90481 - 512-23-109 - Baltimore Panel Study - Final Report - 20250121.pdf

PDF 9 MB Posted

Attached to
J059--AMENDMENT 0002 POST RFI INFORMATION BALTIMORE VA MEDICAL CENTER
Solicitation number
36C24526Q0229
Issued by

About this file

This is a Final Report of Findings for an electrical panel study of the Baltimore VA Medical Center (VAMC) conducted by DavEnergy Solutions under Contract No. 36C24523D0102, Project 512-23-109, dated January 21, 2025. The comprehensive 1,005,000 square-foot facility study systematically examined electrical systems across four quadrants (A, B, C, D) organized by 11 levels (3 parking levels, basement, and 8 floors) to identify deficiencies and compliance issues with applicable codes including the 2020 National Electrical Code, NFPA standards, and VA design manuals.

The study identified 97 total deficiencies categorized by quadrant and room number, with the most prevalent issues being undersized panel covers (affecting multiple panels across all quadrants with estimated costs of $3,500 per remediation), missing or improper equipment labels ($250 per item), panels positioned directly below piping requiring leak trays ($500 per installation), and inadequate working space around electrical equipment requiring busway cover removal ($750–$1,500 per location). Additional findings include difficult-to-open electrical service bay doors, emergency panel identification challenges, NEC violations such as undersized fire pump circuit breakers, storage items obstructing electrical spaces, and missing ground cable connections. The report provides single-line diagrams, final panel schedules documenting circuit assignments across all quadrants, and photographic documentation of representative deficiencies. Estimated remediation costs for identified issues range from $150 to $3,500 per deficiency, with many items marked "In Progress" or "Currently being evaluated by station personnel," indicating ongoing coordination with facility management for resolution.

View the file

Other files

File Type Posted
36C24526Q0229 0002.pdf PDF
36C24526Q0229 0002_1.docx DOCX document
36C24526Q0229 0001.pdf PDF
A712 SUBSTATION.pdf PDF
36C24526Q0229 0001_1.docx DOCX document
VHA Directive1028 Facility Electrical Power Systems.pdf PDF
WAGE DETERMINATION_Service Contract Act WD.pdf PDF
36C24526Q0229.pdf PDF
36C24526Q0229_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Maryland HealthCare System

Contract Number: 36C24523D0102

Project: 512-23-109

BT Electrical Panel Study

Final Report of Findings

Date: January 21, 2025

For:

Baltimore VA Medical Center 10 N Greene St.

Baltimore, MD 21201

Attn: Liana J. Holland Contracting Officer Liana.Holland@va.gov

Author:

Jaime Arellano

P.E.

Electrical Engineer jaime.arellano@davenergy.com Phone: 559-759-4443

Project Number: 512-23-109 VA Maryland HealthCare System - VISN5 – Baltimore Baltimore Electrical Panel Study 01/21/2025 FInal Report of Findings

BASIS OF DESIGN

1.1.0 FACILTY DESCRIPTION

1.1.1 SITE VISIT SUMMARY NARRATIVE

1.1.2 SUMMARY OF ISSUES

1.1.3 CRITERIA/CODES

Appendix A – Findings Appendix B – Final Single line Drawings Appendix C – Final Panel Schedules Appendix D – Final Photo Log

1.1.0 FACILITY DESCRIPTION

This section provides an overview of the Baltimore VA hospital facility situated at 10 N Greene St, Baltimore, MD 21201. The hospital comprises three parking levels, followed by a basement level and eight additional levels above with a total of 1005000 ft2 excluding interstitial space. The facility is organized into four quadrants—A, B, C, and D. Quadrant A is located in the southeast, quadrant B in the southwest, quadrant C in the northwest, and quadrant D in the northeast. Electrical panels throughout the hospital are systematically named based on their respective levels and quadrants.

1.1.1 SITE VISIT SUMMARY NARRATIVE

Davenergy, in collaboration with M.C. Dean employees, spent a month on-site gathering crucial facility electrical system information. The VA supplied a site plan and a single-line diagram, streamlining the data collection process. The first site visit was on October 17, 2023 in which we met with Steve Gorman the electrical shop supervisor at the time to discuss our plan to investigate the electrical systems by quadrants. In this week we started on quadrant A and moved up from the parking levels to the 8th floor. Steve Gorman provided us with a radio and keys to open every electrical room, so we continued like this all they to the end of week two which was on October 27, 2023 where we finished data collection for quadrant B.

The second site visit occurred on November 28, 2023 and was performed in a similar fashion to previous site visit, so quadrant C was investigated by starting in room 1PC-100 which is an electrical service bay and moved up to the 8th floor. Quadrant D was started on December 04, 2023 with service bay 1D-100 and ended in the 8th floor on December 07, 2023. Additional site visits have been performed by M.C. Dean to trace each branch circuit in the electrical system to have updated panel schedules.

1.1.2 SUMMARY OF ISSUES

A notable concern identified was the difficulty in opening the doors to the electrical service bays, which could potentially impede response time during emergencies. Additionally, addressing the issue of labeling the emergency panel with a red label was highlighted to ensure quick identification, particularly when all panels have a black background. Another concern is the fire pump undersized circuit breaker, this is an NEC violation, but Davenergy is working on the switchgear replacement project with project number 512-23-102, so this violation will be addressed. The most common issues found were panel covers that are too small for the enclosure and equipment missing labels. There was a total of 97 issues identified please see Appendix A which provides a comprehensive list of all identified issues and deficiencies, categorized by quadrant and room number for easy reference.

