A712 SUBSTATION.pdf

PDF 62 KB Posted

Attached to
J059--AMENDMENT 0002 POST RFI INFORMATION BALTIMORE VA MEDICAL CENTER
Solicitation number
36C24526Q0229
Issued by

About this file

This is a technical drawing and equipment specification document for a customer-owned electrical substation serving the United States Department of Veterans Administration V.A. Medical Center located at 10 N. Greene Street, Baltimore, MD 21201. The document provides detailed schematics and a material list for an indoor metal-clad switchgear installation operating at 13.8 kV with a 1200 ampere capacity and 500 MVA rating. The substation receives power from three separate feeders: Paca Street Substation (#13709), Greene Street Substation (#7835), and Paca Street Substation (#13708), with the system designed to support automatic transfer capability between normal and standby feeders.

The equipment specification includes 20 itemized components encompassing vacuum circuit breakers, current transformers in multiple ratios (1000:5A, 1200:5A, and 600:5A), potential transformers, surge arresters and suppressors, cable terminations, control power transformers, grounding points, and a ground sensor current transformer. Key operational features include electrical interlocking mechanisms that prevent paralleling of multiple supply feeders and between normal and standby feeders, with a key permissive switch available to Baltimore Gas & Electric Company personnel for controlled parallel operation. The system includes surge protection rated at 12 kV distribution class and 15 kV maximum line-to-line, with General Electric equipment specified throughout. The drawing ID is 712, Revision 5-02/02/11, with engineer S. Founds credited.

View the file

Other files

File Type Posted
36C24526Q0229 0002.pdf PDF
36C24526Q0229 0002_1.docx DOCX document
36C24526Q0229 0001.pdf PDF
36C24526Q0229 0001_1.docx DOCX document
90481 - 512-23-109 - Baltimore Panel Study - Final Report - 20250121.pdf PDF
VHA Directive1028 Facility Electrical Power Systems.pdf PDF
WAGE DETERMINATION_Service Contract Act WD.pdf PDF
36C24526Q0229.pdf PDF
36C24526Q0229_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BALTIMORE GAS & ELECTRIC COMPANY

CUSTOMER OWNED SUBSTATION

UNITED STATES GOVERNMENT

VETERANS ADMINISTRATION

V.A. MEDICAL CENTER

10 N. GREENE STREET

BALTIMORE, MD 21201

CUSTOMER ID # 712

SHEET 2 of 3

ITEM # DESCRIPTION

1 1 - Vacuum Circuit Breaker, GE "VB1-13.8-500-2", 15 kV, 1200 A, 95 kV BIL, 18 kA Short Circuit, 37 kA Close & Latch, 3-Pole, 48 V DC Close & Trip.

2 3 - Current Transformers, 1000:5 A Single Ratio.

(OVERCURRENT TRIP & AUTOMATIC TRANSFER BLOCKING)

3 3 - Current Transformers, 1200:5 A Single Ratio. (BUS

DIFFERENTIAL TRIP)

4 3 - Current Transformers, 600:5 A Single Ratio.

5 2 - Potential Transformers, GE "JVM-5", 14400:120 V, & 4 - Fuses, GE

"EJ-1", 14.4 kV, 0.5 A.

6 1 - Control Power Transformer, 15 KVA, 1-Ph, 13300-120/240 V, & 2 -

Fuses, GE "EJ-1", 15 kV, 5 A, & 1 - Circuit Breaker, 230 V, 100 A, 2-Pole.

7 3 - Surge Arrresters, 12 kV Distribution Class. (COMPANY-OWNED) 8 3 - Cable Terminations. (COMPANY-OWNED) 9 3 - Current Transfomers, GE "JKM-110", 100:5 A.

(COMPANY METER)

10 3 - Potential Transformers, GE "JVM-5", 8400:120 V.

(COMPANY METER)

11 3 - Fuses, GE "EJ-1", 14.4 kV, 0.5 A.

(COMPANY METER)

12 3 - Grounding Points.

13 3 - Surge Suppressors, 15 kV Max L-L, GE OL 0144D2156.

14 3 - Cable Terminations.

15 1 - Ground Sensor Current Transformer, 50:5 A.

16 1 - Indoor GE POWER/VAC Metal-Clad Switchgear, 13.8 kV, 1200 A, 500

MVA, 3-PH, 95 kV BIL, GE S.O. 975451.

17 AUTOMATIC TRANSFER SYSTEM WILL TRANSFER STAND-BY FEEDER

TO EITHER BUS AFTER LOSS OF ASSOCIATED NORMAL FEEDER.

BALTIMORE GAS & ELECTRIC COMPANY

CUSTOMER OWNED SUBSTATION

UNITED STATES GOVERNMENT

VETERANS ADMINISTRATION

V.A. MEDICAL CENTER

10 N. GREENE STREET

BALTIMORE, MD 21201

CUSTOMER ID # 712

SHEET 3 of 3

18 THE TWO STAND-BY FEEDER BREAKERS ARE ELECTRICALLY

INTERLOCKED TO PREVENT PARALLELING THE THREE SUPPLY

FEEDERS.

19 NORMAL FEEDER BREAKER AND ASSOCIATED STAND-BY FEEDER

BREAKER ARE ELECTRICALLY INTERLOCKED TO PREVENT

PARALLELING NORMAL AND STAND-BY FEEDER.

20 KEY PERMISSIVE SWITCH AVAILABLE TO BG&E PERSONNEL FOR

PARALLELING EITHER NORMAL FEEDER WITH STAND-BY FEEDER.

File details come from the government source that posted it. Updated .