36C24620R0041-003.pdf
PDF Posted
- Attached to
- Z2DA--Power Distribution System Upgrade Federal contract opportunity
- Solicitation number
- 36C24620R0041
About this file
This presolicitation notice is for the Department of Veterans Affairs project to upgrade the power distribution system at the Chiller Plant in Building 9 of the Durham VA Medical Center in Durham, North Carolina. The solicitation will be a Total Service-Disabled Veteran Owned Small Business set-aside with an anticipated award value between $1 million to $5 million. The scope of work includes replacing primary switch assemblies, transformers, and distribution equipment to provide a double-ended 2000 KVA substation with new medium voltage terminal cabinet and 15KV switchgear. Additional requirements are a 1500VA UPS for chiller controls, new medium voltage terminal cabinet, and associated electrical upgrades. The solicitation is expected to be released on or about April 1, 2020 with proposals due approximately 28 days later.
36C24620R0041 ATTACHMENT B PROJECT 558-18-277 DRAWING SET.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06. SF30 36C24620R0041 A0004.pdf | ||
| ATTACHMENT H PROJECT 558-18-277 BLDG 9 ASBESTOS REPORT.pdf | ||
| ATTACHMENT G PROJECT 558-18-277 Attendance Sheet.pdf | ||
| S06. SF30 36C24620R0041 A0003 (FE).pdf | ||
| 36C24620R0041-0002000.docx | DOCX document | |
| 36C24620R0041-0001000.docx | DOCX document | |
| 36C24620R0041-005.pdf | ||
| 36C24620R0041-001.pdf | ||
| 36C24620R0041-004.pdf | ||
| 36C24620R0041-006.pdf | ||
| 36C24620R0041-002.pdf | ||
| 36C24620R0041-007.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT # 558-18-277
UPGRADE TO POWER DISTRIBUTION SYSTEM BLDG 9 NORMAL POWER
SWITCHGEAR AND TRANSFORMERS
VA MEDICAL CENTER-DURHAM
CAMPUS LOCATION
VICINITY MAP
CAMPUS MAP
SHEET NO. SHEET LIST BUILDING
Previous testing has identified floor and/or wall coverings, floor adhesives, duct mastic, pipe fittings & pipe insulation in this area may contain asbestos. See the 2017 asbestos re-inspection drawings provided by the Durham VAMC.
During the course of the project the contractor shall take any additional precautions that may be necessary to ensure that the flooring and wall coverings in this area are not disturbed any more than they would be during normal daily operation.
These include, but are not limited to, temporary floor and/or wall protection from falling objects during demolition or construction, additional protection of wall coverings along the construction debris route, etc. any possible disruption of these systems shall be reported to the COR immediately.
COR shall determine if additional action is required.
Contractor shall be responsible for any additional cost required if systems are disturbed such that abatement is required.
This facility contains asbestos that will be removed under a separate contract.
This facility contains asbestos that will be removed under this contract.
This facility contains asbestos that will be removed by the
VAMC
This facility contains no known or suspected asbestos.
ASBESTOS CONTAINING MATERIAL (ACM) STATEMENT
(Place an "X" in the appropriate box.)
