CAT 6 Cable Installation - ICU - RFI Part B.pdf
PDF 90 KB Posted
- Attached to
- J099--Install CAT 6 Cable - ICU Federal contract opportunity
- Solicitation number
- 36C24620Q0622
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| CAT 6 Cable Installation - ICU - RFI Part A.pdf | ||
| WD 2015-4423 Rev 13.pdf | ||
| Attachment D - M Series Arm.pdf | ||
| Attachment A - Salisbury VAMC TeleICU Site Assessment.pdf | ||
| CAT 6 Cable Installation (FInal SOW).pdf | ||
| Attachment G - Monitor.pdf | ||
| Combined Synopsis-CAT 6 Cable Installation.pdf | ||
| Attachment C - Universal Button.pdf | ||
| 36C24620Q0622.docx | DOCX document | |
| Attachment I - Remote Camera.pdf | ||
| Attachment F - Media Link IV.pdf | ||
| Attachment B - Ceiling Speaker.pdf | ||
| Attachment E - M Series Flush Mount.pdf | ||
| Attachment H - ProMCS 1500.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAT 6 Project – ICU Additional Questions
Q: Will each unit/room be barricaded off as a whole or will individual infection control protocols be in place for each room? It is assumed that if the whole section will not be barricaded that a containment cube will be required. Can we get a copy of the infection control procedures & requirements (mats, negative pressure, etc)?
A: You will have the entire room.
Q: Are you providing all hardware and equipment? If so, will we need to install any of the equipment?
A: Contractor is not responsible for providing any A/V listed hardware or installation of that hardware for this requirement.
Q: What is the “backing” referred to for the AV server? Is it referring to plywood backing? And in-wall or on surface of existing walls?
A: Backing is referred to structural support if needed based off A/V equipment installation location listed in site assessment. Preferred backing will be in-wall if it is determined that it is needed based off cut sheets provided.
Q: What type of electrical conduit is needed? Can it be MC(flex), hospital grade MC, or does it need to be EMT conduit? Will this be a dedicated emergency circuit or tie into an existing emergency circuit?
A: EMT. Dedicated
Q: Will the electrical outlets need to be connected to the panel in the electrical closet or tied into existing local circuits?
A: Connected to Closet
Q: Is there currently room on the existing patch panel in the data rack to accommodate the 10 new Cat
6?
A: Plan on installing a separate panel.
Q: What cabling will be needed for the universal buttons?
A: Refer to cut sheets provided for cabling questions.