FIGURE 1: SITE SATELLITE VIEW

1.1.3 CRITERIA/CODES

2018 International Building Code – ICC – First Printing: August 2017

2018 International Existing Building Code – ICC - First Printing: August 2017

Structural Design Manual for Hospital Projects – VA TIL – February 1, 2014

HVAC Design Manual – VA TIL - November 1, 2017, Rev. March 1, 2022

Plumbing Design Manual – VA TIL – June 1, 2022

Electrical Design Manual – VA TIL – December 1, 2019

Architectural Design Manual – VA TIL – August 1, 2014

Physical Security and Resiliency Design Manual – VA TIL – October 1, 2020, Rev. July 1, 2022

2008 A/E Submission Requirements PG-18-15, Volume C

Fire Protection Design Manual – VA TIL – June 1, 2021 o 2021 NFPA 1: Fire Code o 2021 NFPA 3: Standard for Commissioning of Fire Protection and Life Safety Systems o 2021 NFPA 4: Standard for Integrated Fire Protection and Life Safety System Testing o 2022 NFPA 10: Standard for Portable Fire Extinguishers o 2022 NFPA 13: Standard for the Installation of Sprinkler Systems o 2022 NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection o 2020 NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems o 2020 NFPA 70: National Electrical Code o 2021 NFPA 70E: Standard for Electrical Safety in the Workplace o 2022 NFPA 80: Standard for Fire Doors and Other Opening Protectives o 2021 NFPA 99: Health Care Facilities Code o 2021 NFPA 101: Life Safety Code o 2021 NFPA 220: Standard on Types of Building Construction o 2022 NFPA 241: Standard for Safeguarding Construction, Alteration, and Demolition Operations o 2022 NFPA 291: Recommended Practice for Fire Flow Testing and Marking of Hydrants

Draft report of findings

Appendix A – Findings

Item No. Quadrant ROOM Description Solutions Potential Cost

1 A,B,C,D All Unable to quickly identify emergency panels. Clearly color code emergency equipment $250 per piece of equipment

2 A 1PA-101 The electrical substation room doors are difficult to open. Install new locks and with keys Currently being evaluated by station personnel

3 A 1PA-102 Fire pump circuit breaker is undersized. Replace trip with a 225A trip unit based on the 207

LRA

$500

4 A 1PA-101 The room is being used as storage which has a cart close to the transformer and grounding bar wall.

Remove cart from room

5 A 1PA-101 ATS 27, which is now a junction box, has many cables packed inside the enclosure and boxes.

Remove unnecessary cables as this a short circuit hazard $600 - $800

6 A 1PA-101 Panelboard P1A-H sections 1 & 2 do not properly cover existing panelboard backbox. Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

7 A 1PA-101 Panelboard P1A-E3 sections 1 & 2 do not properly cover existing panelboard backbox. Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

8 A Outside 1PA-101 Transformer feeding P1A-HB has no label. Label the 150kVA transformer $250

9 A Outside 1PA-101 Transformer feeding P1A-HB has no disconnect within sight. According to NEC 450.14 add a disconnect within sight of the transformer or field mark the location of the disconnect which is capable of being locked in the open position

In Progress

10 A Outside 1PA-101 Panelboard P1A-ERC has cable terminated with tape. Remove cables or terminate with wire nuts $150 - $600

12 A BA113 The room is being used as storage which has a pallet jack, boxes and chairs. Remove storage from service bay

13 A BA113 Panels BA-E3B and BA-HB are directly below piping which is in the dedicated electrical space.

Install leak tray to protect electrical panels $500

14 A BA113 Transformer feeding disconnects P1A-ERC and BA-ERT is missing label. Label the transformer $250

15 A BA113C Junction box labeled FDR AE2-1 does not have a ground cable connected to the case Install an EGC to the junction box $500

16 A BA113 disconnect feeding transformer T6 which feeds disconnects P1A-ERC and BA-ERT has no label

Label the disconnect $250

17 A BA Kitchen Receptacle is on the ground level in a kitchen environment, with the only support being the conduit.

Replace with a GFCI and cord drop.

$250

18 A 1A-113C Panels 1A-E1, 1A-E1A are directly below piping which is in the dedicated electrical space

Install leak tray to protect electrical panels $500

19 A 1A-113C Disconnect T3/A-E3 is directly below piping which is in the dedicated electrical space Install leak tray to protect disconnect $500

20 A 1A-113C Disconnect T3/A-E3 is mislabeled Label the disconnect. Correct name is T3/1A-E3. $250

21 A 1A-113C Junction box FDR AE3-1 is directly below piping which is in the dedicated electrical space

Install leak tray to protect junction box $500

22 A 2A-114 Panel 2A-HA are directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500

23 A 2A-114 Panel 2A-HA has no label, pencil was used to write name on cover Install proper label $250

24 A 2A-114C transformer feeding panel 2A-L1 is missing label Label the transformer $250

25 A 3A-113 The room is being used as storage which has boxes Remove storage from service bay

26 A 3A-113C Transformer feeding panel 3A-L1 is missing label Label the transformer $250

27 A 4A-113C Transformer feeding panel 4A-L1 is missing label Label the transformer $250

28 A 4A-113C Transformer feeding panel 4A-E3 is missing label Label the transformer $250

29 A 5A-127 Panel 5A-HA and 5A-E3A are directly below piping which is in the dedicated electrical space

Install leak tray to protect electrical panels $500

30 A 5A-127 The room is being used as storage which has boxes Remove storage from service bay

31 A 6A-133 Panel 6A-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500

32 A 7A-101 Panel 7A-E3 has tape covering circuit breaker slots 57 and 59 Install proper cover $150

33 A 8A-102 The room is being used as storage which has cabinets and a table Remove storage from room

34 A 8A-102 This room requires two paths of egress the single door on the south wall is locked Make a door on the east wall at opposite side on the In Progress