VA MEDICAL CENTER-DURHAM
CAMPUS LOCATION
DRAWING
NUMBER
09-27-2019
VAMC DURHAM UPGRADE POWER
DISTRIBUTION SYSTEM BLDG 9
558-18-277
DURHAM, NC
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and
Facilities
Management
PROJECT MANAGER:
ACG Project
NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705
18-238
CONSTRUCTION DRAWINGS
FULLY SPRINKLERED
Structural Engineer:
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
COVER SHEET
G-001
MAHMAH
DocuSign Envelope ID: BF913632-8732-4FB9-8BC3-314F7779D11D
9/26/2019
B9-SWGR-MAIN A
480/277 V, 3200A
50Kaic
B9-SWGR-MAIN B
480/277 V, 3200A
50Kaic
OPEN
TIE
3200 A
LTPU 1 (3200A)
MSA4
1600 A
LTPU 1 (600A)
MSA3
1600 A
LTPU 1 (1200A)
MSA2
1600 A
LTPU 0.5 (500A)
B9-XF-T12
2000 kVA
12470 / 480/277 V
B9-STR-CHILLER1
B9-M-CHILLER1
460V
1-283hp
#4/0-2/Ph
B9-STR-CHILLER2
B9-M-CHILLER2
460V
1-536.1hp
#300-3/Ph
B9-MAIN-MSB1
3200 A
LTPU 1 (3200A)
B9-XF-T13
2000 kVA
12470 / 480/277 V
MSB3
1600 A
LTPU 1 (1200A)
#350-4/Ph
MSB3
1600 A
LTPU 1 (1200A)
N E
# 350-4/Ph
B9-ATS-9
480 V, 1200A
B9-MCC
480V, 1200 A
(B9-B6 ECBS
175 A)
# 350-4/Ph
B9-PG-MCC
1200 A
LTPU 1.00X (1200A)
NE
# 350-4/Ph
B9-PG-CHILLER3
1200 A
LTPU 1.00X (1200A)
B9-PG-XFT1
800 A
B9-SWBD-PG
480 V, 3000A
#500-2/Ph
B7-ECB-2
B7-ECB2
800A
#500-2/Ph
P
S
B7-XF-T1
500 kVA
480/208V
#350-4/Ph
B7-ECB-3
B7-ECB3
1200A
#350-4/Ph
N E
B7-ATS-7
208V, 1200A
# 350-4/Ph
B7-MDP-MAIN
800A
B7-PNL-MDP
208V, 1200A
B7-ECB-1
B7-ECB1
1200A
#350-4/Ph
B9-ATS-8
480V, 1200A
#350-4/Ph
B9-STR-CHILLER3
460V
1 - 685.7 hp
B9-M-CHILLER3
460V
1-685.7 hp
B9-G6 OUTPUT
3000A
LTPU1 (3000A)
# 500-8/Ph
B9-G6 BUS
G
B9-G-6
2500 kVA
480 V
(EX)
(EX)
(EX)
(EX)
(EX)
ATS-9
ATS-8
ATS-7
(EX)
(NEW)
(NEW)
(NEW)
(NEW)
(NEW)
(NEW)
(NEW)
# 2/0-1/Ph
B7-PNL-N7A
208V, 225A
CBL-1506
# 4-1/Ph
B7-PNL-N7C
208V, 225A
B7-N7A-N7C
70A
B6-SL1-MAIN
225A
#4/0-1/Ph
B7-MDP-BLDG6
225A
B7-MDP-BLDG7A
175A
B6-PNL-SL1
208V, 225A
B7-PNL-7P
MCC
208V, 225A
B7-MDP-MEDAIR
225A
#4/0-1/Ph
B9-STR-MEDAIR
B7-MDP-N7MS
250A
#250-1/Ph
B7-MDP-SL
400A
#500-1/Ph
B6-NFS-MAN
208V, 600A
B7-7P-P4
50A
#8-1/Ph
B7-NFS-P4
B7-7P-P3
50A
#8-1/Ph
B7-NFS-P3
B7-7P-P5
50A
#8-1/Ph
B7-NFS-P5
B7-M-P5
208V
1-10hp
B7-M-P4
208V
1-10hp
B7-M-P3
208V
1-10hp
B7-PNL-N7D
208V, 400A
B7-MDP-LP
100A
#8-2/Ph
B9-ECB-9P
B7-MDP-BLDG19
70A
#4-1/Ph
B19-PNL-E19
208V, 60A
B7-MDP-N7B
125A
#2-1/Ph
B7-PNL-N7B
208V, 225A
B7-N7D-BLR1
110A
#2-1/Ph
B7-NFS-BLR1
B7-N7D-BLR2-P5
110A
#2-1/Ph
B7-NFS-BLR2
B7-MDP-BLDG24
225A
#4/0-1/Ph
B24-PNL-24A
208V, 225A
B7-N7D-BLR3
110A
#2-1/Ph
B7-NFS-BLR3
B7-MDP-N7D
300A
B7-MDP-BP1
125A
#4/0-1/Ph
B19-PNL-BP1
208V, 225A
B7-N7D-HEATPMP
110A
#2-1/Ph
B7-NFS-HEATPMP
B7-N7D-AIRCOMP
110A
#2-1/Ph
B9-FS-AIRCOMP2
B7-9P
70A
#8-2/Ph
B9-PNL-9P
208V, 60A
# 2-1/Ph
B9-STR-AIRCOMP2
B9-FS-AIRCOMP2
110A
#8-1/Ph
B7-VFD-BLR3
#4-1/Ph
B7-VFD-BLR2
#6-1/Ph
B7-VFD-BLR1
(NEW)
(NEW)
(NEW)
(NEW)
(NEW)
(EX) (EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX) (EX) (EX) (EX) (EX)
(EX)
(EX) (EX) (EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(TYP-3)
NEW FVNR MOTOR
STARTER SIZE 1
(TYP) DISCONNECT AND
RECONNECT EXISTING
SERVICES. RETAIN AND REUSE
EXISTING FEEDER
CONDUCTORS. EXTEND TO
NEW OC DEVICE AT
SWITCHGEAR AS REQUIRED.
