This document contains a presolicitation notice and responses to questions for a construction project at a VA medical center. The Department of Veterans Affairs is seeking a contractor to construct a new electrophysiology laboratory at the Hunter Holmes McGuire VA Medical Center in Richmond, Virginia for an estimated cost between $2,000,000 and $5,000,000. The project is to be completed within 580 calendar days of the notice to proceed. The NAICS code for the project is 236220 and it is set aside 100% for SDVOSB contractors registered in the Vendor Information Pages VetBiz database. The solicitation is expected to be released on or around February 23, 2020 with proposals due at least 30 days later as disclosed in the solicitation. The notice provides contact information for an optional site visit. Drawings and specifications will be made available with the solicitation.
36C24620R0035 0004 RFP Questions and Answers - 652-203 New EP Lab_AE Response.pdf
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AE Responses dated 3/30/20
Request for Proposals 36C24620R0035
Project: 652-203, Construct New Electrophysiology (EP) Laboratory
Responses to RFP Questions
1. Question: The plan sets provided within the bid documents are 8.5”x11” page size? Can you please provide a full size drawing set?
Answer: The Bid Document Drawings are sized at 30”x 42”. We have provided another set to the VA.
2. Question: There are no exterior elevations shown and only one wall cut showing 2" EIFS but no other plans where we can see the areas of EIFS application. Can you please provide clarification as to the locations of required EIFS application?
Answer: Elevations have been provided. See Elevations 1, 2, & 3 on Dwg. AE201. Follow floor plans and sections for dimensions.
3. Question: Section 230923 page 3; Section 1.1 E. Responsibility Table - Please confirm if Div 26
Electrical is providing power for the terminal vav boxes/controllers and air valves/controllers. Table shows division 26 but I don’t see anything on Electrical Drawings to provide power to the VAVs and
Air Valves.
Answer: The terminal controllers operate on 24-volt power. The HVAC control panel will contain a central transformer(s) and the control wiring from the control panel to the controllers is by Div. 23.