35 B 1PB-101 2500kVA transformer has liquid build up underneath Verify the transformer is not leaking oil $500

36 B UPS-RM None of the equipment in the room is labeled Label the disconnect, panels, transformer and UPS $1,000

Electrical Deficiencies

37 B BB-101 Panelboard BAB-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

38 B BB-137 The room is being used as storage which has a cart Remove storage from service bay

39 B BB-137C The working space between panel BB-E1 and 800A busway feeding transformer T4 is not up to code

Remove the cover around the busway to increase the working distance $1,500

40 B BB-137C Panel BB-E3 has no label, pencil was used to write name on cover Install proper label $250

41 B 1B-141 Lights close to Panel 1B-HA and 1B-E3A do not work Replace light bulbs

42 B 1B-141 The room is being used as storage which many boxes Remove storage from service bay

43 B 1B-141C The working space between panel 1B-E1 and 800A busway feeding disconnect 1A-

BE2 and 1B-BE2 is not up to code

Remove the cover around the busway to increase the working distance $750

44 B 1B-141C The working space between panel 1B-E1A and 800A busway feeding disconnect 1A-

BE2 and 1B-BE2 is not up to code

Remove the cover around the busway to increase the working distance $750

45 B 1B-141C Panelboard 1B-RB cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

46 B 1B-141C Panelboard 1B-RB square wireway is open Close the wireway $250

47 B 2B-110 Panelboard 2B-E3A has stored materials infront preventing access remover materials infront of panel. According to the

NEC at least a 3.5 ft clearance is needed.

48 B 2B-118 Panel 1B-H will be in Panel 1B-L working space in small section There is not enough space in the room to move any panels so its recommended to not do any live work on panel 1B-L

49 B 2B-118 Working space for Panel 2B-HB and 2B-E3B is not up to code because the air handling unit is too close

Relocate Panels In Progress

50 B 2B-118C The wire way for Panel 2B-E1 is blocked by panel 2B-E1A There is not enough space in the room to move any panels and since they are emergency panels an in-depth analysis is needed.

51 B 2B-118C The working space between panel 2B-E1 and the 800A busway is not up to code Remove the cover around the busway to increase the working distance $1,500

52 B 2B-118C Transformer feeding panel 2B-LX is missing label Label the transformer $250

53 B 4B-182 Panel 4B-E3A is directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500

54 B 4B-182C Panelboard 4B-E1A cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

55 B 4B-182C The working space between panel 4B-E1A and busway is not up to code Remove the cover around the busway to increase the working distance $1,500

56 B 5B-182 circuit breaker disconnect for panel 5B-HA is not accessible Relocate the disconnect In Progress

57 B 6B-129 The room is being used as storage which many boxes Remove storage from service bay

58 B 6B-129 Panel 6B-HA and 6B-E3A are directly below piping which is in the dedicated electrical space

Install leak tray to protect electrical panels $500

59 B 6B-129C The working space between panel 6B-E1 and busway is not up to code Remove the cover around the busway to increase the working distance $1,500

60 B 7B-100 Lights close to disconnect EMCC-7B do not work Replace light bulbs

61 B 7B-100 It is hard to access motor riser B junction box 8A-HB Relocate junction box and disconnect In Progress

62 C 1PC-100 The room is being used as storage which has electrical equipment, small cranes Remove storage from room

63 C 1C-100 working space for Panel 1C-E3A is not up to code Relocate Panel In Progress

64 C 1C-100 Busway disconnect labeled 1C-HA is not accessible due to a light fixture Relocate light fixture In Progress

65 C BC-101B Transformer feeding panel BC-LB has no label Label the transformer $250

66 C BC-101B There is water damage on top of transformer T4 feeding panel BC-LB Determine source of water to install a leak tray $500

67 C BC-101C Panel BC-LA has no label, pencil was used to write name on cover Install proper label $250

68 C BC-101C Transformer feeding panel BC-L has no label Label the transformer $250

69 C 2C-124 Circuit breaker in slot 13,15,17 is not properly mounted to panel Mount the circuit breaker correctly $150

70 C 3C-100 Panelboard 3C-E3A cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

71 C 3C-100 Lights close to Panel 3C-E3A do not work Replace light bulbs

72 C 3C-100C Panel 3C-L does not have enough working space, removing the busway cover will not provide enough space

There is not enough space in the room to move any panels so an in-depth analysis is needed.

73 C 3C-100C Panelboard 3C-L2 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

74 C 4C-100C Panelboard 4C-E2 and 4C-L1 cover are too small for the enclosures Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

75 C 4C-100C Panel 4C-L1 does not have enough working space, removing the busway cover will not provide enough space

There is not enough space in the room to move any panels so an in-depth analysis is needed.

76 C 5C-114 The room is being used as storage which consist of boxes Remove storage from service bay

77 C 5C-114C Panel 5C-E3A is missing circuit breaker space covers for slots 2,6,8 Install the missing circuit breaker space covers $75

78 C 5C-114C A small section of Panel 5C-H does not have adequate working space Move panel 5C-E3A and 5C-H to the left In Progress

79 C 6C-100C Panelboard 6C-L1 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

80 C 7C-100 The label from EMCC-7C is using tape to hold it up Replace the label $250

81 D BD-116 The room is being used as storage which consist of many boxes and carts Remove storage from service bay

82 D BD-116A Panel BD-L1 does not have enough working space due to the busway cover Remove the busway cover $1,500

83 D BD-126 The room is being used as storage Remove storage from electrical closet

84 D 1D-166A Panelboard 1D-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

85 D 2D-126 Panel 2D-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500

86 D 2D-126C Panelboard 2D-E1 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

87 D 3D-119C Panelboard 3D-L cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

88 D 3D-119C Panel 3D-L does not have enough working space due to the busway cover Remove the busway cover $1,500

89 D 3D-119C Panel 3D-L1 is missing circuit breaker space cover for slot 30 Install the missing circuit breaker space cover $75

