90481 - 512-23-109 - Baltimore Panel Study - Final Report - 20250121.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24526Q0229
About this file
This is a Final Report of Findings for an electrical panel study of the Baltimore VA Medical Center (VAMC) conducted by DavEnergy Solutions under Contract No. 36C24523D0102, Project 512-23-109, dated January 21, 2025. The comprehensive 1,005,000 square-foot facility study systematically examined electrical systems across four quadrants (A, B, C, D) organized by 11 levels (3 parking levels, basement, and 8 floors) to identify deficiencies and compliance issues with applicable codes including the 2020 National Electrical Code, NFPA standards, and VA design manuals.
The study identified 97 total deficiencies categorized by quadrant and room number, with the most prevalent issues being undersized panel covers (affecting multiple panels across all quadrants with estimated costs of $3,500 per remediation), missing or improper equipment labels ($250 per item), panels positioned directly below piping requiring leak trays ($500 per installation), and inadequate working space around electrical equipment requiring busway cover removal ($750–$1,500 per location). Additional findings include difficult-to-open electrical service bay doors, emergency panel identification challenges, NEC violations such as undersized fire pump circuit breakers, storage items obstructing electrical spaces, and missing ground cable connections. The report provides single-line diagrams, final panel schedules documenting circuit assignments across all quadrants, and photographic documentation of representative deficiencies. Estimated remediation costs for identified issues range from $150 to $3,500 per deficiency, with many items marked "In Progress" or "Currently being evaluated by station personnel," indicating ongoing coordination with facility management for resolution.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24526Q0229 0002.pdf | ||
| 36C24526Q0229 0002_1.docx | DOCX document | |
| 36C24526Q0229 0001.pdf | ||
| A712 SUBSTATION.pdf | ||
| 36C24526Q0229 0001_1.docx | DOCX document | |
| VHA Directive1028 Facility Electrical Power Systems.pdf | ||
| WAGE DETERMINATION_Service Contract Act WD.pdf | ||
| 36C24526Q0229.pdf | ||
| 36C24526Q0229_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Maryland HealthCare System
Contract Number: 36C24523D0102
Project: 512-23-109
BT Electrical Panel Study
Final Report of Findings
Date: January 21, 2025
For:
Baltimore VA Medical Center 10 N Greene St.
Baltimore, MD 21201
Attn: Liana J. Holland Contracting Officer Liana.Holland@va.gov
Author:
Jaime Arellano
P.E.
Electrical Engineer jaime.arellano@davenergy.com Phone: 559-759-4443
Project Number: 512-23-109 VA Maryland HealthCare System - VISN5 – Baltimore Baltimore Electrical Panel Study 01/21/2025 FInal Report of Findings
BASIS OF DESIGN
1.1.0 FACILTY DESCRIPTION
1.1.1 SITE VISIT SUMMARY NARRATIVE
1.1.2 SUMMARY OF ISSUES
1.1.3 CRITERIA/CODES
Appendix A – Findings Appendix B – Final Single line Drawings Appendix C – Final Panel Schedules Appendix D – Final Photo Log
1.1.0 FACILITY DESCRIPTION
This section provides an overview of the Baltimore VA hospital facility situated at 10 N Greene St, Baltimore, MD 21201. The hospital comprises three parking levels, followed by a basement level and eight additional levels above with a total of 1005000 ft2 excluding interstitial space. The facility is organized into four quadrants—A, B, C, and D. Quadrant A is located in the southeast, quadrant B in the southwest, quadrant C in the northwest, and quadrant D in the northeast. Electrical panels throughout the hospital are systematically named based on their respective levels and quadrants.
1.1.1 SITE VISIT SUMMARY NARRATIVE
Davenergy, in collaboration with M.C. Dean employees, spent a month on-site gathering crucial facility electrical system information. The VA supplied a site plan and a single-line diagram, streamlining the data collection process. The first site visit was on October 17, 2023 in which we met with Steve Gorman the electrical shop supervisor at the time to discuss our plan to investigate the electrical systems by quadrants. In this week we started on quadrant A and moved up from the parking levels to the 8th floor. Steve Gorman provided us with a radio and keys to open every electrical room, so we continued like this all they to the end of week two which was on October 27, 2023 where we finished data collection for quadrant B.
The second site visit occurred on November 28, 2023 and was performed in a similar fashion to previous site visit, so quadrant C was investigated by starting in room 1PC-100 which is an electrical service bay and moved up to the 8th floor. Quadrant D was started on December 04, 2023 with service bay 1D-100 and ended in the 8th floor on December 07, 2023. Additional site visits have been performed by M.C. Dean to trace each branch circuit in the electrical system to have updated panel schedules.
1.1.2 SUMMARY OF ISSUES
A notable concern identified was the difficulty in opening the doors to the electrical service bays, which could potentially impede response time during emergencies. Additionally, addressing the issue of labeling the emergency panel with a red label was highlighted to ensure quick identification, particularly when all panels have a black background. Another concern is the fire pump undersized circuit breaker, this is an NEC violation, but Davenergy is working on the switchgear replacement project with project number 512-23-102, so this violation will be addressed. The most common issues found were panel covers that are too small for the enclosure and equipment missing labels. There was a total of 97 issues identified please see Appendix A which provides a comprehensive list of all identified issues and deficiencies, categorized by quadrant and room number for easy reference.