3#350MCM, #4AWG EG
3"C
(EX) VIF
J
(EX) VIF
(EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX)
(EX)
(EX)
(EX)
(EX)
N E
15KV PRIM SW WITH TXF
OVERLOAD PROTECTION
(NEW)
N E
15KV PRIM SW WITH TXF
OVERLOAD PROTECTION
(NEW)
52-ALT A/C
(15KV)
52-PREF A/C
(15KV)
(EX)
(EX)
EXTEND (15KV) FEEDER TO
TEMPORARY SERVICES
SUBSTATION (3-1/C 1 /0 15KV EPR)
RECORDED DEMAND METER DATA
T12/T13 COMBINED AVERAGE 1.8 MVA.
PROVIDE TEMPORARY SERVICES
SUBSTATION AND FEEDERS TO
SUPPORT CHILLER PLANT LOADS (AS
SHOWN ON THE SINGLE LINE )DURING
THE REMOVAL AND REPLACEMENT OF
THE SUBSTATION. COORDINATE
ROUTING OF TEMPORARY SERVICES
CABLING WITH COR AND PLANT
OPERATIONS.
(MIN 2000KVA 480V 3PH,4W)
(3200 A) (3200 A)
(EX)
(3-1/C, #1/0 AWG MV-105 EPR)
(EX)
(3-1/C, #1/0 AWG MV-105 EPR)
NEW MV
TERMINAL
CABINET
(3-1/C, #1/0 AWG MV-105 EPR)
4"C
(EX)
# 350-4/Ph
KKKK
KK
B9-MAIN-MSA1
3200 A
LTPU 1 (3200A)
EM
EM
100A
20A
B19-MCC PNL
208/120V, 100A MCB
(EX)
P
S
(EX)
CHILLER
CONTROL PANEL
(UPS)
(EX)
UTILIZE EXISTING
SPARE 20A-1P
(CKT 16)
09-27-2019
VAMC DURHAM UPGRADE POWER
DISTRIBUTION SYSTEM BLDG 9
558-18-277
DURHAM, NC
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and
Facilities
Management
PROJECT MANAGER:
ACG Project
NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705
18-238
CONSTRUCTION DRAWINGS
FULLY SPRINKLERED
Structural Engineer:
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
ELECTRICAL LEGEND
DUAL-TECHNOLOGY, CEILING MOUNTED, LOW VOLTAGE
OCCUPANCY SENSOR
OCCUPANCY SENSOR SWITCHPACK, WIRE PER
MANUFACTURER'S RECOMMENDATIONS.
3 = THREE WAY
GFI = GROUND FAULT CIRCUIT INTERRUPTER
WIRING SYSTEM-BRANCH OR FEEDER CIRCUIT
120V QUAD RECEPTACLE, MOUNTED 18" AFF UNO
4 = FOUR WAY
JUNCTION BOX
SINGLE POLE SWITCH, MOUNTED 44" AFF UNO.
MODIFIERS FOR SWITCHES:
HOMERUN - 120V OR 277V
HOMERUN - 208V OR 480V
BRANCH OR FEEDER CIRCUIT HOMERUN TO
PANELBOARD, SWITCHBOARD, MOTOR CONTROL
CENTER, OR OTHER POWER DISTRIBUTION DEVICE (PDD).
SUBSCRIPT DENOTES PANELBOARD, SWITCHBOARD,
MOTOR CONTROL CENTER, OR PDD. AND OVERCURRENT
PROTECTION DEVICE NUMBER.
120V DUPLEX RECEPTACLE, MOUNTED 18" AFF UNO
MODIFIERS FOR RECEPTACLES:
TELCO OUTLET MOUNTED 18" AFF UNO
WP = WEATHERPROOF
DM = DIMMER SWITCH
FUSED DISCONNECT
UNFUSED DISCONNECT
PHOTOELECTRIC CELL
DATA/TELCO OUTLET MOUNTED 18" AFF UNO
120V SIMPLEX RECEPTACLE, MOUNTED 18" AFF UNO
220V DUPLEX RECEPTACLE, MOUNTED 18" AFF UNO
WIRING SYSTEM-SWITCHED BRANCH OR FEEDER CIRCUIT
OC = OCCUPANT SENSOR
PC
J
S
A AMPERE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPS INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
C CONDUIT
cd CANDELA
CKT CIRCUIT
CU COPPER
D DEEP
DACT DIGITAL ALARM COMMUNICATOR TERMINAL
DED DEDICATED CIRCUIT
EG EQUIPMENT GROUND
EM ELECTRICAL (DEMAND) METERING
EMT ELECTRICAL METALLIC TUBING
EX EXISTING
EXT EXTERIOR
FACP FIRE ALARM CONTROL PANEL
FAA FIRE ALARM REMOTE ANNUNCIATOR
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
GEC GROUNDING ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRS GALVANIZED RIGID STEEL
H HIGH
HP HORSEPOWER
IBC INTERNATIONAL BUILDING CODE
IG ISOLATED GROUND
KW KILOWATT
KK KIRK KEY INTERLOCK
MBJ MAIN BONDING JUMPER
MC METAL-CLAD CABLE
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
OC OVER CURRENT PROTECTION
PC PHOTOCELL
R RELOCATED
SPD SURGE PROTECTION DEVICE
TBB TELECOMMUNICATIONS GROUNDING
BACKBONE
TCL TOTAL CONNECTED LOAD
TDL TOTAL DEMAND LOAD
TGB TELECOMMUNICATIONS GROUND BAR
TMGB TELECOMMUNICATIONS MAIN GROUND BAR
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
WP WEATHERPROOF
TXF TRANSFORMER
VIF VERIFY IN FIELD
3/PH NUMBER OF CONDUCTORS PER PHASE (TYP)
IE: 1/PH REPRESENTS (1) CONDUCTOR PER
PHASE, 2/PH (2) CONDUCTORS PER PHASE.
ABBREVIATIONS GENERAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S
RECOMMENDED INSTALLATION PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES,
AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS
WHERE THE BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN
ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING
REQUIREMENT AND THE APPLICABLE BUILDING CODES. REFER TO THE ARCHITECTURAL
DRAWINGS AND THE OWNER'S EXISTING AS-BUILT/RECORD DRAWINGS, VERIFY
CONSTRUCTION RATINGS AND PROVIDE PENETRATION ASSEMBLIES SUITABLE FOR THE
PARTICULAR CONSTRUCTION.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL
REQUIRED MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING
CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS
TO AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT
SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF
EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO
INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A
PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE
DESIGNER WILL BE ACCEPTED.
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR
PARTICULAR EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED
ON THE DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR
EQUIPMENT UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE GRS OR EMT UNLESS OTHERWISE NOTED.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL
LISTED BY AN APPROVED THIRD PARTY TESTING AGENCY.
SPECIAL RECEPTACLE, MOUNTED 18" AFF UNO
ELECTRICAL RISER DIAGRAM
NTS
(EX) DENOTES EXISTING TO REMAIN.
VERIFY IN FIELD
LIGHTER LINE WEIGHT DENOTES EXISTING
DEVICES, ASSEMBLIES, AND OR SERVICES
TO REMAIN. VERIFY IN FIELD.
ELECTRICAL NOTES,
ABBREVIATIONS, AND RISER
DIAGRAM
E-001
MAHMAH
NUMBER OF CONDUCTORS PER PHASE (IE 1,3,4)*/PH
DRAWOUT POWER CIRCUIT BREAKER
CIRCUIT BREAKER
MECHANICAL
(CW) PIPING,
FIELD VERIFY
LOCATION
15KV
DUPLEX
SWITCH
T-12
2000KVA
12470Y/
480V
METERING
MAIN
TIE-BKR
METERING
MAIN
DISTB
T-13
2000KVA
12470Y/
480V
15KV
DUPLEX
SWITCH
P
R E
F
A
C
(EX) 15KV FEEDERS
(3-1/0 AWG)
(TYP) EXISTING CONCRETE
PAD FOR ELECTRICAL
EQUIPMENT
(EX)ATS-8
CHILLER (3)
480V TO
REMAIN
A
L T
A
C
E
F
A
C
A
L T
A
C
EXISTING
JUNCTION BOX
ABOVE
SUBSTATION
FOR
ELECTRICAL
FEEDERS
(EX)B9MCC
(1200A MLO)
(EX) CHILLER PLANT
CONTROLS VIF
DISTB
DISTB
(EX) CHILLER (1)
(EX) CHILLER (2)
(EX) CHILLER (3)
(EX)PIPE COLUMN
TO REMAIN
1. DOUBLE ENDED SUBSTATION TO BE REMOVED,
SEE SPECIFICATIONS AND REQUIREMENTS FOR
DISPOSAL.
2. EXISTING (ATS-8). 1200 AMP TRANSFER SWITCH
SERVING CHILLER (3) TO REMAIN. PROTECT
DURING CONSTRUCTION/REPLACEMENT OF
DISTRIBUTION SUBSTATION.
3. PULL BOX LOCATED ABOVE SUBSTATION.
VERIFY LOCATION IN FIELD. RETAIN AND REUSE
FOR DISCONNECT/RECONNECT OF ELECTRICAL
SERVICES FROM SUBSTATION.
4. FLUORESCENT (SUSPENDED) INDUSTRIAL
FIXTURES. RELOCATE AS REQUIRED FOR THE
REPLACEMENT OF THE SUBSTATION. PROVIDE
TEMPORARY LIGHTING FOR CONSTRUCTION
PURPOSES. FIELD VERIFY EXISTING
CIRCUITING.
5. EXISTING FEEDERS FROM B9 SWITCHBOARD
TO CHILLERS, MOTOR CONTROL CENTER, AND
CHILLER PLANT ACCESSORIES. SEE SHEET
E-001 (RISER DIAGRAM). FIELD VERIFY EXISTING
ROUTING, DISCONNECT AND RECONNECT
FEEDERS AT SWITCHBOARD. COORDINATE
WITH NEW SUBSTATION LAYOUT AND ANY
TEMPORARY SERVICES TO SUPPORT CHILLER
PLANT DURING THE CONSTRUCTION PROCESS.
6. AT EXISTING SWITCHBOARD IDENTIFY CIRCUIT
BREAKER CONTROLS AND SERVICES (CIRCUIT)
TO BATTERY CHARGER, RETAIN AND REUSE
ELECTRICAL SERVICES FOR NEW SWITCHGEAR
CONTROLS.
PARTIAL ELECTRICAL DEMOLITION PLAN CHILLER PLANT (BLDG 9)
SCALE: 1/8" = 1'-0"
A. DEMOLITION SHALL INCLUDE BUT NOT BE
LIMITED TO THOSE ITEMS SHOWN HATCHED.
COORDINATE WITH EXISTING CONDITIONS.
B. DISCONNECT AND REMOVAL OF ELECTRICAL
SYSTEMS SHALL BE COORDINATED WITH
PLANT OPERATIONS AND CAMPUS
FACILITIES/OPERATIONS.
C. FIELD VERIFY DIMENSIONS AND LAYOUT OF
EQUIPMENT PAD PRIOR TO DEMOLITION.
RETAIN AND UTILIZE FOR LAYOUT DRAWINGS
RELATED TO NEW EQUIPMENT.
