Boiler Plant ACM Survey Results 11.28.2023.pdf

PDF 3 MB Posted

Attached to
Z2NE--Project 512A5-25-002, Replace Boiler Plant Water Main at Perry Point VAMC, MD
Solicitation number
36C24525R0050
Issued by

About this file

This is an Asbestos Building Survey report for the Perry Point VA Boiler - Building #315, located at 361 Boiler House Road in Perry Point, Maryland. The survey was conducted by Environmental Monitoring & Consulting Associates (EM&CA) on October 25, 2023, with the purpose of identifying suspect asbestos-containing building materials that may be disturbed during boiler replacement. The investigation involved collecting fifteen bulk samples from various locations, which were analyzed using Polarized Light Microscopy (PLM) and Transmission Electron Microscopy (TEM) methods.

The survey findings revealed three materials that tested positive for asbestos: exterior blue paint on metal wall panels (2.2% Chrysotile), exterior grey caulking on metal wall panels (1.5% Chrysotile), and mud pipe fitting insulation on a green fiberglass pipe above the upper level DA feed tank (14% Chrysotile). The boiler building, constructed in 1969, will require asbestos abatement for these materials if they are disturbed during renovation. The report notes that boiler bricks, refractory materials, and gasket samples from Boiler #1 tested negative for asbestos, and the company plans to reassess and prepare abatement plans once design documents are finalized.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS BUILDING SURVEY

PERRY POINT VA BOILER - BUILDING # 315

361 BOILER HOUSE ROAD

PERRY POINT MARYLAND

PREPARED FOR

MR. VINNIE CUOMO

D2X ASSOCIATES

259 St. Ives Drive Talent Oregon 97540

PREPARED BY

ENVIRONMENTAL MONITORING & CONSULTING ASSOCIATE

POST OFFICE BOX SOMERVILLE, NEW JERSEY 08876

NOVEMBER 22, 2023

65/82

Mr. Vinnie Cuomo November 22, 2023 D2X Associates

259 St. Ives Drive Talent Oregon 97540

RE: VA PROJECT # 512A5-21-303 – 30% SUBMISSION

PERRY POINT BOILER BUILDING # 315 ASBESTOS INSPECTION

361 BOILER HOUSE ROAD

PERRY POINT, MARYLAND

Dear Mr. Cuomo:

EM&CA has conducted an asbestos building survey at the above referenced location on October 25, 2023. The purpose of the survey was to identify any suspect asbestos containing building materials that will be disturbed by the replacement of boiler numbers 1, 3 and 4.

SAMPLING METHODS:

After reviewing the proposed scope of work and a previous asbestos building survey report prepared by Aerosol Monitoring & Analysis, Inc. (June 23, 2016) we collected suspect building material bulk samples with a core bore, metal spatula and/or x-acto knife. Samples were then placed in sterilized whirl-pak bags and given a unique sample ID numbers. A chain of custody form was filled out and the samples were sent to ALLAB Analytical Services for testing. Upon receipt of the samples ALLAB analyzed the samples as instructed and issued a bulk sample analytical report.

ANALYTICAL TECHNIQUE:

The suspect building materials were analyzed for asbestos at the ALLAB Laboratory using US EPA Method # 198.1 Polarized Light Microscopy (PLM) with Dispersion Staining. The analysis involves the microscope observation of the suspect asbestos containing materials with a stereoscopic low power microscope to determine the homogeneity of the material. Forcep samples are then immersed in a refractive index solution on a microscope slide, teased apart, covered with a cover glass, and observed with a polarized light microscope.

PLM is not consistently reliable in detecting asbestos in non organically bound materials such as floor tiles mastics, caulking, vinyl base cove moldings etc. Quantitative TEM is currently the only method that can be used to determine if these materials contain asbestos. Non organically bound floor tile and mastic materials were analyzed at ALLAB Analytical Lab using Transmission Electron Microscopy (TEM) ELAP Method # 198.4.

PAGE 1 0F 2

66/82

SAMPLE RESULTS:

Fifteen bulk samples were collected and analyzed at ALLAB NYS ELAP # 12118 (see attached sample analysis report and location maps). Samples were collected by licensed asbestos inspector Mr. Eugene Reyblat.

The following samples tested negative for asbestos:

• Condensate tank insulation

• DA feed tank insulation

• Steam pipe insulation

• Various mud pipe joint fitting insulation (except as noted below)

• Boiler # 1 exhaust duct insulation

• Boiler # 1 door gasket cement

• Boiler # 1 interior fire brick

• Boiler # 1 interior cement lining

• Mens Locker Room 12”x 12” tan floor tile and mastic

The following samples tested positive for asbestos:

• Exterior blue paint on metal wall panels

• Exterior grey caulking on metal wall panels

• Mud pipe fitting insulation on green fiberglass pipe above upper level DA feed tank

SUMMARY AND CONCULSIONS:

The boiler building was constructed in 1969. The blue exterior wall panels contain asbestos paint and caulking and will need to be abated if disturbed by the renovation. The boiler bricks, refractory materials and gasket samples from Boiler # 1 were negative for asbestos. Although we did not sample the interior of Boiler 3 and 4 they are the same boiler manufacturer and most likely similar insulation materials were used.

Once the design documents are prepared we will reassess which ACM materials will require abatement and prepare abatement plans and specifications as necessary.

We will resample areas as design documents are finalized. We did not sample the roof at this time as we were not sure if and were roof penetrations will be needed.

Very truly yours, Joel Russell Joel Russell

President

PAGE 2 0F 2

67/82

68/82

69/82

BULK SAMPLE ANALYSIS REPORT

Laboratory Report

1544 East 13th Street Brooklyn, NY 11230

Phone: (718) 864-3666

Client Name: EM&CA Report ID:

Building Address: 315-361 Boiler House Rd, Perry Pt, VA Report Date:

Client Project: NYS-DOH ELAP #

V erm iculite

TEM

RESULT

Item 198.4

231114-24 11/15/2023 12118

Client ID LAB ID#

L ayer Sample Description Sample Location:

Non- Fibros

Material

PLM NOB

Asbestos

Percentage and

Type

GRAVIMETRIC

HA

No.

A nalytical M ethod

Color

PLM

Friable

Asbestos Percentage and Type

Other Fiber Material

Percentage and Type

O rganic, %

N on-organic,%

C A

C O

3 %

PPB-001 231114-24-1 1 White Tank Insulation Lower Level / Condensate Retur Tank 198.1 White NAD 65% Cellulose 35 ND

PPB-002 231114-24-2 1 White Tank Insulation Upper Level / DA Feed Tank 198.1 White NAD 65% Cellulose 35 ND

PPB-003 231114-24-3 1 Pipe Fitting Insulation White

Upper Level / Low Pressure Steam Pipe 198.1 White NAD 65% Cellulose 35 ND

PPB-004 231114-24-4 1 Green Fiberglass Pippe / ADJ Ceiling Upper Level / Mud Fitting 198.1 Off

White 14%

Chrysotile 35% Fiber Glass 51 ND

PPB-005 231114-24-5 1 Pipe Fiberglass Upper Level / Mud Fitting on Silver Jacket 198.1 White NAD 65% Cellulose 35 ND

PPB-006 231114-24-6 1 Pipe Fiberglass Ground Level / ADJ New Boiler #3 / Mud Fitting on

Metal Silver Jacket

198.1 White NAD 65% Cellulose 35 ND

PPB-007 231114-24-7 1 Grey Door Gasket Cement Ground Level / Boiler #1 198.1 Grey NAD 100 ND

PPB-008 231114-24-8 1 White Door Gasket Fiber Material Ground Level / Boiler #1 198.1 White NAD 100% Fiber Glass 0 ND

PPB-009 231114-24-9 1 Red Fire Brick Ground Level / Inside Boiler #1 198.1 Brown NAD 100 ND

PPB-010 231114-24-10 1 Grey Mortar Cement Lining

Ground Level / Inside Boiler #1 198.1 Brown NAD 100 ND

PPB-011 231114-24-11 1 Red Cement Door Mortar

Ground Level / Inside Boiler #1 198.1 Brown NAD 100 ND

PPB-012 231114-24-12 1 Boiler Exhaust Duct Insulation

Ground Level / Boiler #1 Cat Walk 198.1 Beige NAD 100% Fiber Glass 0 ND

PPB-013.1 231114-24-13 1 12"x12" Tan Floor Tile Mens Locker Room 198.6 Beige Inconclusive

NAD 11 25 63 ND NAD

V erm iculite

TEM

RESULT

Item 198.4

Client ID LAB ID#

L ayer Sample Description Sample Location:

Non- Fibros

Material

PLM NOB

Asbestos

Percentage and

Type

GRAVIMETRIC

HA

No.

A nalytical M ethod

Color

PLM

Friable

Asbestos Percentage and Type

Other Fiber Material

Percentage and Type

70/82

BULK SAMPLE ANALYSIS REPORT

Laboratory Report

1544 East 13th Street Brooklyn, NY 11230

Phone: (718) 864-3666

Client Name: EM&CA Report ID:

Building Address: 315-361 Boiler House Rd, Perry Pt, VA Report Date:

Client Project: NYS-DOH ELAP #

V erm iculite

TEM

RESULT

Item 198.4

231114-24 11/15/2023 12118

Client ID LAB ID#

L ayer Sample Description Sample Location:

Non- Fibros

Material

PLM NOB

Asbestos

Percentage and

Type

GRAVIMETRIC

HA

No.

A nalytical M ethod

Color

PLM

Friable

Asbestos Percentage and Type

Other Fiber Material

Percentage and Type

O rganic, %

N on-organic,%

C A

C O

3 %

V erm iculite

TEM

RESULT

Item 198.4

Client ID LAB ID#

L ayer Sample Description Sample Location:

Non- Fibros

Material

PLM NOB

Asbestos

Percentage and

Type

GRAVIMETRIC

HA

No.

A nalytical M ethod

Color

PLM

Friable

Asbestos Percentage and Type

Other Fiber Material

Percentage and Type

PPB-013.2 231114-24-14 1 Mastic Mens Locker Room 198.6 Ligth Brown

Inconclusive

NAD 20 45 35 ND NAD

PPB-014 231114-24-15 1 Blue Paint on Metal Wall Ground Level / Exterior 198.6 Blue 2.2%

Chrysotile 37 33 28 ND Not Analyzed

PPB-015 231114-24-16 1 Grey Caulking on Metal Wall Ground Level / Exterior 198.6 Grey 1.5%

Chrysotile 46 31 21 ND Not Analyzed

Lab Director:

PLM - Polarized-Light Microscopy. NOB - Non-Friable Organically Bound Materials. TEM - Transmission Electron Microscopy.

198.1 - Method Item 198.1 of ELAP Certification Manual. 198.6 - Method Item 198.6 of ELAP Certification Manual. 198.4 - Method Item 198.4 of ELAP Certification Manual.

EPA 600 - Method EPA 600/M4/82/020 NJ EPA - Method EPA 600/R-93-116

ND - Not Detected NAD - No asbestos detected Trace - Inconclusive. Asbestos detected at 1% or less.

Samples with inconclusive results must not be interpreted as being non-asbestos.

Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.

Results NAD or TRACE by PLM are inconclusive.

The results relate only to the items tested. Samples will be stored for sixty (60) days.

The report shall not be reproduced without the written approval of the laboratory.

The currently approved methods for the analysis of SM-V include NYS DOH Item 198.8 and RJ Lee Groups Method 055.

11/15/2023

Aleksandr Barengolts

Date Collected: 10/25/2023 Date Received: 11/14/2023 Date of Analyses:

71/82

72/82

73/82

74/82