FIGURE 1: SITE SATELLITE VIEW
1.1.3 CRITERIA/CODES
2018 International Building Code – ICC – First Printing: August 2017
2018 International Existing Building Code – ICC - First Printing: August 2017
Structural Design Manual for Hospital Projects – VA TIL – February 1, 2014
HVAC Design Manual – VA TIL - November 1, 2017, Rev. March 1, 2022
Plumbing Design Manual – VA TIL – June 1, 2022
Electrical Design Manual – VA TIL – December 1, 2019
Architectural Design Manual – VA TIL – August 1, 2014
Physical Security and Resiliency Design Manual – VA TIL – October 1, 2020, Rev. July 1, 2022
2008 A/E Submission Requirements PG-18-15, Volume C
Fire Protection Design Manual – VA TIL – June 1, 2021 o 2021 NFPA 1: Fire Code o 2021 NFPA 3: Standard for Commissioning of Fire Protection and Life Safety Systems o 2021 NFPA 4: Standard for Integrated Fire Protection and Life Safety System Testing o 2022 NFPA 10: Standard for Portable Fire Extinguishers o 2022 NFPA 13: Standard for the Installation of Sprinkler Systems o 2022 NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection o 2020 NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems o 2020 NFPA 70: National Electrical Code o 2021 NFPA 70E: Standard for Electrical Safety in the Workplace o 2022 NFPA 80: Standard for Fire Doors and Other Opening Protectives o 2021 NFPA 99: Health Care Facilities Code o 2021 NFPA 101: Life Safety Code o 2021 NFPA 220: Standard on Types of Building Construction o 2022 NFPA 241: Standard for Safeguarding Construction, Alteration, and Demolition Operations o 2022 NFPA 291: Recommended Practice for Fire Flow Testing and Marking of Hydrants
Draft report of findings
Appendix A – Findings
Item No. Quadrant ROOM Description Solutions Potential Cost
1 A,B,C,D All Unable to quickly identify emergency panels. Clearly color code emergency equipment $250 per piece of equipment
2 A 1PA-101 The electrical substation room doors are difficult to open. Install new locks and with keys Currently being evaluated by station personnel
3 A 1PA-102 Fire pump circuit breaker is undersized. Replace trip with a 225A trip unit based on the 207
LRA
$500
4 A 1PA-101 The room is being used as storage which has a cart close to the transformer and grounding bar wall.
Remove cart from room
5 A 1PA-101 ATS 27, which is now a junction box, has many cables packed inside the enclosure and boxes.
Remove unnecessary cables as this a short circuit hazard $600 - $800
6 A 1PA-101 Panelboard P1A-H sections 1 & 2 do not properly cover existing panelboard backbox. Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
7 A 1PA-101 Panelboard P1A-E3 sections 1 & 2 do not properly cover existing panelboard backbox. Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
8 A Outside 1PA-101 Transformer feeding P1A-HB has no label. Label the 150kVA transformer $250
9 A Outside 1PA-101 Transformer feeding P1A-HB has no disconnect within sight. According to NEC 450.14 add a disconnect within sight of the transformer or field mark the location of the disconnect which is capable of being locked in the open position
In Progress
10 A Outside 1PA-101 Panelboard P1A-ERC has cable terminated with tape. Remove cables or terminate with wire nuts $150 - $600
12 A BA113 The room is being used as storage which has a pallet jack, boxes and chairs. Remove storage from service bay
13 A BA113 Panels BA-E3B and BA-HB are directly below piping which is in the dedicated electrical space.
Install leak tray to protect electrical panels $500
14 A BA113 Transformer feeding disconnects P1A-ERC and BA-ERT is missing label. Label the transformer $250
15 A BA113C Junction box labeled FDR AE2-1 does not have a ground cable connected to the case Install an EGC to the junction box $500
16 A BA113 disconnect feeding transformer T6 which feeds disconnects P1A-ERC and BA-ERT has no label
Label the disconnect $250
17 A BA Kitchen Receptacle is on the ground level in a kitchen environment, with the only support being the conduit.
Replace with a GFCI and cord drop.
$250
18 A 1A-113C Panels 1A-E1, 1A-E1A are directly below piping which is in the dedicated electrical space
Install leak tray to protect electrical panels $500
19 A 1A-113C Disconnect T3/A-E3 is directly below piping which is in the dedicated electrical space Install leak tray to protect disconnect $500
20 A 1A-113C Disconnect T3/A-E3 is mislabeled Label the disconnect. Correct name is T3/1A-E3. $250
21 A 1A-113C Junction box FDR AE3-1 is directly below piping which is in the dedicated electrical space
Install leak tray to protect junction box $500
22 A 2A-114 Panel 2A-HA are directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500
23 A 2A-114 Panel 2A-HA has no label, pencil was used to write name on cover Install proper label $250
24 A 2A-114C transformer feeding panel 2A-L1 is missing label Label the transformer $250
25 A 3A-113 The room is being used as storage which has boxes Remove storage from service bay
26 A 3A-113C Transformer feeding panel 3A-L1 is missing label Label the transformer $250
27 A 4A-113C Transformer feeding panel 4A-L1 is missing label Label the transformer $250
28 A 4A-113C Transformer feeding panel 4A-E3 is missing label Label the transformer $250
29 A 5A-127 Panel 5A-HA and 5A-E3A are directly below piping which is in the dedicated electrical space
Install leak tray to protect electrical panels $500
30 A 5A-127 The room is being used as storage which has boxes Remove storage from service bay
31 A 6A-133 Panel 6A-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500
32 A 7A-101 Panel 7A-E3 has tape covering circuit breaker slots 57 and 59 Install proper cover $150
33 A 8A-102 The room is being used as storage which has cabinets and a table Remove storage from room
34 A 8A-102 This room requires two paths of egress the single door on the south wall is locked Make a door on the east wall at opposite side on the In Progress
35 B 1PB-101 2500kVA transformer has liquid build up underneath Verify the transformer is not leaking oil $500
36 B UPS-RM None of the equipment in the room is labeled Label the disconnect, panels, transformer and UPS $1,000
Electrical Deficiencies
37 B BB-101 Panelboard BAB-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
38 B BB-137 The room is being used as storage which has a cart Remove storage from service bay
39 B BB-137C The working space between panel BB-E1 and 800A busway feeding transformer T4 is not up to code
Remove the cover around the busway to increase the working distance $1,500
40 B BB-137C Panel BB-E3 has no label, pencil was used to write name on cover Install proper label $250
41 B 1B-141 Lights close to Panel 1B-HA and 1B-E3A do not work Replace light bulbs
42 B 1B-141 The room is being used as storage which many boxes Remove storage from service bay
43 B 1B-141C The working space between panel 1B-E1 and 800A busway feeding disconnect 1A-
BE2 and 1B-BE2 is not up to code
Remove the cover around the busway to increase the working distance $750
44 B 1B-141C The working space between panel 1B-E1A and 800A busway feeding disconnect 1A-
BE2 and 1B-BE2 is not up to code
Remove the cover around the busway to increase the working distance $750
45 B 1B-141C Panelboard 1B-RB cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
46 B 1B-141C Panelboard 1B-RB square wireway is open Close the wireway $250
47 B 2B-110 Panelboard 2B-E3A has stored materials infront preventing access remover materials infront of panel. According to the
NEC at least a 3.5 ft clearance is needed.
48 B 2B-118 Panel 1B-H will be in Panel 1B-L working space in small section There is not enough space in the room to move any panels so its recommended to not do any live work on panel 1B-L
49 B 2B-118 Working space for Panel 2B-HB and 2B-E3B is not up to code because the air handling unit is too close
Relocate Panels In Progress
50 B 2B-118C The wire way for Panel 2B-E1 is blocked by panel 2B-E1A There is not enough space in the room to move any panels and since they are emergency panels an in-depth analysis is needed.
51 B 2B-118C The working space between panel 2B-E1 and the 800A busway is not up to code Remove the cover around the busway to increase the working distance $1,500
52 B 2B-118C Transformer feeding panel 2B-LX is missing label Label the transformer $250
53 B 4B-182 Panel 4B-E3A is directly below piping which is in the dedicated electrical space Install leak tray to protect electrical panel $500
54 B 4B-182C Panelboard 4B-E1A cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
55 B 4B-182C The working space between panel 4B-E1A and busway is not up to code Remove the cover around the busway to increase the working distance $1,500
56 B 5B-182 circuit breaker disconnect for panel 5B-HA is not accessible Relocate the disconnect In Progress
57 B 6B-129 The room is being used as storage which many boxes Remove storage from service bay
58 B 6B-129 Panel 6B-HA and 6B-E3A are directly below piping which is in the dedicated electrical space
Install leak tray to protect electrical panels $500
59 B 6B-129C The working space between panel 6B-E1 and busway is not up to code Remove the cover around the busway to increase the working distance $1,500
60 B 7B-100 Lights close to disconnect EMCC-7B do not work Replace light bulbs
61 B 7B-100 It is hard to access motor riser B junction box 8A-HB Relocate junction box and disconnect In Progress
62 C 1PC-100 The room is being used as storage which has electrical equipment, small cranes Remove storage from room
63 C 1C-100 working space for Panel 1C-E3A is not up to code Relocate Panel In Progress
64 C 1C-100 Busway disconnect labeled 1C-HA is not accessible due to a light fixture Relocate light fixture In Progress
65 C BC-101B Transformer feeding panel BC-LB has no label Label the transformer $250
66 C BC-101B There is water damage on top of transformer T4 feeding panel BC-LB Determine source of water to install a leak tray $500
67 C BC-101C Panel BC-LA has no label, pencil was used to write name on cover Install proper label $250
68 C BC-101C Transformer feeding panel BC-L has no label Label the transformer $250
69 C 2C-124 Circuit breaker in slot 13,15,17 is not properly mounted to panel Mount the circuit breaker correctly $150
70 C 3C-100 Panelboard 3C-E3A cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
71 C 3C-100 Lights close to Panel 3C-E3A do not work Replace light bulbs
72 C 3C-100C Panel 3C-L does not have enough working space, removing the busway cover will not provide enough space
There is not enough space in the room to move any panels so an in-depth analysis is needed.
73 C 3C-100C Panelboard 3C-L2 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
74 C 4C-100C Panelboard 4C-E2 and 4C-L1 cover are too small for the enclosures Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
75 C 4C-100C Panel 4C-L1 does not have enough working space, removing the busway cover will not provide enough space
There is not enough space in the room to move any panels so an in-depth analysis is needed.
76 C 5C-114 The room is being used as storage which consist of boxes Remove storage from service bay
77 C 5C-114C Panel 5C-E3A is missing circuit breaker space covers for slots 2,6,8 Install the missing circuit breaker space covers $75
78 C 5C-114C A small section of Panel 5C-H does not have adequate working space Move panel 5C-E3A and 5C-H to the left In Progress
79 C 6C-100C Panelboard 6C-L1 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
80 C 7C-100 The label from EMCC-7C is using tape to hold it up Replace the label $250
81 D BD-116 The room is being used as storage which consist of many boxes and carts Remove storage from service bay
82 D BD-116A Panel BD-L1 does not have enough working space due to the busway cover Remove the busway cover $1,500
83 D BD-126 The room is being used as storage Remove storage from electrical closet
84 D 1D-166A Panelboard 1D-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
85 D 2D-126 Panel 2D-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500
86 D 2D-126C Panelboard 2D-E1 cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
87 D 3D-119C Panelboard 3D-L cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
88 D 3D-119C Panel 3D-L does not have enough working space due to the busway cover Remove the busway cover $1,500
89 D 3D-119C Panel 3D-L1 is missing circuit breaker space cover for slot 30 Install the missing circuit breaker space cover $75
90 D 4D-154 Panel 4D-HA has no label, marker was used to write name on tape Install proper label $250
91 D 4D-154 Panel 4D-HA has no panel schedule Create a panel schedule $500
92 D 4D-154A Panel 4D-L does not have enough working space due to the busway cover Remove the busway cover $1,500
93 D 5D-130 There is no access to transformer feeding UPS due to abandoned UPS Remove abandoned UPS In Progress
94 D 5D-130C Panel 5D-E1A does not have enough working space due to the busway cover Remove the busway cover $1,500
95 D 6D-158 Panel 6D-HA is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500
96 D 7D-100 Panel 7D-E1 is directly below piping which is in the dedicated electrical space Install leak tray to protect the panel $500
97 D 7D-100 Panelboard 7D-H cover is too small for the enclosure Remove and Replace existing surface fronts with flush fronts at designated panels in Quadrats A, B , C and D. Flush fronts are 2" larger than the panel box and will eliminate the hazzardous gaps.
$3,500.00
Draft report of findings
Appendix B – Final Single line Drawings
600A AIR INTERRUPTER SWITCH
600A AIR INTERRUPTER SWITCH
1500 KVA
13.2Δ- 480/277Y 65.6A - 1805A
80E
F1
F4
SWITCHGEAR "C"
DOUBLE - ENDED
3000A,3P,4W
480/277,65 KAIC
SEE DWG. E-604
FOR CONTINUATION
SUBSTATION "C"
1500 KVA
13.2Δ- 480/277Y 65.6A - 1805A
600A AIR INTERRUPTER SWITCH
600A AIR INTERRUPTER SWITCH
1500 KVA
13.2Δ- 480/277Y 65.6A - 1805A
80E
80E
F1
F4
SWITCHGEAR "B"
DOUBLE - ENDED
3000A,3P,4W
480/277,65 KAIC
SEE DWG. E-603
FOR CONTINUATION
SUBSTATION "B"
2000 KVA
13.2Δ-4160/2400Y
87.5A - 278A
600A AIR
INTERRUPTER
SWITCH
2000 KVA
13.2Δ- 480/277Y 87.5A - 2405A
2000 KVA
13.2Δ- 480/277Y 87.5A - 2405A
F6
F3
100E
F6
F3
MVA
MVA
MVA
MVA
100E
100E
15KV 4"C-(3)#2/0 + #2 GND 15KV 4"C-(3)#2/0 + #2 GND
15KV 4"C-(3)#4/0 + #2 GND 15KV 4"C-(3)#4/0 + #2 GND
15KV 4"C-(3)#4/0 + #2 GND
15KV 4"C-(3)#4/0 + #2 GND
600A AIR
INTERRUPTER
SWITCH
600A AIR
INTERRUPTER
SWITCH
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
1.
CONTINUATION ON SHEET E-601.3
Department of Veteran Affairs
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE LINE DIAGRAM MEDIUM VOLTAGE
AutoCAD SHX Text
AutoCAD SHX Text E-601.1
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
AutoCAD SHX Text 1/21/25
SUBSTATION "F"
SINGLE-ENDED
CHILLER, 553KW - 3Ø, 4160V. (FLA. 87A.)
CHILLER, 553KW - 3Ø, 4160V. (FLA. 87A.)
CHILLER, 325KW - 3Ø, 4160V. (FLA. 87A.)
SWITCHGEAR "G"
DOUBLE-ENDED
3000A,3P,4W
480/277,65 KAIC
SEE DWG. E-605
FOR CONTINUATION
80E
F5
80E
SUBSTATION "A"
600A AIR INTERRUPTER SWITCH
600A AIR INTERRUPTER SWITCH
600A AIR INTERRUPTER SWITCH
600A AIR INTERRUPTER SWITCH
F2
F5
80E
F2
SUBSTATION "D"
1500 KVA
13.2Δ - 480.277Y
65.6A - 1805A
1500 KVA
13.2Δ - 480.277Y
65.6A - 1805A
SWITCHGEAR "A"
DOUBLE-ENDED
3000A,3P,4W
480/277,65 KAIC
SEE DWG. E-602
FOR CONTINUATION
SWITCHGEAR "D"
DOUBLE-ENDED
3200A,3P,4W
480/277,65 KAIC
SEE DWG. E-605
FOR CONTINUATION
1500 KVA
13.2Δ - 480.277Y
65.6A - 1805A
15KV 4"C-(3)#2/0 + #2 GND
15KV 4"C-(3)#2/0 + #2 GND
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
1.
CONTINUATION ON SHEET E-601.4
Department of Veteran Affairs
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE LINE DIAGRAM MEDIUM VOLTAGE
AutoCAD SHX Text E-601.2
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
MVA
N.C.
BGE
13708
BGE
BGE
13709
NORMAL
FEED #1
MVA
N.O.
TIE A
STANDBY
FEED #3
MVA
N.O.
TIE B
STANDBY
FEED #3
MVA
N.C.
NORMAL
FEED #2
MVA
MVA
MVA
MVA
MVA
MVA
FUTURE FUTURE
F1 F2 F3 F4 F5 F6
13.2KV SWITCHGEAR
1500 KVA
13.2Δ- 480/277Y 65.6A - 1805A
80E
15KV 4"C-(3)#2/0 + #2 GND
15KV 4"C-(3)#2/0 + #2 GND
15KV 4"C-(3)#4/0 + #2 GND 15KV 4"C-(3)#4/0 + #2 GND
INCOMING SERVICE
INCOMING SERVICE
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
1.
CONTINUATION ON SHEET E-601.1
Department of Veteran Affairs
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE LINE DIAGRAM MEDIUM VOLTAGE
AutoCAD SHX Text E-601.3
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
BGE
13709
MVA
N.C.
NORMAL
FEED #2
MVA
MVA
F5 F6
80E
1500 KVA
13.2Δ - 480.277Y 65.6A - 1805A
15KV 4"C-(3)#2/0 + #2 GND
15KV 4"C-(3)#2/0 + #2 GND
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
1.
CONTINUATION ON SHEET E-601.2
Department of Veteran Affairs
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE LINE DIAGRAM MEDIUM VOLTAGE
AutoCAD SHX Text E-601.4
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
JB
JB
JB
JBJB
JB
JB
FDR #AE3-1FDR #AE2-1FDR #AE-1
FDR #AE3-1
FDR #AE3-1
FDR #AE3-1
FDR #AE3-1
ATS 13ATS 5ATS 1
250A
150A
600A 105A
ELEV. 4,5 & 6
JUNCTION BOX
(OLD ATS-27)
3 #250 MCM + #4
GW IN 2 1/2" C.
AE3-1
AE3-2
AE3-3
AE3-4
AE2-1
AE2-2
AE2-3
150A
150A
150A
150A
150A
250A
250A
800A
AE1-1
AE1-2
ATS-E3-A
4P-800A
ATS-E2-A
4P-260AATS-E1-A
4P-260A
(E) EMERGENCY SWITCHBOARD - "A"
JOCKEY PUMP
5 HP, 3PH-480V
JOCKEY PUMP CONTROLLER
FIRE PUMP CONTROLLER &
TRANSFER SWITCH
ATS 28
FIRE PUMP
25 HP, 3PH-480V
FDR. AE3-4
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12MAIN TIE K MAIN K
F2 2500A BUSWAY F5 2500A BUSWAY
(E) SWITCHBOARD "A"
A
A
SP
AR
E
0A
0A
SP
AR
E
0A
FU
TU
R E
0A
0A
0A
SP
AR
E
0A
FU
TU
R E
0A
A
A
A
LEVEL P1
K
2SECT
P1A- H
T3T3
T3
T3 T3
T3
T3
T3
T4
T5
T5
T5
T5
T5
T5
T6
T6
FDR #AE-1
FDR #AE-1
FDR #AE-1
FDR #AE-1
FDR #AE-1
FDR #AE2-1
FDR #AE2-1
FDR #A1 (PLUG-IN BUSWAY)
(1000A BUS)
LEVEL B
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
M1
M2
M3
A
BU
SW
AY
A
BU
SW
AY
0A
B U
SW
AY
125A
T5/AL
100A 4A-H
50A
50A
125A
100A
70A
100A 125A
125A
T5/A-LV, AB-L
1A-H/1AB-H
CAN'T OPEN
175A T6/L1
CAN'T OPEN
125A
T5/A-L, A-LA
CAN'T OPEN
7,9,11
#6
1"C 480Δ
30KVA 150° 5.7%Z
208/120
2"C
20A X 14
PNL:4A-H
225A, 3P, 4W
480/225 KAIC
MLO
480Δ
30KVA 150°
5.7%Z, 208/120
2"C
4A-L
30A
300A
PNL:4A-L,
2 SECT
20A X 42
300A
PNL:4A-H
225A, 3P, 4W
480/225 KAIC
480Δ
30KVA 150° 5.7%Z
208/120
1"C (3)#8+GND
20A X 42
100A 3A-L1 125A, 3P, 4W
208/120, 22 KAIC
2"C (4)#2+GND
20A X 58
300A
3AB-L, 2 SECT
400A, 3P, 4W 208/120
480Δ
112.5KVA 150° 49%Z
208/120
225A
3A-L, 2 SECT
20A
400A
4-1/2" SQ.
(4)4/0+GND#4 2 SETS
2.5"C (4)3/0
+GND
20A X 10 1P
MLO
4-1/2" SQ.
(#4)+GND
2.5"C
20A X 10 1P
3A-H, 30 KAIC
225A, 3P, 4W 480/225
2"C (4)#1+GND
480Δ
45KVA 150° 4.6%Z
208/120
480Δ
75KVA
208/120
#6
1"C
150A
PNL:2A-L1
225A, 3P, 4W 208/120
PNL:2A-L1, 2 SECT
225A, 3P, 4W 208/120
4-1/4"C
2"C (4)#2+GND
30A
MLO
2"C (4)1/0+GND
125A
300A PNL:2A-L
2 SECT
400A, 3P, 4W 208/120
3"C
1.5"C (3)#1+GND
20A X 58
PNL:2AB-H
480, 30 225A, 3P, 4W
208/120, 30 KAIC
20A X 17
MLO
2"C
20A
MLO
50A
225A
PNL:1A-H
225A, 3P, 4W 480/277
2.5"C (4)1/0+GND 1"C
20A X 15
MLO
1.5"C (3)#1+GND
#4
480Δ
75KVA
208/120
100A
300A
PNL:1A-L
2 SECT
150A
225A PNL:BA-H
225A, 3P, 4W, 30 KAIC
480/277
3"C
2.5"C 4/0+GND
MLO
1"C #4
480Δ
75KVA, 150°
208/120
BA-L /
BA-LA
100A
300A
PNL:BA-L
100A
PNL:BA-LA
208/120
BA-L/BA-LA
FUSE: 400A
1"C #4
100A
300APNL:BA-L1
400A, 208/120
100A
PNL:BA-L2
225A, 3P, 4W, 10 KAIC
480/277
BA-L1
CAN'T
OPEN
2"C
3"C (4)3/0+GND
125A P1A-H
(2)3.5"C
2 SETS
(4)350 KCMI/
#2 GRND
400APNL:PIA-E3
3 SECT.
400A, 3P, 4W, 30 KAIC
480/277
15A
JOCKEY
PUMP
(4)#2/0+GND (4)#2+GND (4)#1+GND (4)#4/0+GND
1"C
2"C
(4)#2+GND
100A
PNL:
4A-E1
50A
#2
125A
50A
2"C
PNL:4A-E1A
225A, 3P, 4W 208/120
PNL:4AB-E2
50A T3/E2
480Δ
30KVA 150° 4.9%Z
208/120
4A-E2 5A-E2 6A-E2
125A
100A
PNL:4A-E2
225A, 3P, 4W 208/120
2"C
1.5"C
(4)#2+GND
#6
50A
480Δ
30KVA 150° 4.9%Z
208/120
2"C 125A
100A
PNL:4A-E3
225A, 3P, 4W 208/120
100A
PNL:3AB-E2
125A, 3P, 4W 208/120
PNL:3A-E2
400A, 3P, 4W 208/120
350A
200A
3"C
(4)30 KCMIL+GND50A
T3/E2
3A-E2
3AB-E2
4AB-E2
480Δ
75KVA 150° 5.1%Z
208/120
2"C
(3)#1+GND
PNL:3A-E1A
225A, 3P, 3W
480V, 30 HAIC
MLO
PNL:3A-E1
100A, 3P, 4W 480/277
30 KAIC
(4)#2+GND
100A
100A
PNL:2A-E1A
125A, 3P, 4W 208/120
2"C
(4)#2+GND
MLO
2"C
(4)#2+GND
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
2"C
(4)#2+GND
PNL:2A-E1
100A, 3P, 4W 480/277
30 KAIC
(4)#2+GND
100A
PNL:2A-E2
30A, 2P, 4W
208/120MLO
2"C
(4)#2+GND
480Δ
30KVA 150° 4.9%Z
208/120
PNL:1A-E3
225A, 3P, 4W 208/120
125A
100A
50A
1"C
(3)#6+GND
PNL:1A-E2
225A, 3P, 4W 208/120
(4)#1+GND
100A
2"C
(4)#1+GND
480Δ
30KVA
150° 4.9%Z 208/120
100A
50A
1.5"C
PNL:2A-E1
100A, 3P, 4W 480/277
30 KAIC
125A
50A 100A
PNL:1A-E1A
225A, 3P, 4W 208/120
2"C
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
PNL:BA-E1
(4)#2+GND
100A
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
100A
PNL:BA-E1A
125A, 3P, 4W 208/120
2"C (4)#2 +
#6 GND
MLO
T3-E2
100A
PNL:BA-E2
225A, 3P, 4W
22 KAIC
125A
1.75"C (4)#2+GND
#8
50A
480Δ
30KVA 150° 4.9%Z
208/120
30A
1"C
(3)#6+GND
1"C
(3)#10+GND
DIESEL OIL
PUMPS
125A
3.5"C
(3)250 A CMIL+
#4 GND
3.5"C
(3)250 A CMIL+
#4 GND
#4
PNL:BA-E3
400A, 3P, 4W 208/120
300A
150A T5/E3 &E3A
2"C (4)#2+GND
3"C (4)3/0+GND
Department of Veteran Affairs
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
2.
CONTINUATION ON SHEET E-602.3
AutoCAD SHX Text E-602.1
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
AutoCAD SHX Text 1/21/25
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
QUADRANT "A" SINGLE LINE DIAGRAM
JB
JB
JB
1A-
HB
TO BE DETERMINED
P1A- E2
T3
ELEV. 4,5 & 6
T6
TBI
(4)#1+ #8 GND 480V
PNL:4A-E3
225A, 3P, 4W 208/120
PNL:4A-E3A
225A, 3P, 3W
480V, 30 HAIC
MLO4A-E3A
1.5"C (3)#1+GND
60A
4A-HA
1.5"C (3)#4+GND
PNL:4A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
60A
3A-HA
1.5"C (3)#4+GND
PNL:3A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
60A
2A-HA
1.5"C (3)#4+GND
PNL:2A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
60A
1A-HA
1.5"C (3)#4+GND
PNL:1A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
60A
BA-HA
1.5"C (3)#4+GND
PNL:BA-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
PNL:3A-E3A
225A, 3P, 3W
480V, 30 HAIC
MLO3A-E3A
1.5"C (3)#1+GND
PNL:3A-E3
225A, 3P, 4W 208/120
100A
PNL:2A-E3
125A, 3P, 4W 208/120
2"C
(4)#2+GND
MLO
2"C
(11)#1+GND
2"C
(4)#1+GND
2"C
(4)#1+GND
2"C
(4)#1+GND
PNL:1A-E3
225A, 3P, 4W 208/120
480Δ
75KVA 150° 5.1%Z
208/120
2"C
(4)#1+GND
PNL:BA-E3
400A, 3P, 4W 208/120
PNL:BA-E3AMLO
2"C (4)1/0+GND
DISC:
BA-E3B
225A, 112.5KVA
2"C (3)2/0
480Δ
112.5KVA 150° 4.6%Z
208/120 2.5"C (4)4/0 +
#4 GND
100A 100A
PNL:BA-E3
400A, 3P, 3W
480, 30 HAIC
2.5"C
(3)4/0+GND
PNL:BA-ERT
225A, 3P, 4W 270/120
XFMR
480V
150 KVA 5.6%Z
208/120V
PNL:P1A-HB
208/120
225A
1.5"C
2.5"C (4)4/0 + #4
PNL: P1A-ERCMLO
2"C (4)2/0+GND
LEVEL B
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
Department of Veteran Affairs
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
2.
CONTINUATION ON SHEET E-602.4
AutoCAD SHX Text E-602.2
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
AutoCAD SHX Text 1/21/25
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
QUADRANT "A" SINGLE LINE DIAGRAM
F12 F8 F16 F7 F11 F10 F9 F15 F3 F2 F5 F6 F14 F13 F4 F180
AF
A F
AF
AF
AF
AF
AF
AF
AF
AF
AF
AF
A F
LO
AD
B
AN
K
AT
JBJB
ATS-E3-
PNL. 7A-E3B
4P-800A
FDR. G5
ATS 14
30A CB
8A- E3C
8A- E3B
FED FROM
MCC-8
175A TO S-7,8,9
100A TO S-10
100A TO S-12
150A TO P-1,2,3
8A-H
2SECT
8A- E3A
ATS 23 TO SWBD "G"
FDR G-12
ATS-E3
ELEV. P1,2,3
3P-400A
ELEVATORS P-1,2,3
TO SWBD "G" FDR G-13
ATS 25ELEVATOR S-12
7(8D-HB)
ATS-E3 3P-125A
ELEV. S-12
TO ATS-24 ELEV. S-10
SEE RISER "D" FOR CONTINUATION
ATS 12
ELEVATORS S-7,8,9
ATS-E3
ELE. S-7,8,9
3P-400A
PNL:
7A- E3B
225A CB
TO 8AE3C
70A CB
FDR #AE3-1
T2
T3 T3
T3
T3
T3
T3
T3
T3
T4
T4
T5
T6
FDR #AE-1
FDR #AE-1
FDR #AE2-1
6A-H
13(8D-HB)
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
LEVEL 8
(E) EMERGENCY
DISTRIBUTION
SWITCHBOARD
(EDSB)
EM. SWBD C
EM. SWBD B
EM. SWBD D
EM. SWBD A
AT
S
AT
S
AT
S
AT
S
AT
S
AT
S
AT
S
A F
A T
AT
S
A F
1200A BUSWAY
8A-E3C
XFMR
7A-E3
70A 8,10,12
1.5"C (3)
480V/45 KVA 150° 4.3%Z
208/120
3/4"C #6
1 SET APROX. 4/0
600A, 3P, 4W
480/30 KAIC
MLO
175A
PNL:7A-E3
2 SECT
208/120 225A, 3P, 4W
PNL:6AB-LMLO PNL:6AB-H
225A, 3P, 4W
480/277, 30 HAIC
MLO
2.5"C (4) 4/0+GND 4-1/4" SQV C
(4) #4+#10 GND
PNL:7A-HB
225A, 3P, 4W
480, 30 HAIC 20A
2" C (4) #1+GND
100A
7A-HB
20A
FCU1
15A
FRU3
20A
FRU2
DISC #3
70A 7A-L
PNL:7A-H
2 SECT
225A, 3P, 4W
480/277, 30 HAIC
7A-L
15A
FRU3
125A
PNL:7A-L
225A, 208/120 3P, 4W
FRU3
7A-L
4" C (4) 500 KCMIL + GND
MLO
1.5"C (4) #2+GND
1"C
70A T4/A-L
100A
DISC
50A T5/5A-L1
175A
T6/A-L3, AB-L
100A
5A-H/5AB-H
125A
T5/AL
100A 4A-H
50A
50A
125A
1.5"C (3)#4+GND
2"C (4)#1+GND
3/4"C (3)#6+GND
6A-L1
6A-L
480Δ
30KVA 150° 4.5%Z
208/120
480Δ
45KVA 150° 4.3%Z
208/120
2"C (4)2/0+GND
1-1/2"C (4)#3+GND
20A X 40
100A
PNL:6A-L1
125A, 3P, 4W
30A
175A
PNL:6A-L
2SECT
100A
PNL:6A-H
30HAIC, 100A,
3P, 3W, 480V
#8
1"C 480Δ
30KVA 150° 4.5%Z
208/120
1-1/4"C (4)#3+GND
20A X 42
100A
PNL:5A-L1
125A, 3P, 4W 208/120
PNL:5AB-L
2SECT2.5"C
(4)4/0+GND
PNL:
5A-H
50A 7,9,11
225A, 3P, 4W
480/30 KAIC MLO
2"C (4)#1+GND
20A X 8
PNL:5AB-H
225A, 3P, 4W
480/225 KAIC
MLO
PNL:
5A-L
2SECT
200A
2 SETS
2.5"C (4)3/0+GND
400A
5A-L/5AB-L
#6
1"C 480Δ
30KVA 150° 5.7%Z
208/120
2"C
20A X 14
PNL:4A-H
225A, 3P, 4W
480/225 KAIC
MLO
480Δ
30KVA 150°
5.7%Z, 208/120
2"C
4A-L
30A
300A
PNL:4A-L,
2 SECT
20A X 42
300A
PNL:4A-H
225A, 3P, 4W
480/225 KAIC
480Δ
30KVA 150° 5.7%Z
208/120
1"C (3)#8+GND
100A
20A X 9
PNL:6A-E1
100A, 3P, 4W
30 KAIC
2"C
(4)#2/0+GND
2"C
(4)#2+GND
20A X 5
PNL:6A-E1A
125A, 3P, 4W 208/120
MLO
60A
30A
PNL:NO LABEL
OLD: 6A-E2
100A
20A X 28
PNL:6AB-E2
125A, 3P, 4W 208/120
2"C
(4)#1+GND
2.5"C
(4)#4/0+GND
2"C
(4)#1+GND
100A
PNL:5A-E1
100A, 3P, 4W 480/277
30 KAIC
2"C
(4)#2/0+GND
#2
100A
PNL:5A-E1A
100A, 3P, 4W 480/277
30 KAIC
2"C
(4)#2+GND
MLO
2"C
(4)#2+GND
100A
PNL:5A-E2
2"C
(4)#1+GND
2"C
(4)#1+GND
100A
PNL:5AB-E2
2.5"C
(4)#4/0+GND
2.5"C
(4)#4/0+GND
MLO
2"C
(4)#1+ #8 GND
1"C
2"C
(4)#2+GND
100A
PNL:
4A-E1
50A
#2
125A
50A
2"C
PNL:4A-E1A
225A, 3P, 4W 208/120
PNL:4AB-E2
50A T3/E2
480Δ
30KVA 150° 4.9%Z
208/120
4A-E2 5A-E2 6A-E2
125A
100A
PNL:4A-E2
225A, 3P, 4W 208/120
2"C
1.5"C
(4)#2+GND
#6
50A
480Δ
30KVA 150° 4.9%Z
208/120
2"C 125A
100A
PNL:4A-E3
225A, 3P, 4W 208/120
3A-E2
3AB-E2
4AB-E2
480Δ
75KVA 150° 5.1%Z
2"C
(3)#1+GND(4)#2+GND
100A
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
2"C
(4)#2/0+GND
Department of Veteran Affairs
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
2.
CONTINUATION ON SHEET E-602.1
AutoCAD SHX Text E-602.3
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
AutoCAD SHX Text 1/21/25
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FDR. G1
G1 G2 G3 G4 G5 G6
750 KW GENERATORS
400A TO MOTOR RISER B
400A TO MOTOR RISER A
ATS-E3-MTR
RISER-B
4P-800A
F5 F6 F14 F13 F4 F180
AF
AF
AF
A F
LO
AD
B
AN
K
ATS 16
FDR. G2
REMOTE RADIATOR
FAN CONTROLLER (TYP.)
8A-HB
400A CB
MOTOR RISER A
JB
JB
JB
PNL:
7A- E3B
70A CB
TO FDR.
GE3-1B
T3
T4
400A CB
MOTOR
RISER B
TO EMERGENCY
MOTOR RISER B
ATS E3-G3
500A GE3-2C
12 13
AT
S
AT
S
AT
S
A F
TO EMERGENCY
MOTOR RISER A
70A 8,10,12
1.5"C (3)
480V/45 KVA 150° 4.3%Z
208/120
3/4"C #6
2"C (4) 2/0+GND
MLO
175A
PNL:7A-E3
2 SECT
208/120 225A, 3P, 4W
PNL:7A-E3A
600A, 3P, 4W
480, 30 HAIC
MLU
2 SETS
2.5" C (3) 250 UCMIL + GND
EMCC-7A
DISC. 100A
SEC.1 300A SEC.2 300A SEC.3 300A
EMCC-7A
600A, 480, 3P, 3W
2" C PNL:7A-HA
225A, 3P, 4W
480, 30 HAIC
MLO
7A-HA DISC. 60A
1.5"C (3) #4+GND
100A
20A X 28
PNL:6AB-E2
125A, 3P, 4W 208/120
20A X 6
PNL:6A-E3
125A, 3P, 4W 208/120
MLO 6A-E3A
60A
6A-HA
1.5"C (3)#1+GND
PNL:6A-E3A
225A, 3P, 2W
480V, 30 HAIC
MLO
1.5"C (3)#4+GND
PNL:6A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
2"C
(4)#1+GND
100A
PNL:5AB-E2
2.5"C
(4)#4/0+GND
2.5"C
(4)#4/0+GND
MLO
100A
PNL:5A-E3
(4)#2 + #8 GND
2"C
(4)#1+ #8 GND
MLO
2"C
(4)#1+ #8 GND
5A-E3A
1.5"C (3)#1+GND
PNL:5A-E3A
225A, 3P, 3W
480V, 30 HAIC
MLO
480V
60A
6A-HA
1.5"C (3)#4+GND
PNL:5A-HA
225A, 3P, 3W
480, 30 HAIC
60A
3/4"C (3)#8+GND
480V
#6
480Δ
30KVA 150° 4.9%Z
208/120 1.5"C (3)#1+GND
LEVEL 5
LEVEL 6
LEVEL 7
LEVEL 8
Department of Veteran Affairs
Scale: NTS
C O
N
TI
N U
AT
IO
N O
N S
H
EE
T E-
2.
CONTINUATION ON SHEET E-602.2
AutoCAD SHX Text E-602.4
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
NOT FOR CONSTRUCTION
AutoCAD SHX Text DAVENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
BALTIMORE PANEL STUDY
AutoCAD SHX Text 512-23-109
AutoCAD SHX Text
JA
AutoCAD SHX Text
ALS
AutoCAD SHX Text 1/21/2025
AutoCAD SHX Text Dwg. of 20
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text 12/20/24
AutoCAD SHX Text Location
AutoCAD SHX Text VA MARYLAND HEALTHCARE SYSTEM – VISN5 – BALTIMORE VISN5 – BALTIMORE BALTIMORE 10 NORTH GREENE STREET, BALTIMORE, MD 21201
AutoCAD SHX Text
REVISION FINAL
AutoCAD SHX Text 1/21/25
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) SWITCHBOARD "B"
T4
T4
T4
T3 T3
T5
T4
T5
T5
T6
T6
T7
T6
FDR #BE1-1
FDR #BE1-1
FDR #BE1-1
TO MRI EQUIPMENT
CB1 RM 1B161
1B-E1
4.25"C SQ.
1B-E1
4.25"C SQ.
FDR #B3
F1 2500A BUSWAY F4 2500A BUSWAY
A
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11MAIN TIE MAIN
K K K
A
0A
A
SP
AR
E
0A
A
A
A
0A
0A
0A
SP
AR
E
0A
FU
TU
R E
FU
TU
R E
BM-1
BM-2
BM-3
BE1-1
BE1-2
BE2-1
BE2-2
BE3-1
BE3-2
BE3-3
BE3-4
ATS 2 ATS 6 ATS 20
250A
800A
600A
150A
105A 105A
800A 400A 75A
250A
105A
SPARE
ATS-E1-B
4P-260A
(E) EMERGENCY SWITCHBOARD-"B"
ATS-E2-B
4P-800A
ATS-E3-B
4P-600A
LEVEL P1
LEVEL B
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
EDSB
FDR #8
1200A
BUSWAY
A
BU
SW
AY
A
BU
SW
AY
A
BU
SW
AY
800A BUSWAY
125A
T5-BL
DISC
4B-H/4AB-H
DISC
DISC
200A
400A
PNL:4B-H PNL:4AB-H
1.5"C
2"C (4)#1
300A
3"C
PNL:4B-L
2 SECT
480Δ
75 KVA
208/120
PNL:4B-E1 PNL:4B-E1A
208/122
2"C
2"C
2" (4)#3+GND
MLO
PNL:3B-H PNL:3B-L
2 SECT PNL:
3B-LA
PNL:
3B-LB
PNL:
3B-LC
PNL:
3B-LR
PNL:
3B-E1
PNL:
3B-E1A
MLO
PNL:
2B-E1
PNL:
2B-E1A
2"C 2"C
2"C2"C
70A
T4/B-LB
B-LC
125A T5/B-L 2B-L
100A 2B-H
2AB-H
2B-LX
DISC
PNL:
2B-HA
2"C 4.25"C
2"C
3"C
50A
PNL:
2B-H
PNL:
2AB-H
RM:
2A-105
PNL:
2B-L
2 SECT
PNL:
2B-2B113
2 SECT
4…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .