36C24620R0035-0008001.pdf

PDF Posted

Attached to
Z2DA--Project 652-203, Construct New EP Laboratory Federal contract opportunity
Solicitation number
36C24620R0035
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document contains a presolicitation notice and responses to questions regarding a federal contract opportunity. The Department of Veterans Affairs Hunter Holmes McGuire VA Medical Center is soliciting proposals for Project 652-203 to construct a new Electrophysiology Laboratory. The estimated value is between $2-5 million. The NAICS code is 236220 and it is set aside 100% for SDVOSB. The solicitation is expected to be available on or around February 23, 2020 with proposals due at least 30 days later. It will be posted on SAM.gov. A site visit will be outlined in the solicitation. The document also includes responses to contractor questions on civil and environmental CQC representatives, third party QC personnel, equipment details, and replacing an electric strike with a magnetic lock.

36C24620R0035 0008 Additional RFI Responses - 652-203 New EP Lab.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Project 652-203, Construct New EP Laboratory, newest first.
File Type Posted
36C24620R0035-0010000.docx DOCX document
36C24620R0035-0010001.pdf PDF
36C24620R0035-0009002.pdf PDF
36C24620R0035-0009001.pdf PDF
36C24620R0035-0009000.docx DOCX document
36C24620R0035-0008002.pdf PDF
36C24620R0035-0008000.docx DOCX document
36C24620R0035-0008003.pdf PDF
36C24620R0035-0007000.docx DOCX document
36C24620R0035-0007001.pdf PDF
36C24620R0035-0007002.pdf PDF
36C24620R0035-0006001.pdf PDF
36C24620R0035-0006000.docx DOCX document
36C24620R0035-0006002.pdf PDF
36C24620R0035-0005003.pdf PDF
36C24620R0035-0005000.docx DOCX document
36C24620R0035-0005001.pdf PDF
36C24620R0035-0005002.pdf PDF
36C24620R0035-0005004.pdf PDF
36C24620R0035-0004002.pdf PDF
36C24620R0035-0004001.pdf PDF
36C24620R0035-0004000.docx DOCX document
36C24620R0035-0003000.docx DOCX document
36C24620R0035-0002000.docx DOCX document
36C24620R0035-0002001.pdf PDF
36C24620R0035-0002002.pdf PDF
36C24620R0035-0002003.pdf PDF
36C24620R0035-0001001.pdf PDF
36C24620R0035-0001002.pdf PDF
36C24620R0035-0001000.docx DOCX document
36C24620R0035-002.docx DOCX document
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request for Proposals 36C24620R0035

Project: 652-203, Construct New Electrophysiology (EP) Laboratory

Additional Responses to RFIs

1. Question: Specification 014500 – 3.4 – C calls for specific technical CQC personnel to be directly employed by the General Contractor and cannot be employed by a supplier or subcontractor on this project. The technical trades include civil, mechanical, electrical, structural, architectural, environmental, submittals, concrete, TAB and Design Quality control.

a. This project does not have heavy civil work. Is a Civil CQC representative required?

Answer: Civil CQC is not required.

b. This project does not have Environmental work. Is an Environmental representative required?

Answer: Environmental CQC is not required.

c. This project is not a Design-Build project. Is a Design QC manager required?

Answer: Design QC manager is not required.

2. Question: Specification 014500 – 3.4 – C calls for specific technical CQC personnel to be directly employed by the General Contractor and cannot be employed by a supplier or subcontractor on this project. The technical trades include civil, mechanical, electrical, structural, architectural, environmental, submittals, concrete, TAB and Design Quality control.

a. Can the technical QC personnel be contracted by the GC as 3rd party QC (not an employee of a supplier or subcontractor performing work on the project) for this project?

Answer: 3rd party QC will fulfill the requirements.

3. Can you please provide the product data/equipment connection details for the Siemens equipment that is to be provided by the VA?

Answer: The drawings have been requested from the Service currently responsible for them.

4. Is there an environmental report available for the asbestos abatement to be done?

Answer: AE Response: See attached Survey Report. Asbestos Abatement should follow

Spec Section 02 82 11 Traditional Asbestos Abatement and the Hazardous Materials

Abatement drawings HA101i and HA101. VA response: Please reference attached survey.

5. Hardware set 10H calls for an Lead Lined Electric Strike. We have been unable to locate any manufacturer that has a lead lined electric strike. Please advise.

Answer: AE Response: We were following the VA Masterspec for that door’s hardware needs. Other jobs we have done that use similar lead lined doors and frames use a magnetic lock instead of an electric strike. Both can be activated via prox card. The mag lock cut sheet is attached (M680E) for reference. We would recommend the mag lock. VA response: example attached see A/E response.

File details come from the government source that posted it. Updated .