

GENERATOR 1, 2, & 3 660x192x84 350000 -398 0.04 8 15 26 29 30 23 17 15

SL-1-2 VIBRO ACOUSTICS RD-MHV-316

GENERATOR 1 168x192x60 108800 482 0.23 5 9 23 39 42 37 24 17

SL-2-2 VIBRO ACOUSTICS RD-MHV-316

GENERATOR 2 168x192x60 108800 482 0.23 5 9 23 39 42 37 24 17

SL-3-2 VIBRO ACOUSTICS RD-MHV-316

GENERATOR 3 168x192x60 108800 482 0.23 5 9 23 39 42 37 24 17

NOTES:

1. VELOCITY SHOWN IS + (FORWARD FLOW) OR - (REVERSE FLOW) AS DEFINED BY ASTM E477-20.

2. IDEAL PRESSURE DROP AS DETERMINED PER ASTM E477-20 IN A NVLAP-ACCREDITED ACOUSTICAL LABORATORY.

3. PRESSURE DROP PER ASTM E477-20 PLUS SYSTEM EFFECTS FOR NEARBY DUCT ELEMENTS.

4. MINIMUM DYNAMIC INSERTION LOSS DETERMINED PER ASTM E477-20 IN A NVLAP-ACCREDITED ACOUSTICAL LABORATORY.

5. MANUFACTURER SHALL PROVIDE, FOR APPROVAL, PROFESSIONAL ENGINEER STAMPED ACOUSTICAL CALCULATIONS FOR ALL SYSTEMS WITH SILENCERS TO DEMONSTRATE THAT THE

RESULTANT DUCTBORNE FAN SOUND LEVELS, INCLUDING AIRBORNE AND BREAKOUT NOISE, MEET THE REQUIRED CRITERIA.

6. MANUFACTURER SHALL PROVIDE, FOR APPROVAL, PROFESSIONAL ENGINEER STAMPED PRESSURE DROP CALCULATIONS FOR ALL SYSTEMS WITH SILENCERS TO DEMONSTRATE THAT THE

RESULTANT INSTALLED PRESSURE DROP WITH SYSTEM EFFECTS DOES NOT EXCEED SCHEDULED VALUES.

7. TEST SILENCER AS SCHEDULED IN ACCORDANCE WITH ASTM E477-20 IN A NVLAP-ACCREDITED FACILITY, WITNESSED BY THE ENGINEER AT THE ENGINEER'S OPTION.

8. CONTRACTOR IS FINANCIALLY RESPONSIBLE TO ENSURE NOISE CONTROL SOLUTION IS DELIVERED TO ACHIEVE SPECIFIED NC LEVEL IN SPACES.

9. SILENCER DESIGNED TO ACHIEVE 65DBA AT 176FT PROPERTY LINE

NOTES:

1. MOUNTING BRACKET SHALL BE PROVIDED BY EQUIPMENT MANUFACTURER.

2. ELECTRIC UNIT HEATERS TO BE CONTROLLED FROM LOCALLY-MOUNTED T-STAT.

3. PROVIDE REQUISITE COMMUNICATION PROTOCOL TO INTERFACE WITH CAMPUS BAS.

4. UH-4 IS A VERTICAL UNIT HEATER. MOUNT IN CENTER OF ROOM, AS SHOWN ON PLANS.

NOTES:

1. FOT-1 & FOT-2 SHALL BE DOUBLE-WALL UL 142 LISTED. SEE SPECIFICATIONS AND DETAILS FOR TANK CONFIGURATION AND

ACCESSORIES.

NOTES:

1. PROVIDE INTEGRATED CONTROL PANEL.

2. PROVIDE INTEGRAL PUMP WITH DUPLEX STRAINER.

AIR INTAKE/EXHAUST LOUVER SCHEDULE

MARK MANUFACTURER MODEL NO. DESIGN CFM VELOCITY (FPM)

STATIC PRESSURE

(IN. W.G.)

DIMENSIONS

(W"xH"xD") WEIGHT (LBS)

GLP-1 GREENHECK EM-40 3400 1500 0.11 in-wg 42x28x36 86

NOTES:

1. PROVIDE BACKDRAFT DAMPER GREENHECK MODEL: EM-40.

NOTES:

1. CONTRACTOR TO PROVIDE DRAIN PAN BELOW EACH INDOOR UNIT.

SPLIT AIR CONDITIONING UNIT SCHEDULE

MARK

INDOOR UNIT OUTDOOR UNIT

SUPPLY FAN COOLING COIL - DX HEATING COIL - HEAT PUMP ELECTRICAL

MARK NOM. TONS SEER

AMBIENT

TEMPERATURE

ELECTRICAL

WEIGHT (LBS)NOMINAL CFM ESP (IN-WG)

MOTOR

HP EAT (F° DB) EAT (F° WB) MAX. LAT (F° DB)

GROSS

TOTAL MBH

GROSS

SENSIBLE MBH REFRIGERANT HP LAT HP CAPACITY V/PH/HZ

MCA/MOP

(UNIT)

V/PH/HZ

MCA MOCP

IDU-1 1375 0.5" 0.5 80 67 55 46.5 35 R-410A 85 38 208/1/60 3.6/15 ODU-1 4 15.3 95 208/1/60 29.1 35 225

IDU-2 1130 0.5" 0.5 80 67 55 35 28 R-410A 85 28 208/1/60 3.1/15 ODU-2 3 16.9 95 208/1/60 29.1 35 225

FUEL OIL DAY TANK W/INTEGRAL PUMP SCHEDULE

MARK MODEL NO. MAKE TYPE

CAPACITY

(GAL)

GPH OIL GRADE VISCOCITY OIL TEMP (F)

MINIMUM SYSTEM

PRESSURE (PSIG)

PUMP DISCHARGE

PRESSURE (PSIG)

MOTOR HP

(EACH)

MOTOR RPM V/PH/HZ

DT-1 DTBG-290-2227

PREFERRED

UTILITIES

UL 142 ASSEMBLY 290 900 2 45 SSU 45 6.5 30 3/4 1750 120/1/60

DT-2 DTBG-290-2227

PREFERRED

UTILITIES

UL 142 ASSEMBLY 290 900 2 45 SSU 45 6.5 30 3/4 1750 120/1/60

DT-3 DTBG-290-2227

PREFERRED

UTILITIES

UL 142 ASSEMBLY 290 900 2 45 SSU 45 6.5 30 3/4 1750 120/1/60

NOTES:

1. PROVIDE WITH INTEGRAL DISCONNECT.

2. PROVIDE WITH SINGLE POINT 120V/1PH ELECTRICAL SUPPLY FOR DAY TANK CONTROLLER POWER AND PUMP POWER. PROVIDE WITH FACTORY

120V/1-PH STEP DOWN TRANSFORMER FOR CONTROLS.

3. PROVIDE TEFC PUMP MOTORS.

4. PROVIDE INLET VALVE ASSEMBLY FOR LEVEL CONTROL.

5. UNIT SHALL BE DUPLEX TYPE WITH REDUNDANT PUMPS.

NOTES:

1. PROVIDE PACKAGED DUPLEX TYPE PUMP SKID WITH REDUNDANT PUMPS. PROVIDE WITH SINGLE POINT POWER CONNECTION.

R

EG I S T E R E

D

G E

O F

F R

EY S . CHEN

O

W E

T H

NO . 2 8 8 35

M A RO F

E

LNO A

S

P

S

O F E

R

I

E T

S A T

E E R

N

N G

I

D

A

N

L Y

Revisions Date

2 BID BULLETIN 2 03/31/2026

1 BID BULLETIN 1 11/27/2024

Sheets
M-801 - MECHANICAL SCHEDULES

File details come from the government source that posted it. Updated .