90 D 4D-154 Panel 4D-HA has no label, marker was used to write name on tape Install proper label $250

91 D 4D-154 Panel 4D-HA has no panel schedule Create a panel schedule $500

92 D 4D-154A Panel 4D-L does not have enough working space due to the busway cover Remove the busway cover $1,500

93 D 5D-130 There is no access to transformer feeding UPS due to abandoned UPS Remove abandoned UPS In Progress

94 D 5D-130C Panel 5D-E1A does not have enough working space due to the busway cover Remove the busway cover $1,500

95 D 6D-158 Panel 6D-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500

96 D 7D-100 Panel 7D-E1 is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500

97 D 7D-100 Panelboard 7D-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.

$3,500.00

Draft report of findings

Appendix B – Final Single line Drawings

600A AIR INTERRUPTER SWITCH

600A AIR INTERRUPTER SWITCH

1500 KVA

13.2Δ- 480/277Y 65.6A - 1805A

80E

F1

F4

SWITCHGEAR "C"

DOUBLE - ENDED

3000A,3P,4W

480/277,65 KAIC

SEE DWG. E-604

FOR CONTINUATION

SUBSTATION "C"

1500 KVA

13.2Δ- 480/277Y 65.6A - 1805A

600A AIR INTERRUPTER SWITCH

600A AIR INTERRUPTER SWITCH

1500 KVA

13.2Δ- 480/277Y 65.6A - 1805A

80E

80E

F1

F4

SWITCHGEAR "B"

DOUBLE - ENDED

3000A,3P,4W

480/277,65 KAIC

SEE DWG. E-603

FOR CONTINUATION

SUBSTATION "B"

2000 KVA

13.2Δ-4160/2400Y

87.5A - 278A

600A AIR

INTERRUPTER

SWITCH

2000 KVA

13.2Δ- 480/277Y 87.5A - 2405A

2000 KVA

13.2Δ- 480/277Y 87.5A - 2405A

F6

F3

100E

F6

F3

MVA

MVA

MVA

MVA

100E

100E

15KV 4"C-(3)#2/0 + #2 GND 15KV 4"C-(3)#2/0 + #2 GND

15KV 4"C-(3)#4/0 + #2 GND 15KV 4"C-(3)#4/0 + #2 GND

15KV 4"C-(3)#4/0 + #2 GND

15KV 4"C-(3)#4/0 + #2 GND

600A AIR

INTERRUPTER

SWITCH

600A AIR

INTERRUPTER

SWITCH

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

1.

CONTINUATION ON SHEET E-601.3

Department of Veteran Affairs

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SINGLE LINE DIAGRAM MEDIUM VOLTAGE

AutoCAD SHX Text

AutoCAD SHX Text E-601.1

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

AutoCAD SHX Text 1/21/25

SUBSTATION "F"

SINGLE-ENDED

CHILLER, 553KW - 3Ø, 4160V. (FLA. 87A.)

CHILLER, 553KW - 3Ø, 4160V. (FLA. 87A.)

CHILLER, 325KW - 3Ø, 4160V. (FLA. 87A.)

SWITCHGEAR "G"

DOUBLE-ENDED

3000A,3P,4W

480/277,65 KAIC

SEE DWG. E-605

FOR CONTINUATION

80E

F5

80E

SUBSTATION "A"

600A AIR INTERRUPTER SWITCH

600A AIR INTERRUPTER SWITCH

600A AIR INTERRUPTER SWITCH

600A AIR INTERRUPTER SWITCH

F2

F5

80E

F2

SUBSTATION "D"

1500 KVA

13.2Δ - 480.277Y

65.6A - 1805A

1500 KVA

13.2Δ - 480.277Y

65.6A - 1805A

SWITCHGEAR "A"

DOUBLE-ENDED

3000A,3P,4W

480/277,65 KAIC

SEE DWG. E-602

FOR CONTINUATION

SWITCHGEAR "D"

DOUBLE-ENDED

3200A,3P,4W

480/277,65 KAIC

SEE DWG. E-605

FOR CONTINUATION

1500 KVA

13.2Δ - 480.277Y

65.6A - 1805A

15KV 4"C-(3)#2/0 + #2 GND

15KV 4"C-(3)#2/0 + #2 GND

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

1.

CONTINUATION ON SHEET E-601.4

Department of Veteran Affairs

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SINGLE LINE DIAGRAM MEDIUM VOLTAGE

AutoCAD SHX Text E-601.2

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

MVA

N.C.

BGE

13708

BGE

BGE

13709

NORMAL

FEED #1

MVA

N.O.

TIE A

STANDBY

FEED #3

MVA

N.O.

TIE B

STANDBY

FEED #3

MVA

N.C.

NORMAL

FEED #2

MVA

MVA

MVA

MVA

MVA

MVA

FUTURE FUTURE

F1 F2 F3 F4 F5 F6

13.2KV SWITCHGEAR

1500 KVA

13.2Δ- 480/277Y 65.6A - 1805A

80E

15KV 4"C-(3)#2/0 + #2 GND

15KV 4"C-(3)#2/0 + #2 GND

15KV 4"C-(3)#4/0 + #2 GND 15KV 4"C-(3)#4/0 + #2 GND

INCOMING SERVICE

INCOMING SERVICE

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

1.

CONTINUATION ON SHEET E-601.1

Department of Veteran Affairs

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SINGLE LINE DIAGRAM MEDIUM VOLTAGE

AutoCAD SHX Text E-601.3

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

BGE

13709

MVA

N.C.

NORMAL

FEED #2

MVA

MVA

F5 F6

80E

1500 KVA

13.2Δ - 480.277Y 65.6A - 1805A

15KV 4"C-(3)#2/0 + #2 GND

15KV 4"C-(3)#2/0 + #2 GND

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

1.

CONTINUATION ON SHEET E-601.2

Department of Veteran Affairs

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SINGLE LINE DIAGRAM MEDIUM VOLTAGE

AutoCAD SHX Text E-601.4

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

JB

JB

JB

JBJB

JB

JB

FDR #AE3-1FDR #AE2-1FDR #AE-1

FDR #AE3-1

FDR #AE3-1

FDR #AE3-1

FDR #AE3-1

ATS 13ATS 5ATS 1

250A

150A

600A 105A

ELEV. 4,5 & 6

JUNCTION BOX

(OLD ATS-27)

3 #250 MCM + #4

GW IN 2 1/2" C.