BOOTH
A
D
C
B
E
F
M
R
I
I
C
U
F
U
L
T
O
N
S
T
R
E
E
T
E
R
W
I
A
D
09-27-2019
VAMC DURHAM UPGRADE POWER
DISTRIBUTION SYSTEM BLDG 9
558-18-277
DURHAM, NC
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and
Facilities
Management
PROJECT MANAGER:
ACG Project
NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705
18-238
CONSTRUCTION DRAWINGS
FULLY SPRINKLERED
Structural Engineer:
KEY PLAN:
AREA OF WORK
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
ED-101
MAHMAH
PARTIAL ELECTRICAL DEMOLITION PLAN
CHILLER PLANT (BLDG 9)
0 4' 8' 16'
E
F
(EX) 15KV
FEEDERS
(3-1/0 AWG)
A
L T
A
C
(NEW) MV TERM
CABINET
2 SETS
3/C 15KV
#1/0 AWG,4"C
DOUBLE
ENDED
SUBSTATION
12470/7200-
480/277V
2000 KVA
EXISTING JUNCTION BOX
ABOVE SUBSTATION FOR
ELECTRICAL FEEDERS/DISTB
(TYP) EXISTING CONCRETE
PAD FOR ELECTRICAL
EQUIPMENT
(EX)ATS-8
CHILLER
(3)
480V TO
REMAIN
(EX)B9MCC
(1200A MLO)
(EX) CHILLER PLANT
CONTROLS VIF
E
F
A
L T
A
C
UPS
B9MCC PNL-20
(TEMP) 15KV FEEDER TO TEMP
SERVICES SUBSTATION
SEE E-001
APPROXIMATE
LOCATION OF
TEMPORARY
SERVICES
SUBSTATION.
TXF,DISTB
SWGR,AND
FEEDERS TO
EXISTING CHILLER
PLANT LOADS.
COORDINATE
LOCATION WITH
COR AND PLANT
OPERATORS.
(EX) CHILLER (1)
(EX) CHILLER (2)
(EX) CHILLER (3)
(EX)PIPE COLUMN
TO REMAIN
1. NEW DOUBLE ENDED SUBSTATION 2000
KVA. SEE SPECIFICATIONS AND
ELECTRICAL RISER DIAGRAM.
2. PROVIDE (1500VA) UPS FOR ELECTRICAL
SERVICE (120V) TO CHILLER CONTROL
PANEL. CIRCUIT TO ADJACENT
RECEPTACLE PANEL (120/208V) WITHIN THE
EXISTING MCC (B9-MCC).
UTILIZE EXISTING SPARE BREAKER. UPS
TO BE WALL MOUNTED DIRECTLY
ADJACENT TO CONTROL PANEL.
3. MV TERMINAL CABINET WITH LOCKABLE
LATCH, BARFIELD MFG BGSSE236730TP
WITH 15KV CLASS LOAD BREAK JUNCTION ,
(2) THREE WAY (COOPER 500-15) OR
EQUAL. PROVIDE FOR LOAD BREAK
ELBOWS AND CONNECTIONS TO 15KV
CABLING (EXISTING AND NEW) AT THIS
LOCATION. PROVIDE FIBERGLASS
BASE/HOUSING FOR INSTALLATION OF
TERMINAL CABINET.
PARTIAL ELECTRICAL PLAN CHILLER PLANT (BLDG 9)
SCALE: 1/8" = 1'-0"
BOOTH
A
D
C
B
E
F
M
R
I
I
C
U
F
U
L
T
S
T
R
E
E
T
E
R
W
I
A
D
09-27-2019
VAMC DURHAM UPGRADE POWER
DISTRIBUTION SYSTEM BLDG 9
558-18-277
DURHAM, NC
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and
Facilities
Management
PROJECT MANAGER:
ACG Project
NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705
18-238
CONSTRUCTION DRAWINGS
FULLY SPRINKLERED
Structural Engineer:
KEY PLAN:
AREA OF WORK
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
E-102
MAHMAH
PARTIAL ELECTRICAL PLAN
CHILLER PLANT (BLDG 9)
A. SEE SHEET E-001 FOR CONDUCTOR AND
RACEWAYS SIZING.
B. ALL WORK IS TO BE SCHEDULED WITH COR.
WORK SCHEDULES WILL BE AT THE
DISCRETION OF THE HOSPITAL AND COR.
0 4' 8' 16'
FINISHED GRADE
M
A
X
GROUND ROD SHALL NOT BE
ANGLED MORE THAN 30° FROM
VERTICAL. ANGLE AWAY FROM
SHELTER OR PAD WHERE
POSSIBLE.
GEC
3 /4" DIAMETER
COPPER CLAD
STEEL GROUND
SERVICE
EQUIPMENT
MAIN BONDING JUMPER
CONDUCTOR-#2/0 AWG
B
G
N
GROUNDING ELECTRODE CONDUCTOR
NOTES:
1. GROUNDING CONDUCTORS AND MAIN BONDING JUMPER SHALL BE
BARE COPPER UNO AND SHALL BE SIZED AS INDICATED IN
ELECTRICAL RISER.
3/4" PVC CONDUIT-TYPICAL FOR GROUNDING
ELECTRODE CONDUCTOR CONDUIT
NEUTRAL (GROUNDED
CONDUCTOR) BAR
BOND EQUIPMENT
GROUNDING CONDUCTOR
TO SERVICE RACEWAY(S)
BOND TO METAL UNDERGROUND
WATER PIPE ON SUPPLY SIDE OF
MAIN COLD WATER VALVE
BOND TO STRUCTURAL STEEL VERTICAL COLUMN (NOT
BEAM) OR METAL FRAME OF BLDG., WHERE EFFECTIVELY
GROUNDED-CONDUCTOR SHALL BE CONTINUOUS FROM
GROUND BAR TO WATER PIPING
BOND
CONDUCTOR TO
RACEWAY-TYPICAL
BOND TO 3-3/4" x 10' COPPERCLAD STEEL
DRIVEN GROUND ROD(S)- SPACE 10'
APART EQUILATERALLY
GROUNDING ELECTRODE CONDUCTOR
GROUND BAR-BOND TO ENCLOSURE
3/0 AWG
6 AWG
6 AWG
6 AWG
3/4" X 10' GROUND ROD,
INSTALL INSIDE
CONCRETE PAD
OPENING (GROUNDING
CONNECTIONS SHALL
BE ACCESSIBLE)
NOTES:
1. BOND 15 KV ELBOW CONNECTORS.
AND PRIMARY CABLE SHIELDS TO
THE GROUNDING CONDUCTOR.
2. IF THE RESISTANCE OF THE
GROUND ROD EXCEEDS 25 OHMS,
INSTALL AN ADDITIONAL GROUND
ROD AT LEAST 10' AWAY.
INTER-CONNECT THE TWO USING
3/O AWG BARE TINNED CU
GROUND WIRE.
3. COMPLETE INSTALLATION MUST
BE IN COMPLIANCE WITH THE
NATIONAL ELECTRICAL SAFETY
CODE, ANSI C2.
CONNECT TO SWITCH
WITH 3/0 AWG
COPPER
TYPICAL PVC
CONDUIT
ENTRANCE
WITH BELL END
CONNECT TO CABLE
SHIELD WITH 6 AWG
COPPER AND BOND
TO 3/O AWG
GROUNDING
CONDUCTOR.
BOND
CONCRETE PAD
3/4"' X 10'
COPPER-CLAD
STEEL GROUND
ROD
3/0 AWG BARE
CU GROUNDING
CONDUCTOR
(TYP.)
6 AWG
(TYPICAL)
3/0 AWG
BOND TO STRUCTURAL STEEL VERTICAL COLUMN (NOT
BEAM) OR METAL FRAME OF BLDG., WHERE EFFECTIVELY
GROUNDED-CONDUCTOR SHALL BE CONTINUOUS FROM
GROUND BAR TO WATER PIPING
6 AWG
(TYPICAL)
09-27-2019
VAMC DURHAM UPGRADE POWER
DISTRIBUTION SYSTEM BLDG 9
558-18-277
DURHAM, NC
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and
Facilities
Management
PROJECT MANAGER:
ACG Project
NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705
18-238
CONSTRUCTION DRAWINGS
FULLY SPRINKLERED
Structural Engineer:
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
GROUND ROD DETAIL
NTS
ELECTRICAL DETAILS AND
SCHEDULES
E-103
MAHMAH
SERVICE ENTRANCE GROUNDING DETAIL
NTS
MV TERMINAL CABINET GROUNDING DETAIL
NTS