ROOFSCAN REPORT.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24625B0013
About this file
This document is a RoofScan Report for the Hampton VA Medical Center, conducted on January 20, 2023, using qualitative infrared thermographic roof scanning techniques. The survey was performed by a certified thermographer and FAA-licensed UAV pilot, using FLIR thermal imaging cameras with high-resolution thermal sensitivity. The inspection identified multiple areas of probable moisture across two roof areas (Area 1 and Area 2), totaling approximately 2,806.26 square feet of probable moisture detection.
The report provides detailed infrared and visual imagery for each identified moisture area, marking specific regions with potential subsurface moisture using red crosshatched overlays. The survey was conducted in the evening to capture optimal thermal anomalies, with weather conditions of 37-60°F, sunny to cloudy skies, and winds at 17 mph. The report recommends a thorough visual examination and potentially destructive testing (core sample) to confirm the infrared analysis findings. The roof condition was described as "Fair" with the last recorded rainfall on January 13, 2023 being 0.14 inches.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HANDRAIL SUBMITTALS REDACTED.pdf | ||
| 36C24625B0013 0005.docx | DOCX document | |
| 36C24625B0013 0004.docx | DOCX document | |
| 36C24625B0013 0003.docx | DOCX document | |
| SITE VISIT ATTENDEES LOG SHEET - 28 April 2025.pdf | ||
| 36C24625B0013 0002.docx | DOCX document | |
| SITE VISIT ATTENDEES LOG SHEET.pdf | ||
| 36C24625B0013 0001.docx | DOCX document | |
| MARKET SURVEY CONSTRUCTION MATERIALS TEMPLATE.xlsx | XLSX spreadsheet | |
| SPECIFICATIONS.pdf | ||
| DRAWINGS.pdf | ||
| 36C24625B0013_IFB.docx | DOCX document | |
| BID ITEMS COST BREAKDOWN.xlsx | XLSX spreadsheet | |
| WAGE DETERMINATIONS - DAVIS-BACON ACT.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RoofScan Report
Qualitative Infrared Thermographic Roof Scan of Hampton VA Medical Center
Location:
100 Emancipation Dr.
Hampton, VA 23667
Survey Date:
1/20/2023
Prepared For:
Prepared by:
Aerial Visual Image Hampton VA Medical Center – Roof Area 1
January 20, 2023
Aerial Visual Probable/Possible Moisture Hampton VA Medical Center – Roof Area 1
PROBABLE POSSIBLE
MOISTURE MOISTURE
2806.26 sqft 0.00 sqft
Aerial Visual Image Hampton VA Medical Center – Roof Area 2
Aerial Visual Probable/Possible Moisture Hampton VA Medical Center – Roof Area 2
PROBABLE POSSIBLE
MOISTURE MOISTURE
2806.26 sqft 0.00 sqft