AE3-1

AE3-2

AE3-3

AE3-4

AE2-1

AE2-2

AE2-3

150A

150A

150A

150A

150A

250A

250A

800A

AE1-1

AE1-2

ATS-E3-A

4P-800A

ATS-E2-A

4P-260AATS-E1-A

4P-260A

(E) EMERGENCY SWITCHBOARD - "A"

JOCKEY PUMP

5 HP, 3PH-480V

JOCKEY PUMP CONTROLLER

FIRE PUMP CONTROLLER &

TRANSFER SWITCH

ATS 28

FIRE PUMP

25 HP, 3PH-480V

FDR. AE3-4

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12MAIN TIE K MAIN K

F2 2500A BUSWAY F5 2500A BUSWAY

(E) SWITCHBOARD "A"

A

A

SP

AR

E

0A

0A

SP

AR

E

0A

FU

TU

R E

0A

0A

0A

SP

AR

E

0A

FU

TU

R E

0A

A

A

A

LEVEL P1

K

2SECT

P1A- H

T3T3

T3

T3 T3

T3

T3

T3

T4

T5

T5

T5

T5

T5

T5

T6

T6

FDR #AE-1

FDR #AE-1

FDR #AE-1

FDR #AE-1

FDR #AE-1

FDR #AE2-1

FDR #AE2-1

FDR #A1 (PLUG-IN BUSWAY)

(1000A BUS)

LEVEL B

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

M1

M2

M3

A

BU

SW

AY

A

BU

SW

AY

0A

B U

SW

AY

125A

T5/AL

100A 4A-H

50A

50A

125A

100A

70A

100A 125A

125A

T5/A-LV, AB-L

1A-H/1AB-H

CAN'T OPEN

175A T6/L1

CAN'T OPEN

125A

T5/A-L, A-LA

CAN'T OPEN

7,9,11

#6

1"C 480Δ

30KVA 150° 5.7%Z

208/120

2"C

20A X 14

PNL:4A-H

225A, 3P, 4W

480/225 KAIC

MLO

480Δ

30KVA 150°

5.7%Z, 208/120

2"C

4A-L

30A

300A

PNL:4A-L,

2 SECT

20A X 42

300A

PNL:4A-H

225A, 3P, 4W

480/225 KAIC

480Δ

30KVA 150° 5.7%Z

208/120

1"C (3)#8+GND

20A X 42

100A 3A-L1 125A, 3P, 4W

208/120, 22 KAIC

2"C (4)#2+GND

20A X 58

300A

3AB-L, 2 SECT

400A, 3P, 4W 208/120

480Δ

112.5KVA 150° 49%Z

208/120

225A

3A-L, 2 SECT

20A

400A

4-1/2" SQ.

(4)4/0+GND#4 2 SETS

2.5"C (4)3/0

+GND

20A X 10 1P

MLO

4-1/2" SQ.

(#4)+GND

2.5"C

20A X 10 1P

3A-H, 30 KAIC

225A, 3P, 4W 480/225

2"C (4)#1+GND

480Δ

45KVA 150° 4.6%Z

208/120

480Δ

75KVA

208/120

#6

1"C

150A

PNL:2A-L1

225A, 3P, 4W 208/120

PNL:2A-L1, 2 SECT

225A, 3P, 4W 208/120

4-1/4"C

2"C (4)#2+GND

30A

MLO

2"C (4)1/0+GND

125A

300A PNL:2A-L

2 SECT

400A, 3P, 4W 208/120

3"C

1.5"C (3)#1+GND

20A X 58

PNL:2AB-H

480, 30 225A, 3P, 4W

208/120, 30 KAIC

20A X 17

MLO

2"C

20A

MLO

50A

225A

PNL:1A-H

225A, 3P, 4W 480/277

2.5"C (4)1/0+GND 1"C

20A X 15

MLO

1.5"C (3)#1+GND

#4

480Δ

75KVA

208/120

100A

300A

PNL:1A-L

2 SECT

150A

225A PNL:BA-H

225A, 3P, 4W, 30 KAIC

480/277

3"C

2.5"C 4/0+GND

MLO

1"C #4

480Δ

75KVA, 150°

208/120

BA-L /

BA-LA

100A

300A

PNL:BA-L

100A

PNL:BA-LA

208/120

BA-L/BA-LA

FUSE: 400A

1"C #4

100A

300APNL:BA-L1

400A, 208/120

100A

PNL:BA-L2

225A, 3P, 4W, 10 KAIC

480/277

BA-L1

CAN'T

OPEN

2"C

3"C (4)3/0+GND

125A P1A-H

(2)3.5"C

2 SETS

(4)350 KCMI/

#2 GRND

400APNL:PIA-E3

3 SECT.

400A, 3P, 4W, 30 KAIC

480/277

15A

JOCKEY

PUMP

(4)#2/0+GND (4)#2+GND (4)#1+GND (4)#4/0+GND

1"C

2"C

(4)#2+GND

100A

PNL:

4A-E1

50A

#2

125A

50A

2"C

PNL:4A-E1A

225A, 3P, 4W 208/120

PNL:4AB-E2

50A T3/E2

480Δ

30KVA 150° 4.9%Z

208/120

4A-E2 5A-E2 6A-E2

125A

100A

PNL:4A-E2

225A, 3P, 4W 208/120

2"C

1.5"C

(4)#2+GND

#6

50A

480Δ

30KVA 150° 4.9%Z

208/120

2"C 125A

100A

PNL:4A-E3

225A, 3P, 4W 208/120

100A

PNL:3AB-E2

125A, 3P, 4W 208/120

PNL:3A-E2

400A, 3P, 4W 208/120

350A

200A

3"C

(4)30 KCMIL+GND50A

T3/E2

3A-E2

3AB-E2

4AB-E2

480Δ

75KVA 150° 5.1%Z

208/120

2"C

(3)#1+GND

PNL:3A-E1A

225A, 3P, 3W

480V, 30 HAIC

MLO

PNL:3A-E1

100A, 3P, 4W 480/277

30 KAIC

(4)#2+GND

100A

100A

PNL:2A-E1A

125A, 3P, 4W 208/120

2"C

(4)#2+GND

MLO

2"C

(4)#2+GND

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

2"C

(4)#2+GND

PNL:2A-E1

100A, 3P, 4W 480/277

30 KAIC

(4)#2+GND

100A

PNL:2A-E2

30A, 2P, 4W

208/120MLO

2"C

(4)#2+GND

480Δ

30KVA 150° 4.9%Z

208/120

PNL:1A-E3

225A, 3P, 4W 208/120

125A

100A

50A

1"C

(3)#6+GND

PNL:1A-E2

225A, 3P, 4W 208/120

(4)#1+GND

100A

2"C

(4)#1+GND

480Δ

30KVA

150° 4.9%Z 208/120

100A

50A

1.5"C

PNL:2A-E1

100A, 3P, 4W 480/277

30 KAIC

125A

50A 100A

PNL:1A-E1A

225A, 3P, 4W 208/120

2"C

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

PNL:BA-E1

(4)#2+GND

100A

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

100A

PNL:BA-E1A

125A, 3P, 4W 208/120

2"C (4)#2 +

#6 GND

MLO

T3-E2

100A

PNL:BA-E2

225A, 3P, 4W

22 KAIC

125A

1.75"C (4)#2+GND

#8

50A

480Δ

30KVA 150° 4.9%Z

208/120

30A

1"C

(3)#6+GND

1"C

(3)#10+GND

DIESEL OIL

PUMPS

125A

3.5"C

(3)250 A CMIL+

#4 GND

3.5"C

(3)250 A CMIL+

#4 GND

#4

PNL:BA-E3

400A, 3P, 4W 208/120

300A

150A T5/E3 &E3A

2"C (4)#2+GND

3"C (4)3/0+GND

Department of Veteran Affairs

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

2.

CONTINUATION ON SHEET E-602.3

AutoCAD SHX Text E-602.1

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

AutoCAD SHX Text 1/21/25

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

QUADRANT "A" SINGLE LINE DIAGRAM

JB

JB

JB

1A-

HB

TO BE DETERMINED

P1A- E2

T3

ELEV. 4,5 & 6

T6

TBI

(4)#1+ #8 GND 480V

PNL:4A-E3

225A, 3P, 4W 208/120

PNL:4A-E3A

225A, 3P, 3W

480V, 30 HAIC

MLO4A-E3A

1.5"C (3)#1+GND

60A

4A-HA

1.5"C (3)#4+GND

PNL:4A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

60A

3A-HA

1.5"C (3)#4+GND

PNL:3A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

60A

2A-HA

1.5"C (3)#4+GND

PNL:2A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

60A

1A-HA

1.5"C (3)#4+GND

PNL:1A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

60A

BA-HA

1.5"C (3)#4+GND

PNL:BA-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

PNL:3A-E3A

225A, 3P, 3W

480V, 30 HAIC

MLO3A-E3A

1.5"C (3)#1+GND

PNL:3A-E3

225A, 3P, 4W 208/120

100A

PNL:2A-E3

125A, 3P, 4W 208/120

2"C

(4)#2+GND

MLO

2"C

(11)#1+GND

2"C

(4)#1+GND

2"C

(4)#1+GND

2"C

(4)#1+GND

PNL:1A-E3

225A, 3P, 4W 208/120

480Δ

75KVA 150° 5.1%Z

208/120

2"C

(4)#1+GND

PNL:BA-E3

400A, 3P, 4W 208/120

PNL:BA-E3AMLO

2"C (4)1/0+GND

DISC:

BA-E3B

225A, 112.5KVA

2"C (3)2/0

480Δ

112.5KVA 150° 4.6%Z

208/120 2.5"C (4)4/0 +

#4 GND

100A 100A

PNL:BA-E3

400A, 3P, 3W

480, 30 HAIC

2.5"C

(3)4/0+GND

PNL:BA-ERT

225A, 3P, 4W 270/120

XFMR

480V

150 KVA 5.6%Z

208/120V

PNL:P1A-HB

208/120

225A

1.5"C

2.5"C (4)4/0 + #4

PNL: P1A-ERCMLO

2"C (4)2/0+GND

LEVEL B

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

Department of Veteran Affairs

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

2.

CONTINUATION ON SHEET E-602.4

AutoCAD SHX Text E-602.2

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

AutoCAD SHX Text 1/21/25

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

QUADRANT "A" SINGLE LINE DIAGRAM

F12 F8 F16 F7 F11 F10 F9 F15 F3 F2 F5 F6 F14 F13 F4 F180

AF

A F

AF

AF

AF

AF

AF

AF

AF

AF

AF

AF

A F

LO

AD

B

AN

K

AT

JBJB

ATS-E3-

PNL. 7A-E3B

4P-800A

FDR. G5

ATS 14

30A CB

8A- E3C

8A- E3B

FED FROM

MCC-8

175A TO S-7,8,9

100A TO S-10

100A TO S-12

150A TO P-1,2,3

8A-H

2SECT

8A- E3A

ATS 23 TO SWBD "G"

FDR G-12

ATS-E3

ELEV. P1,2,3

3P-400A

ELEVATORS P-1,2,3

TO SWBD "G" FDR G-13

ATS 25ELEVATOR S-12

7(8D-HB)

ATS-E3 3P-125A

ELEV. S-12

TO ATS-24 ELEV. S-10

SEE RISER "D" FOR CONTINUATION

ATS 12

ELEVATORS S-7,8,9

ATS-E3

ELE. S-7,8,9

3P-400A

PNL:

7A- E3B

225A CB

TO 8AE3C

70A CB

FDR #AE3-1

T2

T3 T3

T3

T3

T3

T3

T3

T3

T4

T4

T5

T6

FDR #AE-1

FDR #AE-1

FDR #AE2-1

6A-H

13(8D-HB)

LEVEL 4

LEVEL 5

LEVEL 6

LEVEL 7

LEVEL 8

(E) EMERGENCY

DISTRIBUTION

SWITCHBOARD

(EDSB)

EM. SWBD C

EM. SWBD B

EM. SWBD D

EM. SWBD A

AT

S

AT

S

AT

S

AT

S

AT

S

AT

S

AT

S

A F

A T

AT

S

A F

1200A BUSWAY

8A-E3C

XFMR

7A-E3

70A 8,10,12

1.5"C (3)

480V/45 KVA 150° 4.3%Z

208/120

3/4"C #6

1 SET APROX. 4/0

600A, 3P, 4W

480/30 KAIC

MLO

175A

PNL:7A-E3

2 SECT

208/120 225A, 3P, 4W

PNL:6AB-LMLO PNL:6AB-H

225A, 3P, 4W

480/277, 30 HAIC

MLO

2.5"C (4) 4/0+GND 4-1/4" SQV C

(4) #4+#10 GND

PNL:7A-HB

225A, 3P, 4W

480, 30 HAIC 20A

2" C (4) #1+GND

100A

7A-HB

20A

FCU1

15A

FRU3

20A

FRU2

DISC #3

70A 7A-L

PNL:7A-H

2 SECT

225A, 3P, 4W

480/277, 30 HAIC

7A-L

15A

FRU3

125A

PNL:7A-L

225A, 208/120 3P, 4W

FRU3

7A-L

4" C (4) 500 KCMIL + GND

MLO

1.5"C (4) #2+GND

1"C

70A T4/A-L

100A

DISC

50A T5/5A-L1

175A

T6/A-L3, AB-L

100A

5A-H/5AB-H

125A

T5/AL

100A 4A-H

50A

50A

125A

1.5"C (3)#4+GND

2"C (4)#1+GND

3/4"C (3)#6+GND

6A-L1

6A-L

480Δ

30KVA 150° 4.5%Z

208/120

480Δ

45KVA 150° 4.3%Z

208/120

2"C (4)2/0+GND

1-1/2"C (4)#3+GND

20A X 40

100A

PNL:6A-L1

125A, 3P, 4W

30A

175A

PNL:6A-L

2SECT

100A

PNL:6A-H

30HAIC, 100A,

3P, 3W, 480V

#8

1"C 480Δ

30KVA 150° 4.5%Z

208/120

1-1/4"C (4)#3+GND

20A X 42

100A

PNL:5A-L1

125A, 3P, 4W 208/120

PNL:5AB-L

2SECT2.5"C

(4)4/0+GND

PNL:

5A-H

50A 7,9,11

225A, 3P, 4W

480/30 KAIC MLO

2"C (4)#1+GND

20A X 8

PNL:5AB-H

225A, 3P, 4W

480/225 KAIC

MLO

PNL:

5A-L

2SECT

200A

2 SETS

2.5"C (4)3/0+GND

400A

5A-L/5AB-L

#6

1"C 480Δ

30KVA 150° 5.7%Z

208/120

2"C

20A X 14

PNL:4A-H

225A, 3P, 4W

480/225 KAIC

MLO

480Δ

30KVA 150°

5.7%Z, 208/120

2"C

4A-L

30A

300A

PNL:4A-L,

2 SECT

20A X 42

300A

PNL:4A-H

225A, 3P, 4W

480/225 KAIC

480Δ

30KVA 150° 5.7%Z

208/120

1"C (3)#8+GND

100A

20A X 9

PNL:6A-E1

100A, 3P, 4W

30 KAIC

2"C

(4)#2/0+GND

2"C

(4)#2+GND

20A X 5

PNL:6A-E1A

125A, 3P, 4W 208/120

MLO

60A

30A

PNL:NO LABEL

OLD: 6A-E2

100A

20A X 28

PNL:6AB-E2

125A, 3P, 4W 208/120

2"C

(4)#1+GND

2.5"C

(4)#4/0+GND

2"C

(4)#1+GND

100A

PNL:5A-E1

100A, 3P, 4W 480/277

30 KAIC

2"C

(4)#2/0+GND

#2

100A

PNL:5A-E1A

100A, 3P, 4W 480/277

30 KAIC

2"C

(4)#2+GND

MLO

2"C

(4)#2+GND

100A

PNL:5A-E2

2"C

(4)#1+GND

2"C

(4)#1+GND

100A

PNL:5AB-E2

2.5"C

(4)#4/0+GND

2.5"C

(4)#4/0+GND

MLO

2"C

(4)#1+ #8 GND

1"C

2"C

(4)#2+GND

100A

PNL:

4A-E1

50A

#2

125A

50A

2"C

PNL:4A-E1A

225A, 3P, 4W 208/120

PNL:4AB-E2

50A T3/E2

480Δ

30KVA 150° 4.9%Z

208/120

4A-E2 5A-E2 6A-E2

125A

100A

PNL:4A-E2

225A, 3P, 4W 208/120

2"C

1.5"C

(4)#2+GND

#6

50A

480Δ

30KVA 150° 4.9%Z

208/120

2"C 125A

100A

PNL:4A-E3

225A, 3P, 4W 208/120

3A-E2

3AB-E2

4AB-E2

480Δ

75KVA 150° 5.1%Z

2"C

(3)#1+GND(4)#2+GND

100A

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

2"C

(4)#2/0+GND

Department of Veteran Affairs

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

2.

CONTINUATION ON SHEET E-602.1

AutoCAD SHX Text E-602.3

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

AutoCAD SHX Text 1/21/25

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FDR. G1

G1 G2 G3 G4 G5 G6

750 KW GENERATORS

400A TO MOTOR RISER B

400A TO MOTOR RISER A

ATS-E3-MTR

RISER-B

4P-800A

F5 F6 F14 F13 F4 F180

AF

AF

AF

A F

LO

AD

B

AN

K

ATS 16

FDR. G2

REMOTE RADIATOR

FAN CONTROLLER (TYP.)

8A-HB

400A CB

MOTOR RISER A

JB

JB

JB

PNL:

7A- E3B

70A CB

TO FDR.

GE3-1B

T3

T4

400A CB

MOTOR

RISER B

TO EMERGENCY

MOTOR RISER B

ATS E3-G3

500A GE3-2C

12 13

AT

S

AT

S

AT

S

A F

TO EMERGENCY

MOTOR RISER A

70A 8,10,12

1.5"C (3)

480V/45 KVA 150° 4.3%Z

208/120

3/4"C #6

2"C (4) 2/0+GND

MLO

175A

PNL:7A-E3

2 SECT

208/120 225A, 3P, 4W

PNL:7A-E3A

600A, 3P, 4W

480, 30 HAIC

MLU

2 SETS

2.5" C (3) 250 UCMIL + GND

EMCC-7A

DISC. 100A

SEC.1 300A SEC.2 300A SEC.3 300A

EMCC-7A

600A, 480, 3P, 3W

2" C PNL:7A-HA

225A, 3P, 4W

480, 30 HAIC

MLO

7A-HA DISC. 60A

1.5"C (3) #4+GND

100A

20A X 28

PNL:6AB-E2

125A, 3P, 4W 208/120

20A X 6

PNL:6A-E3

125A, 3P, 4W 208/120

MLO 6A-E3A

60A

6A-HA

1.5"C (3)#1+GND

PNL:6A-E3A

225A, 3P, 2W

480V, 30 HAIC

MLO

1.5"C (3)#4+GND

PNL:6A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

2"C

(4)#1+GND

100A

PNL:5AB-E2

2.5"C

(4)#4/0+GND

2.5"C

(4)#4/0+GND

MLO

100A

PNL:5A-E3

(4)#2 + #8 GND

2"C

(4)#1+ #8 GND

MLO

2"C

(4)#1+ #8 GND

5A-E3A

1.5"C (3)#1+GND

PNL:5A-E3A

225A, 3P, 3W

480V, 30 HAIC

MLO

480V

60A

6A-HA

1.5"C (3)#4+GND

PNL:5A-HA

225A, 3P, 3W

480, 30 HAIC

60A

3/4"C (3)#8+GND

480V

#6

480Δ

30KVA 150° 4.9%Z

208/120 1.5"C (3)#1+GND

LEVEL 5

LEVEL 6

LEVEL 7

LEVEL 8

Department of Veteran Affairs

Scale: NTS

C O

N

TI

N U

AT

IO

N O

N S

H

EE

T E-

2.

CONTINUATION ON SHEET E-602.2

AutoCAD SHX Text E-602.4

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

BALTIMORE PANEL STUDY

AutoCAD SHX Text 512-23-109

AutoCAD SHX Text

JA

AutoCAD SHX Text

ALS

AutoCAD SHX Text 1/21/2025

AutoCAD SHX Text Dwg. of 20

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text 12/20/24

AutoCAD SHX Text Location

AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201

AutoCAD SHX Text

REVISION FINAL

AutoCAD SHX Text 1/21/25

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(E) SWITCHBOARD "B"

T4

T4

T4

T3 T3

T5

T4

T5

T5

T6

T6

T7

T6

FDR #BE1-1

FDR #BE1-1

FDR #BE1-1

TO MRI EQUIPMENT

CB1 RM 1B161

1B-E1

4.25"C SQ.

1B-E1

4.25"C SQ.

FDR #B3

F1 2500A BUSWAY F4 2500A BUSWAY

A

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11MAIN TIE MAIN

K K K

A

0A

A

SP

AR

E

0A

A

A

A

0A

0A

0A

SP

AR

E

0A

FU

TU

R E

FU

TU

R E

BM-1

BM-2

BM-3

BE1-1

BE1-2

BE2-1

BE2-2

BE3-1

BE3-2

BE3-3

BE3-4

ATS 2 ATS 6 ATS 20

250A

800A

600A

150A

105A 105A

800A 400A 75A

250A

105A

SPARE

ATS-E1-B

4P-260A

(E) EMERGENCY SWITCHBOARD-"B"

ATS-E2-B

4P-800A

ATS-E3-B

4P-600A

LEVEL P1

LEVEL B

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

EDSB

FDR #8

1200A

BUSWAY

A

BU

SW

AY

A

BU

SW

AY

A

BU

SW

AY

800A BUSWAY

125A

T5-BL

DISC

4B-H/4AB-H

DISC

DISC

200A

400A

PNL:4B-H PNL:4AB-H

1.5"C

2"C (4)#1

300A

3"C

PNL:4B-L

2 SECT

480Δ

75 KVA

208/120

PNL:4B-E1 PNL:4B-E1A

208/122

2"C

2"C

2" (4)#3+GND

MLO

PNL:3B-H PNL:3B-L

2 SECT PNL:

3B-LA

PNL:

3B-LB

PNL:

3B-LC

PNL:

3B-LR

PNL:

3B-E1

PNL:

3B-E1A

MLO

PNL:

2B-E1

PNL:

2B-E1A

2"C 2"C

2"C2"C

70A

T4/B-LB

B-LC

125A T5/B-L 2B-L

100A 2B-H

2AB-H

2B-LX

DISC

PNL:

2B-HA

2"C 4.25"C

2"C

3"C

50A

PNL:

2B-H

PNL:

2AB-H

RM:

2A-105

PNL:

2B-L

2 SECT

PNL:

2B-2B113

2 SECT

4…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .